Fleishman_Park_Shade_Structures_Plans_Final_Rev01_DS.pdf
PDF 5 MB Posted
- Attached to
- Fleishman Park Improvements State and local contract opportunity
- Solicitation number
- 25-020-ITB
- Issued by
- Lee County, Fort Lauderdale City, Florida
About this file
These are structural design plans for the Fleishman Park Improvements project, prepared by the City of Fort Myers Public Works Department and Highspans Engineering, Inc. The project involves replacing twelve dugout shade structures and ten bleacher shade structures at the park, located at 1750 Matthew Drive in Fort Myers, Florida. The design documents include detailed technical specifications for steel frames, drilled shaft foundations, roof structures, and associated components for both dugout and bleacher areas. The project is scheduled for implementation in September 2024, with the final submittal dated October 2024 and contract number 0039-23.
The structural plans specify precise engineering details for each structure, including steel frame configurations, concrete roof volumes, foundation requirements, and material specifications. The designs account for local environmental conditions, with wind load specifications of 176 mph, Category IV, and Exposure C. Soil borings indicate the site consists primarily of fine sand with varying silt content and potential seasonal water table fluctuations. The project includes provisions for extending existing chain-link fencing, color matching existing structures, and careful coordination with park activities to minimize disruption. The engineering approach utilizes Load and Resistance Factor Design (LRFD) methodology and follows Florida Department of Transportation (FDOT) standard specifications for 2024-2025.
View the file
Other files for this state and local contract opportunity
Show all 29
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T H
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BLVD.
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
BLEACHER STEEL FRAME DETAILS
DUGOUT STEEL FRAME DETAILS
DRILLED SHAFT DETAILS
BLEACHER SHADE STRUCTURE
DUGOUT SHADE STRUCTURE
SUMMARY OF QUANTITIES
PROJECT LAYOUT
GENERAL NOTES
KEY SHEET
SHEET DESCRIPTION
LOCATION OF PROJECT
LOCATION OF PROJECT
https://maps.app.goo.gl/2xSTEL6dD19kmgzWA
ON ANY ELECTRONIC COPIES.
AND THE SIGNATURE MUST BE VERIFIED
NOT CONSIDERED SIGNED AND SEALED
PRINTED COPIES OF THIS DOCUMENT ARE
ON THE DATE ADJACENT TO THE SEAL
SIGNED AND SEALED BY
THIS ITEM HAS BEEN DIGITALLY
STATE OF
No 55460
R E
E
NI
GNE LANOIS
SE
F O
R P
ESNECIL
ADIROL
F
ST
IA
W .M SAMO
HT
REVISIONS:
Sheets 2, 3, 4, & 7 (Revised 10/1/2024)
NO.
SHEET
YEAR
FISCAL
S a b ri n a
/2
/2
:5
:1
P M
H
P ro je c t2
\2
S a m F le is h m a n
P a rk \S tr u c tu re s \K e y S h e e t0
.d g n
CONTRACT NO.
PROJECT MANAGER:
CITY OF FORT MYERS
SEPTEMBER 2024
FINAL SUBMITTAL
STRUCTURE PLANS
CITY OF FORT MYERS
PUBLIC WORKS DEPARTMENT
SHEET NO.
following website: http://www.fdot.gov/design/standardplans
Standard Plans for Road Construction and associated IRs are available at the
Bridge Construction and applicable Interim Revisions (IRs).
Florida Department of Transportation, FY 2024-25 Standard Plans for Road and http://www.fdot.gov/programmanagement/Implemented/SpecBooks for Road and Bridge Construction at the following website:
Florida Department of Transportation, FY 2024-25 Standard Specifications
EXPRESSWAY
TU
RN
PIK
E
PENSACOLA FORT WALTON
BEACH
PANAMA
CITY
CHIPLEY
TALLAHASSEE
JACKSONVILLE
ST AUGUSTINE
GAINESVILLE
OCALA DAYTONA BEACH
DELAND
NEW PORT RICHEY
TAMPA
LAKELAND
MELBOURNE -
COCOA
ORLANDO
BARTOWST PETERSBURG
SARASOTA -
BRADENTON
FT PIERCE
FT MYERS
WEST PALM
BEACH
FT LAUDERDALE
MIAMI
NAPLES
KEY WEST
CITY
LAKE
FLO
RID
A'S
BEACH LINE
AYOUB AL-BAHOU, P.E.
ENGINEER OF RECORD:
STRUCTURE PLANS
240039-23
FORT MYERS, FL 33907
1750 MATTHEW DRIVE
S
C L
E V
E L
A N
D A
V E
N U
E
U S
BOY SCOUT DRIVE
S U
M M
E R
L
IN
R D
C
R
FLEISHMAN PARK IMPROVEMENTSINDEX OF STRUCTURE PLANS
GOVERNING DESIGN STANDARDS:
GOVERNING STANDARD SPECIFICATIONS:
COLONIAL BOULEVARD
1 ADDED NOTESDS10/1/2024
T H
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BOULEVARD
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
GENERAL NOTES
GENERAL NOTES GENERAL NOTES (CONTINUED)
MINIMUM SECTION PROPERTIES FOR ALL COLD-FORMED STEEL SECTIONS ARE AS FOLLOWS:f.
COLOR TO MATCH NEIGHBORING BUILDING AND SHALL SUBMIT COLOR TO EOR FOR APPROVAL.
ROOF SYSTEM SHALL BE 22 GAGE SRS 3-1.5 BY CENTRIA OR EOR APPROVED EQUAL. CONTRACTOR SHALL SELECTe.
EQUIVALENT, AND SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
STAY-IN-PLACE FORM SHALL BE 16-GAGE GALVANIZED TYPE 1.5 CDI BY NEW MILLENNIUM, OR ENGINEER APPROVEDd.
Z-PURLINS AND EAVE STRUTS FOR THE FULL BLEACHER ROOF WIDTH OF 24'-6" WITHOUT SPLICES.
MANUFACTURE AND INSTALL STEEL DECK FOR A MINIMUM TWO-SPAN CONDITION. MANUFACTURE AND INSTALLc.
AT 6" O.C., UNLESS OTHERWISE NOTED.
RECOMMENDATIONS AND FASTENER PATTERN NOTED ON PLANS. FASTEN ROOF FLASHING TO ROOF EDGE SUPPORT
FASTEN STANDING SEAM ROOF PANEL DECK TO PURLINS AND EAVE STRUTS FOLLOWING MANUFACTURER'Sb.
