g26ra087_Drawings.pdf
PDF 20 MB Posted
- Attached to
- B90176 Hangar Door Expansion (HADES)
- Solicitation number
- W9126G26RA087
About this file
This is a set of design drawings and construction documents for the B90176 Hangar Door Expansion (HADES) project at Fort Hood, Texas, issued May 28, 2026. The document package includes architectural, structural, civil, mechanical, electrical, plumbing, and fire protection design sheets totaling 95 sheets. The project involves replacing two existing rolling sectional hangar doors with new 120-foot-wide vertical lift fabric doors to accommodate the ME-11B aircraft. Key structural modifications include removal and replacement of wind posts, grade beams, spandrel beams, and concrete slab sections. The hangar is classified as an aircraft storage and servicing occupancy (IIB construction type) with a maximum occupant load of 184 persons and a floor area of 121,200 square feet across four hangar bays (HA, HB, HC, HD). Design standards reference UFC 1-200-01, UFC 3-600-01, UFC 4-211-01, 2024 IBC, 2024 IEBC, NFPA 101, NFPA 72, NFPA 13, and NFPA 409.
The design accommodates a basic wind speed of 105 mph (Risk Category II, Exposure C), ground snow load of 14 psf, and seismic design category A per ASCE 7-22. Concrete specifications require 4,000 psi minimum compressive strength with non-shrink grout and ASTM A615 Grade 60 reinforcing steel. Civil work includes removal and replacement of eight concrete pavement panels, installation of four-inch HDPE stormwater drain lines with multiple tees and cleanouts, demolition of three bollards with replacement of nine new bollards, and site restoration. The design incorporates accessibility requirements per IBC/ANSI/ADAAG standards, includes life safety egress planning with exits spaced at 150-foot maximum intervals, and provides detailed specifications for construction joints, expansion joints, and joint sealants. Design firms involved are Larson Design Group (architectural, Oklahoma City) and Citrine-Olsson JV (structural and civil). The contract number is W9126G26BA005, with solicitation number W9126G26RA087.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AM0005 15JUL26.pdf | ||
| am_04.pdf | ||
| Site Visit-07JUL26.pdf | ||
| Site Visit-22JUN26.pdf | ||
| AM0003.pdf | ||
| am_2.pdf | ||
| am_01.pdf | ||
| g26ra087.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FORT HOOD
PROJECT LOCATION
PROJECT LOCATION
S
TA
TE
OF OKLAHO
M A
L
IC
ENSED ARCHIT
EC
T
BRIAN
BOURN
A08515
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
US Army Corps of Engineers ®
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
VOLUME:
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
3817 NW EXPRESSWAY
SUITE 840
OKLAHOMA CITY, OK 73112
(405) 722-7270
Larson Design Group
MAY 28, 2026
A u to d e s k D o c s
/U S
A C
E F t W o rt h
B H a n g a r
D o o r
E x p a n s io n
F t H o o d /B
H a n g a r
D o o r
E x p a n s io n
R
A rc h .r v t
/2
/2
:3
:2
P
M
G-001
C O
V E
R S
H E
E T
F O
R T
H O
O D
T
X F
O R
T W
O R
T H
D
IS
T R
IC
T
T
A Y
L O
R S
T F
O R
T W
O R
T H
T
X
L A
R S
O N
D E
S
IG
N G
R O
U P
N
W E
X P
R E
S S
W A
Y S
U
IT
E
O K
L A
H O
M A
C
IT
Y O
K
B B
O U
R N
B B
O U
R N
T K
U R
G A
N
B H
U N
T E
R
M A
Y
W G
B
A
B H
A N
G A
R D
O O
R E
X P
A N
S
IO
N
H A
D E
S M
IS
S
IO
N
S U
P P
O R
T
FORT WORTH DISTRICT
W9126G26BA005
MAY 28, 2026
DESIGN PACKAGE
FORT HOOD, TX
B90176 HANGAR DOOR EXPANSION - HADES
MISSION SUPPORT
VICINITY
LOCATION
DRAWING INDEX
MATERIALS LEGEND SYMBOLS LEGEND ABBREVIATIONS
COMPLETE LISTING OF MATERIALS ON THE JOB.
STANDARD AND ARE NOT INTENDED AS A
NOTE: ABOVE MATERIAL INDICATIONS ARE
( DISCONTINUOUS MEMBER )
( CONTINUOUS MEMBER )
MISCELLANEOUS METAL
RIGID INSULATION BOARD
EARTH FILL
BATT INSULATION
ALUMINUM
FINISH WOOD
WOOD BLOCKING
WOOD FRAMING
INSULATED PANEL
PLYWOOD
LARGER SCALE DETAIL MARK
WALL SECTION CUT MARK
BUILDING SECTION CUT MARK
STRUCTURAL GRID COORDINATES
DOOR NUMBER
SQUARE CONCRETE COLUMN
WIDE FLANGE STEEL COLUMN
SQUARE STEEL COLUMN
ROUND STEEL COLUMN
FRAME PARTITION ( METAL STUD )
CONCRETE BLOCK
FOR PLANS AND DETAILS
GYPSUM BOARD
CONCRETE
FACE BRICK
EXISTING BUILDING TO BE MODIFIED
EXISTING BUILDING TO BE REMOVED
EXISTING BUILDING TO REMAIN
BENCHMARK / SPOT ELEVATION
FINISH GRADE CONTOUR
EXISTING TREE TO BE PROTECTED
EXISTING GRADE CONTOUR
EXISTING TREE TO BE REMOVED
PROPERTY LINE
PAVING ( CONCRETE )
PAVING ( ASPHALT )
CONCRETE WALK
TEST HOLE
NEW BUILDING
FENCE X X
15' O
AK
18' E
LM
EXISTING SPOT ELEVATION
FINISH SPOT ELEVATION
100.25
X
FRAME ELEVATION
PARTITION TYPE
ROOM NAME AND NUMBER
INTERIOR
ELEVATION REF.
A101
SIM
DETAIL SECTION CUT MARK
Room name
1t
NORTH ARROW SYMBOLS
PLAN
NORTH
TRUE
NORTH
FOR DETAILS
SHEET WHERE
ELEV IS DRAWN
ELEV INDICATED
EXTERIOR
ELEVATION REF.SHEET WHERE
ELEV IS DRAWN
ELEV INDICATED
CASEWORK
TAG, REF.
CASEWORK
SECTION
SHEETS
CASEWORK
SECTION
IDENTIFICATION
NUMBER
1i
AB ABOVE
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
ALUM ALUMINUM
APPROX, APP APPROXIMATELY
ATFP, AT/FP ANTI-TERRORISM/FORCE PROTECTION
AWC ACOUSTICAL WALL COVERING
BLDG BUILDING
BM BENCH MARK
BRG BEARING
BTM BOTTOM
C CENTERLINE
CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CFOI CONTRACTOR FURNISHED, OWNER INSTALLED
CJ CONTROL JOINT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DTL DETAIL
DWR DRAWER
EJ, EXP JT EXPANSION JOINT
ELEC ELECTRICAL
ELEV ELEVATION
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXIST, EXSTG EXISTING
EXT, EXTR EXTERIOR
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTINGUISHER CABINET
FF, FIN FLR FINISH FLOOR
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIO FOR INFORMATION ONLY
F FLOW LINE
GA GAUGE
GI GALVANIZED IRON
GWB, GYP BD GYPSUM BOARD
HC, HDCP HANDICAPPED (ACCESSIBLE)
HD HEAD
HDWR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
INSUL INSULATION
INT, INTR INTERIOR
JST JOIST
JT JOINT
LAM LAMINATE
LAV LAVATORY
LP LIGHT POLE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MFR, MFG MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OPNG OPENING
OPP OPPOSITE
PL PLATE
PLYWD PLYWOOD
R RADIUS OR RISER
RE:, REF REFER
REINF REINFORCING / REINFORCED
REQD REQUIRED
RI ROUGH IN
RM ROOM
RO ROUGH OPENING
SB SMART BOARD
SC SOLID CORE
SCHED SCHEDULE / SCHEDULED
SIM SIMILAR
SJ SCORED JOINT
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STL STEEL
STRUCT STRUCTURAL
TB TACK BOARD
TOC TOP OF CURB
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
WD WOOD
L
L
SHEET WHERE
DETAIL IS DRAWN
DETAIL INDICATED
EXISTING WALL
GYPSUM SHEATHING
A101
SIM
A101
SIM
A101
SIM
A101
SIM
NOTE: ADDITIONAL SYMBOLS/ABBREVIATIONS NOT SHOWN OR DEFINED WITHIN THIS SHEET MAY OCCUR AND ARE DEFINED ON OTHER DRAWINGS.
3-DIMENSIONAL
ISOMETRIC
VIEW REF.
3-DIMENSIONAL
CAMERA/
PERSPECTIVE
VIEW REF.
