Full MDNR_Otsego State Park_Restroom Bldg_ACM LCP Survey Report_2023_0116.pdf
PDF 2 MB Posted
- Solicitation number
- RFP - 171 - 230000000765
- Issued by
- Otsego County, Michigan
About this file
This document is a Pre-Demolition Asbestos and Limited Lead-Containing Paint Survey report prepared by Atlas Technical Consultants LLC on behalf of the Michigan Department of Natural Resources. The survey was conducted at the Toilet and Shower Building located in Otsego State Park in Gaylord, Michigan. The purpose was to identify and collect samples of suspected asbestos-containing materials (ACMs) and lead-containing paint (LCP) prior to demolition activities. The survey found two materials containing greater than 1% asbestos - gasket material (50% chrysotile) and ceramic tile grout (8% chrysotile). Three paint samples were found to contain lead levels exceeding laboratory reporting limits.
The report provides recommendations for handling any identified ACMs and LCP in accordance with applicable regulations during renovation or demolition work. It also notes that any additional suspect materials discovered would need to be assumed as ACM until proven otherwise. The report does not contain information about a specific state or local contract opportunity, but rather details the findings of a pre-demolition environmental survey conducted in support of planned facility upgrades at Otsego State Park.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PRE-DEMOLITION ASBESTOS AND LIMITED LEAD-CONTAINING PAINT SURVEY
OTSEGO STATE PARK
TOILET AND SHOWER BUILDING
7136 OLD HIGHWAY 27 SOUTH,
GAYLORD, MI 49735
Project #188BS22768
PREPARED FOR:
Michigan Department of Natural Resources
PREPARED BY:
Atlas Technical Consultants LLC 46555 Humboldt Drive, Suite 100 Novi, Michigan 48377 January 16, 2023
Page | 1
46555 Humboldt Drive, Suite 100 Novi, Michigan 48377
(248) 669-5147 | oneatlas.com
January 16, 2023
Mr. David M Dekett Unit Supervisor Clear Lake State Park 20500 M-33 North Atlanta, Michigan 49709
Subject: Pre-Demolition Asbestos and Limited Lead-Containing Paint Survey Otsego State Park Toilet and Shower Building 7136 Old Highway 27 South Gaylord, MI 49735
Dear Mr. Dekett:
Atlas is pleased to present this report detailing the findings of the pre-demolition asbestos and limited lead-containing paint survey performed at the above referenced site. The purpose of this sampling was to identify and collect samples of suspect asbestos containing materials (ACMs) and lead-containing paint (LCP) prior to demolition activities.
The pre-demolition asbestos and limited lead-containing paint sampling was conducted on December 9, 2022 by Industrial Hygienist, Mr. Andrew DeLodder, State of Michigan certified asbestos inspector. The sampling was conducted in accordance with sampling criteria specified in the Occupational Safety and Health Administration’s (OSHA) Asbestos Construction Industry Standard (29 CFR 1926.1101), and the Asbestos Hazard and Emergency Response Act of 1987
(AHERA).
If you have any questions, please call us at 248.669.5140.
Respectfully submitted, Andrew DeLodder Martin Gamble State of Michigan Asbestos Inspector Project Manager Atlas Technical Consultants LLC Atlas Technical Consultants LLC
Page | i
CONTENTS
EXECUTIVE SUMMARY
1. INTRODUCTION
1.1 Purpose
1.2 Pre-Demolition Asbestos Survey
2. GENERAL SITE CONDITIONS
2.1 General Property and Building Information
2.2 Exterior Finish Descriptions
2.3 Interior Building Descriptions
3. PRE-DEMOLITION ASBESTOS SURVEY
3.1 Homogeneous Areas
3.2 Hazard Assessment Factors
3.3 Laboratory Analytical Methodology
3.4 Sampling Results
4. LEAD-CONTAINING PAINT SAMPLING
5. CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos-Containing Materials
5.2 Lead-Containing Paint
6. ASSUMPTIONS AND LIMITATIONS
TABLES
Table 3-1 ACM Sampling Results
Table 4-1 Lead-Containing Paint Sampling Results
APPENDICES
Appendix A Asbestos Laboratory Report Appendix B Lead-Based Paint Laboratory Report
Page | 2
EXECUTIVE SUMMARY
Atlas representative Mr. Andrew DeLodder completed the pre-demolition asbestos and limited lead-containing paint survey of the Toilet and Shower Building, located in Otsego State Park, at 7136 Old
Highway 27 S, in Gaylord, Michigan, on December 9, 2022.
