The file is a set of technical drawings detailing the installation of Remote Generator Annunciator Panels for the St. Cloud VA Health Care System. The project involves installing five hardwired remote generator annunciator panels for emergency generators across multiple buildings, including Buildings 4, 5, 7, 8, 9, 28, 50, 51, 96, 111, 112, 113, 114, 117, 118, 119, and a Parking Structure. The technical drawings specify detailed requirements for new conduit installation, fiber jumpers, copper-to-fiber converters, UPS systems, and communication network connections, with specific notes about utilizing existing infrastructure and avoiding asbestos disturbance.

The associated federal contract opportunity is a 100% Service-Disabled Veteran Owned Small Business (SDVOSB) set-aside solicitation (Solicitation Number: 36C26325R0029) for the Department of Veterans Affairs. The project requires installing remote generator annunciators compatible with CAT EMCP 4 RS-485 generators, with all cabling, conduit, media converters, and fiber-jumpers to be provided by the contractor. The project has a performance period of 100 calendar days from the Notice to Proceed, with a total project value between $100,000 and $250,000. Offerors must be registered and certified in the Veteran Small Business Certification (VetCert) and comply with specific registration requirements in the SAM database.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Building 114 Generator

Building 96 IT Fiber Termination Cabinet

Building 51 Eng Fiber Termination Cabinet

Room 22

Building 117 Generator

Building 113 Generator

Building 50 Eng Fiber Termination Cabinet

Room 23A

Building 119 Generator

Building 9 Eng Fiber Termination Cabinet

Room 15

Building 112 GeneratorBuilding 7 Boiler Plant Control Room and Eng Fiber Termination Cabinet Room 104

Building 5 Eng Fiber Termination Cabinet

Room 117

Building 8 Eng Fiber Termination Cabinet

Room 11

Building 111 Eng Fiber Termination Cabinet

Room 27

Building 28 Eng Fiber Termination Cabinet

Room 72B

Parking Structure Eng Fiber Termination

Cabinet Room B10

Building 118 Eng Fiber Termination Cabinet

Room 4

Building 7 OIT Fiber Switch Room 102A

Building 4 – Generator 119 Notes:

- This drawing is for reference only.

- Jumper fiber from B8 to B7 (Gen 119).

Existing Engineering Fiber Termination Cabinet

Building 5 – Generators 113 and 117 Notes:

- This drawing is for reference only.

- Jumper fibers from B51 to B7 (Gen 113 and 117).

Building 7 – All Generators

- This drawing is for reference only.

- The yellow highlighted section below shows the path in which new conduit is needed.

- The red highlighted section below shows existing wire tray.

- Install new conduit where existing wire tray does not exist.

- New Remote Generator Annunciator Panels to be installed on south wall of 104.

- New UPS(s) for Remote Generator

Annunciator Panels to be installed on north wall of 103.

- New copper-to-fiber converters, along with suitable UPS(s) on south wall of 102A.

Existing Wire Tray

102A

New Fiber Converters and UPS(s)

New Conduit

New Remote Annunciator Panels

New Remote Annunciator Panel UPS(s)

Existing OIT Fiber Switch

Existing Engineering Fiber Cabinet

Building 8 – Generator 119

- This drawing is for reference only.

- Jumper fiber from B118 to B4 (Gen 119).

Building 9 – Generator 119

- This drawing is for reference only.

- Utilize existing conduit from B119.

- Install new conduit where existing conduit / wire tray does not exist.

- New copper-to-fiber converter to be installed on north wall of Room 15. Jumper fiber from converter to 111.

Existing Engineering Fiber Termination Cabinet

Provide new copper‐to‐ fiber converter, along with suitable UPS.

Existing Conduit from B119

Building 28 – Generator 119

- This drawing is for reference only.

- Jumper fiber from 111 to Parking Structure

(Gen 119).

Building 50 – Generator 113

- This drawing is for reference only.

- Utilize existing conduit in the sub-basement and basement of B50 to pull new OEM recommended copper to B50 Rom 23A

- Install new conduit where existing conduit / wire tray does not exist.

- New copper-to-fiber converter to be installed on north wall of 23A.

- Work activities in the sub-basement of B50 may require work adjacent to asbestos.

Work for this project will not disturb any asbestos and does not require abatement.

102A

Existing Engineering Fiber Termination Cabinet

Provide new copper‐to‐ fiber converter, along with suitable UPS.

Building 51 – Generators 113 and 117 Notes:

- This drawing is for reference only.

- Utilize existing conduit in the sub-basement of B51 to pull new OEM recommended copper to B51 Rom 22.

- Install new conduit where existing conduit / wire tray does not exist.

- New copper-to-fiber converter to be installed on north wall of 22. Jumper fiber from converter to B5 (Gen 117).

- Jumper fiber from B51 to B5 (Gen 113).

- Work activities in the sub-basement of B51 may require work adjacent to asbestos.

Work for this project will not disturb any asbestos and does not require abatement.

Existing Engineering Fiber Termination Cabinet

Provide new copper‐to‐ fiber converter, along with suitable UPS.

Building 96 – Generator 114

- This drawing is for reference only.

- Utilize existing conduit from B114 to B96 to pull new OEM recommended copper to Room 104B.

- Install new conduit where existing conduit / wire tray does not exist.

- New copper-to-fiber converter to be installed on south wall of Room 104B.

Jumper fiber from converter to OIT Fiber Switch.

Provide new copper‐to‐ fiber converter, along with suitable UPS.

Existing OIT Fiber Switch

Building 111 – Generator 119

- This drawing is for reference only.

- Jumper fiber from 9 to 28 (Gen 119).

Building 112 – Generator 112

- This drawing is for reference only.

- The yellow highlighted section below shows the path in which new conduit is needed.

New Conduit

To Existing Steam Tunnel Wire Tray

Building 113 – Generator 113

- This drawing is for reference only.

- The yellow highlighted section below shows the path in which new conduit is needed.

- Utilize existing conduit in the sub-basement and basement of B50 to pull new OEM recommended copper to B50 Room 23A

102A

New Conduit Path

Building 114 – Generator 114

- This drawing is for reference only.

- The yellow highlighted section below shows the path in which new conduit is needed.

- Utilize existing conduit from B114 to B96 to pull new OEM recommended copper to B96 Room 104B

- Install new conduit where existing conduit does not exist.

Building 117 – Generator 117

- This drawing is for reference only.

- The yellow highlighted section below shows the path in which new conduit is needed.

- Utilize existing conduit in the sub-basement and basement of B51 to pull new OEM recommended copper to B51 Room 22

Building 118 – Generator 119

- This drawing is for reference only.

- Jumper fiber from Parking Structure to B8

(Gen 119).Existing Engineering Fiber

Building 119 – Generator 119

- This drawing is for reference only.

- Contractor to verify all pathways and dimensions.

- The highlighted section below shows the path in which new conduit is needed.

Existing Generator

Existing Conduit Running to Building 9 Room 15

Parking Structure – Generator 119 Notes:

- This drawing is for reference only.

- Jumper fiber from Parking Structure to

B118 (Gen 119).

File details come from the government source that posted it. Updated .