3-DIMENSIONAL
ISOMETRIC NORTH
ARROW SYMBOL
PLAN
NORTH
1/A101
1/A101
SHEET WHERE
VIEW IS DRAWN
VIEW INDICATED
GENERAL
DIRECTION OF
VIEW
SHEET WHERE
VIEW IS DRAWN
VIEW INDICATED
GENERAL
DIRECTION OF
VIEW
SYMBOLS LEGEND
A-201
L8
A-201
L8
S
TA
TE
OF OKLAHO
M A
L
IC
ENSED ARCHIT
EC
T
BRIAN
BOURN
A08515
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
3817 NW EXPRESSWAY
SUITE 840
OKLAHOMA CITY, OK 73112
(405) 722-7270
Larson Design Group
MAY 28, 2026
A u to d e s k D o c s
/U S
A C
E F t W o rt h
B H a n g a r
D o o r
E x p a n s io n
F t H o o d /B
H a n g a r
D o o r
E x p a n s io n
R
A rc h .r v t
/2
/2
:3
:2
P
M
G-002
S H
E E
T I
N D
E X
S
Y M
B O
L S
A N
D A
B B
R E
V
IA
T
IO
N S
F O
R T
H O
O D
T
X F
O R
T W
O R
T H
D
IS
T R
IC
T
T
A Y
L O
R S
T F
O R
T W
O R
T H
T
X
L A
R S
O N
D E
S
IG
N G
R O
U P
N
W E
X P
R E
S S
W A
Y S
U
IT
E
O K
L A
H O
M A
C
IT
Y O
K
B B
O U
R N
B B
O U
R N
T K
U R
G A
N
B H
U N
T E
R
M A
Y
W G
B
A
B H
A N
G A
R D
O O
R E
X P
A N
S
IO
N
H A
D E
S M
IS
S
IO
N
S U
P P
O R
T
NUMBER NAME
GENERAL
G-001 COVER SHEET
G-002 SHEET INDEX, SYMBOLS AND ABBREVIATIONS
G-003 ACCESSIBILITY REQUIREMENTS
G-004 GENERAL CONVENTIONS
LIFE SAFTEY
LP001 LIFE SAFETY CODE COMPLIANCE PLAN
LP101 LIFE SAFETY FLOOR PLAN - OVERALL
CIVIL
GC001 GENERAL NOTES
CD101 DEMOLITION PLAN
CS101 SITE PLAN
CS102 PROJECT LOCATION AND STAGING AREA MAP
CS501 SITE DETAILS
STRUCTURAL
S-001 GENERAL STRUCTURAL NOTES, DESIGN LOADS & ABBREVIATIONS
S-002 GENERAL STRUCTURAL NOTES
SD101 DEMO FOUNDATION PLAN AREA - HA, HB, HC & HD
SD102 ENLARGED DEMO FLOOR PLAN AREA HB & HC
SD201 DEMO ELEVATION PLAN AREA HB & HC
SD202 ENLARGED DEMO ELEVATION PLAN - AREA HB
SD203 ENLARGED DEMO ELEVATION PLAN - AREA HC
S-101 OVERALL NEW FOUNDATION PLAN
S-102 ENLARGED NEW FOUNDATION PLAN
S-111 OVERALL NEW CATWALK FRAMING PLAN - AREA HB & HC
S-112 NEW CATWALK FRAMING PLAN - AREA HB
S-113 NEW CATWALK FRAMING PLAN - AREA HC
S-121 OVERALL ROOF FRAMING PLAN
S-122 NEW FRAMING PLAN - AREA HB
S-123 NEW FRAMING PLAN - AREA HC
S-200 NEW CONSTRUCTION OVERALL ELEVATION AREA HB & HC
S-201 ENLARGED NEW CONSTRUCTION ELEVATION AREA - HB
S-202 ENLARGED NEW CONSTRUCTION ELEVATION AREA - HC
S-203 OVERALL INTERIOR FRAMING ELEVATION AREA - HB & HC
S-204 ENLARGED INTERIOR FRAMING ELEVATION - AREA HB
S-205 ENLARGED INTERIOR FRAMING ELEVATION - AREA HC
S-206 NEW CATWALK FRAMING ELEVATIONS AND SECTION
S-301 STRUCTURAL SECTIONS
S-500 CONCRETE DETAILS
S-501 TYPICAL STRUCTURAL DETAILS
S-502 STRUCTURAL DETAILS
S-503 STRUCTURAL DETAILS
S-504 STRUCTURAL DETAILS
S-505 STRUCTURAL DETAILS
S-506 STRUCTURAL DETAILS
S-901 STRUCTURAL FRAMING ISOMETRIC
ARCHITECTURAL
AD101 DEMOLITION FIRST FLOOR PLAN
AD301 DEMOLITION BUILDING ELEVATION
A-101 FIRST FLOOR PLAN - OVERALL
A-104 FIRST FLOOR PLAN - AREA HA
A-105 FIRST FLOOR PLAN - AREA HB
A-106 FIRST FLOOR PLAN - AREA HC
A-107 FIRST FLOOR PLAN - AREA HD
A-109 FIRST FLOOR PLAN - OVERALL - VEHICLE TOW PLAN
A-111 HANGAR REFLECTED CEILING PLAN
A-113 HANGAR CATWALK ENLARGED PLAN
A-201 EXTERIOR ELEVATIONS
A-310 WALL SECTIONS
A-311 WALL SECTIONS
A-601 DOOR SCHEDULE
INTERIORS
I-100 OVERALL FINISH FLOOR PLAN
I-110 OVERALL SIGNAGE PLAN
I-114 OVERALL STRIPING PLAN
I-501 FINISH DETAILS
I-502 SIGNAGE DETAILS
I-601 FINISH MATERIAL COLOR LEGEND
NUMBER NAME
FIRE PROTECTION
FA001 GENERAL FIRE ALARM INFORMATION
FAD101 FIRE ALARM DEMO FLOOR PLAN - HB
FAD102 FIRE ALARM DEMO FLOOR PLAN - HC
FA101 FIRE ALARM FLOOR PLAN - OVERALL
FA102 FIRE ALARM FLOOR PLAN - HB
FA103 FIRE ALARM FLOOR PLAN - HC
FP001 GENERAL FIRE PROTECTION INFORMATION
FP101 FIRE PROTECTION FLOOR PLAN - OVERALL
PLUMBING
P-001 PLUMBING LEGEND
PD100 DEMOLITION PLAN - PLUMBING - OVERALL
PD101 DEMOLITION PLAN - PLUMBING - AREA HB
PD102 DEMOLITION PLAN - PLUMBING - AREA HC
P-100 FLOOR PLAN - PLUMBING - OVERALL
P-101 FLOOR PLAN - PLUMBING - AREA HB
P-102 FLOOR PLAN - PLUMBING - AREA HC
P-301 PLUMBING SECTION
P-501 PLUMBING DETAILS
P-601 PLUMBING SCHEDULES
ELECTRICAL
E-000 LEGEND, ABBREVIATIONS & NOTES
ED101 FLOOR PLAN - DEMO - OVERALL
ED501 DEMO ELECTRICAL SCHEDULES
E-101 FLOOR PLAN - POWER - OVERALL
E-102 FLOOR PLAN - POWER - AREA A
E-103 FLOOR PLAN - POWER - AREA B
E-104 FLOOR PLAN - POWER - AREA HA
E-105 FLOOR PLAN - POWER - AREA HB
E-106 FLOOR PLAN - POWER - AREA HC
E-107 FLOOR PLAN - POWER - AREA HD
E-201 ELEVATION - POWER - AREA HB
E-202 ELEVATION - POWER - AREA HC
E-501 ELECTRICAL SCHEDULES
E-601 EXISTING ONE-LINE DIAGRAM
E-602 HANGAR DOOR ELECTRICAL LOAD DIAGRAM
TOTAL SHEETS IN SET: 95
FRONT APPROACHES
NOTE: X=12 IN. IF DOOR HAS
BOTH A CLOSER AND LATCH
PUSH SIDE
PULL SIDE
NOTE: Y=48 IN. MIN. IF DOOR HAS
CLOSER
LATCH SIDE APPROACHES
NOTE: X=54 IN. MIN. IF DOOR
HAS CLOSER
PUSH SIDE
PULL SIDE
IBC/ANSI/ADAAG - ACCESSIBLE ROUTE
(TYPICAL FOR ALL DOORS)
M
IN
M
IN
. 18"
MIN.
X
24"
MIN.
X
M
IN
Y
M
IN
24"
MIN.
X=42 IN. MIN. IF Y=54 IN.
NOTE: Z=48 IN. MIN. IF DOOR HAS
BOTH A CLOSER AND LATCH.
NOTE: X=36 IN. MIN. IF Y=60 IN.
HINGE SIDE APPROACHES
PUSH SIDE
PULL SIDE
X Y
Z
M
IN
54" MIN.
T-TURN FOR
WHEELCHAIR ACCESS
ACCESSIBLE ELEMENT
60" WHEELCHAIR
TURNING AREA
ACCESSIBLE PARKING
SPACE FOR CARS OR
VANS OR ACCESSIBLE
SEAT
ACCESSIBLE ENTRANCE
ACCESSIBLE ROUTE TO
ACCESSIBLE
ENTRANCES OR
FACILITIES
LEGEND
AREA OF REFUGE
HC
AR
IBC/ANSI/ADAAG SECTION 308 - ADULT REACH RANGES
OBSTRUCTED FORWARD REACHUNOBSTRUCTED FORWARD REACH OBSTRUCTED FORWARD REACH
M
IN
M A
X
20"
MAX.
M A
X
M A
X
25"
MAX.
M A
X
M A
X
OBSTRUCTED SIDE REACHUNOBSTRUCTED SIDE REACH OBSTRUCTED SIDE REACH
M
IN
M A
X
10"
MAX.
M A
X
M A
X
24"
MAX.
M A
X
M A
X
TYPICAL HANDICAP ACCESSIBLE MOUNTING HEIGHTS ABOVE FINISH FLOOR
DIMENSION NAME ELEMENT
DRINKING FOUNTAIN (STANDING) 602.4 SPOUT HT.M1
MOUNTING HEIGHT REFERENCE ABOVE F.F. ADDITIONAL COMMENTS
602.4 SPOUT HT.M2
GRAB BAR AT TOILET - 18" VERTICAL 604.5 TO BOTTOM OF RAILM3
GRAB BARS AT TOILET - HORIZONTAL 604.9 & 609.4 TO TOP SURFACE OF RAILM4 THE GRAB BAR ON REAR WALL OF NON-ADULT TOILETS CAN BE SPLIT WHEN IT CONFLICTS WITH WATER
VALVE
HANDRAILS 505.4 TO TOP SURFACE OF RAILM5A M5A = ADULT DIMENSION, DIMENSION OF SECOND HANDRAIL TO F.F.
LAVATORY 606.3 TO HIGHEST POINT OF LAVATORY
RIM OR COUNTER
M6
MIRROR 606.3M7
MIRROR ABOVE LAVATORY 606.3M8
TOILET PAPER DISPENSOR 604.7 & 604.10 TO BOTTOM OF DISPENSER OUTLETM9
URINAL 605 TO RIM, 13-1/2" MIN PROJECTIONM10
URINAL FLUSH CONTROLS 605.4 & 309 TO TOP OF CONTROLM11
TOILET SEAT HEIGHT 604.4M12
WATER CLOSET FLUSH CONTROLS 604.6 LOCATED ON WHEELCHAIR SIDEM13
DRINKING FOUNTAIN (WHEELCHAIR)
ANSI A117.1
GUIDELINE
REFERENCE
TO BOTTOM EDGE OF REFLECTING SURFACE
TO BOTTOM EDGE OF REFLECTING SURFACE
WATER CLOSET CENTERLINE FROM WALL 604.2 WALL TO CENTERLINE OF WATER CLOSETP1
FIRE EXTINGUISHER 308 TO RELEASE CLAMP
FOR SPOUT 30" OR LESS, 24" KNEE AND 12" TOE CLEARANCE NOT REQUIRED IF PARALLEL APPROACH IS
PROVIDED
HANDICAP ACCESSIBILITY ANALYSIS
I. APPLICABLE CODES AND CRITERIA
IN ORDER TO PROVIDE THE BEST
ACCESSIBILITY, THE MOST
STRINGENT REQUIREMENTS OF
THE GUIDELINES BELOW HAVE
BEEN EMPLOYED IN THIS DESIGN.
INTERNATIONAL BUILDING CODE
2018 (IBC) INTERNATIONAL CODE
COUNCIL / AMERICAN NATIONAL
STANDARDS INSTITUTE ICC / ANSI
A117.1 - 2003
ARCHITECTURAL BARRIERS ACT
(ABA) STANDARD (DESIGN
REQUIREMENTS MANUAL, SECTION
1.9)
A.
B.