Thirty-three (33) asbestos bulk samples, taken from eleven (11) homogenous areas, were collected and submitted for analysis by Polarized Light Microscopy (PLM). Of the 33 samples submitted forty-one (41) sample layers were analyzed. The results of laboratory testing indicated that two (2) of the suspect materials contained greater than 1 percent asbestos.
Three (3) representative samples of paint, taken from interior and exterior areas of the building, were collected and submitted for analysis by Flame AAS. The results of laboratory testing of the paint chip samples indicated that all three (3) samples contained levels of lead greater than the laboratory reporting limits.
If any additional materials are discovered during renovation/demolition activities, such materials must be assumed to contain asbestos until sampling and analysis proves otherwise.
Page | 3
1. INTRODUCTION
1.1 Purpose
The purpose of this project was to conduct a pre-demolition asbestos and limited lead-containing paint survey of the Toilet and Shower Building at Otsego State Park located at 7136 Old Highway 27 S, in
Gaylord, Michigan.
1.2 Pre-Demolition Asbestos Survey
The scope of the pre-demolition asbestos survey included the following:
Review of existing asbestos reports for the building, if available;
Survey of the property building(s);
Identification of accessible suspect asbestos-containing materials (ACMs);
Collection and analysis of bulk samples of suspect friable and non-friable materials.
2. GENERAL SITE CONDITIONS
2.1 General Property and Building Information
General property and building information is presented in the following table:
General Property and Building Information
Date of Inspection: December 9, 2022
Inspectors Andrew Delodder, Inspector # A48677
Property Address: 7136 Old Highway 27 S, in Gaylord, Michigan 49735
Property Owner Michigan Department of Natural Resources
Building Description:
2.2 Exterior Finish Descriptions
The exterior of the building included brick and masonry with a shingled-sloped roof.
2.3 Interior Building Descriptions
The interior finishes of the building included plastered walls and ceiling, and floor tiled floors.
3. PRE-DEMOLITION ASBESTOS SURVEY
Atlas representative Mr. Andrew DeLodder conducted the pre-demolition asbestos inspection of the property building on December 9, 2022. Mr. DeLodder is a State of Michigan Certified Asbestos Inspector’s
(Certification No. A48677). The building was visually inspected for the presence of building materials that are suspected to contain asbestos. Bulk samples of suspect ACMs were collected and placed into individual containers for transport to a National Voluntary Lab Accreditation Program (NVLAP)-accredited laboratory for analysis. Materials typically known as non-asbestos items (i.e. fibrous glass, foam rubber, wood, etc.) were not sampled. The asbestos inspection consisted of the following three basic procedures:
> Conducting a visual inspection of the structures;
> Identifying homogeneous areas (HAs) of suspect surfacing, thermal system insulation, and miscellaneous materials; and
> Sampling accessible, friable and non-friable suspect materials.
Otsego State Park - Toilet Shower Building
Page | 4
3.1 Homogeneous Areas
Prior to collecting any samples, homogenous areas (HAs) were identified. A homogeneous sampling area can be described as one or more areas of material that are similar in appearance and texture and that have the same apparent installation date, appearance and function. Actual number of samples collected from each homogeneous sampling area may vary, based on the type of material and professional opinion of the inspector.
3.2 Hazard Assessment Factors
From the list of suspect homogeneous areas, a physical assessment was performed for each material on the list. A physical assessment includes evaluating the condition, assessing the potential for disturbance, and determining the friability of each material. By definition, "friable" materials are those that can be crumbled or reduced to powder by hand pressure when dry. Each material identified was further classified into one of three categories: surfacing materials, thermal systems insulation (TSI) and miscellaneous materials. Each of the three categories have specific sampling requirements, outlined below.
Surfacing Materials: Refers to spray-applied or troweled surfaces such as plaster ceilings and walls, fireproofing, textured paints, textured plasters, and spray-applied acoustical surfaces.
Thermal System Insulation: Refers to insulation used to inhibit heat gain or loss on pipes, boilers, tanks, ducts, and various other building components.
Miscellaneous Materials: Refers to friable and non-friable products and materials that do not fit in any of the above two categories such as resilient floor covering, baseboards, mastics, adhesives, roofing material, caulking, glazing, and siding. This category also contains wallboard and ceiling tile.
