GEMS 15 kVA UPS Technical Specifications - BY_Knotts.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
EMA - GEMS Facility UPS Units - ARG
Solicitation number
25-588IEMA-MGMTA-B-45482
Issued by
St. Clair County, Illinois

About this file

This document contains the technical specifications for a 15 kVA Uninterruptible Power Supply (UPS) system required for the GEMS project at the Byron Nuclear Generating Station and the GEMS Test Bay in Springfield, Illinois. The UPS system is an Eaton 9355 model with a 3-high cabinet style and 64 batteries, providing 15 kVA / 13.5 kW of power at 0.9 power factor. The UPS system requires 208/120V AC, 3-phase, 4-wire (plus ground) Wye input power at 60 Hz, and provides 208/120V AC, 3-phase, 4-wire (plus ground) Wye output power at 60 Hz. The UPS system must meet various technical requirements, including a minimum of 91% efficiency, 1% voltage regulation, and 70 minutes of battery runtime at full load.

The document also specifies the required communications and diagnostic capabilities, as well as the warranty and service requirements, including 24/7 on-site emergency response within 8 hours of notification and the need for a certified vendor to perform the initial startup of the unit.

View the file

Other files

File Type Posted
Questions and Answers~11.docx DOCX document
standard terms and conditions~7.pdf PDF
standard-illinois-certifications-v.23.1~62.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 GEMS UPS Technical Specifications

Tech Specs
ModelEaton 9355
Cabinet Style3 High w/ 64 Battery
Power
Ratings15 KVA / 13.5KW @ 0.9 P.F.
TopologyDouble Conversion
Input
Input Voltage208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Input Frequency60 Hz ± 5 Hz
Voltage Correction Range176-228.8V AC
Power Factor (Full Load)0.99 typical
Output
Waveform (On-Line)Sinewave
Waveform (On-Battery)Sinewave
Output Voltage (RMS)208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Output Frequency60 Hz
Efficiency (Full Load / On-Line)91% typical
Voltage Regulation± 1%
Input Current Distortion<= 5% THD
Overload Capabilities125% (1 min.) / 150% (5 sec.) / 110% (10 mins.)
Battery
Battery TypeVRLA, 9AH, maintenance free (Field replacable)
Typical Backup Time (Full Load)> 70 min @ full load (> 8 hours @ 15% full load)
External Battery Cabinet (EBM) ConfigurationEBM 96 (Qty 2 for BY unit only) (Knotts St. unit = Qty 0)
Operation / General
DiagnosticsFull system self-test @ startup
UPS BypassAutomatic on overload or UPS failure
On-Line Transfer Time1 ms typical
Audible Noise (Full Load @ 1m)< 58 dBA
Communications
Minimum RequirementsGraphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card, network communications card (INDGW-X2 Industrial Gateway Card)
Network typeFactory Installed MS Network Card (SNMP)
Certifications
QualityISO 9001
Warranty
Standard1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification.
Customer Service
Initial Start UpVendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Byron Nuclear Generating Station and Knotts St. GEMS Test Bay in Springfield, IL.
Tech Support Availability24/7 (Unlimited)