II. PROJECT SCOPE
A. REMODEL
III. PRIMARY USER GROUPS
A. ADULTS
IV. ASSEMBLY SEATING ANALYSIS -
NOT APPLICABLE
S
TA
TE
OF OKLAHO
M A
L
IC
ENSED ARCHIT
EC
T
BRIAN
BOURN
A08515
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
3817 NW EXPRESSWAY
SUITE 840
OKLAHOMA CITY, OK 73112
(405) 722-7270
Larson Design Group
MAY 28, 2026
A u to d e s k D o c s
/U S
A C
E F t W o rt h
B H a n g a r
D o o r
E x p a n s io n
F t H o o d /B
H a n g a r
D o o r
E x p a n s io n
R
A rc h .r v t
/2
/2
:3
:2
P
M
G-003
A C
C E
S S
IB
IL
IT
Y
R E
Q U
IR
E
M E
N T
S
F O
R T
H O
O D
T
X F
O R
T W
O R
T H
D
IS
T R
IC
T
T
A Y
L O
R S
T F
O R
T W
O R
T H
T
X
L A
R S
O N
D E
S
IG
N G
R O
U P
N
W E
X P
R E
S S
W A
Y S
U
IT
E
O K
L A
H O
M A
C
IT
Y O
K
B B
O U
R N
B B
O U
R N
T K
U R
G A
N
B H
U N
T E
R
M A
Y
W G
B
A
B H
A N
G A
R D
O O
R E
X P
A N
S
IO
N
H A
D E
S M
IS
S
IO
N
S U
P P
O R
T
10'-6"
TYPICAL RULES FOR DETERMINING MOUNTING HEIGHTS, LOCATIONS AND CONFIGURATIONS
GRID
C
C
RULE 1 RULE 3
RULE 7
RULE 2
RULE 5 RULE 6
RULE 4
RULE 8
WHEN COMPLETELY DIMENSIONED ON PLANS NOT DIMENSIONED AND LOCATED ON COLUMN OR PILASTER
NOT DIMENSIONED AND LOCATED ADJ TO DOOR AND ON WALL AGAINST WHICH DOOR SWINGS
NOT DIMENSIONED AND LOCATED ON COLUMN OR PILASTER
NOT DIMENSIONED AND LOCATED ADJ TO MIN STRIKE-SIDE OF DOOR NOT DIMENSIONED AND LOCATED ADJACENT TO DOOR (OR WINDOW)
NOT DIMENSIONED AND LOCATED ON COLUMN OR PILASTER
WHEN NOT DIMENSIONED AND LOCATED ADJACENT TO CHANGE IN WALL DIRECTION
LOCATE ITEMS AS INDICATED WHEN SHOWN DIMENSIONED (BOTH HORIZ AND
VERT) BY A PLAN OR DETAIL PLAN.
SPECIFIC VERT DIMENSIONS SHOWN BY ELEVATIONS, SECTIONAL
ELEVATIONS, OR DETAIL ELEVATIONS AND SPECIFIC HORIZ DIM SHOWN BY
PLANS AND DETAIL PLANS TAKE PRECEDENCE OVER TYPICAL MOUNTING
HEIGHTS AND LOCATION RULES.
NON-TYPICAL MOUNTING HEIGHTS MAY BE INDICATED
BY SYMBOL (AS SHOWN), BY KEYED NOTE, OR BY
NOTATION ON PLANS.
WHEN APPLICABLE, COMBINE THIS RULE WITH RULE 2 (PREVIOUS) TO
SYMMETRICALLY ARRANGE GROUPS OF ITEMS HAVING BOTH DIFFERING AND
SIMILAR MOUNTING HEIGHTS.
WHEN NOT DIMENSIONED AND SHOWN LOCATED ON A COLUMN OR PILASTER,
AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: HORIZ
CENTER GROUP OF SIMILAR ITEMS HAVING THE SAME MOUNTING HEIGHT(S)
ABOUT THE CENTERLINE OF THE COLUMN OR PILASTER.
WHEN NOT DIMENSIONED AND SHOWN LOCATED ADJACENT TO DOOR, AND
WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: MOUNT ITEMS
IN RELATION TO SWING USING TYP OFFSET DIMENSION. VERTICALLY ALIGN
CENTERS OF ITEMS MOUNTED AT DIFFERENT HEIGHTS.
WHEN MULTIPLE ITEMS HAVING THE SAME TYP MOUNTING HEIGHT ARE
INDICATED, MOUNT FIRST ITEM IN RELATION TO SWING USING TYP OFFSET
DIMENSION AND PLACE REMAINING ITEMS ADJACENT TO FIRST ON SIDE
OPPOSITE FRAME AS ILLUSTRATED BY THIS DIAGRAM.
FOR PURPOSES OF THESE RULES, ITEMS SHOWN APPROX. LOCATED WITHIN
4 FEET OF OPEN DOOR ARE CONSIDERED TO BE ADJACENT TO DOOR.
WHEN MULTIPLE ITEMS HAVING THE SAME TYP MTG HGT ARE INDICATED,
MOUNT FIRST ITEM IN RELATION TO FRAME USING TYP OFFSET DIM AND
PLACE REMAINING ADJ TO FIRST ON SIDE OPP FRAME AS ILLUSTRATED BY
THIS DIAGRAM. DO NOT CROWD MULTIPLE ITEMS AGAINST WALL OR
RESTRICTION.
WHEN NOT DIMENSIONED AND SHOWN LOCATED ADJ TO STRIKE SIDE OF DOOR,
AND WHEN STRIKE-SIDE CLEARANCE IS BETWEEN 12 INCHES AND 18 INCHES,
AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: MOUNT
ITEMS IN RELATION TO FRAME USING TYP OFFSET
DIMENSION. VERTICALLY ALIGN CENTERS OF ITEMS MOUNTED AT DIFFERENT
HEIGHTS.
LINE OF WALL OR OTHER
RESTRICTION ON STRIKE-
SIDE OF DOOR.
STRIKE-SIDE OF DOOR.
WHEN MULTIPLE ITEMS HAVING THE SAME TYP MOUNTING HEIGHT ARE
INDICATED, MOUNT FIRST ITEM IN RELATION TO FRAME USING TYP OFFSET
DIMENSION AND PLACE REMAINING ITEMS ADJACENT TO FIRST ON SIDE
OPPOSITE FRAME AS ILLUSTRATED BY THIS DIAGRAM.
SIMILAR RULE APPLIES WHEN ADJACENT TO WINDOW. FOR PURPOSES OF
THESE RULES, ITEMS SHOWN APPROX LOCATED WITHIN 4 FEET OF DOOR ARE
CONSIDERED TO BE ADJACENT TO DOOR (OR WINDOW).
WHEN PROVIDED,
UTILIZE TYP MOUNTING
DIAGRAMS TO
DETERMINE
DIMENSIONS
MULTIPLE ITEMS
AT SAME
HEIGHT
WHEN NOT DIMENSIONED AND SHOWN LOCATED ADJACENT TO DOOR, AND
WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES: MOUNT ITEMS
IN RELATION TO FRAME USING TYP OFFSET DIMENSION. VERTICALLY ALIGN
CENTERS OF ITEMS MOUNTED AT DIFFERENT HEIGHTS.
MULTIPLE ITEMS AT SAME HEIGHT
DOOR WHEN SWUNG AGAINST WALL
WHEN MULTIPLE ITEMS HAVING THE SAME TYP MOUNTING HEIGHT ARE
INDICATED, HORIZONTALLY CENTER GROUP OF ITEMS ON FACE OF COLUMN OR
PILASTER (SEE RULE 3).
WHEN NOT DIMENSIONED AND SHOWN LOCATED ON A COLUMN OR PILASTER,
AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES:
HORIZONTALLY CENTER ITEM ON FACE OF COLUMN OR PILASTER. ALIGN
VERTICALLY CENTERS OF MULTIPLE ITEMS HAVING DIFFERING TYPICAL
MOUNTING HEIGHTS.
ON PLANS, ITEMS TO BE
VERTICALLY ALIGNED MAY BE
SHOWN ADJACENT.
ARRANGE ITEMS AT
SAME HEIGHT
SYMMETRICALLY
ABOUT CENTERLINE
MULTIPLE SIMILAR ITEMS AT SAME HEIGHT
FOR PURPOSES OF THESE RULES, ITEMS SHOWN APPROX LOCATED WITHIN 4
FEET OF PLANE CHANGE ARE CONSIDERED TO BE ADJACENT TO CHANGE IN
PLANE.
WHEN MULTIPLE SIMILAR ITEMS HAVING THE SAME TYP MTG HEIGHT ARE
INDICATED, MOUNT FIRST ITEM IN RELATION TO PLANE CHANGE USING TYP
OFFSET DIMENSION AND PLACE REMAINING ITEMS ADJACENT TO FIRST ON SIDE
OPPOSITE PLANE CHANGE AS ILLUSTRATED BY THIS DIAGRAM.
WHEN NOT DIMENSIONED AND SHOWN LOCATED ADJ TO CHANGE IN PLANE OF
WALL, AND WHEN NO OTHER TYP CONFIGURATION DIAGRAM APPLIES: MOUNT
ITEMS IN RELATION TO PLANE CHANGE USING TYP OFFSET DIM. VERTICALLY
ALIGN CENTERS OF ITEMS MOUNTED AT DIFFERENT HEIGHTS.
WHEN APPLICABLE, COMBINE THIS RULE WITH RULE 2 AND/OR RULE 3 (PREVIOUS)
TO SYMMETRICALLY ARRANGE GROUPS OF ITEMS HAVING DIFFERING, SIMILAR,
AND CONFLICTING MOUNTING HEIGHTS.
WHEN NOT DIMENSIONED AND SHOWN LOCATED ON A COLUMN OR PILASTER,
AND WHEN NO OTHER TYPICAL CONFIGURATION DIAGRAM APPLIES:
HORIZONTALLY CENTER GROUP OF DISSIMILAR ITEMS HAVING CONFLICTING
MOUNTING HEIGHT(S) ABOUT THE CENTERLINE OF THE COLUMN OR PILASTER.
GRID
ARRANGE ITEMS AT
CONFLICTING HEIGHTS
SYMMETRICALLY ABOUT
CENTERLINE
GRID GRID
ARCHITECTURAL DIMENSIONING CONVENTIONS
DIMENSION ON PLANS
EQ EQ
EQ EQ
6".
EQ EQ
EQEQ
18" MIN. SWING SIDE
12" MIN. OPP. SWING SIDE
3" MIN.
8" TYP. 8" TYP.
4'-0". 4'-0". DOOR SWING
8" TYP.
8" TYP.
4'-0".
EQ EQ
EQEQEQEQEQEQ
1. EXCEPT WHERE DIRECTED TO PLACE ITEMS OF THE WORK
AT THE "APPROXIMATE LOCATION SHOWN," DO NOT SCALE
THE DRAWINGS FOR DIMENSIONAL INFORMATION.
2. ALL ELEMENTS OF THE DRAWINGS MAY NOT BE DRAWN TO
EXACT SCALE. ALL DIMENSIONS REQUIRED ARE SHOWN (OR
MAY BE DERIVED FROM THOSE SHOWN OR NOTED) ONT HE
FLOOR PLANS, DETAIL PLANS, ELEVATIONS, SECTIONS,
SCHEDULES, CONFIGURATION DETAILS AND SPECIFICATIONS.
SEE THE NOTES BELOW AND "SYMBOLS AND
ABBREVIATIONS" SHEET FOR DIMENSIONING, GRAPHIC AND
OTHER TYPICAL CONVENTIONS USED ON THIS PROJECT.