All materials were assessed related to their condition in one of the three categories: good (intact), fair
(damaged) or poor (significantly damaged) per Title 40 Code of Federal Regulations Part 763. Material with localized, significant damage was also assessed as poor.
3.3 Laboratory Analytical Methodology
Bulk samples were analyzed by Environmental Testing Laboratories, Inc. (ETL) using polarized-light microscopy (PLM) and dispersion staining (Method Reference: 40 CFR Part 763, Volume 47, No. 103, May
27, 1982 pg. 23376). This laboratory participates in the National Voluntary Laboratory Accreditation Program
(NVLAP #201028-0), a quality assurance program for PLM analysis, and is accredited by the National Institute of Standards and Technology (NIST) as well as accreditation requirements under 15 CFR Part 25.
Copies of the laboratory analytical report and corresponding chain-of-custody forms are included in
Appendix A. Positive sample results are reported in percent asbestos by volume of the sample and the type of asbestos material within the sample. Other common non-asbestos components may also be noted on the analytical reports.
3.4 Sampling Results
Bulk samples were collected from the site building and analyzed by polarized light microscopy (PLM), EPA
Method 600/R-93/116.
The following table provides a summary of accessible suspect and confirmed ACMs from the Site buildings:
Page | 5
Table 3-1 ACM Sampling Results
Sample ID/Material
Location of Materials
Material Estimated Quantity
Asbestos Content
1-RM-A,B,C EA-5
Roofing Materials –
Beige Asphalt Shingle
NA ND
2-CC-A,B,C EA-1 Concrete Chip - Exterior Concrete NA ND
3-CC-A,B,C FS-2
Concrete Chip -
Poured Concrete Pad Foundation
NA ND
4-EC-A,B,C EA-1
Exterior Caulk -
White Caulk , Painted Beige, on Wood Siding, Roofline
NA ND
5-GTM-A,B,C EA-1,3
Gasket Material - White Gasket, Around Glass of Recessed Lighting 4 SF 50% Chrysotile
6-CA-A,B,C EA-1,3
Construction Adhesive - Dark Grey, Under Concrete Pylons
NA ND
7-GM-A,B,C FS-1,9
12” Beige Tiles-
Ceramic tile, Grout, & Mortar
NA ND
8-GM-A,B,C FS-1,3
1” Multi-Colored Tiles-
Ceramic tile, Grout, & Mortar 1,250
8% Chrysotile (Grout Layer Only)
9-IC-A,B,C FS-1,3
Interior Caulk: White, Soft-
Around Toilets, Sinks, Urinals
NA ND
10-GM-A,B,C FS-5,6,7
8" Beige Tile-
Ceramic tile, Grout, & Mortar
NA ND
11-FC-A,B,C FS-5,6,8 Floor Covering - Red Epoxy NA ND
EA=Exterior Area FS Functional Space NA=Not Applicable ND= None Detected
In the event additional suspect material is discovered during renovation activities, this material should be treated as presumed asbestos-containing material (PACM) in accordance with regulations 29 CFR
1926.1101 and 1910.1001 and other applicable state and local regulations and either sampled to confirm or nullify asbestos content or be treated as ACM and handled accordingly.
4. LEAD-CONTAINING PAINT SAMPLING
Atlas representative Mr. Andrew DeLodder conducted the lead-containing paint (LCP) sampling of the property building on December 9, 2022. The sampling included physical sampling of paint coatings that were deemed representative of the predominant paint coatings observed.
Three (3) paint chip samples were collected and submitted to Accurate Analytical Testing Laboratory, 30105
Beverly Road, Romulus, Michigan for lead analysis. Bulk samples were analyzed using the Environmental
Protection Agency's Test Method SW 846-7420 and 3050B using Flame AAS to determine lead concentration in percent (%) by weight. Copies of the laboratory analytical report and corresponding chain-of-custody forms are included in Appendix B.