STAY-IN-PLACE FORMS, AND POUR STOPS SHALL BE ASTM A653 GRADE 33 WITH A G90 PROTECTIVE ZINC COATING.
COLD-FORMED STEEL FOR ROOF Z-PURLINS, DOUBLE-SLOPE EAVE STRUTS, STANDING SEAM ROOF PANELS,a.
COLD-FORMED STEEL2.
DAMAGED DURING SHIPPING / INSTALLATION.
INCLUDE A MINIMUM OF 2 TOPCOATS, AND A RUST-INHIBITING PRIMER. TOUCH UP ANY COATING AREA EXPOSED OR
WITH THE FDOT SPECIFICATIONS SECTION 560: " COATING NEW STRUCTURAL STEEL." COATING SYSTEM SHALL
ASTM D6386. STEEL FRAME IS TO RECEIVE A SHOP-APPLIED, UV-RESISTANT COATING SYSTEM IN ACCORDANCE
AFTER FABRICATION AND GALVANIZING STEEL FRAME SHALL BE PREPARED FOR PAINTING IN ACCORDANCE WITHd.
SPECIFICATIONS SECTION 562.
GALVANIZED. DAMAGED GALVANIZING SHALL BE TOUCHED UP IN ACCORDANCE WITH FDOT STANDARD
IN ACCORDANCE WITH AWS D1.1 STRUCTURAL WELDING CODE. AFTER WELDING, STEEL FRAMES SHALL BE HOT-DIP
MATERIALS PRIOR TO WELDING. UTILIZE QUALIFIED WELDERS, WELD PROCEDURES, AND INSPECTION PERSONNEL
AMERICAN WELDING SOCIETY. USE E70 SERIES ELECTRODES, AND REMOVE GALVANIZING OR PRIMER FROM
WELDING OPERATIONS MUST BE CONDUCTED IN ACCORDANCE WITH AWS D1.1 STRUCTURAL WELDING CODE BY THEc.
GALVANIZING.
REQUIRED FOR GALVANIZING ARE TO BE INCLUDED IN SHOP DRAWINGS AND SHALL BE PLUGGED AFTER
MATCHING OPEN-ENDED SHAPE. DRAIN HOLES ARE TO BE PROVIDED AS SHOWN IN THE PLANS. ADDITIONAL HOLES
SEAL ALL OPEN ENDED HSS MEMBERS WITH 1/8" PLATE SEAL-WELDED ALL AROUND WITH FILLETS AT CORNERSb.
SHALL BE ASTM A500 GRADE B FOR HSS SECTIONS AND ASTM A36 FOR STEEL PLATES.
STRUCTURAL STEEL FOR STEEL FRAME IS TO BE HOT-DIP GALVANIZED IN ACCORDANCE WITH ASTM A123 ANDa.
STRUCTURAL STEEL1.
MATERIALSG.
UTILITIES: NO ALLOWANCE FOR UTILITY LOADS HAS BEEN INCLUDED IN THIS DESIGN.4.
WIND LOAD: BASIC WIND SPEED = 176 MPH, CAT. IV, EXP. C3.
LIVE ROOF LOAD: 20 PSF2.
STRUCTURAL STEEL: 490 PCF
REINFORCED CONCRETE: 150 PCF
DEAD LOADS:1.
DESIGN LOADINGSF.
ALLOWABLE STRESS DESIGN (ASD) METHOD EXCLUSIVELY FOR FOUNDATION STABILITY.2.
LOAD AND RESISTANCE FACTOR DESIGN (LRFD) METHOD USING STRENGTH AND SERVICE LIMIT STATES.1.
DESIGN METHODOLOGYE.
OTHERWISE NOTED.
ALL DIMENSIONS IN THESE PLANS ARE MEASURED IN FEET EITHER HORIZONTALLY OR VERTICALLY UNLESS2.
DO NOT SCALE DRAWINGS FOR DIMENSIONS NOT GIVEN.1.
DRAWINGS AND DIMENSIONSD.
VERTICAL DATUM: N/AC.
BY CONTRACT DOCUMENTS.
APPENDED HEREIN, AND FY 2024-25 STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION, AS AMENDED
FLORIDA DEPARTMENT OF TRANSPORTATION, FY 2024-25 STANDARD PLANS AND REVISED INDEX DRAWINGS AS
GOVERNING STANDARDS AND CONSTRUCTION SPECIFICATIONSB.
2016 EDITION.
AISI S100-16 NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS,5.
AISC STEEL CONSTRUCTION MANUAL, 15TH ED. (2017).4.
ACI 318-19 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, 2019 EDITION.3.
ASCE/SEI 7-22 MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND OTHER STRUCTURES. 2.
FLORIDA BUILDING CODE - BUILDING, 8TH EDITION (2023).1.
DESIGN SPECIFICATIONSA.
PRIOR TO INSTALLATION. STEEL FRAME SHALL BE COATED GREEN TO MATCH OF EXISTING BUILDING COLUMNS.
APPROVAL. APPLY WHITE MATCHING EXISTING BUILDING ROOF TO ALL STANDING SEAM ROOF PANELS AND ROOF FLASHING
CONTRACTOR SHALL SELECT COLORS TO MATCH EXISTING CONCESSION BUILDING AND SUBMIT COLORS TO EOR FOR
AESTHETICSO.
SCHEDULE PRIOR TO START.
ANTICIPATE AND COORDINATE CONSTRUCTION STOP WORKS WITH THE CITY OF FORT MYERS AND SHALL PROVIDE A WORK
PARK WILL BE UNAVAILABLE FOR CONSTRUCTION ACTIVITIES DURING CERTAIN SPORT SEASONS. THE CONTRACTOR SHALL
HOURS WITH CITY OF FORT MYERS OFFICIALS IN ORDER TO AVOID CONFLICTS WITH NORMAL PARK ACTIVITIES. THE
CONTRACTOR SHALL COORDINATE ALL CONSTRUCTION ACTIVITIES SUCH AS DELIVERIES, STORAGE, PARKING, AND WORK
COORDINATIONN.
SITE ACCESS WILL BE RESTRICTED AND SUBJECT TO OWNER'S SECURITY PROCEDURES.5.
WORK HOURS: COORDINATE WITH THE OWNER.4.
STORAGE IS NECESSARY, OBTAIN AND PAY FOR SUCH STORAGE OFF SITE.
MATERIALS AND LOCATION OF STORAGE TO AREAS IN THE IMMEDIATE VICINITY OF THE WORK. IF ADDITIONAL
DO NOT UNREASONABLY ENCUMBER THE SITE WITH MATERIALS OR EQUIPMENT AND CONFINE STOCKPILING OF3.