3. EXCEPT WHERE SPECIFICALLY NOTED TO THE CONTRARY,
ALL DIMENSIONS SHOWN ON THE ARCHITECTURAL
DRAWINGS CONFORM TO THE FOLLOWING CONVENTIONS:
A. GENERALLY, DIMENSIONS ARE MEASURED TO:
• STRUCTURAL OR DIMENSIONAL GRID LINES.
• CENTERLINE OF STUD (EXCLUSIVE OF GWB,
AND ANY APPLIED FINISHES HAVING
THICKNESS WHICH MAY BE ADDED TO SUCH
WALLS) AT PARTITIONS FRAMED WITH METAL
STUDS. REFER TO "PARTITION TYPES"
SCHEDULE TO DETERMINE THICKNESS OF
EACH PARTITION TYPE.
• FACE OF CONCRETE OR MASONRY WALL
(EXCLUSIVE OF ANY FURRING OR APPLIED
FINISHES HAVING THICKNESS WHICH MAY BE
ADDED TO SUCH WALLS) AT WALLS WITH
CONCRETE OR MASONRY COMPONENTS.
REFER TO STRUCTURAL DRAWINGS AND
"PARTITION TYPES" SCHEDULE TO DETERMINE
THICKNESS OF EACH PARTITION TYPE.
• FACE OF APPLIED FINISH IF NOTED AS A "FACE
OF FINISH" OR "CLEAR" DIMENSION. SEE NOTE
'B' BELOW.
• OUTSIDE EDGE OF HOLLOW METAL DOOR
AND WINDOW FRAMES. REFER TO THE
"DOOR SCHEDULE" AND "FRAME ELEVATIONS"
FOR ADDITIONAL DIMENSIONAL INFORMATION.
• INSIDE EDGE OF FINISHED WALL OPENING AT
OTHER DOORS, WINDOWS AND CURTAIN
WALLS. REFER TO THE "DOOR SCHEDULE"
AND "FRAME ELEVATIONS" FOR ADDITIONAL
DIMENSIONAL INFORMATION.
• DIMENSION OR WORK POINTS AS INDICATED
ON RELATED ARCH DETAIL, PLAN, SECTION,
ELEVATION, LAYOUT OR CONFIGURATION
DETAIL, OR CONSTRUCTION DETAIL.
B. WHERE "FACE OF FINISH" OR "CLEAR"
DIMENSIONS ARE SPECIFICALLY NOTED, THE
DIM IS MEASURED TO:
• FINISH FACES AT THE MOST NARROW OR
CONSTRICTED POINT OF SECTION WHERE
DIMENSION IS SHOWN, WHEN THE DIMENSION
OCCURS ACROSS AN OPEN SPACE. IN THIS
CASE, A "FACE OF FINISH" DIMENSION IS
EQUIVALENT TO A "CLEAR" DIMENSION.
• FINISH FACES AT THE WIDEST OR MOST
EXPANSIVE POINTS OF THE SECTION THE
DIMENSION IS SHOWN WHEN THE DIMENSION
OCCURS ACROSS AN OBJECT OR GROUP OF
OBJECTS.
C. WHERE "EQUAL" DIMENSIONS ARE USED:
• IN CASEWORK AND OTHER SUCH ELEMENTS, "EQUAL"
DIMENSIONS ARE NOT INTENDED TO REQUIRE CUSTOM
COMPONENTS. SUCH "EQUAL" ELEMENTS SHALL BE THE
SAME SIZE, AT THE STANDARD SIZE INCREMENT THAT
MOST NEARLY EQUALS THE DESIGNED OVERALL
DIMENSION. IN THESE CONDITIONS, EQUAL SIZE FILLER
PANELS ARE INTENDED AND REQUIRED AT EACH END OF
THE RUN.
D. WHERE "EQUAL" DIMENSIONS ARE USED ON
REFLECTED CEILING PLANS TO LOCATE CEILING
GRID WORK POINTS, MEASURE DIMENSIONS TO:
• EDGE OF THE INDICATED CEILING AT THE FACE OF THE
ADJACENT APPLIED FINISH, MEASURED AT THE PLANE OF
THE CEILING.
• CAUTION: DUE TO THE POSSIBLE APPLICATION OF APPLIED
FINISHES (THE THICKNESS OF WHICH MAY VARY BETWEEN
FLOOR AND CEILING AND IS NOT ACCOUNTED FOR BY THE
DIMENSIONS SHOWN ON THE FLOOR PLANS, EXCEPT AS
INDICATED BY "FACE OF FINISH" OR "CLEAR"), THE
CONTRACTOR MUST ADJUST, AS NECESSARY, THE FLOOR
PLAN DIMENSIONS TO REFLECT THE ACTUAL DIMENSIONS
FOUND AT THE PLANE OF THE CEILING.
4. WHERE WALLS AND/OR PARTITIONS OF UNEQUAL
THICKNESS ABUT, ALIGN EXPOSED FACES, UNLESS
OTHERWISE NOTED.
5. WHERE DIMENSIONS ARE NOT PROVIDED ON FLOOR
PLANS TO LOCATE DOOR OPENINGS, APPLY THE
FOLLOWING RULES IN ORDER, TO DETERMINE THE
LOCATION OF DOOR OPENINGS:
A. DOOR OPENINGS MAY BE DIMENSIONED ON
DRAWINGS OTHER THAN THE FLOOR PLANS.
REFER TO THE SECTIONS, ELEVATIONS, DETAILS
AND DOOR SCHEDULE NOTES FOR ADDITIONAL
DIMENSIONAL INFORMATION.
B. WHERE THE HINGE-SIDE OF A DOOR IS SHOWN ADJACENT
TO A WALL, OR WALLS, PERPENDICULAR TO THE WALL IN
WHICH THE DOOR OPENING OCCURS:
• AT DOORS OCCURRING IN METAL FRAMED GYPSUM BOARD
PARTITIONS, LOCATE THE HINGE-SIDE OF THE DOOR
FINISHED OPENING 4 INCHES FROM THE FACE (EXCLUSIVE
OF APPLIED FINISHES) OF THE CLOSEST PERPENDICULAR
WALL OR PARTITION ASSEMBLY.
• AT DOORS OCCURRING IN WALLS OF CONCRETE OR
CONCRETE MASONRY CONSTRUCTION, LOCATE THE
HINGE-SIDE OF THE DOOR FINISHED OPENING 10 INCHES
FROM THE FACE (EXCLUSIVE OF APPLIED FINISHES) OF
THE CLOSEST PERPENDICULAR WALL OR PARTITION
ASSEMBLY.
C. WHERE DOOR OCCURS NOT ADJACENT TO A
PERPENDICULAR WALL, AND EITHER "DIM E" OR "DIM F" IS
16'-0" OR LESS, LOCATE DOOR UTILIZING THE FOLLOWING
MINIMUM DIMENSIONS:
• DIMENSION A = 18 INCHES MIN
• DIMENSION B = 12 INCHES MIN
• DIMENSIONS C = DOOR WIDTH + 2 INCHES MINIMUM
• DIMENSION D = 4 INCHES MIN AT METAL
FRAMED GYP BD PARTITIONS
• DIMENSIONS E AND F = AS SHOWN ON PLANS
• DIMENSION G = 36 INCHES MIN
• DIMENSION H = 60 INCHES MIN
• IF SPACE ALLOWS, CENTER DOOR IN WALL SHOWN ON THE DRAWINGS SO
THAT EITHER "DIM A" EQUALS "DIM C", OR "DIM B" EQUALS "DIM D".
D. IF "DIM E" IN DIAGRAMS BELOW IS LESS THAN THE SUM OF 2 TIMES THE DOOR
WIDTH PLUS 20 INCHES, LOCATE DOOR SO THAT MINIMUMS STATED BY NOTE 4C
ABOVE FOR "DIM A", "DIM B", AND "DIM D" ARE MET, MAXIMIZING "DIM A" AND
MINIMIZING "DIM D" TO THE EXTENT POSSIBLE.
MEASURED AT CLG PLANE
"EQUAL" DIM AT CEILING
MEASURED TO FACE OF PTN
TYP. DIM ON CEILING PLAN
4".
4".
A
E
C G
B D
F
H
E
A
B D
E
A D
B
ALIGN
10".
10".
S
TA
TE
OF OKLAHO
M A
L
IC
ENSED ARCHIT
EC
T
BRIAN
BOURN
A08515
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
3817 NW EXPRESSWAY
SUITE 840
OKLAHOMA CITY, OK 73112
(405) 722-7270
Larson Design Group
MAY 28, 2026
A u to d e s k D o c s
/U S
A C
E F t W o rt h
B H a n g a r
D o o r
E x p a n s io n
F t H o o d /B
H a n g a r
D o o r
E x p a n s io n
R
A rc h .r v t
/2
/2
:3
:3
P
M
G-004
G E
N E
R A
L C
O N
V E
N T
IO
N
S
F O
R T
H O
O D
T
X F
O R
T W
O R
T H
D
IS
T R
IC
T
T
A Y
L O
R S
T F
O R
T W
O R
T H
T
X
L A
R S
O N
D E
S
IG
N G
R O
U P
N
W E
X P
R E
S S
W A
Y S
U
IT
E
O K
L A
H O
M A
C
IT
Y O
K
B B
O U
R N
B B
O U
R N
T K
U R
G A
N
B H
U N
T E
R
M A
Y
W G
B
A
B H
A N
G A
R D
O O
R E
X P
A N
S
IO
N
H A
D E
S M
IS
S
IO
N
S U
P P
O R
T
PROJECT DATA AND CODE INFORMATION
PROJECT DATA
APPLICABLE CODES
LIFE SAFETY INFORMATION
USE OR OCCUPANCY CLASSIFICATION
TYPE OF CONSTRUCTION
REFERENCE
PROJECT NAME
PROJECT ADDRESS
OWNER
DOD BUILDING CODEUFC 1-200-01, CHANGE 4
US ARMY CORPS OF ENGINEERS
FORT HOOD, TX
B90176 HANGAR DOOR EXPANSION - HADES MISSION SUPPORT
OCCUPANCY (OCCUPANT LOAD)
CONSTRUCTION TYPE
BEARING WALLS: INT./EXT.
FIRE PROTECTION REQUIREMENTS REQUIRED PROVIDED
AIRCRAFT HANGAR, AIRCRAFT STORAGE AND SERVICING AREAS
IIB (SPRINKLERED, SINGLE-STORY)
UFC 3-600-01 TABLE 10-1
2024 IBC, SECTION 602
DESIGN LIMITATIONS
NONBEARING WALLS: INT./EXT.
ROOF / CEILING
FLOOR / CEILING
HANGAR SEPARATIONS
0 HR. / 0 HR.
0 HR. / 0 HR. 0 HR. / 0 HR.
0 HR. / 0 HR.
0 HR. / 1 HR. 0 HR. / 0 HR.
1 HR. 1 HR. & 0 HR.
2024 IBC, SECTION 602
2024 IBC, SECTION 602
2024 IBC, SECTION 602
2024 IBC, SECTION 602
UFC 4-211-01 section 3-3.1.3
MEANS OF EGRESS
HEIGHT
AREA
STORIES
TRAVEL DISTANCE TO EXIT
OCCUPANT LOAD
MAX. ALLOWED PROVIDED
MAX. ALLOWED PROVIDED
75'-0"
UNLIMITED
71'-0"
121,200 SQ. FT.