The following table provides a summary of the LCP sampling:
Page | 6
Table 4-1 Lead-Containing Paint Sampling Results
Sample ID Sample Location Color Lead
Content
1-LBP-Beige Exterior Paint Beige 0.0041
2-LBP-White Interior Paint White 0.0004
3-LBP-Beige Interior Paint Beige 0.0004
5. CONCLUSIONS AND RECOMMENDATIONS
5.1 Asbestos Containing Materials
The results of laboratory testing during the pre-renovation asbestos survey conducted at the property indicate that the following materials sampled were found to contain asbestos:
Sample ID /Material
Location of Materials
Material Estimated Quantity
Asbestos Content
5-GTM-A,B,C EA-1,3
Gasket Material -
White Gasket, Around Glass of Recessed Lighting
4 SF 50% Chrysotile
8-GM-A,B,C FS-1,3
1” Multi-Colored Tiles-
Ceramic tile, Grout, & Mortar
1,250 SF
8% Chrysotile (Grout Layer
Only)
If any additional materials are discovered during renovation/demolition activities, such materials must be assumed to contain asbestos until sampling and analysis proves otherwise.
5.2 Lead-Containing Paint
Three (3) representative samples of paint, taken from interior and exterior areas of the buildings, were collected and submitted for analysis by Flame AAS. The results of laboratory testing during the limited lead-containing paint sampling conducted at the property indicate that three (3) samples contained levels of lead greater than the laboratory reporting limits.
The presence of lead-containing paint requires, under OSHA 1926.62 requirements, that the contractor performing renovation, surface preparation, and other activities that impact or potentially impact the lead-coated components, evaluate potential worker exposures to airborne lead. This evaluation can be based, for the specific activities denoted in 1926.62, on objective data obtained by the contractor on other, similar, worksites within the prior calendar year. In addition, lead-containing paint and lead-coated waste and construction debris must be evaluated and, on a case-by-case basis depending on this evaluation, quantitative analysis be performed on these waste steams to ensure compliance with EPA waste disposal regulations.
The presence of Lead-Containing Paint (LCP) and/or Lead-Based Paint (LBP) does not, in itself, trigger regulatory compliance actions. However, when these materials are disturbed, the requirements of OSHA
(1926.1101) and EPA may become operative. Appropriate actions in terms of removal methods, emissions control, worker protection, and waste disposal should be considered by the general contractor and applicable subcontractors while completing renovation activities.
Page | 7
6. ASSUMPTIONS AND LIMITATIONS
The results, findings, conclusions, and recommendations expressed in the report are based only on conditions that were noted during the NESHAP inspections conducted on December 9, 2022 performed by
Atlas. Selection of sample locations and frequency of sampling were based on EPA Guidance documents, Atlas’s observations, and the assumption that building vintage and renovation history information presented to Atlas allowed the proper designation of homogenous materials for each building.
This document does not contain the elements necessary for an Abatement Work plan, and this document does not contain, nor should it take the place of technical specifications for ACM removal.
Our professional services have been performed, our findings obtained, and our conclusions and recommendations prepared in accordance with customary principles and practices in the fields of environmental science and engineering. This statement is in lieu of other statements either expressed or implied. This report does not warrant against changes to material from future operations or conditions, nor does it warrant against operations or conditions against present ACM material in locations not investigated.
The scope of services performed in execution of this evaluation may not be appropriate to satisfy the needs of other users, and use or re-use of this document or the findings, conclusions, or recommendations is at the risk of said user.
APPENDIX A
ASBESTOS LABORATORY REPORT
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive Romulus, Michigan 48174
(734) 955-6600
Fax: (734) 955-6604
To:
Attention:
Atlas - Novi
46555 Humboldt Dr. Suite 100
Novi, Michigan 48377
Project Location:
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
Client Project: 188BS22768
253484ETL Job:
Report Date: 12/30/2022
Robert Smith
Lab Sample Number Client Sample Number Sample Type Completed
1436007 Asbestos1-RM-A 12/29/2022
1436008 Asbestos1-RM-B 12/29/2022
1436009 Asbestos1-RM-C 12/29/2022
1436010 Asbestos2-CC-A 12/29/2022
1436011 Asbestos2-CC-B 12/29/2022
1436012 Asbestos2-CC-C 12/29/2022
1436013 Asbestos3-CC-A 12/29/2022
1436014 Asbestos3-CC-B 12/29/2022
1436015 Asbestos3-CC-C 12/29/2022
1436016 Asbestos4-EC-A 12/29/2022
1436017 Asbestos4-EC-B 12/29/2022
1436018 Asbestos4-EC-C 12/29/2022
1436019 Asbestos5-GTM-A 12/29/2022
1436020 Asbestos5-GTM-B 12/29/2022
1436021 Asbestos5-GTM-C 12/29/2022
1436022 Asbestos6-CA-A 12/29/2022
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify ETL immediately. Thank you.