ENGAGED IN PROJECT CONSTRUCTION.
BEYOND AREAS ON WHICH WORK IS INDICATED ARE NOT TO BE DISTURBED. CONFORM TO SITE RULES WHILE
CONFINE OPERATIONS AT THE SITE TO THE AREAS PERMITTED UNDER THE CONTRACT. PORTIONS OF THE SITE2.
OF THE EXISTING BUILDINGS AND FACILITIES THROUGHOUT CONSTRUCTION.
LIMIT THE USE OF THE PREMISES TO ACTIVITIES DESIGNATED IN THE PLANS AND ALLOW FOR OWNER OCCUPANCY1.
USE OF THE PREMISESM.
BE REPLACED WHICH SHALL INCLUDE TWELVE DUGOUT SHADE STRUCTURES AND TEN BLEACHER SHADE STRUCTURES.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR DEMOLITION AND DISPOSAL OF ALL EXISTING SHADE STRUCTURES TO
REMOVAL OF EXISTING STRUCTURESL.
CONSTRUCTION JOINTS OR ALTERATIONS TO THOSE SHOWN SHALL REQUIRE APPROVAL OF THE ENGINEER.
CONSTRUCTION JOINTS WILL BE PERMITTED ONLY AT THE LOCATIONS INDICATED IN THE PLANS. ADDITIONAL
JOINTS IN CONCRETEK.
APPLIED.
STANDARD SECTION 522. C.I.P. ROOFS SHALL BE FINISHED SMOOTH AND SHALL HAVE A RUBBERIZED ROOF COATING
APPLY BROOM SURFACE FINISH TO THE TOP SURFACE OF ALL C.I.P. SLABS AND C.I.P. DRILLED SHAFTS PER FDOT
CONCRETE FINISH COATINGJ.
CONSTRUCTION.
RELEVANT UTILITY LOCATIONS AND COORDINATE RELOCATIONS AS NEEDED WITH CITY OF FORT MYERS PRIOR TO
ALL KNOWN UTILITIES ARE IRRIGATION AND MINOR ELECTRIC UNDERGROUND LINES. CONTRACTOR SHALL VERIFY ALL
UTILITIESI.
ACHIEVE A NUT ROTATION OF 1/6 TURN. ALL OTHER BOLTS SHALL BE SNUG TIGHT.
THE FLAT SURFACE OF NUT AND A CORRESPONDING MARK ON THE BASE PLATE OF EACH BOLT, AND TURN NUT TO
TIGHT POSITION, MARK REFERENCE POSITION OF EACH NUT IN A SNUG TIGHT POSITION WITH A SUITABLE MARK ON
BASE PLATE BOLTS SHALL BE INSTALLED USING THE TURN-OF-THE-NUT METHOD. TIGHTEN THE NUTS TO A SNUG1.
BOLT INSTALLATIONH.
CENTERLINE OF BAR EXCEPT WHERE CLEAR DIMENSION IS NOTED TO FACE OF CONCRETE.
TOLERANCES. ALL DIMENSIONS PERTAINING TO THE LOCATION OF REINFORCING STEEL ARE TO
TOLERANCES UNLESS SHOWN AS "MINIMUM COVER". SEE SPECIFICATIONS SECTION 415 FOR ALLOWABLE
CONCRETE COVER DIMENSIONS SHOWN IN THE PLANS DO NOT INCLUDE PLACEMENT AND FABRICATION*
ALL CAST IN PLACE CONCRETE SHALL USE TYPE II CEMENT.c.
STRUCTURAL GROUT SHALL BE IN ACCORDANCE WITH FDOT STANDARD SPECIFICATIONS 934.b.
ALL CONCRETE SHALL BE IN ACCORDANCE WITH FDOT STANDARD SPECIFICATIONS 346.a.
CONCRETE5.
C.I.P. ROOF, SLAB ON GRADE, AND DRILLED SHAFTS: ASTM A615, GRADE 60 CARBON STEELa.
REINFORCING MATERIALS4.
PLATE WASHERS: ASTM A36 (2 PER BOLT)e.
NUTS: ASTM A563 GRADE A HEAVY-HEX (5 PER ANCHOR BOLT)d.
OTHER BOLTS: ASTM A307 GRADE Ac.
ANCHOR BOLTS: ASTM F1554 GRADE 55b.
OTHERWISE NOTED.
ALL BOLTS, NUTS, AND WASHERS SHALL BE HOT-DIPPED GALVANIZED IN ACCORDANCE WITH ASTM F2329, UNLESSa.
BOLT ASSEMBLIES3.
CONCRETE CLASS
COMPRESSIVE STRENGTH (PSI)
MIN. 28-DAY
IN STRUCTURE
LOCATION OF CONCRETE
II 3,400 C.I.P. ROOF
IV (DRILLED SHAFT) 4,000 C.I.P. DRILLED SHAFT
SLUMP (IN)
TARGET
3 ±1
±12
COVER (IN) *
CONCRETE
II 3,400 SLAB ON GRADE 2
3 ±1 3
RLP 4/24
TMW 4/24
TMW 4/24
RLP 4/24
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
ROAD NO. COUNTY CITY PROJECT NO.
REVISIONS
DATE BY DESCRIPTION DATE BY DESCRIPTION
LEE 0039-23
/2
/2
:5
:3
P
M
H
P r o je c t2
\2
S a m
F le is h m a n P a r k \S tr u c tu r e s \G e n e r a lN o te s .d g n
SECTION LOCATION
(in)
DEPTH
(in)
WIDTH
GAGE
(in3)
Sp
(in3)
Sn
Z-PURLIN BLEACHER 4" 2½" 14 1.029 -
C-CHANNEL EAVE STRUT * BLEACHER 4" 2½" 14 0.952 -
C-CHANNEL EDGE BEAM BLEACHER 4" 2½" 14 0.952 -
STANDING SEAM ROOF PANEL ** BLEACHER 3" - 22 0.123 0.094
STAY-IN-PLACE FORM ** DUGOUT 1½" - 16 0.390 0.395
POUR STOP DUGOUT 3½" SEE DETAILS 10 - -
* EAVE STRUT SHALL BE FABRICATED WITH A HIGH/LOW DOUBLE-SLOPE 2:12 PITCH.
** Sp AND Sn VALUES ARE PER FOOT OF WIDTH.
FLEISHMAN PARK IMPROVEMENTS
1 ADDED BORINGSSDS10/1/2024
T H
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BOULEVARD
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
PROJECT LAYOUT
MATTHEW DRIVE
AS DETAILED HEREIN.