2024 IBC, TABLE 504.3
2024 IBC, SECTION 507.4
2024 IBC, SECTION 507.4
250'-0"
PERSONS
NFPA 101 SECTION 40.2.6
UFC 3-600-01 TABLE 10-1
0 HR. / 0 HR. 0 HR. / 0 HR.
HANGAR BAY HANGAR BAY
224'-0"
2025 EDITION NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE
EGRESS WIDTH PER OCCUPANT
STAIRS
DOORS
MIN. ALLOWED PROVIDED
N/A
32"
N/A
NFPA 101 SECTION 7.3.4.1(2)
NFPA 101 TABLE 7.3.3.1
HIGH-HAZARD
36"
(33" CLEAR)
PROJECT DATA
LIFE SAFETY CODE2024 EDITION NFPA 101
II (000) NFPA 220 TABLE 4.1.1 AS
REFERENCED BY NFPA 101 SECTION
8.2.1.2
HIGH-HAZARD
AIRCRAFT MAINTENANCE HANGARSUFC 4-211-01, CHANGE 3
FIRE PROTECTION ENGINEERING FOR FACILITIES UFC 3-600-01, CHANGE 6
DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGSUFC 4-010-01, CHANGE 3
DESIGN AND O&M: MASS NOTIFICATION SYSTEMSUFC 4-021-01, DATED 04/09/2008
STANDARD ON TYPES OF BUILDING CONSTRUCTION2024 EDITION NFPA 220
STANDARD ON AIRCRAFT HANGARS2022 EDITION NFPA 409
STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS2025 EDITION NFPA 13
OCCUPANCY (MEANS OF EGRESS)
2024 EDITION IBC INTERNATIONAL BUILDING CODE
2024 EDITION IEBC INTERNATIONAL EXISTING BUILDING CODE
TRAVEL DISTANCE TO HANGAR EXITS 150'-0" NFPA 101 SECTION 40.6.2.2
OCCUPANCY (CONSTRUCTION
TYPE )
GENERAL INDUSTRIAL
NFPA 101 CHAPTER 7
IBC SECTION 311.2
S-1 STORAGE
FIRE CODE2024 EDITION NFPA 1
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
IT
R
IN
E -O
L S
S O
N J
V
A u to d e s k D o c s
/U S
A C
E F t W o rt h
B H a n g a r
D o o r
E x p a n s io n
F t H o o d /B
H a n g a r
D o o r
E x p a n s io n
R
F ir e .r v t
/2
/2
:3
:2
A
M
LP001
L
IF
E S
A F
E T
Y C
O D
E C
O M
P L
IA
N C
E P
L A
N
F O
R T
H O
O D
T
X F
O R
T W
O R
T H
D
IS
T R
IC
T
T
A Y
L O
R S
T F
O R
T W
O R
T H
T
X
C
IT
R
IN
E -O
L S
S O
N G
R A
N D
A V
E G
R A
N D
J U
N C
T
IO
N C
O
J W
H
IT
C O
M B
N C
H A
P A
P T
U R
N E
R
M A
Y
W G
B
A
B H
A N
G A
R D
O O
R E
X P
A N
S
IO
N
H A
D E
S M
IS
S
IO
N
S U
P P
O R
T
W G
F
THIS PROJECT CONSISTS OF THE REPLACEMENT OF TWO EXISTING ROLLING SECTIONAL HANGAR DOORS WITH NEW 120-FOOT-WIDE VERTICAL LIFT FABRIC DOORS. THE HANGAR WAS ORIGINALLY DESIGNED FOR HOUSING UNMANNED AERIAL SYSTEMS AND WILL BE RENOVATED WITH LARGER HANGAR BAY DOORS TO ACCOMMODATE THE ME-11B AIRCRAFT. ALL AREAS OUTSIDE OF HANGAR BAYS ARE OUT OF SCOPE.
05/28/2026
2.1
3.8
7.1
141 FT NEW EXIT SPACING 140 FT NEW EXIT SPACING
A D E F G H J K L M N P Q RC.8 S
192 FT.
OCCUPANT LOAD: 184
SUPPORT AREA NOT IN SCOPE OF WORK
36"
EXISTING EXIT
36"
EXISTING EXIT
36"
EXISTING EXIT
36"
EXISTING EXIT
36"
EXISTING EXIT
36"
EXISTING EXIT
36"
36"
36"
EXISTING EXIT
224 FT.
EXIT EXITEXIT EXIT EXIT
E X
IT
E
X
IT
E X
IT E
X
IT
E
X
IT
E X
IT
FEB
FEB
FEB
FEB
EXIT
36"
NEW EXIT
EXIT TO BE DEMOLISHEDEXIT TO BE DEMOLISHED
NEW EXIT NEW EXIT
EGRESS LEGEND
START OF COMMON PATH AND
TRAVEL DISTANCE
END OF COMMON PATH
TRAVEL DISTANCE
DEAD END PATH
PATH OF EXIT
X
XX"
XXX
MAX EXPECTED OCCUPANTS AT EXIT
BASED ON OCCUPANT LOAD FACTOR
ACTUAL WIDTH OF EXIT
MAX ALLOWABLE OCCUPANTS AT
EXIT BASED ON EXIT WIDTH
EGRESS DATA
OCCUPANCY EXIT ROUTE TYPE
MAXIMUM
ALLOWABLE
100'-0"COMMON PATH (NFPA 101 SECTION 40.2.5)
SYMBOLS LEGEND
MAXIMUM TRAVEL DISTANCE TO EXIT
(NFPA 101 SECTION 40.2.6)
250'-0"
FIRE EXTINGUISHER IN SEMI-RECESSED
FIRE EXTINGUISHER CABINET
WALL BRACKET - MOUNTED FIRE
EXTINGUISHER
REFER TO ELECTRICAL SHEETS FOR EMERGENCY LIGHT
AND EXIT LIGHT SCHEDULES AND DETAILS.
FEB
REFER TO ARCHITECTURAL SHEETS FOR FIRE
EXTINGUISHER CABINET SCHEDULES AND DETAILS.
WALL MOUNTED EMERGENCY LIGHT
WITH BATTERY PACK
EXIT LIGHT FIXTURE DIRECTION
ARROWS AS SHOWN (SHADED
QUADRANT INDICATES FACE(S) OF
FIXTURE)
WALL MOUNTED EMERGENCY LIGHT
WITH BATTERY PACK
FEC
EXISTING 1 HOUR FIRE BARRIER
OCCUPANT LOAD
OCCUPANCY FUNCTION AREA (SF)
APPROXIMATE
CODE OCCUPANT LOAD
FACTOR (SF/PERSON)
OCCUPANT
LOAD
AIRCRAFT HANGAR, AIRCRAFT STORAGE AND SERVICING
AREAS (UFC 3-600-01 TABLE 10-1)
92,000 500 GROSS 184
NOT IN SCOPE OF WORK
HATCH PATTERN
NOTE: ALL EXISTING AREAS OUTSIDE OF THE HANGAR BAYS ARE OUT OF SCOPE OF WORK AND ARE NOT INCLUDED IN THE OCCUPANT LOAD
FACTORS FOR THE HANGAR BAY.
HB HC
HDHA
A B
N
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
KEY PLAN
C
IT
R
IN
E -O
L S
S O
N J
V
A u to d e s k D o c s
/U S
A C
E F t W o rt h
B H a n g a r
D o o r
E x p a n s io n
F t H o o d /B
H a n g a r
D o o r
E x p a n s io n
R
F ir e .r v t
/2
/2
:3
:3
A
M
LP101
L
IF
E S
A F
E T
Y F
L O
O R
P L A
N
O V
E R
A L L
F O
R T
H O
O D
T
X F
O R
T W
O R
T H
D
IS
T R
IC
T
T
A Y
L O
R S
T F
O R
T W
O R
T H
T
X
C
IT
R
IN
E -O
L S
S O
N G
R A
N D
A V
E G
R A
N D
J U
N C
T
IO
N C
O
J W
H
IT
C O
M B
N C
H A
P A
P T
U R
N E
R
M A
Y
W G
B
A
B H
A N
G A
R D
O O
R E
X P
A N
S
IO
N
H A
D E
S M
IS
S
IO
N
S U
P P
O R
T
W G
F
SHEET KEYNOTESXX
GENERAL SHEET NOTES
1" = 30'-0"
LIFE SAFETY FLOOR PLAN - OVERALL
A. MEANS OF EGRESS TRAVEL DISTANCE REQUIREMENTS ARE
BASED ON NFPA 101 INDUSTRIAL OCCUPANCY AS DIRECTED BY
UFC 4-211-01 SECTION 3-3.1.9 FOR ARMY BASES.
B. OCCUPANT LOADS ARE BASED ON UFC 3-600-01 TABLE 10-1 FOR
AIRCRAFT HANGARS - AIRCRAFT STORAGE AND SERVICING
AREAS.
C. EXITS REQUIRED AT MAXIMUM OF 150 FT INTERVALS IN EXTERIOR
HANGAR WALLS IN ACCORDANCE WITH NFPA 101 SECTION
10.6.2.2.
1. REFER TO ELECTRICAL SHEETS FOR EXIT SIGNS.
2. A MEANS OF EGRESS PATH IS NOT REQUIRED FROM THE
CATWALKS PER NFPA 101 SECTION 7.14.3, AS THEY ARE
CONSIDERED NORMALLY UNOCCUPIED BUILDING SERVICE
EQUIPMENT SUPPORT AREAS PER NFPA 101 SECTION 7.14.
REFER TO RFI-016 FOR INFORMATION REGARDING THE
OCCUPANCY OF THE CATWALK SYSTEMS.
SCALE:
15' - 0" 30' - 0" 60' - 0"
0' - 1" = 30' - 0"
US Army Corps of Engineers ®
SHEET ID
FO
R
T H
O O
D , T
X U
S
AR
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T, F O
R W
O R
TH
, T
X
C
IT
R
IN
E- O
LS
SO
N
G
R
AN
D E
AV
E
G R
AN
D
J U
N C
TI
O
N C
O , 8
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
D . H
O
LM
ES
C . F
ER
G
U
SO
N
M
AY
8, W
G
BA
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E
B9
H
AN
G
AR
D
O O
R E
XP
AN
SI
O
N
H
AD
ES
M
IS
SI
O N
S U
PP
O
R T
W
G
F0
M
AR
K D
ES
C
R
IP
TI
O
N
2/
/2
:0 9:
P
M Fi le P at h:
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
KEY PLAN
HB HC
HDHA
A B
A.