Lab Sample Number Client Sample Number Sample Type Completed
1436023 Asbestos6-CA-B 12/29/2022
1436024 Asbestos6-CA-C 12/29/2022
1436025 Asbestos7-GM-A 12/29/2022
1436026 Asbestos7-GM-B 12/29/2022
1436027 Asbestos7-GM-C 12/29/2022
1436028 Asbestos8-GM-A 12/29/2022
1436029 Asbestos8-GM-B 12/29/2022
1436030 Asbestos8-GM-C 12/29/2022
1436031 Asbestos9-IC-A 12/29/2022
1436032 Asbestos9-IC-B 12/29/2022
1436033 Asbestos9-IC-C 12/29/2022
1436034 Asbestos10-GM-A 12/29/2022
1436035 Asbestos10-GM-B 12/29/2022
1436036 Asbestos10-GM-C 12/29/2022
1436037 Asbestos11-FC-A 12/29/2022
1436038 Asbestos11-FC-B 12/29/2022
1436039 Asbestos11-FC-C 12/29/2022
Reviewed by:
Summary
Sample Layer MasticMethod
PLM 41Emily Nowacki
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
Lab Sample Number Client Sample Number Sample Type Completed
This report is intended for use solely by the individual or entity to which it is addressed. This report may not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this
Certificate of Analysis
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
PLM None Detected 1436007
1-RM-A
PLM 96% OtherPLM 2% Cellulose
PLM 2% Fiberglass
BeigeShingle
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436008
1-RM-B
PLM 92% OtherPLM 4% Cellulose
PLM 4% Fiberglass
BeigeShingle
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436009
1-RM-C
PLM 96% OtherPLM 2% Cellulose
PLM 2% Fiberglass
BeigeShingle
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436010
2-CC-A
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436011
2-CC-B
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436012
2-CC-C
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
PLM None Detected 1436013
3-CC-A
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436014
3-CC-B
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436015
3-CC-C
PLM 98% OtherPLM 2% CelluloseGrayConcrete Chip
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436016
4-EC-A
PLM 98% OtherPLM 2% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436017
4-EC-B
PLM 98% OtherPLM 2% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436018
4-EC-C
PLM 98% OtherPLM 2% CelluloseGrayExterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
PLM 50% Chrysotile1436019
5-GTM-A
PLM 10% OtherPLM 40% CelluloseGrayGasket Material
Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
1436020
5-GTM-B
Positive Stop
Analyst: Chris Canilao
Date Analyzed : 12/29/2022
Sample Not Analyzed
1436021
5-GTM-C
Positive Stop
Analyst: Chris Canilao
Date Analyzed : 12/29/2022
Sample Not Analyzed
PLM None Detected 1436022
6-CA-A
PLM 98% OtherPLM 2% CelluloseBrownConstruction Adhesive
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436023
6-CA-B
PLM 98% OtherPLM 2% CelluloseBrownConstruction Adhesive
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436024
6-CA-C
PLM 98% OtherPLM 2% CelluloseBrownConstruction Adhesive
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
PLM None Detected 1436025
7-GM-A
PLM 98% OtherPLM 2% CelluloseRedCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436025
7-GM-A
PLM 98% OtherPLM 2% CelluloseBrownMortar
Non-Fibrous
Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM 8% Chrysotile1436025
7-GM-A
PLM 90% OtherPLM 2% CelluloseWhiteGrout
Non-Fibrous
Homogenous Layer-3 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436026
7-GM-B
PLM 98% OtherPLM 2% CelluloseRedCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436026
7-GM-B
PLM 98% OtherPLM 2% CelluloseBrownMortar
Non-Fibrous
Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
1436026
7-GM-B
Positive Stop
Layer-3 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
Layer Not Analyzed
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
PLM None Detected 1436027
7-GM-C
PLM 98% OtherPLM 2% CelluloseRedCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436027
7-GM-C
PLM 98% OtherPLM 2% CelluloseBrownMortar
Non-Fibrous
Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
1436027
7-GM-C
Positive Stop
Layer-3 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
Layer Not Analyzed
PLM None Detected 1436028
8-GM-A
PLM 98% OtherPLM 2% CelluloseBlueCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436028
8-GM-A
PLM 98% OtherPLM 2% CelluloseBrownGrout and Mortar
Non-Fibrous
Non-Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