ALL TWELVE DUGOUT ROOFS LABELED IN THE PLAN VIEW SHALL BE REPLACED2.
AS DETAILED HEREIN.
ALL TEN BLEACHER ROOFS LABELED IN THE PLAN VIEW SHALL BE REPLACED1.
NOTES:
LEGEND
- APPROXIMATE HAND AUGER BORING LOCATION
CB - CONCESSION BUILDING
- DUGOUT ROOF (SEE NOTE 2)DR
- BLEACHER ROOF (SEE NOTE 1)BR
- SOFTBALL FIELDSOF
- BASEBALL FIELDBSB
SOF-06
DR11
DR12
BSB-01BSB-03
BSB-02
SOF-04
SOF-05
DR9
DR10
DR8
BR8
DR7
BR7
DR2
BR2
BR1
DR1
DR3
BR3
BR4
DR4
DR7
DR6
BR6
BR5
DR5
APPROX. PROPERTY BOUNDARY
BR9
BR10
CB
B-3
B-4
B-1
B-2
RLP 4/24
TMW 4/24
TMW 4/24
RLP 4/24
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
ROAD NO. COUNTY CITY PROJECT NO.
REVISIONS
/2
/2
:5
:4
P
M
H
P r o je c t2
\2
S a m
F le is h m a n
P a r k
\S tr u c tu r e s \P r o je c tL a y o u t.
d g n
1 REVISED QUANTITIESSDS10/1/2024
147.3
147.3
147.3
147.3
147.3
147.3
206.2
206.2
147.3
147.3
147.3
147.3
176.7
176.7
176.7
176.7
176.7
176.7
176.7
176.7
176.7
176.7
T H
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BOULEVARD
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
SUMMARY OF QUANTITIES
DUGOUT AND BLEACHER ROOF QUANTITIES ARE FOR BIDDING PURPOSES ONLY.
NOTE:
RLP 4/24
TMW 4/24
TMW 4/24
RLP 4/24
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
ROAD NO. COUNTY CITY PROJECT NO.
REVISIONS
/2
/2
:5
:0
P
M
H
P r o je c t2
\2
S a m
F le is h m a n P a r k \S tr u c tu r e s \S u m m a r y O f Q u a n ti ti e s .d g n
DUGOUT ROOF TABLE OF QUANTITIES
I.D.
TYPE
PER STRUCT.
NUMBER OF FRAMES PLAN AREA CONC. ROOF VOL. CONC. FND. VOL. EST. WT. PER FRAME
(SEE PLAN VIEWS) (SF) (CF) (CF) (LB)
DR1 1 5 336.0 73.2 171.8 405
DR2 1 5 336.0 73.2 171.8 405
DR3 1 5 336.0 73.2 171.8 405
DR4 1 5 336.0 73.2 171.8 405
DR5 1 5 336.0 73.2 171.8 405
DR6 1 5 336.0 73.2 171.8 405
DR7 2 7 443.6 96.0 240.5 405
DR8 2 7 443.6 96.0 240.5 405
DR9 1 5 336.0 73.2 171.8 405
DR10 1 5 336.0 73.2 171.8 405
DR11 1 5 336.0 73.2 171.8 405
DR12 1 5 336.0 73.2 171.8 405
BLEACHER ROOF TABLE OF QUANTITIES
I.D.
PER STRUCT.
NUMBER OF FRAMES PLAN AREA ROOF AREA EST. EAVE STRUT LENGTH EST. EDGE BEAM LENGTH EST. PURLIN LENGTH CONC. FND. VOL. EST. FRAME WT.
(SF) (SF) (LF) (LF) (LF) (CF) (LB)
BR1 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR2 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR3 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR4 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR5 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR6 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR7 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR8 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR9 4 392.0 397.4 49.0 32.4 122.5 216.0 924
BR10 4 392.0 397.4 49.0 32.4 122.5 216.0 924
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BOULEVARD
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
DUGOUT SHADE STRUCTURE
ELEVATION VIEW
LINK FENCE
EXISTING CHAIN
EXPANSION JOINT. SUBMIT PRODUCTS TO EOR FOR APPROVAL.
THE EXPANSION JOINT ABOVE AND BELOW THE WATERSTOP. NO REINFORCEMENT SHALL EXTEND ACROSS THE
RECOMMENDATIONS. 1/2" THICK PREFORMED JOINT FILLER CONFORMING TO ASTM D8139 SHALL BE USED TO COMPLETE
EQUAL SHALL BE EMBEDDED MID-HEIGHT IN THE EXPANSION JOINT IN ACCORDANCE WITH MANUFACTURER'S
BE CENTERED ON A 2" THICK SECTION OF CONCRETE. A SIKA GREENSTREAK #701 WATERSTOP OR EOR APPROVED
4. A CONTINUOUS EXPANSION JOINT SHALL BE PROVIDED ALONG THE LENGTH OF THE ROOF AS SHOWN. THE JOINT SHALL
CLEARANCE TO STEEL FRAME. ALL CHAIN-LINK EXTENSION MATERIALS SHALL MATCH EXISTING.
REPLACED TO MATCH EXTENDED FRONT POSTS. POST EXTENSIONS SHALL BE FIELD CUT TO PROVIDE 1" OF
THE TWO FRONT POSTS SHALL HAVE AN EXTENSION SPLICED AND THE TWO 6'-0" PANELS OF CHAIN-LINK SHALL BE
1 THROUGH 10, EXISTING CHAIN-LINK WALL SHALL BE EXTENDED HIGHER AS SHOWN. FOR EACH OF THESE DUGOUTS, FOR DUGOUTS 11 AND 12, NO CHAIN-LINK WALL EXISTS, AND THE EXISTING CMU WALL HEIGHT IS 6'-0". FOR DUGOUTS3.
SHALL BE TAKEN TO AVOID POSSIBILITY OF WATER PONDING.
CURING WITH TUNDRA SILICONE RUBBERIZED WHITE ROOF COATING BY KOOL SEAL OR EOR APPROVED EQUAL. CARE
THROUGHOUT WITH A MINIMUM COVER OF 1". CONCRETE SHALL BE FINISHED SMOOTH AND SHALL BE COATED AFTER
PROPOSED CONCRETE ROOF SHALL BE CAST 2" THICK AND SHALL HAVE 6x6xW1.4xW1.4 WELDED WIRE FABRIC2.
DRILLED SHAFT DETAIL SHEET.
