This document summarizes a federal contract solicitation to modernize a basement kitchen and morgue. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 15 seeking offers for project number 589A4-20-157 to modernize the kitchen and morgue. Offerors should respond with final drawings by the closing date of the solicitation, number 36C25522R0092, to upgrade these facilities. The solicitation provides the opportunity for contractors to modernize a VA medical center's basement-level kitchen and morgue spaces through renovation of the existing areas.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COLUMBIA, MO VA MEDICAL CENTER

DEPARTMENT OF VETERANS AFFAIRS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

F i l e

P a t h

P

M

BID SET DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

MODERNIZE BASEMENT

KITCHEN AND MORGUE

COLUMBIA, MO VAMC

589A4-20-157

Project Director

05/06/2022Revisions: Date:

1 - SCHEMATIC DOCUMENTS

2 - DESIGN DEVELOPMENT

3 - 60% CONSTRUCTION DOCUMENTS

01/10/2021 05/14/2021 07/23/2021

PROJECT NO.: 20-003

Omaha, Nebraska 68137-5566

PH: (402) 496-4115

14216 Dayton Cir - Suite #5 21 Delta Engineers, LLC

Fax: (402) 384-8900

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - 100% BID SET DOCUMENTS 05/06/2022

MODERNIZE BASEMENT KITCHEN & MORGUE

PROJECT NO.: 589A4-20-157

BID SET DOCUMENTS

AutoCAD SHX Text

NO SCALE

AutoCAD SHX Text

CAMPUS MAP

AutoCAD SHX Text

DRAWING LIST

AutoCAD SHX Text

DRAWING #

AutoCAD SHX Text

DRAWING NAME

AutoCAD SHX Text G0.01

AutoCAD SHX Text

COVER SHEET

AutoCAD SHX Text

GENERAL

AutoCAD SHX Text

AD1.01

AutoCAD SHX Text

KITCHEN DEMOLITION PLAN

AutoCAD SHX Text

ARCHITECTURAL

AutoCAD SHX Text

PROJECT LOCATION

AutoCAD SHX Text

GI0.01

AutoCAD SHX Text

COVER SHEET, INDEX

AutoCAD SHX Text

OF DRAWINGS,

AutoCAD SHX Text

LOCATION MAP

AutoCAD SHX Text

AutoCAD SHX Text

PJM

AutoCAD SHX Text

PJM

AutoCAD SHX Text

THIS CAMPUS IS TOBACCO FREE

AutoCAD SHX Text

FOOD SERVICE

AutoCAD SHX Text

QF1.00

AutoCAD SHX Text

FOOD SERVICE EQUIPMENT PLAN AND ELEVATIONS

AutoCAD SHX Text

MD1.01

AutoCAD SHX Text

BASEMENT - DEMOLITION MORGUE AREA

AutoCAD SHX Text

MD1.02

AutoCAD SHX Text

BASEMENT - DEMOLITION KITCHEN AREA

AutoCAD SHX Text

AD1.02

AutoCAD SHX Text

MORGUE DEMOLITION PLAN

AutoCAD SHX Text

AE1.01

AutoCAD SHX Text

KITCHEN MODERNIZATION PLAN

AutoCAD SHX Text

AE1.02

AutoCAD SHX Text

MORGUE MODERNIZATION PLAN

AutoCAD SHX Text

MECHANICAL

AutoCAD SHX Text

AE1.03

AutoCAD SHX Text

DOCK ROOF & FLOOR PLAN

AutoCAD SHX Text

AI4.01

AutoCAD SHX Text

MORGUE - INTERIOR ELEVATIONS

AutoCAD SHX Text

AI4.02

AutoCAD SHX Text

KITCHEN - INTERIOR ELEVATIONS

AutoCAD SHX Text

AI7.01

AutoCAD SHX Text

BASEMENT FINISH PLAN

AutoCAD SHX Text

AI7.02

AutoCAD SHX Text

FINISH SCHEDULE

AutoCAD SHX Text

AI7.03

AutoCAD SHX Text

INTERIOR DETAILS

AutoCAD SHX Text

ED1.01

AutoCAD SHX Text

BASEMENT - DEMOLITION MORGUE

AutoCAD SHX Text

ED1.02

AutoCAD SHX Text

BASEMENT - DEMOLITION KITCHEN

AutoCAD SHX Text

EL1.01

AutoCAD SHX Text

BASEMENT - MORGUE LIGHTING

AutoCAD SHX Text

EP1.01

AutoCAD SHX Text

BASEMENT - MORGUE POWER

AutoCAD SHX Text

ELECTRICAL

AutoCAD SHX Text

QF1.01

AutoCAD SHX Text

PARTIAL FOOD SERVICE EQUIPMENT AND DETAILS

AutoCAD SHX Text

QF1.03

AutoCAD SHX Text

FOOD SERVICE EQUIPMENT SCHEDULE

AutoCAD SHX Text

QF1.02

AutoCAD SHX Text

PARTIAL FOOD SERVICE EQUIPMENT PLAN AND DETAILS

AutoCAD SHX Text G1.01

AutoCAD SHX Text

PHASING - KITCHEN

AutoCAD SHX Text G1.02

AutoCAD SHX Text

PHASING - MORGUE

AutoCAD SHX Text

MI0.01

AutoCAD SHX Text

MECHANICAL NOTES, SYMBOLS, LEGEND, AND ABBREVIATIONS

AutoCAD SHX Text

EI0.01

AutoCAD SHX Text

ELECTRICAL NOTES, SYMBOLS, LEGEND, AND ABBREVIATIONS

AutoCAD SHX Text

MH1.01

AutoCAD SHX Text

BASEMENT - HVAC MORGUE AREA

AutoCAD SHX Text

MH1.02

AutoCAD SHX Text

BASEMENT - NEW HVAC PLAN KITCHEN AREA (PARTIAL)