S
LY
TE
R
C
IT
R
IN
E- O
LS
SO
N J
V
G
EN
ER
AL
C
IV
IL
N
O
TE
S
GC001
1. ALL REFERENCES CONTAINED WITHIN THESE PLANS TO THE ENGINEER ARE HEREBY A REFERENCE TO OLSSON.
2. THE EXISTING UTILITY LOCATIONS SHOWN ON THE PLANS ARE APPROXIMATE AND MAY NOT INCLUDE ALL LINES PRESENT.
THE CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN ANY NECESSARY DIG PERMITS. THE CONTRACTOR SHALL BE RESPONSIBLE TO CALL "811", AND COORDINATE FIELD LOCATION OF EXISTING UNDERGROUND UTILITIES PRIOR TO
BEGINNING EXCAVATION ACTIVITIES. !!STOP!! CALL BEFORE YOU DIG!!
3. UTILITIES AS SHOWN WERE OBTAINED FROM INFORMATION INDICATED ON THE SURVEY OR BY FIELD OBSERVATION.
CONTRACTOR SHALL FIELD VERIFY ALL HORIZONTAL AND VERTICAL LINES AND GRADES OF EXISTING UTILITIES PRIOR TO THE CONSTRUCTION OF IMPROVEMENTS. CONTRACTOR SHALL NOTIFY THE GOVERNMENT IMMEDIATELY UPON DISCOVERY OF A DISCREPANCY BETWEEN THE CONTRACT DRAWINGS AND ACTUAL FIELD CONDITIONS.
4. CONTRACTOR SHALL NOT CHANGE OR DEVIATE FROM THE PLANS WITHOUT FIRST OBTAINING WRITTEN APPROVAL FROM
THE GOVERNMENT.
5. CONTRACTOR SHALL BE RESPONSIBLE TO OBTAIN ALL PERMITS AND PAY ALL FEES AS REQUIRED BY THE CONSTRUCTION
COVERED IN THESE PLANS.
6. ALL WORK AND MATERIALS SHALL BE SUBJECT TO INSPECTION AND APPROVAL BY THE GOVERNMENT.
7. ANY ESTIMATES OF QUANTITIES ARE FOR INFORMATIONAL PURPOSES ONLY. CONTRACTOR AND SUBCONTRACTOR(S) SHALL BE RESPONSIBLE FOR DETERMINING ALL QUANTITIES. CONTRACTOR SHALL PROVIDE ALL WORK AND MATERIALS
TO COMPLETE CONSTRUCTION AS SHOWN ON PLANS.
8. CONTRACTOR SHALL TAKE CARE NOT TO DAMAGE ANY EXISTING STREET, RUNWAY, CURB AND GUTTER, SIDEWALK, DRIVEWAYS OR STRUCTURE UNLESS SHOWN TO BE REMOVED. DAMAGE SHALL BE REPAIRED TO THE SATISFACTION OF
THE GOVERNMENT.
9. ALL TRAFFIC CONTROL SHALL BE IN CONFORMANCE WITH THE MANUAL OF UNIFORM TRAFFIC CONTROL DEVICES
(MUTCD).
10. THE CONTRACTOR IS RESPONSIBLE FOR ATTENDING TO AND CORRECTING UNSUITABLE SOIL CONDITIONS RELATED TO PLOW ZONES, WET SOILS AND OTHER CONDITIONS. THE UNSUITABLE CONDITIONS MUST BE CORRECTED PER THE
GEOTECHNICAL ENGINEER'S REPORT, WHERE REQUIRED, TO MEET PROJECT NEEDS.
11. CONTRACTOR SHALL BE PROHIBITED FROM DISRUPTING UTILITY SERVICES TO THE EXISTING BUILDING.
12. CONTRACTOR SHALL MAINTAIN SAFETY PRACTICES THAT CONFORM TO OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION (OSHA) REGULATIONS AND USACE EM385-1-1.
1. ACCESS AND HAUL ROUTES FOR ALL CONTRACTOR PERSONNEL, VEHICLES, AND EQUIPMENT ARE
SUBJECT TO THE APPROVAL OF THE GOVERNMENT. IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO COMMUNICATE OFF-SITE HAUL ROUTES WITH THE APPROPRIATE AUTHORITY
WHO HAS JURISDICTION OVER THE AFFECTED ROUTE. ACCESS ROUTES AND HAUL ROUTES ARE
SUBJECT TO CHANGE AT THE DIRECTION OF THE GOVERNMENT AND MAY CHANGE BASED ON
OPERATIONAL REQUIREMENTS OF THE PROJECT SITE.
2. CONTRACTOR SHALL COMMUNICATE ACTIVITIES AND MAINTAIN ALL ACCESS AND HAUL ROUTES IN A
MANNER THAT ALLOWS UNOBSTRUCTED EMERGENCY ACCESS TO ALL PROJECT AREAS AND
EXISTING ROADWAYS AT ALL TIMES WITHOUT DELAY TO EMERGENCY AND SECURITY VEHICLE
RESPONSE TIME.
3. IF ANY EMERGENCY ROUTES REQUIRE CLOSURE DUE TO CONSTRUCTION ACTIVITIES, CONTRACTOR SHALL NOTIFY THE BASE, POLICE, LOCAL FIRE AUTHORITY AND ALL OTHER EMERGENCY SERVICES
OF CLOSURE.
4. CONTRACTOR SHALL MAINTAIN ACCESS AND HAUL ROUTES TO BE FREE FROM DEBRIS CAUSED
FROM CONSTRUCTION ACTIVITIES ON A DAILY BASIS.
5. CONTRACTOR SHALL RESTRICT ALL OPERATIONS TO AREAS WITHIN THE CONSTRUCTION LIMITS
UNLESS COMMUNICATED OTHERWISE WITH THE GOVERNMENT.
6. CONTRACTOR IS RESPONSIBLE FOR ESTABLISHING A STAGING AND STOCKPILE AREA FOR
MATERIALS AND EQUIPMENT. LOCATION OF CONTRACTOR'S STAGING IS SUBJECT TO THE
APPROVAL OF THE GOVERNMENT. CONTRACTOR MAY SUBMIT ALTERNATIVES TO THE STAGING
AREA LOCATIONS AS SHOWN. CONTRACTOR'S STAGING AREA IS SUBJECT TO CHANGE AT THE
DIRECTION OF THE GOVERNMENT AND MAY CHANGE BASED ON OPERATIONAL REQUIREMENTS OF
THE PROJECT SITE.
7. WHEN NOT ENGAGED IN CONSTRUCTION ACTIVITIES, CONTRACTOR'S EQUIPMENT AND VEHICLES
SHALL BE PARKED IN THE STAGING AREA.
8. CONTRACTOR SHALL PROVIDE A MINIMUM NOTICE OF 48 HOURS TO THE GOVERNMENT REGARDING
CONSTRUCTION DELIVERIES PRIOR TO THOSE DELIVERIES.
9. ALL CONTRACTOR VEHICLES AND PERSONNEL SHALL BE RESPONSIBLE FOR COMMUNICATING AND
COMPLYING WITH FORT HOOD BASE SECURITY POLICY.
GENERAL NOTES POLLUTION PREVENTION NOTES
1. CONTAINERS MUST BE PROVIDED FOR COLLECTION OF WASTE MATERIAL INCLUDING CONSTRUCTION DEBRIS, TRASH, AND OTHER MATERIALS GENERATED ON-SITE. CONTRACTOR MUST CONDUCT THREE (3) FOREIGN OBJECT DEBRIS
CHECKS DAILY OF THE CONSTRUCTION SITE.
2. WASTE MATERIALS MUST NOT BE BURIED ON-SITE. ALL WASTE MATERIAL SHALL BE DISPOSED OF PROPERLY PER LOCAL, STATE AND FEDERAL REGULATIONS.
3. THE CONTRACTOR MUST KEEP ALL POLLUTANTS, INCLUDING BUT NOT LIMITED TO SEDIMENT, CONSTRUCTION DEBRIS, CONSTRUCTION RELATED CHEMICALS, UNTREATED DEWATERING DISCHARGES, AND POTENTIALLY HAZARDOUS
MATERIALS FROM ENTERING THE STORM SEWER SYSTEM OR WATER COURSES.
4. THE DISCHARGE OF CONCRETE WASHWATERS TO THE STORMWATER SYSTEM IS PROHIBITED. ALL CONCRETE WASTE SHALL BE PROPERLY CLEANED UP AND DISPOSED OF AT AN APPROPRIATE LOCATION. THE CLEANING OF CONCRETE DELIVERY TRUCK CHUTES IS TO BE RESTRICTED TO APPROVED LOCATIONS. IF CONCRETE WASHWATERS ARE TO BE GENERATED ONSITE, THE CONTRACTOR SHALL CONSTRUCT, UTILIZE AND MAINTAIN A CONCRETE TRUCK WASH OUT
BASIN ON-SITE.
5. THE CONTRACTOR SHALL STORE FUEL AND OIL AS FAR FROM ANY STORM SEWER, WETLAND OR SURFACE WATER AS PRACTICABLE (UNLESS A SPECIFIED DISTANCE IS DESIGNATED BY AUTHORITY HAVING JURISDICTION). EQUIPMENT FUELING AND MAINTENANCE SHALL BE PERFORMED ONLY IN AN AREA DESIGNATED FOR THAT PURPOSE. BEST MANAGEMENT PRACTICES (BMPS) SUCH AS CONTAINMENT BERMS AND DRIP PANS SHALL BE IN PLACE AT THE
DESIGNATED AREA TO MINIMIZE THE SPILLING OR LEAKING OF HAZARDOUS MATERIALS.
6. ALL PAINT, SOLVENTS, PETROLEUM PRODUCTS, PETROLEUM WASTE PRODUCTS, AND STORAGE CONTAINERS (SUCH AS DRUMS, CANS, OR CARTONS) SHALL BE STORED ACCORDING TO BMPS. THE MATERIALS EXPOSED TO PRECIPITATION SHALL BE STORED IN WATERTIGHT, STRUCTURALLY SOUND, CLOSED CONTAINERS. IF SUBSTANCES SUCH AS OIL, DIESEL FUEL, HYDRAULIC FLUID, ANTIFREEZE, ETC. ARE SPILLED, LEAKED, OR RELEASED ONTO SOIL, THE SOIL SHALL BE DUG UP AND PROPERLY DISPOSED OF IN ACCORDANCE WITH THE AUTHORITY HAVING JURISDICTION'S REQUIREMENTS. SPILLS ON PAVEMENT SHALL BE ABSORBED WITH SAWDUST, KITTY LITTER, OR PRODUCT DESIGNED FOR THAT PURPOSE AND DISPOSED OF AT A LICENSED SANITARY LANDFILL. HAZARDOUS OR INDUSTRIAL WASTES SUCH AS SOLVENTS, GASOLINE, OIL-BASED PAINTS, AND CONCRETE CURING COMPOUNDS REQUIRE SPECIAL HANDLING. THESE MATERIALS WILL BE REMOVED FROM THE SITE AND RECYCLED OR DISPOSED OF IN ACCORDANCE WITH THE AUTHORITY HAVING
JURISDICTION'S SPECIFIC REGULATIONS.