TO BE SAW-CUT AND REMOVED AS NEEDED TO ALLOW INSTALLATION OF DRILLED SHAFT ADJACENT TO CMU WALL. SEE
DRILLED SHAFT SHALL BE FINISHED FLUSH WITH EXISTING CONCRETE SLAB. MINIMAL EXISTING CONCRETE SLAB IS1.
NOTE:
DR 1-12 (SEE NOTE 3)
PLAN VIEW (TYPE 1)
PROPOSED SHADE ROOF
LINK FENCE
EXISTING CHAIN
DR 1-6 & DR 9-12
PLAN VIEW (TYPE 2)
DR 7-8
LINK FENCE
EXISTING CHAIN
PROPOSED SHADE ROOF
42'-0"
32'-0"
" (TYP.)4
7'-5
FRAME (TYP.)
STRUCTURAL STEEL
FRAME (TYP.)
PROPOSED STEEL
SHAFT (TYP.)
PROPOSED DRILLED
SHAFT (TYP.)
PROPOSED DRILLED
CHAIN LINK WALL
EXISTING CMU AND
CHAIN LINK WALL
EXISTING CMU AND
"2
1'-129'-9""2
1'-1
"2
1'-139'-9""2
1'-1
6'-0"
(SEE NOTE 3)
CHAIN-LINK WALL
EXISTING
SLAB
CONCRETE
EXISTING
(SEE NOTE 3)
CMU WALL
EXISTING COLUMN
STEEL
FORMS (SEE NOTE 2)
STAY-IN-PLACE DECK
CONCRETE ROOF WITH
10'-6"
(TYP.)
STEEL BRACE
(SEE NOTE 1)
SHAFT
DRILLED
STEEL CANTILEVER
EXTENSION (SEE NOTE 3)
PROPOSED CHAIN-LINK WALL
"4
10"16
1'-2
1'-3"
4'-8"
JOINT (SEE NOTE 4)
CONCRETE EXPANSION
30'-0"
" (TYP.)2
6'-7
RLP 4/24
TMW 4/24
TMW 4/24
RLP 4/24
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
ROAD NO. COUNTY CITY PROJECT NO.
REVISIONS
/2
/2
:5
:0
P
M
H
P r o je c t2
\2
S a m
F le is h m a n P a r k \S tr u c tu r e s \D u g o u t.
d g
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BOULEVARD
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
BLEACHER SHADE STRUCTURE
LINK FENCE
EXISTING CHAIN
SLAB
CONCRETE
EXISTING
STEEL COLUMN
ROOF PANELS (SEE NOTE 5)
STRUCTURAL STEEL STANDING SEAM
"2
16'-02'-0"
(SEE NOTE 3)
BLEACHERS
EXISTING
FRAME (TYP.)
STRUCTURAL STEEL
24'-6"
ROOF (SEE NOTE 4)
PROPOSED SHADE
LINK FENCE
EXISTING CHAIN
FOUNDATION (TYP.)
DRILLED SHAFT
LOCATION
BLEACHER
PROPOSED
(SEE NOTE 1)
DRILLED SHAFT
ELEVATION VIEW
SUBMITTED TO EOR FOR APPROVAL.
ROOFING FELT SHALL BE APPLIED TO TOP SURFACE. SEALANT STAIN AND ROOFING FELT PRODUCT SHALL BE
INSTALATION OF PLYWOOD FASTENERS, SEALANT STAIN SHALL BE APPLIED ON ALL SURFACES OF THE PLYWOOD, AND
BE FASTENED TO ALL PURLINS WITH SIMPSON STRONG-TIE PPHDQ134 #10 SCREWS AT 6" O.C. SPACING. AFTER
JOIN EDGES PER MANUFACTURER'S RECOMMENDATIONS WITH A MAXIMUM CLIP SPACING OF 1'-0" O.C. PLYWOOD SHALL
THAT DO NOT TERMINATE DIRECTLY OVER STEEL PURLINS SHALL UTILIZE SIMPSON STRONG-TIE PSCL3/4 CLIPS TO
PLYWOOD PANELS SHALL BE AB MARINE GRADE PRESSURE-TREATED FIR PLYWOOD PER ASTM 2559. ALL PANEL EDGES6.
HEX HEAD TYPE "A" SCREWS SHALL BE USED TO ANCHOR TO PLYWOOD.
HEX HEAD TYPE "AB" SELF TAPPING SCREWS SHALL BE USED TO ANCHOR CLIPS TO PURLINS. OTHERWISE, #14-10x3/4
TWO FASTENERS SHALL BE USED PER CLIP AND ALL FASTENERS SHALL BE ZINC-PLATED CARBON STEEL. #1/4-14x1
ANCHOR CLIPS SHALL BE SPACED AT 1'-6" O.C. MAX AND SHALL BE PLACED AT EVERY PURLIN-SEAM INTERSECTION.
ANCHOR CLIPS SHALL BE INSTALLED IN THE STANDING SEAMS PER THE MANUFACTURER'S RECOMMENDATIONS.5.
LOCATIONS OF THE PROPOSED STRUCTURES FOR APPROVAL BY EOR.
FENCE. PRIOR TO REMOVAL OF THE EXISTING STRUCTURES, CONTRACTOR SHALL SUBMIT PLAN SHOWING DIMENSIONED
CENTERED ON THE EXISTING SHADE STRUCTURE FOUNDATIONS IN THE DIRECTION PARALLEL TO THE CHAIN-LINK
PROPOSED SHADE STRUCTURE IS TO BE DISTANCED FROM EXISTING CHAIN-LINK FENCE AS SHOWN AND SHALL BE4.
ANCHORS SHALL BE EMPLOYED WITH A MINIMUM DIAMETER AND LENGTH OF 1/2" AND 6", RESPECTIVELY.
AT A MINIMUM, FOUR EPOXYANCHORED TO CONCRETE SLAB WITH EPOXY ANCHORS MATCHING EXISTING SIZES.
EXISTING BLEACHERS SHALL BE RELOCATED DURING CONSTRUCTION TO THE PROPOSED LOCATION SHOWN AND3.
HOLES IN BOTTOM FLANGE AT IT'S LOWEST POINT @ 24" O.C. TO PREVENT MOISTURE RETENTION.
ORIENT PURLINS WITH BOTTOM FLANGE DOWN SLOPE. FOR ALL PURLINS AND EAVE STRUTS, PROVIDE 1/4" Ø DRAIN2.
SEE DRILLED SHAFT DETAIL SHEET.REMOVED SHALL BE RECAST AFTER DRILLED SHAFT INSTALLATION.