AutoCAD SHX Text

PL1.01

AutoCAD SHX Text

PIPE BASEMENT - PLUMBING SANITARY MORGUE AREA

AutoCAD SHX Text

PL1.02

AutoCAD SHX Text

PIPE BASEMENT - PLUMBING SANITARY KITCHEN AREA

AutoCAD SHX Text

ET1.01

AutoCAD SHX Text

BASEMENT - MORGUE COMMUNICATIONS

AutoCAD SHX Text

EL1.02

AutoCAD SHX Text

BASEMENT - KITCHEN LIGHTING

AutoCAD SHX Text

EP1.02

AutoCAD SHX Text

BASEMENT - KITCHEN POWER

AutoCAD SHX Text

ET1.02

AutoCAD SHX Text

BASEMENT - KITCHEN COMMUNICATIONS

AutoCAD SHX Text

ED1.03

AutoCAD SHX Text

BASEMENT - DEMOLITION KITCHEN

AutoCAD SHX Text

AE1.00

AutoCAD SHX Text

SITE PLAN

AutoCAD SHX Text

AC1.01

AutoCAD SHX Text

KITCHEN - REFLECTED CEILING PLAN

AutoCAD SHX Text

AC1.02

AutoCAD SHX Text

MORGUE - REFLECTED CEILING PLAN

AutoCAD SHX Text

AE1.06

AutoCAD SHX Text

DOOR SCHEDULE & DETAILS

AutoCAD SHX Text

AE2.01

AutoCAD SHX Text

DOCK - ELEVATION, SECTION & DETAILS

AutoCAD SHX Text

AI7.04

AutoCAD SHX Text

BASEMENT - FF&E PLAN

AutoCAD SHX Text

NOT FOR CONSTRUCTION

AutoCAD SHX Text

DOCUMENT SIGNATURE BLOCK

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

MEDICAL CENTER DIRECTOR

AutoCAD SHX Text

ASSOCIATE DIRECTOR

AutoCAD SHX Text

CHIEF OF STAFF

AutoCAD SHX Text

ASSOCIATE DIRECTOR OF PATIENT SERVICES

AutoCAD SHX Text

ASSISTANT DIRECTOR

AutoCAD SHX Text

HRO DIRECTOR

AutoCAD SHX Text

CHIEF ENGINEER

AutoCAD SHX Text

INFECTION CONTROL PRACTITIONER

AutoCAD SHX Text

SAFETY OFFICER

AutoCAD SHX Text

CHIEF OF FOOD SERVICES

AutoCAD SHX Text

LABORATORY DIRECTOR

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

PRINT NAME

AutoCAD SHX Text

SIGNATURE

AutoCAD SHX Text

AE0.01

AutoCAD SHX Text

GENERAL NOTES

AutoCAD SHX Text

AE0.02

AutoCAD SHX Text

UL RATINGS

AutoCAD SHX Text

AD1.03

AutoCAD SHX Text

KITCHEN CEILING DEMOLITION PLAN

AutoCAD SHX Text

AD1.04

AutoCAD SHX Text

MORGUE CEILING DEMOLITION PLAN

AutoCAD SHX Text

STRUCTURAL

AutoCAD SHX Text S1.01

AutoCAD SHX Text

KITCHEN STRUCTURAL FLOOR PLAN

AutoCAD SHX Text S1.02

AutoCAD SHX Text

LOADING DOCK ROOF PLAN & SECTION

AutoCAD SHX Text

ED1.04

AutoCAD SHX Text

BASEMENT - DEMO ELECTRICAL PANEL SCHEDULES

AutoCAD SHX Text

ED1.05

AutoCAD SHX Text

BASEMENT - DEMO ELECTRICAL PANEL SCHEDULES

AutoCAD SHX Text

EP6.01

AutoCAD SHX Text

BASEMENT - DEMO ELECTRICAL PANEL SCHEDULES

AutoCAD SHX Text

EP6.02

