This document is a technical schematic and specification sheet for telecommunications infrastructure installation at location B1146, with external connectivity from Remote Site Unit (RSU) B1159.

The specification details a complete telecommunications cabinet installation requiring the following components and services: 25-pair OSP copper cabling, 12-strand OSP fiber optic cabling, 1RU fiber optic patch panel (FOPP), 24-port patch panel for CAT3 copper punch-down termination, 48-port patch panel, 66-block termination block, and bonding/grounding of all metal telecommunications cabinets and supporting structures (ladder racks, conduit, and cable trays) per I3A/TIA-607C standards with ground connection to service equipment per TIA-607C standards. The installation includes a dedicated 5-20R quad receptacle with emergency shut-off switch mounted at the cabinet base, a Telecommunication Cabinet TRIPP-LITE Model SRW18USDP by EATON with integrated horizontal wire management between patch panels and equipment, and ¾-inch fire-rated plywood backboard for equipment mounting painted with fire-rated paint while preserving the fire rating stamp. The schematic shows two Cisco Catalyst 3550 switches configured within an 18U cabinet with associated network equipment and cabling infrastructure connecting to the external OSP network infrastructure.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

18 U

1 U 21 43 65 21 43 65 21 43 65

SYSTEM

RPS

STATUS

UTIL

DUPLEX

SPEED

MODE

1X

2X

15 X

16 X

15 161 2 3 4 5 6 7 8 9 10 11 12 13 14 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

17 X

18 X

31 X

32 X

33 X

34 X

47 X

48 X

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

Catalyst 3550

SYSTEM

RPS

STATUS

UTIL

DUPLEX

SPEED

MODE

1X

2X

15 X

16 X

15 161 2 3 4 5 6 7 8 9 10 11 12 13 14 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

17 X

18 X

31 X

32 X

33 X

34 X

47 X

48 X

33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48

Catalyst 3550

1 U

2 U

2 U

1 U

1 U

QUAD

5-20

1. 25PR OSP Copper

2. 12SM Strands OSP Fiber

3. 1RU FOPP

4. 24-Port Patch Panel for punch down of 25PR CAT3 Copper.

5. 48-Port Patch Panel

6. 66-Block

7. TMGB - Bond/Ground all Metal telecommunications Cabinets and horizontal distribution supporting structures(cable trays, Ladder Racks, Conduit and baskets) to Bus Bar per I3A/TIA-607C Standards. Ground TMGB back to Service Equipment Ground per TIA-607C Standards.

8. 25PR PET

9. Install dedicated 5-20R quad receptacle inside bottom of cabinet w/switch for emergency shut-off.

10. Install Telecommunication Cabinet TRIPP- LITE Model SRW18USDP by EATON. include horizontal wire management between patch panels and equipment.

11. ¾”Fire-Rated plywood Backboard for Equipment mounting. Paint using fire rated paint leaving fire rating stamp exposed.

SWITCH

OSP from

RSU

B1159

B1146