7. SPILLS INCLUDING, BUT NOT LIMITED TO, PETROLEUM PRODUCTS, SOLVENTS AND CEMENT SHALL BE CONTAINED AND CLEANED UP IMMEDIATELY. FEDERAL LAW REQUIRES THE RESPONSIBLE PARTY TO REPORT ANY RELEASE OF OIL IF IT REACHES OR THREATENS A STORM SYSTEM, LAKE, CREEK, STREAM, RIVER, GROUNDWATER, WETLAND OR AN AREA
THAT DRAINS INTO ONE OF THESE ENTITIES (E.G. ROADSIDE DITCH).
8. THE CONTRACTOR SHALL PROVIDE AND MAINTAIN SUFFICIENT TEMPORARY SANITARY WASTE FACILITIES TO SERVE THE NUMBER OF WORKERS ON THE SITE. THE FACILITIES SHALL BE PLACED, AND SECURED TO PREVENT TIPPING. FACILITIES SHALL NOT BE PLACED ON ROADS OR ON TOP OF STORMWATER INLETS. FACILITIES SHALL BE MAINTAINED PER
MANUFACTURER'S SPECIFICATIONS.
9. CONTRACTOR SHALL RETAIN FLOATABLE WIND BLOWN MATERIALS ON SITE BY STORING ALL TRASH AND BUILDING MATERIAL WASTE IN ENCLOSURES UNTIL PROPER DISPOSAL AT AN OFF-SITE FACILITY. CONTRACTOR TO CHECK ADJACENT AREAS DAILY AND PICK UP CONSTRUCTION WASTE MATERIALS AND DEBRIS THAT HAVE BLOWN OR WASHED
OFF-SITE.
10. CONTRACTOR SHALL BE RESPONSIBLE TO CONTROL DOWNSTREAM EROSION AND SILTATION DURING ALL PHASES OF
CONSTRUCTION.
11. CONTRACTOR SHALL PROTECT ANY STORM INLETS FROM SEDIMENT THAT TAKE STORM WATER FROM THE AREA OF
CONSTRUCTION.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR KEEPING THE SURROUNDING STREETS IN THE VICINITY OF THE JOB SITE
CLEAN AND FREE OF ROCKS, SOIL/MUD AND DEBRIS DURING ALL PHASES OF CONSTRUCTION.
13. CONTRACTOR SHALL CLEAN OUT ALL EXISTING AND PROPOSED INLETS, PIPES AND MANHOLES OF DEBRIS AND SEDIMENTATION AT COMPLETION OF SITEWORK. THIS WORK SHALL BE DONE TO THE SATISFACTION OF THE
GOVERNMENT.
14. CONTRACTOR SHALL COORDINATE WITH ADJACENT CONTRACTORS FOR RAMP CLOSURES.
ACCESS AND STAGING
CTL X CUT IN CONC
CTL X CUT IN CONC
CTL
CTL
EM
TB
RD
RD
ELO
W
ELO
ELO
W
ELO
RD
COL
E
COL
E
EXPANSION GAP
(TYP.) 1019.50
SD
SD
EXISTING 8" STORM
FL = 1018.14 PER AS-BUILTS
EXISTING 8" STORM
FL = 1018.01 PER AS-BUILTS
DEMOLITION PLAN
1" = 20' HORIZONTALA1
NORTH
0 10'
1" = 20'-0" GRAPHIC SCALE
20' 40' 60' 80'
US Army Corps of Engineers ®
SHEET ID
FO
R
T H
O O
D , T
X U
S
AR
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T, F O
R W
O R
TH
, T
X
C
IT
R
IN
E- O
LS
SO
N
G
R
AN
D E
AV
E
G R
AN
D
J U
N C
TI
O
N C
O , 8
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
D . H
O
LM
ES
C . F
ER
G
U
SO
N
M
AY
8, W
G
BA
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E
B9
H
AN
G
AR
D
O O
R E
XP
AN
SI
O
N
H
AD
ES
M
IS
SI
O N
S U
PP
O
R T
W
G
F0
M
AR
K D
ES
C
R
IP
TI
O
N
2/
/2
:0 9:
P
M Fi le P at h:
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
KEY PLAN
HB HC
HDHA
A B
A.
S
LY
TE
R
C
IT
R
IN
E- O
LS
SO
N J
V
D
EM
O
LI
TI
O
N P
LA
N
CD101
SAWCUT ALONG PAVEMENT JOINTS.
REMOVE AND REPLACE SEVEN (7)
PANELS OF EXISTING CONCRETE
PAVEMENT
REMOVE THREE (3)
EXISTING BOLLARDS
REMOVE THREE (3)
EXISTING BOLLARDS
GENERAL SHEET NOTES
1. REFER TO GC001 FOR GENERAL NOTES APPLICABLE TO
THIS DRAWING.
2. UTILITY DEMOLITION MUST BE COORDINATED WITH THE
CONTRACTING OFFICER PRIOR TO BEGINNING WORK.
SITE FEATURE TO BE REMOVED
CONCRETE PAVEMENT TO BE
REMOVED
EXISTING BOLLARD
TO REMAIN
EXISTING BOLLARD
TO REMAIN
LEGEND
SAWCUT ALONG PAVEMENT JOINTS.
REMOVE AND REPLACE EIGHT (8)
PANELS OF EXISTING CONCRETE
PAVEMENT
REMOVE BOLLARD 2" BELOW
GRADE AND REPAIR WITH
NON-SHRINK GROUT FLUSH
WITH EXISTING ADJACENT
PAVEMENT
REMOVE BOLLARD 2" BELOW
GRADE AND REPAIR WITH
NON-SHRINK GROUT FLUSH
WITH EXISTING ADJACENT
PAVEMENT
CTL X CUT IN CONC
CTL
CTL
EM
TB
RD
RD
W
W
ELO
RD
COL
E
COL
E
EXPANSION GAP
(TYP.) 1019.50
SD
SD
EXISTING 8" STORM
FL = 1018.14 PER AS-BUILTS
EXISTING 8" STORM
FL = 1018.01 PER AS-BUILTS
PROPOSED BOLLARD (1)
RE: K1 / CS501
SD
SD
SD
SD
SD
SD
SD
SD
SD
CO
CO
CO
CO
EJ/TE
EJ/TE
EJ/TE
EJ/TE
EJ/TE
EJ/TE
EJ/TE
MULLION PIT DRAIN LINE
RE: S-500
4X4 TEE AND CLEANOUT
FL = 1018.21
RE: F1 / CS501
CONNECT TO PLUG OF
EXISTING 8" STORM
4X4 TEE AND CLEANOUT
FL = 1018.62
RE: F1 / CS501
82.46 LF OF 4" HDPE @
0.50%
10.00 LF OF 4" HDPE @
0.50%
13.42 LF OF 4" HDPE @
0.50%
MULLION PIT DRAIN LINE
RE: S-500
10.00 LF OF 4" HDPE @
0.50%
4X4 TEE AND CLEANOUT
FL = 1018.55
RE: F1 / CS501
4X4 TEE AND CLEANOUT
FL = 1018.06
RE: F1 / CS501
97.71 LF OF 4" HDPE @
0.50%
10.17 LF OF 4" HDPE @
0.50%
CONNECT TO PLUG OF
EXISTING 8" STORM
PROPOSED BOLLARDS (3)
RE: K1 / CS501
PROPOSED BOLLARDS (3)
RE: K1 / CS501
PROPOSED BOLLARDS (3)
RE: K1 / CS501
SITE PLAN
1" = 20' HORIZONTALA1
SI
TE
P
LA
N
CS101
NORTH
0 10'
1" = 20'-0" GRAPHIC SCALE
20' 40' 60' 80'
US Army Corps of Engineers ®
SHEET ID
FO
R
T H
O O
D , T
X U
S
AR
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T, F O
R W
O R
TH
, T
X
C
IT
R
IN
E- O
LS
SO
N
G
R
AN
D E
AV
E
G R
AN
D
J U
N C
TI
O
N C
O , 8
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
D . H
O
LM
ES
C . F
ER
G
U
SO
N
M
AY
8, W
G
BA
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E
B9
H
AN
G
AR
D
O O
R E
XP
AN
SI
O
N
H
AD
ES
M
IS
SI
O N
S U
PP
O
R T
W
G
F0
M
AR
K D
ES
C
R
IP
TI
O
N
2/
/2
:0 9:
P
M Fi le P at h:
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
KEY PLAN
HB HC
HDHA
A B
A.
S
LY
TE
R
C
IT
R
IN
E- O
LS
SO
N J
V
GENERAL SHEET NOTES
1. REFER TO GC001 FOR GENERAL NOTES APPLICABLE TO
THIS DRAWING.
10.50" CONCRETE PAVEMENT
RE: K7 / CS501
LEGEND
SD
EJ/TE
DOWELED CONSTRUCTION JOINT
RE: B7 AND B14 / CS501
CONTRACTION JOINT
RE: K14 / CS501
THICKENED EDGE EXPANSION JOINT
RE: B14 AND F7 / CS501
STORMWATER LINE
PROJECT LOCATION AND STAGING AREA MAP
1" = 500' HORIZONTALA1
NORTH
0 250'
1" = 500'-0" GRAPHIC SCALE
500' 1000' 1500' 2000'
US Army Corps of Engineers ®
SHEET ID
FO
R
T H
O O
D , T
X U
S
AR
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T, F O
R W
O R
TH
, T
X
C
IT
R
IN
E- O
LS
SO
N
G
R
AN
D E
AV
E
G R
AN
D
J U
N C
TI
O
N C
O , 8
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
D . H
O
LM
ES
C . F
ER
G
U
SO
N
M
AY
8, W
G
BA
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E
B9
H
AN
G
AR
D
O O
R E
XP
AN
SI
O
N
H
AD
ES
M
IS
SI
O N
S U
PP
O
R T
W
G
F0
M
AR
K D
ES
C
R
IP
TI
O
N
2/
/2
:0 9:
P
M Fi le P at h:
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
KEY PLAN
HB HC
HDHA
A B
A.
S
LY
TE
R
C
IT
R
IN
E- O
LS
SO
N J
V
PROJECT LOCATION
PR
O
JE
C
T
LO
C
AT
IO
N
A N
D S
TA
G
IN
G
A R
EA
M
AP
CS102
STAGING AREA
COBRA DR.
GRAY EAGLE DR.
MOHAWK RD.
GENERAL SHEET NOTES
1. REFER TO GC001 FOR GENERAL NOTES APPLICABLE TO
THIS DRAWING.
2. CONTRACTOR TO REFER TO DIVISION 00 AND 01 OF THE
SPECIFICATIONS FOR ADDITIONAL ACCESS
REQUIREMENTS.
INITIAL FINAL
CONTRACTION JOINT
D
1/2"-5/8" SEE NOTE 2
1/8" INITIAL SAW
CUT
1/2"-5/8"
1/8" INITIAL SAW CUT
T
FINAL SAW
CUT FOR JOINT SEAL
NOTES:
1. D = DEPTH AS RECOMMENDED BY MANUFACTURER OF JOINT SEAL.
T = DEPTH OF INITIAL SAWCUT TYPE JOINT FORMER (CONTRACTION JOINT)
A. 1/4 SLAB THICKNESS +/- 1/2" FOR PAVEMENT LESS THAN 12 INCHES
B. 3 INCHES FOR PAVEMENTS 12-18 INCHES
C. 1/6 SLAB THICKNESS FOR PAVEMENTS MORE THAN 18 INCHES
2. TOP OF SEALANT SHALL BE 1/8 INCH TO 1/4 INCH BELOW PAVEMENT SURFACE. IN AREAS TO BE
GROOVED, THE JOINT SEAL SHALL BE RECESSED BELOW THE DEPTH OF THE GROOVES.
