Fire Alarm Inspection Report.pdf

PDF 341 KB Posted

Attached to
Amendment 01 Textile Warehouse Office Addition and Renovation
Solicitation number
W91QF426BA001Amendment01
Issued by

About this file

This is a Fire Alarm Inspection Report documenting the annual inspection and testing of the fire alarm system at Building 1146 (USDB Warehouse) located at 1301 N. Warehouse Rd., Ft. Leavenworth, Kansas 66027. The inspection was conducted on June 28, 2019, at 0700 hours by David Schaumburg (NICET #90525) of Siemens Industry, Inc., representing the service organization BKS1 Ft. Leavenworth. The system is monitored by DES/Jeff Jackson and approved by the Ft. Leavenworth Fire Department under Contract #2600112458, with a contract period from April 10, 2019, to April 10, 2020.

The fire alarm system utilizes a Notifier Model 500 control unit with Class B circuit style and includes two manual pull stations, one system smoke detector, one waterflow device, and two other supervisory initiating devices. The system is powered by 120VAC primary supply (20-amp breaker) with a 12 AH sealed lead acid battery providing 24-hour backup capacity. All system components—including the control unit, interface equipment, lamps/LEDs, primary power supply, disconnect switches, secondary power, and notification appliances—passed visual and functional testing. All six initiating, supervisory, and notification devices tested successfully. The report notes that tampers cause alarm conditions and waterflow must be reset at the panel to silence alarm conditions. The system was restored to normal operation at 1430 hours on June 28, 2019, and testing was performed in accordance with applicable NFPA standards. Building management, the monitoring agency, and building occupants were notified before and after testing completion.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Alarm Inspection Report

Building Technologies

© Siemens Industry, Inc., Smart Infrastructure Division, 2009-2019. All rights reserved.

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 1 of 4

INSPECTION AND TESTING FORM

SITE NAME: Ft. Leavenworth

SYSTEM NAME: 1146 - USDB Warehouse

PANEL LOCATION: Front Office PANEL ADDRESS: 1301 N. Warehouse Rd., Ft. Leavenworth, KS 66027

DATE: 28 JUN 2019 CONTRACT #: 2600112458

TIME: 0700 NOTIFICATION #: 5003714623

SYSTEM INFORMATION

Service Organization Property Name (User)

Name: SIEMENS Name: BKS1 Ft. Leavenworth (30406961)

Address:

8066 Flint Street Lenexa, KS 66214

Address:

1301 N. Warehouse Rd.

Ft. Leavenworth, KS 66027

Representative : David Schaumburg Owner Contact: Raymond Murphy

License No.: NICET #90525 Telephone: 913-684-7788

Telephone: 913-905-6734

Contract# 2600112458

Contract Start Date: 4/10/2019

Contract End Date: 4/10/2020

Monitoring Entity Approving Agency

Contact: DES / Jeff Jackson Contact: Ft. Leavenworth Fire Dept.

Telephone: 913-684-2111 / 913-684-3501 Telephone: 913-684-2111

Monitoring Account Ref. No.: Bldg 1146

Type Transmission: Digital Service Type: Annual

Control Unit Manufacturer: Notifier

Model Number: 500

Circuit Styles: Class B

Number of Circuits: 0

Software Rev.:

Last Date System Had Any Service Performed: 28 Jun 2019

Last Date that Any Software or Configuration Was Revised:

COMMENTS:

TAMPERS CAUSE ALARM CONDITION

WATERFLOW MUST BE RESET AT PANEL TO SILENCE ALARM CONDITION

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 2 of 4

ALARM-INITIATING DEVICES INFORMATION

System Qty Report Qty Device Type 2 2 Manual Pull Station

1 1 System Smoke Detector (P) 1 1 Waterflow Device

Alarm Verification Feature is ☑ Disabled ☐ Enabled

SUPERVISORY SIGNAL-INITIATING DEVICES INFORMATION

System Qty Report Qty Device Type 2 2 Other Supervisory Initiating Device

INITIATING AND NOTIFICATION CIRCUIT INFORMATION

Circuit Type Qty Class/Style Survivability

Level Separate Pathway

Level Supervised

Initiating Device Circuits 0 Yes

Signaling Line Circuits 0 No

Notification Circuits 0 Class B Yes

SYSTEM POWER SUPPLIES

(a) Primary (Main) Nominal Voltage: 120VAC Amps 20

Overcurrent Protection Type: Breaker Amps 20

Location (of Primary Supply Panel Board):

Disconnecting Means Location: Warehouse CIR #2

(b) Secondary (Standby):

Sealed Lead Acid Storage Battery: Amp-Hour Rating 12 AH

Calculated Capacity to operate system, in Hours: 24 Hrs

No Engine-driven generator dedicated to fire alarm system:

NOTIFICATIONS MADE PRIOR TO ANY TESTING

Yes No Who Time

Monitoring Entity ☑ ☐ DES

Building Occupants ☑ ☐ David Ray

Building Management ☑ ☐ Jeff Jackson

Other (Specify) ☐ ☑

AHJ Notified of Any Impairments ☐ ☑

SYSTEM TESTS AND INSPECTIONS

Type Visual/ Functional/ Not

Tested/ Failed Comments

Control Unit Visual, Functional

Interface Equipment Visual, Functional

Lamps/LEDS Visual, Functional

Fuses Visual

Primary Power Supply Visual, Functional

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 3 of 4

Disconnect Switches Visual, Functional

SECONDARY POWER

Type Visual/ Functional/ Not Tested/ Failed

Comments

Battery Condition Visual, Functional

Load Voltage Visual, Functional

Discharge Test Visual, Functional

Charger Test Visual, Functional

NOTIFICATION APPLIANCES

Type Visual/ Functional/ Not Tested/ Failed

Comments

Audible Visual, Functional

Visual Visual, Functional

INITIATING, SUPERVISORY, AND NOTIFICATION DEVICE TESTS AND INSPECTIONS

Location & S/N Device Type Functional Test Dev. Reading Pass Fail

01-001-001 OFFICE Smoke Detector X 2.5 X

01-001-002 FRONT ENTERANCE PULL Pull Station X X

01-001-003 BACK EXIT PULL Pull Station X X

01-001-004 SMALL WAREHOUSE Waterflow Device X X

01-001-005 SMALL WAREHOUSE Tamper X X

01-001-006 SMALL WAREHOUSE HIGH/LOW PRESS SW Pressure Switch X X

SUPERVISING STATION MONITORING

Yes No Time Comments

Alarm Signal ☑ ☐

Alarm Restoration ☑ ☐

NOTIFICATIONS THAT TESTING IS COMPLETE

Yes No Who Time

Building Management ☑ ☐ Jeff Jackson

Monitoring Agency ☑ ☐ DES

Building Occupants ☑ ☐ David Ray

This report was created by TechAdvance+™, a service of Siemens Industry, Inc. Page 4 of 4

System restored to normal operation: Date: 28 Jun 2019 Time: 1430

This Testing Was Performed in Accordance with Applicable NFPA Standards.

Name of Inspector: David Schaumburg

Signature:

Name of Owner or Representative: Raymond Murphy

Signature:

2019-06-28T11:40:19-0500