IS TO BE SAW-CUT AND REMOVED AS NEEDED TO ALLOW INSTALLATION OF DRILLED SHAFT. ANY EXCESS SLAB
MINIMAL EXISTING CONCRETE SLABDRILLED SHAFT SHALL BE FINISHED FLUSH WITH EXISTING CONCRETE SLAB. 1.
NOTE:
"2
3'-2
STEEL CANTILEVER
(SEE NOTE 2)
Z-PURLINS
STEEL BRACE (TYP.)
ROOF FRAMING PLAN
BR 1-10
"16
2'-18'-9"4'-0"
(SEE NOTE 2)
EAVE STRUT
1'-0"7'-6"7'-6"7'-6"1'-0"
(TYP.)
STEEL Z PURLIN
SYSTEM (SEE NOTE 5)
STANDING SEAM ROOFING
(SEE NOTE 6)
" PLYWOOD PANELS4
EAVE STRUT (TYP.)
STEEL C-CHANNEL
EDGE BEAM (TYP.)
STEEL C-CHANNEL
RLP 4/24
TMW 4/24
TMW 4/24
RLP 4/24
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
ROAD NO. COUNTY CITY PROJECT NO.
REVISIONS
/2
/2
:5
:0
P
M
H
P r o je c t2
\2
S a m
F le is h m a n
P a r k
\S tr u c tu r e s \B le a c h e r .d g
TABLE, ADDED NOTES
REVISED QUANTITIES, ADDED BORING
SDS10/1/2024
T H
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BOULEVARD
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
C
O V
E R
(T O
P
WASHER (TYP.)
DOUBLE NUT WITH
& � COLUMN
� DRILLED SHAFT
'DB'
COLUMN
BASE PLATE
(SEE NOTE 2)
GROUT PAD
'D A
S H
A F
T L
E N
G T
H
(SEE NOTE 1 & 3)
" � ANCHOR BOLTS8
4" COVER
(TYP.)
EQUALLY SPACED
'RB' # 'RA' BARS
FOUNDATION ELEVATION
(SEE DRILLED SHAFT DATA TABLE FOR VARIABLES)
FOUNDATION PLAN
DRILLED SHAFT
CENTER OF
'DB'
SHAFT DIAMETER
2'-0" LAP (MIN.)
(TYP.)
EQUALLY SPACED
'RB' # 'RA' BARS
#4 TIE BARS
BASE PLATE CONNECTION PLAN
AND COLUMN
SHAFT, BASE PLATE,
CENTER OF DRILLED
ANCHOR BOLTS
� COLUMN AND
EDGE OF FOUNDATION
COLUMN
BASE PLATE
EDGE OF (SEE NOTE 1 & 3)
" � ANCHOR BOLTS8
DRILLED SHAFT DETAILS
AFTER DRILLED SHAFT CONSTRUCTION, SLAB SHALL BE RECAST TO FULL DEPTH OF SURROUNDING SLAB.
CONTRACTOR SHALL REMOVE AND DISPOSE A MINIMAL AREA OF SLAB ON GRADE AS REQUIRED AT LOCATIONS OF PROPOSED DRILLED SHAFTS.6.
TO AVOID COLLAPSE.
THE WATER TABLE MAY VARY SEASONALLY AND BE FOUND AT SHALLOW DEPTHS. THE CONTRACTOR SHOULD ASSUME CASING MAY BE REQUIRED5
ACHIEVE REQUIRED DEPTH.
DUE TO SHALLOW LIMESTONE PRESENCE IN GEOLOGIC AREA CONTRACTOR SHOULD ASSUME DRILLING THROUGH ROCK MAY BE REQUIRED TO4.
POURED AT THE SAME TIME SO THAT TEMPLATE AND ANCHOR BOLTS CAN BE INSTALLED AND ADJUSTED PRIOR TO CONCRETE CURING.
ANCHOR BOLTS SHALL MATCH THE BASE PLATE DIMENSIONS AND OVERALL SPACING. EACH STRUCTURE SHALL HAVE ALL DRILLED SHAFTS BE ONE CONTINUOUS CONSTRUCT THAT HOLDS ALL ANCHOR BOLTS IN PLACE DURING CONCRETE CURING. HOLES IN THE TEMPLATE FOR THE TO ENSURE CORRECT ALIGNMENT OF ANCHOR BOLTS, A TEMPORARY TEMPLATE SHALL BE USED DURING CONSTRUCTION. THIS TEMPLATE SHALL3.
MANUFACTURER'S RECOMMENDATIONS.
DIRT AND DEBRIS. INSTALL SELF-CONSOLIDATING STRUCTURAL GROUT PAD IN ACCORDANCE WITH FDOT SPECIFICATIONS 934 AND WITH STRUCTURAL GROUT AS SHOWN. PRIOR TO GROUT INSTALLATION, FLUSH THE TOP OF THE DRILLED SHAFT WITH WATER TO REMOVE ANY AFTER TIGHTENING OF THE BASE PLATE BOLT ASSEMBLIES, THE VOID BETWEEN THE BASE PLATE AND THE DRILLED SHAFT SHALL BE FILLED2.
MATCH FRAME COLOR.
NOTES. INDIVIDUAL NUT COVERS SHALL BE PROVIDED TO EACH BASE PLATE BOLT MADE FROM GALVANIZED STEEL AND SHOP-PAINTED TO THE RETAINER NUTS AND THEN THE ANCHOR NUTS SHALL BE TIGHTENED USING THE TURN-OF-THE-NUT METHOD DEFINED IN THE GENERAL
3/8" AWAY THE DRILLED SHAFT. UPON ADJUSTING THE LEVELING NUTS TO THEIR FINAL CONDITION,-WITH THE BASE PLATE AND LESS THAN 1 LEVELING NUTS SHALL BE ADJUSTED SO THAT FRAME IS IN PROPOSED ORIENTATION, AND LEVELING NUTS SHALL ALL BE IN SOLID CONTACT1.
NOTES:
"8
1"
T
IE
B A
R S
T
IE
B A
R S
R E
M A
IN
IN
G
S
P A
C E
S
S P
A C
E S
M A
X
RLP 4/24
TMW 4/24
TMW 4/24
RLP 4/24
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
ROAD NO. COUNTY CITY PROJECT NO.
