This document contains the technical specifications for a 15 kVA Uninterruptible Power Supply (UPS) system to be installed at the Byron Nuclear Generating Station and the Knotts St. GEMS Test Bay in Springfield, Illinois. The UPS system is specified as an Eaton 9355 model in a 3-high cabinet configuration with 64 batteries, capable of providing 15 kVA / 13.5 kW of power at 0.9 power factor. The UPS features a double conversion topology, sinewave output, automatic bypass, and remote monitoring and control capabilities. The UPS must be certified for initial startup by the manufacturer and have 24/7 technical support available.

The document outlines detailed technical requirements for the UPS system, including input and output voltages, frequencies, power factor, efficiency, and noise levels. It also specifies the required communications interfaces, quality certifications, and warranty terms, which include 1-year full parts and labor coverage with 8-hour on-site emergency response.

View the file

Other files

File Type Posted
standard terms and conditions~7.pdf PDF
Questions and Answers~11.docx DOCX document
standard-illinois-certifications-v.23.1~62.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 GEMS UPS Technical Specifications

Tech Specs
ModelEaton 9355
Cabinet Style3 High w/ 64 Battery
Power
Ratings15 KVA / 13.5KW @ 0.9 P.F.
TopologyDouble Conversion
Input
Input Voltage208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Input Frequency60 Hz ± 5 Hz
Voltage Correction Range176-228.8V AC
Power Factor (Full Load)0.99 typical
Output
Waveform (On-Line)Sinewave
Waveform (On-Battery)Sinewave
Output Voltage (RMS)208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Output Frequency60 Hz
Efficiency (Full Load / On-Line)91% typical
Voltage Regulation± 1%
Input Current Distortion<= 5% THD
Overload Capabilities125% (1 min.) / 150% (5 sec.) / 110% (10 mins.)
Battery
Battery TypeVRLA, 9AH, maintenance free (Field replacable)
Typical Backup Time (Full Load)> 70 min @ full load (> 8 hours @ 15% full load)
External Battery Cabinet (EBM) ConfigurationEBM 96 (Qty 2 for BY unit only) (Knotts St. unit = Qty 0)
Operation / General
DiagnosticsFull system self-test @ startup
UPS BypassAutomatic on overload or UPS failure
On-Line Transfer Time1 ms typical
Audible Noise (Full Load @ 1m)< 58 dBA
Communications
Minimum RequirementsGraphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card, network communications card (INDGW-X2 Industrial Gateway Card)
Network typeFactory Installed MS Network Card (SNMP)
Certifications
QualityISO 9001
Warranty
Standard1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification.
Customer Service
Initial Start UpVendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Byron Nuclear Generating Station and Knotts St. GEMS Test Bay in Springfield, IL.
Tech Support Availability24/7 (Unlimited)