AutoCAD SHX Text

BASEMENT - DEMO ELECTRICAL PANEL SCHEDULES

AutoCAD SHX Text

DRAWING LIST

AutoCAD SHX Text

DRAWING #

AutoCAD SHX Text

DRAWING NAME

AutoCAD SHX Text

PLUMBING

AutoCAD SHX Text

PL1.03

AutoCAD SHX Text

BASEMENT - PLUMBING SANITARY MORGUE AREA

AutoCAD SHX Text

PL1.04

AutoCAD SHX Text

BASEMENT - PLUMBING SANITARY KITCHEN AREA

AutoCAD SHX Text

PL2.01

AutoCAD SHX Text

PIPE BASEMENT - PLUMBING DOMESTIC WATER MORGUE AREA

AutoCAD SHX Text

PL2.02

AutoCAD SHX Text

PIPE BASEMENT - PLUMBING DOMESTIC WATER KITCHEN AREA

AutoCAD SHX Text

PL2.03

AutoCAD SHX Text

BASEMENT - PLUMBING DOMESTIC WATER MORGUE AREA

AutoCAD SHX Text

PL2.04

AutoCAD SHX Text

BASEMENT - PLUMBING DOMESTIC WATER KITCHEN AREA

AutoCAD SHX Text

PL3.01

AutoCAD SHX Text

BASEMENT - PLUMBING NATURAL GAS KITCHEN AREA

AutoCAD SHX Text

PL3.02

AutoCAD SHX Text

BASEMENT - PLUMBING NATURAL GAS KITCHEN AREA

AutoCAD SHX Text

PL5.01

AutoCAD SHX Text

PLUMBING RISER DIAGRAMS

AutoCAD SHX Text

PL5.02

AutoCAD SHX Text

PLUMBING RISER DIAGRAMS

AutoCAD SHX Text

PL5.03

AutoCAD SHX Text

PLUMBING RISER DIAGRAMS

AutoCAD SHX Text

PL5.04

AutoCAD SHX Text

PLUMBING RISER DIAGRAMS

AutoCAD SHX Text

MH5.01

AutoCAD SHX Text

MECHANICAL SCHEDULES

AutoCAD SHX Text

QFD1.0

AutoCAD SHX Text

PARTIAL FOOD SERVICE DEMOLITION PLAN

AutoCAD SHX Text

QFD1.1

AutoCAD SHX Text

PARTIAL FOOD SERVICE DEMOLITION PLAN AND SCHEDULE

AutoCAD SHX Text

MD1.03

AutoCAD SHX Text

BASEMENT - DEMOLITION HVAC PIPING MORGUE

AutoCAD SHX Text

MD1.04

AutoCAD SHX Text

BASEMENT - DEMOLITION HVAC PIPING KITCHEN

AutoCAD SHX Text

PD1.03

AutoCAD SHX Text

PIPE BASEMENT - DEMOLITION SANITRY WASTE KITCHEN

AutoCAD SHX Text

PD1.04

AutoCAD SHX Text

BASEMENT - DEMOLITION SANITRY WASTE KITCHEN

AutoCAD SHX Text

PD1.05

AutoCAD SHX Text

PIPE BASEMENT - DEMOLITION NATURAL GAS KITCHEN

AutoCAD SHX Text

PD1.06

AutoCAD SHX Text

BASEMENT - DEMOLITION NATURAL GAS KITCHEN

AutoCAD SHX Text

PD1.07

AutoCAD SHX Text

PIPE BASEMENT - DEMOLITION DOMESTIC WATER KITCHEN

AutoCAD SHX Text

PD1.08

AutoCAD SHX Text

BASEMENT - DEMOLITION DOMESTIC WATER KITCHEN

AutoCAD SHX Text

PD1.09

AutoCAD SHX Text

PIPE BASEMENT - DEMOLITION DOMESTIC WATER MORGUE

AutoCAD SHX Text

PD1.10

AutoCAD SHX Text

BASEMENT - DEMOLITION DOMESTIC WATER MORGUE

AutoCAD SHX Text

FIRE PROTECTION