PLM None Detected 1436029
8-GM-B
PLM 98% OtherPLM 2% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436029
8-GM-B
PLM 98% OtherPLM 2% CelluloseBrownGrout and Mortar
Non-Fibrous
Non-Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436030
8-GM-C
PLM 98% OtherPLM 2% CelluloseGrayCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436030
8-GM-C
PLM 98% OtherPLM 2% CelluloseBrownGrout and Mortar
Non-Fibrous
Non-Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436031
9-IC-A
PLM 98% OtherPLM 2% CelluloseWhiteInterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436032
9-IC-B
PLM 98% OtherPLM 2% CelluloseWhiteInterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
PLM None Detected 1436033
9-IC-C
PLM 98% OtherPLM 2% CelluloseWhiteInterior Caulk
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436034
10-GM-A
PLM 98% OtherPLM 2% CelluloseBrownCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436034
10-GM-A
PLM 95% OtherPLM 5% CelluloseBrownGrout and Mortar
Non-Fibrous
Non-Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436035
10-GM-B
PLM 98% OtherPLM 2% CelluloseBrownCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436035
10-GM-B
PLM 95% OtherPLM 5% CelluloseBrownGrout and Mortar
Non-Fibrous
Non-Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
PLM None Detected 1436036
10-GM-C
PLM 98% OtherPLM 2% CelluloseBrownCeramic Tile
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436036
10-GM-C
PLM 95% OtherPLM 5% CelluloseBrownGrout and Mortar
Non-Fibrous
Non-Homogenous Layer-2 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436037
11-FC-A
PLM 98% OtherPLM 2% CelluloseWhite/RedFloor Covering Epoxy
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436038
11-FC-B
PLM 98% OtherPLM 2% CelluloseWhite/RedFloor Covering Epoxy
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
PLM None Detected 1436039
11-FC-C
PLM 98% OtherPLM 2% CelluloseWhite/RedFloor Covering Epoxy
Non-Fibrous
Homogenous Layer-1 Analyst: Chris Canilao
Date Analyzed : 12/29/2022
Lab Supervisor/Other Signatory
Chris Canilao
Analyst:
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
Polarized Light Microscopy Asbestos Analysis Report
Location :
To :
Novi,Michigan 48377
Atlas - Novi
46555 Humboldt Dr. Suite 100
Otsego State Park
7136 Old Highway 27 S., Gaylord, MI 49735
ETL Job :
Client Project :
253484
188BS22768
Environmental Testing Laboratories, Inc.
37575 W Huron River Drive
Romulus, Michigan 48174
(734) 955-6600, Fax: (734) 955-6604
Sample Description Appearance % Fibrous % Non-Fibrous % Asbestos
12/09/2022
12/27/2022
Date Collected :
Date Received :
400 Point Count Results by EPA 600/R-93/116 PLM (denoted by "PC")
Item 198.1: PLM Methods for Identifying and Quantitating Asbestos in Bulk Samples
Item 198.6: PLM Methods for Identifying and Quantitating Asbestos in Non-Friable Organically Bound Bulk Samples
EPA 600/R-93/116: Method for Determination of Asbestos in Bulk Building Materials
EPA 600/M4-82-020: Interim Method for Determination of Asbestos in Bulk Insulation Samples
A % Asbestos result of "Trace" indicates that the analyzed material was found to contain less than 1% asbestos and would not be considered an Asbestos Containing Material (ACM).
ETL, Inc. maintains liability limited to cost of analysis. This report relates only to the samples reported and may not be reproduced without written approval by ETL, Inc. Test Method EPA 600/R-93-116 & EPA 600/M4-82/020 or NYSDOH-ELAP item 198.1 and/or 198.6 was used to analyze all samples. Matrix interference and/or resolution limits (i.e. detecting asbestos in non-friable organically bound materials) may yield false results in certain circumstances. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing. Interpretation and use of test results are the responsibility of the client. ETL, Inc. is not responsible for the accuracy of the results when requested to physically separate and analyze layered samples. Any
PLM results below 10% should be re-analyzed using the EPA recommended Point Count method. Any material that has greater than 1% asbestos content is considered to be an Asbestos Containing Material (ACM). These materials are regulated by both OSHA and the EPA and must be treated accordingly. Results are related to only to samples that were tested. An estimate of uncertainty can be provided at the client's request.
