B-51543 Q and A.docx
DOCX document 13 KB Posted
- Attached to
- EMA - GEMS Facility UPS - 15KVA
- Solicitation number
- 26-588IEMA-MGMTA-B-51543
- Issued by
- Illinois
About this file
This is a Question and Answer document issued by the Illinois Emergency Management Agency, Office of Homeland Security, for contract opportunity 26-588IEMA-MGMTA-B-51543 regarding an EMA GEMS Facility UPS system with 15KVA capacity. The document addresses technical specifications for the uninterruptible power supply backup capability required for the project. The single clarification provided confirms that the backup system must deliver greater than 70 minutes of runtime at full load capacity, with extended runtime of greater than 8 hours available at 15 percent full load operation.
No additional information regarding pricing terms, set-asides, incumbents, funding sources, response deadlines, or other contractual provisions is contained within this question and answer document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| GEMS 15 kVA UPS Technical Specifications - BR LS.xlsx | XLSX spreadsheet | |
| Standard Illinois Certifications v.26.2.pdf | ||
| standard-terms-and-conditions 4~51.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Illinois Emergency Management Agency – Office of Homeland Security
26-588IEMA-MGMTA-B-51543
Question and Answer
Q: Could you please confirm the desired backup time at load?
A: >70 min @ full load (>8 hours @ 15% full load).