3. JOINTS TO BE IN CONFORMANCE WITH SPECIFICATION 32 13 73.19.
4. COMPRESSION SEALS MUST BE IN COMPRESSION AT ALL TIMES.
PREFORMED ELASTOMERIC
SEAL. WIDTH OF SEAL SHALL
BE TWICE THE WIDTH OF THE
JOINT RESERVOIR.
INITIAL FINAL
D
FINAL SAWCUT FOR JOINT
SEALANT RESERVOIR.
DEPTH AS REQUIRED FOR
SEALANT, SEALANT RECESS,
AND BACKER ROD.
NOTES:
1. D = DEPTH OF SEALANT (1.0 TO 1.5 x WIDTH OF JOINT) OR AS RECOMMENDED BY MANUFACTURER.
2. TOP OF SEALANT SHALL BE 1/8 INCH TO 1/4 INCH BELOW PAVEMENT SURFACE OR 1/8 INCH BELOW BOTTOM EDGE OF RADIUS. IN AREAS TO BE GROOVED, THE JOINT SEAL SHALL BE RECESSED BELOW
THE DEPTH OF THE GROOVES.
3. JOINTS TO BE IN CONFORMANCE WITH SPECIFICATION 32 01 19.61.
4. A HEAT-RESISTANT BACKER ROD MUST BE USED WITH ASTM D6690 (HOT-POURED) SEALANT.
5. DIAMETER OF BACKER ROD MATERIAL = WIDTH OF SEALANT + 1/8".
3/4" POURED JOINT SEALANT
1/8" R (TYP)
BRING JOINT FILLER
TO SURFACE DURING
INITIAL CONSTRUCTION
3/4"
1/8" R (TYP)
PREFORMED
NON-EXTRUDING JOINT
FILLER
PREFORMED
NON-EXTRUDING JOINT
FILLER
NONMOISTURE ABSORPTIVE,
NONRACTIVE BACKER ROD
MATERIAL TO FIT SNUG IN JOINT
D
5/8" POURED JOINT SEALANT
CONSTRUCTION
JOINT
NONMOISTURE ABSORPTIVE,
NONRACTIVE BACKER ROD
MATERIAL TO FIT SNUG IN JOINT
EXPANSION JOINT
5/8"
CONSTRUCTION
JOINT
FINAL SAW
CUT DEPTH AS REQUIRED
FOR SEALANT, SEALANT
RECESS, AND BACKER
ROD
1/8" R (TYP)
TOOL EDGES AT
CONSTRUCTION JOINTS
TO DELINEATE THE JOINT
LOCATION FOR SAWING
INITIAL FINAL
CONSTRUCTION JOINT
4"
10.5" PORTLAND CEMENT CONCRETE
NO 4 REBAR @ 12" ON
CENTER / EACH WAY
REBAR CHAIRS
NEW 10" AGGREGATE BASE COURSE COMPACTED
TO AT LEAST 100% OF LABORATORY MAXIMUM
DENSITY (ASTM D1557) WITH 20% OR LESS
PASSING THE #200 SIEVE IN TWO LIFTS
NEW 6" RAW SUBGRADE COMPACTED
TO AT LEAST 95% OF LABORATORY
MAXIMUM DENSITY (ASTM D1557)
NOTES:
1. CONTRACTOR SHALL USE FLOW FILL MATERIAL FOR BACKFILL (BEDDING TO BOTTOM OF PROPOSED
CONCRETE) OF 4" STORMWATER LINE WITHIN NEW PAVEMENT PANELS.
T
3/4"
10' OR TO NEAREST JOINT
1.25T
EXPANSION JOINT SEALANT
REF: B14 / CS501
EXISTING GRADE BEAM
SI
TE
D
ET
AI
LS
CS501
US Army Corps of Engineers ®
SHEET ID
FO
R
T H
O O
D , T
X U
S
AR
M Y
C O
R
PS
O F
EN
G
IN
EE
R S
FO
R
T W
O R
TH
D
IS
TR
IC
T
TA
YL
O R
S T, F O
R W
O R
TH
, T
X
C
IT
R
IN
E- O
LS
SO
N
G
R
AN
D E
AV
E
G R
AN
D
J U
N C
TI
O
N C
O , 8
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
D . H
O
LM
ES
C . F
ER
G
U
SO
N
M
AY
8, W
G
BA
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E
B9
H
AN
G
AR
D
O O
R E
XP
AN
SI
O
N
H
AD
ES
M
IS
SI
O N
S U
PP
O
R T
W
G
F0
M
AR
K D
ES
C
R
IP
TI
O
N
2/
/2
:0 9:
P
M Fi le P at h:
Pl ot
D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
A.
S
LY
TE
R
C
IT
R
IN
E- O
LS
SO
N J
V
6"
PAINT POST TO MATCH OTHER
SET POST IN CONCRETE
FILL POST WITH CONCRETE
2" WIDE, WHITE REFLECTIVE TAPE
STEEL PIPE, MATCH EXISTING DIAMETERS AND LENGTHS
GRADE
3"
36"
18"
27"
6"
FINISH GRADE COUNTERSUNK PLUG
15" SQUARE CONC.
SLAB 6" THICK
4"x4" WYE (C.I.)
4" PLUG
OMIT PLUG WHERE
SEWER JOINS HOUSE
CONNECTION
4" C.I. PIPE
BEND (C.I.)
BOLLARDS ON SITE
FOR HANGAR DOORS AND PEDESTRIAN DOORS
NOTES:
1. HOLES APPROXIMATELY 1/8 INCH GREATER IN DIAMETER THAN THE DOWELS SHALL
BE DRILLED IN THE EXISTING CONCRETE AND THE DOWELS SHALL BE BONDED IN
THE DRILLED HOLES USING AN EPOXY RESIN GROUT.
2. STOP PROPOSED PAVEMENT REINFORCEMENT 3" FROM THE CONSTRUCTION JOINT.
REBAR SHALL BE PLACED ABOVE DOWEL.
SCALE: NTS
PREFORMED COMPRESSION JOINT SEALANTSK14
SCALE: NTS
POURED JOINT SEALANTSB14
SCALE: NTS
10.50" CONCRETE PAVEMENTK7
SCALE: NTS
THICKENED EDGE EXPANSION JOINTF7
GROUT DOWEL
DRILL AND EPOXY
JOINT SEAL
RE: B14 / CS501
5.
.5
0"
PAINT AND OIL END OF DOWEL
1" DIAMETER DOWEL
L = 16" @ 12" OC SPACING
NEW PAVEMENT
1/2 DOWEL LENGTH
EXISTING
PAVEMENT
SCALE: NTS
DOWELED CONSTRUCTION JOINTB7
SCALE: NTS
BOLLARD DETAILK1
SCALE: NTS
ONE-WAY CLEANOUTF1
(05 50 13)
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
A u to d e s k D o c s
/U S
A C
E F t W o rt h
B H a n g a r
D o o r
E x p a n s io n
F t H o o d /S
B
H a n g a r
D o o r
E x p a n s io n -0
R
.r v t
/2
/2
:4
:3
P
M
S-001
G E
N E
R A
L S
T R
U C
T U
R A
L N
O T
E S
D
E S
IG
N
L O
A D
S
A B
B R
E V
IA
T
IO
N
S
F O
R T
H O
O D
T
X F
O R
T W
O R
T H
D
IS
T R
IC
T
T
A Y
L O
R S
T F
O R
T W
O R
T H
T
X
C
IT
R
IN
E O
L S
S O
N J
V G
R A
N D
E A
V E
G R
A N
D J
U N
C T
IO
N
C
O
J B
A T
Y
D F
A V
A Z
Z A
C
IT
R
IN
E -O
L S
S O
N J
V
W M c C
A N
N
M A
Y
W G
B
A
B H
A N
G A
R D
O O
R E
X P
A N
S
IO
N
H A
D E
S M
IS
S
IO
N
S U
P P
O R
T
W G
F
GENERAL NOTES
NO. GENERAL NOTES DESCRIPTION
1 THE PROJECT SPECIFICATIONS ARE A PART OF THE CONTRACT DOCUMENTS.
2 THE CONTRACTOR SHALL EXAMINE THE STRUCTURAL DRAWINGS AND SHALL NOTIFY THE CONTRACTING OFFICER OF ANY
DISCEPANCIES BEFORE PROCEESING WITH ANY WORK
3 THE DRAWINGS AND SPECFICATIONS REPRESENT THE COMPLETED STRUCTURE. THEY DO NOT INDICATED THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES AND MEANS NECESSARY TO PROTECT PERSONS AND STRUCTURES DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO BRACING, SHORING, ETC.
OBSERVATION BY THE ARCHITECT, ENGINEER OR CONTRACTING OFFICER DOES NOT INCLUDE REVIEW OF THESE MEASURES.
4 NOTES AND DETAILS ON THE STRUCTURAL DRAWINGS TAKE PRECEDENCE OVER GENERAL NOTES. TYPICAL DETAILS SHALL BE
USED WHENEVER APPLICABLE. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
5 ALL WORK NOT DETAILED OR NOTED SHALL BE CONSTRUCTED IN ACCORDANCE WITH OTHER SIMILAR WORK SHOWN ON THE DRAWINGS AND TYPICAL DETAILS. DIMENSIONS SHALL TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.
DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES.
6 NO PIPES OR DUCTS SHALL BE PLACED IN OR PENETRATE STRUCTURAL MEMBERS UNLESS SPECIFICALLY DESIGNED AND
DETAILED.
7 REFER TO ARCHITECTURAL DRAWINGS FOR THE FOLLOWING:
A) SIZE AND LOCATION OF DOOR AND WINDOW OPENINGS, EXCEPT AS NOTED.
B) SIZE AND LOCATION OF INTERIOR AND EXTERIOR NONBEARING PARTITIONS.
C) SIZE AND LOCATION OF CURBS, FLOOR DRAINS, SLOPES, DEPRESSED AREAS, CHANGES IN LEVEL, RAMPS, CHAMFERS GROOVES, INSERTS, ETC.
D) SIZE AND LOCATION OF FLOOR AND ROOF OPENINGS IF NOT DIMENSIONED ON THESE DRAWINGS.
E) FLOOR AND ROOF FINISHES.
F) STAIR FRAMING AND DETAILS EXCEPT AS SHOWN HEREIN.
G) DIMENSIONS NOT SHOWN ON STRUCT DWGS.
8 REFER TO MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS FOR THE FOLLOWING:
A) PIPE RUNS, SLEEVES, HANGERS, EQUIPMENT, SLAB OPENINGS, NOT SHOWN OR NOTED HEREIN.
B) ELECTRICAL CONDUIT, BOXES, OUTLETS.
C)…
This is the start of the file's text. The full file is on GovTribe.