GEMS 15 kVA UPS Technical Specifications - BY_Knotts.xlsx
XLSX spreadsheet 15 KB Posted
- Attached to
- EMA - GEMS Facility UPS Units - ARG
- Solicitation number
- 25-588IEMA-NCLRF-B-45018
- Issued by
- Sangamon County, Illinois
About this file
This document contains the technical specifications for a 15 kVA Uninterruptible Power Supply (UPS) system to be installed at the Byron Nuclear Generating Station and the Knotts St. GEMS Test Bay in Springfield, Illinois. The UPS system is specified as an Eaton 9355 model in a 3-high cabinet configuration with 64 batteries, capable of providing 15 kVA / 13.5 kW of power at 0.9 power factor. The UPS features a double conversion topology, sinewave output, automatic bypass, and remote monitoring and control capabilities. The UPS must be certified for initial startup by the manufacturer and have 24/7 technical support available.
The document outlines detailed technical requirements for the UPS system, including input and output voltages, frequencies, power factor, efficiency, and noise levels. It also specifies the required communications interfaces, quality certifications, and warranty terms, which include 1-year full parts and labor coverage with 8-hour on-site emergency response.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| standard terms and conditions~7.pdf | ||
| Questions and Answers~11.docx | DOCX document | |
| standard-illinois-certifications-v.23.1~62.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 GEMS UPS Technical Specifications
| Tech Specs | |
| Model | Eaton 9355 |
| Cabinet Style | 3 High w/ 64 Battery |
| Power | |
| Ratings | 15 KVA / 13.5KW @ 0.9 P.F. |
| Topology | Double Conversion |
| Input | |
| Input Voltage | 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Input Frequency | 60 Hz ± 5 Hz |
| Voltage Correction Range | 176-228.8V AC |
| Power Factor (Full Load) | 0.99 typical |
| Output | |
| Waveform (On-Line) | Sinewave |
| Waveform (On-Battery) | Sinewave |
| Output Voltage (RMS) | 208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye |
| Output Frequency | 60 Hz |
| Efficiency (Full Load / On-Line) | 91% typical |
| Voltage Regulation | ± 1% |
| Input Current Distortion | <= 5% THD |
| Overload Capabilities | 125% (1 min.) / 150% (5 sec.) / 110% (10 mins.) |
| Battery | |
| Battery Type | VRLA, 9AH, maintenance free (Field replacable) |
| Typical Backup Time (Full Load) | > 70 min @ full load (> 8 hours @ 15% full load) |
| External Battery Cabinet (EBM) Configuration | EBM 96 (Qty 2 for BY unit only) (Knotts St. unit = Qty 0) |
| Operation / General | |
| Diagnostics | Full system self-test @ startup |
| UPS Bypass | Automatic on overload or UPS failure |
| On-Line Transfer Time | 1 ms typical |
| Audible Noise (Full Load @ 1m) | < 58 dBA |
| Communications | |
| Minimum Requirements | Graphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card, network communications card (INDGW-X2 Industrial Gateway Card) |
| Network type | Factory Installed MS Network Card (SNMP) |
| Certifications | |
| Quality | ISO 9001 |
| Warranty | |
| Standard | 1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification. |
| Customer Service | |
| Initial Start Up | Vendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Byron Nuclear Generating Station and Knotts St. GEMS Test Bay in Springfield, IL. |
| Tech Support Availability | 24/7 (Unlimited) |
File details come from the government source that posted it. Updated .