REVISIONS
/2 /2
:5
:0
P
M
H P ro je c t2
\2
S a m
F le is h m a n P a rk
\S tr u c tu re s \D ri ll e d S h a ft D e ta il s .d g n
HAND AUGER BORING TABLES
Location : B-1 (SEE PROJECT LAYOUT SHEET)
Elevation (Approximate): +20 Feet
Depth From (Feet) Depth To (Feet) Soil Description Soil Classification (USCS)
0.0 2.5 Dark brown fine sand with silt SP-SM
2.5 5.0 Brown fine silty sand SM
5.0 6.5 Light brown fine sand with trace shell SP
6.5 8.5 Brown fine sand with silt SP-SM
8.5 + Hole caving, possible water table No sample collected
Location : B-2 (SEE PROJECT LAYOUT SHEET)
Elevation (Approximate): +20 Feet
Depth From (Feet) Depth To (Feet) Soil Description Soil Classification (USCS)
0.0 2.5 Dark brown fine sand with silt SP-SM
2.5 9.5 Light brown fine sand with trace shell SP
9.5 + Hole caving, possible water table No sample collected
Location : B-3 (SEE PROJECT LAYOUT SHEET)
Elevation (Approximate): +20 Feet
Depth From (Feet) Depth To (Feet) Soil Description Soil Classification (USCS)
0.0 0.5 Dark brown fine sand with silt SP-SM
0.5 4.5 Brown fine sand with trace shell SP
4.5 5.0 White fine sand SP
5.0 + Hand auger refusal, possible rocky stratum or limestone No sample collected
Location : B-4 (SEE PROJECT LAYOUT SHEET)
Elevation (Approximate): +20 Feet
Depth From (Feet) Depth To (Feet) Soil Description Soil Classification (USCS)
0.0 1.0 Light brown fine sand SP
1.0 8.0 Dark brown fine sand with trace shell and trace roots SP
8.0 + Hole caving, possible water table No sample collected
DRILLED SHAFT DATA TABLE
LOCATION
(ft)
DA
(ft)
DB
RA RB
DRILLED SHAFTS
QUANTITY OF
DUGOUT 7 2.5 9 8 64
BLEACHER 11 2.5 9 8 40
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BOULEVARD
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
DUGOUT STEEL FRAME DETAILS
DUGOUT STEEL FRAME
W.P.
PLT.
x2
WELD DETAIL
SEE BRACE TO HSS
PLT.
x2
H
S S x x
SEE GENERAL NOTES)
ENDED MEMBERS (TYP.,
PLATE SEAL-WELD OPEN
PLATE DETAIL
SEE DUGOUT BASEBRACE TO HSS WELD DETAIL
SECTION A-A
8"
"2
10 (SEE NOTE 6)
STIFFENER PLT.
CONNECTION TO
SLOTTED HSS
" BASE PLATE THK.4
DUGOUT BASE PLATE DETAIL
TO STIFFENER PLT.
SLOTTED CONNECTION
W/ 16
HSS 6x3x
" STIFFENER PLT.2
"x2
IN BASE PLATE (TYP.)
INDICATED LOCATIONS
" HOLE AT4
PROVIDE 1
" BASE PLATE THK.4
CONNECTION
AT SLOTTED
6"
" PLT.8
"x2
EACH HSS MEMBER
CENTERED ON
PLACE BRACE PLT.
AA
2""2
82"
° 4
"16
111'-2
"16 19'-5
"16
"8 51'-2
CONNECTION DETAIL
DUGOUT COLUMN
"8
"8
"4
HSS COLUMN
(2 PER FRAME)
SIDE OF CONNECTION
" STL. PLT. ON EA.8
HSS CANTILEVER
6"
CONNECTION DETAIL
SEE DUGOUT COLUMN
1-12 @ 12" O.C.
" � HOLE8
1 1-12
1L2x2x
5HSS 6x3x
CONNECTION DETAIL
DUGOUT ROOF
DUGOUT ROOF CANTILEVER END DETAIL
DUGOUT ROOF OVERHANG DETAIL
WELDING OF THE HSS SECTION.
DURING FABRICATION, ALL STIFFENER PLATE TO BASE PLATE WELDS SHALL BE COMPLETED PRIOR TO ADDITION AND6.
5. CLEAR SILICONE CAULK IS TO BE USED TO SEAL ALL SEAMS BETWEEN HSS SECTIONS.
AWAY FROM THE EDGE AS SHOWN IN DUGOUT ROOF OVERHANG DETAIL.
4. EXTERIOR STEEL FRAMES SHALL BE FABRICATED SO THAT L2x2x1/8 SECTION IS ON THE HSS 4x3x1/4 SIDE THAT IS
MANUFACTURER'S RECOMMENDATIONS.
CENTERED OVER HSS SECTION. ALL BUTT JOINTS SHALL BE ACCOMPLISHED IN ACCORDANCE WITH ALL S.I.P. FORM
3. IF S.I.P. DECK FORMS REQUIRE SPLICES TO ACHIEVE REQUIRED LENGTH, BUTT JOINTS SHALL BE USED AND SHALL BE FLAT HEAD CONCRETE SCREWS @ 6" SPACING O.C. (MAX). APPLY COOL-SEAL COATING TO TOP OF ROOF PER GENERAL NOTES.
FASTEN THE FLASHING TO CONCRETE AND SIDE OF POUR STOP WITH EPOXY SEALANT AND 3/16" x 1-1/4” TAPCON STAR2.
FREE OF GREASE AND DEBRIS. FILL SAW CUTS WITH RAPID CURE SILICONE AND INSTALL FLASHING.
EARLY ENTRY SAW CUTTING IS REQUIRED PER FDOT SPECIFICATIONS SECTION 400-9.7. SAW CUTS SHALL BE CLEAN AND1.
NOTES:
.5
1'-0" OVERHANG
5HSS 6x3x
(SEE NOTE 4)8
1L 2x2x
" � BOLTS @ 12" O.C.4
S.I.P. FORMS W/ END CAP
")2 1(1'-5"x3
10 GAGE POUR STOP
VERTICAL HEIGHT)
EDGE FLASHING (6" MIN.
24 GAGE Z-SHAPE DRIP
POUR STOP (SEE NOTE 2)
TO CONCRETE AND
FASTEN THE FLASHING
HOOKED BARS @ 12" O.C.
2'-0" #3 STANDARD 180-DEG
6x6xW1.4xW1.4 WWF
" SAW CUT (SEE NOTE 1)2
1L 2x2x
5HSS 6x3x
POUR STOP AT EACH FRAME
BOLTED CONNECTIONS FOR
PROVIDE A MINIMUM OF TWO
(SEE NOTE 1)
" SAW CUT2
S.I.P. FORMS
VERTICAL HEIGHT)
EDGE FLASHING (6" MIN.