APPENDIX B
LEAD-CONTAINING PAINT LABORATORY REPORT
Certificate of Analysis: Lead In Paint by EPA SW-846 Method 7000B/3050B*
Client Project :
868387
12/22/2022
12/23/2022
Date Reported :
Date Analyzed :
Date Received :
AAT Project :
Phone :
Email :
Fax : 248-669-5147 dawn.lecesne@oneatlas.com
248-669-5140
Dawn LeCesne
Atlas Technical Consultants
Attn :
Client :
7136 OLD HIGHWAY 27 GAYLORD MIProject Location :
188BS22768
Novi, MI 48377
46555 Humboldt Dr.
30105 Beverly Road
Romulus, MI 48174
Ph: 734-629-8161; Fax: 734-629-8431
Sampling Date : 12/09/2022
12/23/2022
Lab Sample ID Result Lead
(% by weight) PPMSample DescriptionClient Code
Calculated R L
(% by weight)
1-LBP-BEIGE EXT BEIGE PAINT8066978 41 0.0041 0.0031
2-LBP-WHITE INT WHITE PAINT8066979 4 0.0004 0.0009
3-LBP-BEIGE INT BEIGE PAINT8066980 4 0.0004 0.0005
Analyst Signature
Tom Hamlin
868387 AAT Project:Date Printed: 12/23/2022 12:00PM
ND = Not Detected, N/A = Not Available, RL = Reporting Limit, Analytical Reporting Limit is 5 ug/sample. For true values assume (2) significant figures. The method, batch, and sample Quality Control are acceptable unless otherwise stated. AAT internal SOP S218. The laboratory operates in accord with ISO 17025 guidelines and holds limited scopes of accreditation under AIHA-LAP and NY State DOH ELAP programs. These results are submitted pursuant to AAT, LLC current terms and conditions of sale, including the company's standard warranty and limitation of liability provisions. Analytical results relate to the samples as received by the lab. Results in mg/cm2 are calculated based on sample area dimensions supplied by the client.AAT will not assume any liability or responsibility for the manner in which the results are used or interpreted. Reproduction of this document other than in its entirety is not authorized by AAT, LLC. AAT does not blank correct reported values. Sample data apply only to items analyzed. Current EPA/HUD Interim Standard for lead in paint samples is: 5000 PPM (parts per million) or ug/g which is equivalent to 0.5% by weight. EPA definition of lead-based paint: 1.0 mg/cm2. New York City Regulatory Limits: 0.25% by weight or 0.5 mg/cm2 for investigations for a child. MD and Philadelphia definition of lead-based paint: 0.7 mg/cm2. Note: Samples are stored for 15 days following report date. *=
Validated modified method
AIHA LAP- Lab ID #100986, NY State DOH ELAP -Lab ID #11864, State of Ohio- Lab ID # 10042
Atlas Technical ConsultantsTo :
Attn :
Phone :
AAT Project :
Client Project :
Date Reported :
Project Location :
Email :Dawn LeCesne
248-669-5140 dawn.lecesne@oneatlas.com
868387
188BS22768
7136 OLD HIGHWAY 27 GAYLORD MI
46555 Humboldt Dr.
Novi, MI 48377
30105 Beverly Road
Romulus, MI 48174
Ph: 734-629-8161; Fax: 734-629-8431
12/23/2022
Sample CompletedAnalysis RequestedClient Code Analyst
8066978 12/23/2022Lead Paint1-LBP-BEIGE Tom Hamlin
8066979 12/23/2022Lead Paint2-LBP-WHITE Tom Hamlin
8066980 12/23/2022Lead Paint3-LBP-BEIGE Tom Hamlin
Quality Assurance Coordinator
Reviewed By Elyse Bidle
868387 AAT Project:Date Printed: 12/23/2022 12:00PM
This report is intended for use solely by the individual or entity to which it is addressed. It may contain information that is privileged, confidential and otherwise exempt by law from disclosure. If the reader of this information is not the intended recipient or an employee of its intended recipient, you are herewith notified that any dissemination, distribution or copying of this information is strictly prohibited. If you have received this information in error, please notify AAT immediately. Thank you.
NY State DOH ELAP -Lab ID #11864, Michigan State Lab # 9996