GEMS 15 kVA UPS Technical Specifications - BR LS.xlsx

XLSX spreadsheet 15 KB Posted

Attached to
EMA - GEMS Facility UPS - 15KVA
Solicitation number
26-588IEMA-MGMTA-B-51543
Issued by
Illinois

About this file

This is a technical specifications document for a GEMS 15 kVA UPS system required for the Braidwood and LaSalle Nuclear Generating Stations. The specifications detail an Eaton 9355 UPS unit with a 3-high cabinet configuration and 64 battery capacity, rated at 15 KVA / 13.5 KW at 0.9 power factor. The system operates on double conversion topology with input voltage of 208/120V AC, 3-phase, 4-wire (plus ground) in a Wye configuration, and delivers output at the same voltage and phase specifications. The unit includes two external battery cabinets (EBM 96 configuration), a graphical LCD display with backlight, RS-232 communications, industrial relay and gateway cards, and a factory-installed MS Network Card with SNMP capability. The UPS operates at 91% efficiency at full load with automatic bypass functionality on overload or UPS failure and an online transfer time of 1 millisecond typical.

The warranty includes one year of full parts and labor coverage with 24/7 on-site emergency response within 8 hours of notification. The vendor must be certified by the manufacturer to perform initial startup of the unit on-site. Technical support availability is 24/7 with unlimited assistance. The unit maintains voltage regulation within ±1%, input frequency tolerance of ±5 Hz, audible noise below 58 dBA at full load at one meter distance, and demonstrates voltage correction range of 176-228.8V AC. The system includes full self-diagnostic testing at startup and holds ISO 9001 quality certification.

View the file

Other files

File Type Posted
B-51543 Q and A.docx DOCX document
Standard Illinois Certifications v.26.2.pdf PDF
standard-terms-and-conditions 4~51.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 GEMS UPS Technical Specifications

Tech Specs
ModelEaton 9355
Cabinet Style3 High w/ 64 Battery
Power
Ratings15 KVA / 13.5KW @ 0.9 P.F.
TopologyDouble Conversion
Input
Input Voltage208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Input Frequency60 Hz ± 5 Hz
Voltage Correction Range176-228.8V AC
Power Factor (Full Load)0.99 typical
Output
Waveform (On-Line)Sinewave
Waveform (On-Battery)Sinewave
Output Voltage (RMS)208/120V AC, 3Ø, 4 Wire (+ Gnd), Wye
Output Frequency60 Hz
Efficiency (Full Load / On-Line)91% typical
Voltage Regulation± 1%
Input Current Distortion<= 5% THD
Overload Capabilities125% (1 min.) / 150% (5 sec.) / 110% (10 mins.)
Battery
Battery TypeVRLA, 9AH, maintenance free (Field replacable)
Typical Backup Time (Full Load)> 70 min @ full load (> 8 hours @ 15% full load)
External Battery Cabinet (EBM) ConfigurationEBM 96 (Quantity 2)
Operation / General
DiagnosticsFull system self-test @ startup
UPS BypassAutomatic on overload or UPS failure
On-Line Transfer Time1 ms typical
Audible Noise (Full Load @ 1m)< 58 dBA
Communications
Minimum RequirementsGraphical LCD w/ backlight display, RS-232, X-slot Industrial Relay Card (P/N: 103003055), X-slot Industrial Gateway Card (P/N: INDGW-X2)
Network typeFactory Installed MS Network Card (SNMP)
Certifications
QualityISO 9001
Warranty
Standard1 Year Full Parts & Labor, including 24/7 on-site emergency response within 8 hours of notification.
Customer Service
Initial Start UpVendor must be certified to perform initial startup of the unit per manufacturer requirements. Location: On-site @ Braidwood and LaSalle Nuclear Generating Stations
Tech Support Availability24/7 (Unlimited)