24 GAGE Z-SHAPE DRIP
POUR STOP (SEE NOTE 2)
TO CONCRETE AND
FASTEN THE FLASHING
")2 1STOP (1'-5"x3
10 GAGE POUR
AT BOTTOM END OF HSS
" � DRAIN HOLE2
1PROVIDE
AT BOTH SIDES OF HSS
" � DRAIN HOLE2
1PROVIDE
HSS 6x3x
"8
1'-4
SEE NOTE 5
RLP 4/24
TMW 4/24
TMW 4/24
RLP 4/24
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
ROAD NO. COUNTY CITY PROJECT NO.
REVISIONS
/2 /2
:5
:0
P
M
H P ro je c t2
\2
S a m
F le is h m a n P a rk
\S tr u c tu re s \D u g o u tS te e lF ra m e D e ta il s .d g
E O
F F
I C
I A
L R
E C
O R
D O
F T
H I S
S H
E E
T I
S T
H E
E L
E C
T R
O N
I C
F I L
E D
I G
I T
A L
L Y
S I G
N E
D A
N D
S E
A L
E D
U N
D E
R R
U L
E
G
.0
F
.A .C
FORT MYERS, FL 33901
SUITE 200
2121 MCGREGOR BOULEVARD
HIGHSPANS ENGINEERING, INC.
P.E. LICENSE NUMBER 55460
THOMAS M. WAITS, P.E.
BLEACHER STEEL FRAME DETAILS
BLEACHER STEEL FRAME
HSS 6x5x
W.P.
PLT.4
5x
PLT.4
5x
H S
S x x
PLATE DETAIL
SEE BLEACHER BASE
BRACE TO HSS WELD DETAIL
3" "2
8 3"
A
TO STIFFENER PLT.
SLOTTED CONNECTION
W/8
HSS 9x5x" STIFFENER PLT.2
"x2
1'-1
IN BASE PLATE (TYP.)
INDICATED LOCATIONS
" HOLE AT4
PROVIDE 1
1" BASE PLATE THK.
5CONNECTION
AT SLOTTED 16
10"
"2
1'-1
STIFFENER PLT. (SEE NOTE 2)
SLOTTED HSS CONNECTION TO
1" BASE PLATE THK.
9"
CLEAR SILICONE CAULK IS TO BE USED TO SEAL ALL SEAMS BETWEEN HSS SECTIONS. 3.
COMPLETED PRIOR TO ADDITION AND WELDING OF THE HSS SECTION.
DURING FABRICATION, ALL STIFFENER PLATE TO BASE PLATE WELDS SHALL BE2.
SEAM ROOF PANEL MANUFACTURER'S RECOMMENDATIONS.
ALL DRIP EDGE FLASHING SHALL BE MANUFACTURED AND INSTALLED PER STANDING1.
NOTES:
BLEACHER ROOF CANTILEVER END DETAIL
/ EAVE STRUT CONNECTION DETAIL
BLEACHER ROOF OVERHANG AND Z-PURLIN
SECTION A-A
BLEACHER BASE PLATE DETAIL
.5
1'-11"
"4 12'-8
"2
"2
"8
'-2
° 45°
6 SP. @ ±2'-8¼" = 16'-1½" (CLEAT/BRACKET)
DETAIL
CONNECTION
COLUMN
BLEACHER
SEE
STRUT ORIENTATION.
CLEAT. MATCH EAVE
"x3"x3" SINGLE4
PLT.4
5x
EACH HSS MEMBER
CENTERED ON
PLACE BRACE PLT.
A
1" MIN.
OVERHANG
STRUTS @ 6" O.C. MAX.
PANELS AND EAVE
FASTEN TO ROOF
SEE NOTE 1
EAVE STRUTS @ 6" O.C. MAX.
FASTEN TO ROOF PANELS AND
VERTICAL HEIGHT)
EDGE FLASHING (9" MIN.
24 GAGE Z-SHAPE DRIP
HSS 6x5x
STRUT (TYP.)
DOUBLE SLOPE EAVE
TO FIT AROUND PURLINS
FLANGE LIPS AS NECESSARY
EDGE 4" C-PURLIN, TRIM
1'-0"
HSS 6x5x
Z-PURLIN OR EAVE STRUT
CONTINUOUS 24'-6"
SEE NOTE 1
" � BOLTS (TYP.)8
3W/
ANGLE BRACKET 4
1OR L3x3x
"x3"x3" SINGLE CLEAT4
STRUT TO C-PURLIN CONNECTION (TYP.)
LEGS) AT EACH Z-PURLIN & EAVE
14 GAGE ANGLE PLATE (3" HEIGHT, 3"
VERTICAL HEIGHT)
EDGE FLASHING (9" MIN.
24 GAGE Z-SHAPE DRIP
CONNECTION DETAIL
BLEACHER COLUMN
"16 31 "16
31"8
9"
HSS COLUMN
CONNECTION (2 PER FRAME)
" STL. PLT ON EA. SIDE OF2
HSS CANTILEVER
"2 13'-0
13'-1"
CONNECTION (TYP.)
BRACKET FOR Z PURLIN
ANGLE4
13x3x3" LONG L
SEE NOTE 3
ON EACH LEG
ZINC-COATED SCREWS
2-#14x1" SELF-DRILLING
ON BOTH SIDES OF HSS
" � DRAIN HOLES2
1 PROVIDE
RLP 4/24
TMW 4/24
TMW 4/24
RLP 4/24
REF. DWG. NO.
SHEET NO.
SHEET TITLE:
PROJECT NAME:
DRAWN BY:
CHECKED BY:
DESIGNED BY:
CHECKED BY:
ROAD NO. COUNTY CITY PROJECT NO.
REVISIONS
/2 /2
:5
:0
P
M
H
P ro je c t2
\2
S a m F le is h m a n
P a rk \S tr u c tu re s \B le a c h e rS te e lF ra m e
D e ta il s .d g
| KeySheet01 |
| GeneralNotes |
| ProjectLayout |
| SummaryOfQuantities |
| Dugout |
| Bleacher |
| DrilledShaftDetails |
| DugoutSteelFrameDetails |
| BleacherSteelFrameDetails |
| Printed copies of this document are not considered signed and sealed and all SHA-1 authentication codes must be verified on any electronic copies. | |
| 2024-10-02T13:47:03-0400 | |
| This document has been digitally signed and sealed by Thomas M. Waits, PE, using an SHA-1 authentication code on the date below. Printed copies of this document are not considered signed and sealed and all SHA-1 authentication codes must be verified on any electronic copies. | |
| Thomas M Waits | |
| I am the author of this document |
File details come from the government source that posted it. Updated .