This document includes plans for a generator replacement project and details of a related federal contract opportunity. The plans outline the removal of an existing 100kW generator and installation of a new 70kW generator at a facility, including modifying the concrete pad, routing electrical feeders and conduits, and replacing lighting and remote monitoring equipment. The related solicitation is for the FPECK JDC Generator Replacement opportunity issued by the Department of the Interior Bureau of Indian Affairs Rocky Mountain Region. The solicitation number is 140A0423R0010 and seeks to replace the generator as specified in the provided plans.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ME1.1

FLOOR P

MECHANI

DARK DASHED LINES, EX

LIGHT SOLID LINES, EXIS

LINETYPE LEG

ELECTRICAL NOTES

1 REMOVE THE EXISTING 100KW, 120/208V, GENERAC GENERATOR.

THE EXISTING 300A, 120/208V, TRANSFER SWITCH SHALL REMAIN.

THE EXISTING DISCONNECT SWITCH SHALL REMAIN.

EXISTING BOILER TO REMAIN.

EXISTING WATER HEATER TO REMAIN.

MECHANICAL NOTES

A REMOVE FLUE. CAP WEATHER TIGHT ABOVE ROOF LINE.

REMOVE ABOVE FLOOR PIPING FROM ABANDON REMOTE RADIATOR.

REMOVE PIPING TO EXTERIOR REMOTE RADIATOR.

REMOVE REMOTE RADIATOR.

REMOVE WELDED GAS PIPING ABANDON LEG TO MAIN. CAP AT MAIN UNION.

B

C

D

E

E1.2

FLOO

DARK SOLID LINES, NEW WORK.

DARK DASHED LINES, EXISTING TO BE REMOVED.

LIGHT SOLID LINES, EXISTING TO REMAIN.

LINETYPE LEGEND

ELECTRICAL NOTES

REMOVE THE EXISTING 100KW, REMOTE RADIATOR.

PROVIDE THE NEW 70KW, 120/208V, 3-PHASE, 4-WIRE GENERATOR. MODIFY

EXISTING CONCRETE PAD, AS REQUIRED. PAD TO EXTEND 2' IN ALL DIRECTIONS

FROM NEW EQUIPMENT.

ROUTE THE ELECTRICAL FEEDERS AND GROUNDING CONDUCTOR UNDER THE

SLAB AND STUB UP AT THE BUILDING TO AN ELBOW SURFACE MOUNTED ON THE

WALL. ROUTE TIGHT TO THE INTERIOR WALL AND STUB DOWN AT THE EXISTING

TRANSFER SWITCH AND GROUNDING ELECTRODE.

PROVIDE FOUR 20A/1P CIRCUIT BREAKERS, IN THE NEAREST 120/208V PANEL

FOR ELECTRICAL SERVICE TO THE BATTERY HEATING PAD, BATTERY CHARGE,

COOLANT HEATER AND 120V, GFCI. OUTLET.

PROVIDE A 20A/2P CIRCUIT BREAKER IN THE NEAREST 120/208V PANELBOARD

FOR ELECTRICAL SERVICE TO THE 240V OUTLET.

INSTALL THE GENERATOR PROVIDED EMERGENCY STOP BOTTOM. PROVIDE

CABLE, IN CONDUIT, UNDER SLAB AND STUB UP INTO THE GENERATOR.

REPLACE EXISTIGN WALL PACK WITH LSI, MODEL NUMBER

WPSLL-6L-UNV-40-PC120-CWBB-BZA, MVOLT, 6000-LUMEN, DARK BRONZE WALL

PACK WITH COLD WEATHER EMERGENCY BATTERY PACK. VERIFY FIXTURE

OPERATION IS FROM DUSK TO DAWN VIA AN INTEGRAL PHOTOCELL.

EC TO REMOVE THE EXISTING GENERATOR REMOTE ANNUNCIATOR AND REPLACE

WITH THE NEW REMOTE ANNUNCIATOR. PROVIDE NEW CABLE AND CONDUIT

AND TIE INTO THE EXISTING CONDUIT. EXTEND NEW CABLE TO THE NEW

REMOTE ANNUNCIATOR.

GENERAL NOTES:

1. INFORMATION WAS GATHERED FROM SITE SURVEYS AND AS-BUILT DRAWINGS.

EC SHALL FIELD VERIFY CIRCUITS AND REPORT ANY AND ALL DISCREPANCIES

TO THE ARCHITECT/ENGINEER.

2. DEMOLITION NOTES ARE FOR REFERENCE ONLY AND DO NOT REFLECT ALL OR

ACCURATE EXISTING ELECTRICAL CONDITION. ELECTRICAL CONTRACTOR TO

VISIT JOB SITE, ASCERTAIN EXISTING CONDITIONS AND MAKE ALLOWANCES

THEREOF PRIOR TO BID.

3. ALL DEMOLISHED ELECTRICAL CIRCUITS TO HAVE CONDUIT REMOVED FROM

THE PANEL, INCLUDING FEEDERS. ELECTRICAL CONTRACTOR TO LEAVE

CIRCUIT BREAKERS AND PROVIDE A NEW TYPED PANEL DIRECTORY

INDICATING ALL EXISTING LOADS, CHANGED LOADS AND SPARE LOADS.

4. CIRCUITRY: WHERE EQUIPMENT REMOVAL INTERRUPTS CIRCUITS FEEDING

EQUIPMENT THAT MUST REMAIN ENERGIZED. EXTEND EXISTING CIRCUIT AS

REQUIRED PER NEC. PROVIDE NEW BOXES, CONDUIT, CONDUCTORS, ETC.

5. ELECTRICAL CONTRACTOR SHALL REVIEW ALL POWER, MECHANICAL AND

PLUMBING DEMOLITION DRAWINGS CONCERNING WORK THAT WILL AFFECT

ELECTRICAL WORK.

6. ELECTRICAL CONTRACTOR RESPONSIBLE FOR DISCONNECTING AND/OR

DE-ENERGIZING ALL ELECTRICAL EQUIPMENT INCLUDING LIGHTING, POWER,

FIRE ALARM, VOICE DATA, ETC. FIXTURES, DEVICES, APPARATUS,

DISCONNECTS, MOTOR STARTERS, BOXES, CONDUIT, FEEDERS, WIRING

DEVISES, ETC TO BE REMOVED BY THE GENERAL CONTRACTOR UNDER THE

SUPERVISION OF THE ELECTRICAL CONTRACTOR.

GENERAL NOTES:

7. ELECTRICAL CONTRACTOR TO VERIFY WHICH DEMO

ELECTRICAL EQUIPMENT IS TO BE RETAINED BY TH

AS WELL AS DIRECT THE GENERAL CONTRACTOR TO

STOCKPILE IT ON SITE AS DIRECTED BY THE OWNE

8. THE EC SHALL FIELD VERIFY EXISTING CONDITIONS

BID AND INCLUDE ALL NECESSARY DEMOLITION WO

INCLUDING THE SUPPORTING OF EXISTING CONDU

9. NOTIFICATION: ANY DEMOLITION OR MODIFICATIO

QUESTION SHALL BE DIRECTED TO THE ARCHITECT

AND/OR ENGINEER.

10.COORDINATE THE LOCATIONS OF ALL DEVICES WIT

GC/OWNER PRIOR TO INSTALLATION.

EXISTING

UTILITY

TRANSFORMER

MECHANICAL NO

REMOVE ABANDON PIPING FROM REMOTE RADIATO

EXTEND 11

2" GAS LINE FROM 3" WELDED MAIN ACR

SUPPORT WITH MANUFACTURED ROOF SUPPORTS 4

SECURE GAS DROP TIGHT TO EXISTING ROOF COLU

A

B

C

NOTES

REMOVE 4" CONCRETE

SLAB FOR REQUIRED

WORK. REPLACE WITH

4000 PSI CONCRETE

DOWELED INTO

EXISTING SLAB. FINISH

TO MATCH ADJACENT.

A

D

EXISTING

GENERATOR

3 4

EX. MDP

EX. 'EFS'

PANEL REMOVE THE E

NATURAL GAS,

AIR, GAS LINE

THE EXISTING

THE EXISTING

SHALL REMAIN

THE EXISTING

BRANCH FEEDER NO

REMOVE THE

TRANSFER S

THE EXISTIN

TRANSFER S

THE EXISTIN

TRANSFER S

THE EXISTIN

A

B

C

D

E2.1

POWER ONE-LINE (DEMO)

A

EXISTING

GENERATOR

EX. MDP

EX. 'EFS'

PANEL PROVIDE A 70

THE EXISTING

THE EXISTING

THE EXISTING

BRANCH FEEDER NO

REMOVE THE

TRANSFER S

THE EXISTIN

TRANSFER S

THE EXISTIN

TRANSFER S

CONNECT TO

PROVIDE A #

A

B

C

D

E2.1