AutoCAD SHX Text

FD1.01

AutoCAD SHX Text

BASEMENT - DEMO MORGUE FIRE ALARM

AutoCAD SHX Text

FD1.02

AutoCAD SHX Text

BASEMENT - DEMO MORGUE FIRE SPRINKLER

AutoCAD SHX Text

FD1.03

AutoCAD SHX Text

BASEMENT - DEMO KITCHEN FIRE ALARM

AutoCAD SHX Text

FD1.04

AutoCAD SHX Text

BASEMENT - DEMO KITCHEN FIRE SPRINKLER

AutoCAD SHX Text

FA1.01

AutoCAD SHX Text

BASEMENT - MORGUE FIRE ALARM

AutoCAD SHX Text

FA1.02

AutoCAD SHX Text

BASEMENT - KITCHEN FIRE ALARM

AutoCAD SHX Text

FX1.01

AutoCAD SHX Text

BASEMENT - MORGUE FIRE SPRINKLER

AutoCAD SHX Text

FX1.02

AutoCAD SHX Text

BASEMENT - KITCHEN FIRE SPRINKLER

AutoCAD SHX Text

PD1.01

AutoCAD SHX Text

PIPE BASEMENT - DEMOLITION SANITARY WASTE MORGUE

AutoCAD SHX Text

PD1.02

AutoCAD SHX Text

BASEMENT - DEMOLITION SANITARY WASTE MORGUE

AutoCAD SHX Text

PI0.01

AutoCAD SHX Text

PLUMBING NOTES, SYMBOLS, LEGEND, AND ABBREVIATIONS

AutoCAD SHX Text

PLUMBING

AutoCAD SHX Text G1.03

AutoCAD SHX Text

LIFE SAFETY PLAN

AutoCAD SHX Text

PD1.11

AutoCAD SHX Text

BASEMENT - DEMOLITION GAS MORGUE AREA

AutoCAD SHX Text

PL3.03

AutoCAD SHX Text

BASEMENT - PLUMBING NATURAL GAS MORGUE AREA

AutoCAD SHX Text

MH1.03

AutoCAD SHX Text

BASEMENT - NEW HVAC PLAN KITCHEN AREA (PARTIAL)

AutoCAD SHX Text

MH1.04

AutoCAD SHX Text

BASEMENT - NEW HVAC PLAN KITCHEN AREA (PARTIAL)

R Q P N.2B Na N M.2 M La L K

6.2

6.7

0 8' 16'4'

PHASE 3

PHASE 2

PHASE 1

PHASE 1

4'-0"

B002D

B002G

B002F

B002K

B002E

C009

C009B

C009C

C009A

B001E B001B

B001D B001F

B

C

C009E

C009F

C009G

C J

C009I

C009K

C008

C010

B002

B001A

B002A

PHASING LEGEND:

PHASE 1

PHASE 2

PHASE 3

TEMPORARY WALLS

SHALL BE CONSTRUCTED TO BE A

1HR PARTITION. DOOR ASSEMBLIES

TO BE 45 MIN RATED

PHASING NOTES:

1. THE PHASING PLANS ARE INTENDED TO PROVIDE A

GUIDE FOR THE ACCOMPLISHMENT OF THE WORK

TO BE COMPLETED & ARE GENERAL IN NATURE.

REVIEW DETAILED PHASING WORK WITH THE

OWNER IN ADVANCE OF ALL WORK.

2. THE EXISTING FACILITIES ARE TO BE OCCUPIED

THROUGHOUT THE CONSTRUCTION TIME PERIOD.

COORDINATE ALL WORK WITH THE OWNER DURING

THE ACCOMPLISHMENT OF THE WORK.

3. UPDATE THE OWNER WITH ALL ENVISIONED

CHANGES FOR PHASING THE WORK; NO CHANGES

ARE TO BE MADE WITHOUT FIST CLEARING SUCH

CHANGES WITH THE OWNER IN ADVANCE OF SUCH

CHANGES.

4. ALL DEMOLITION AND CONSTRUCTION WORK IN THE

MORGUE IS TO BE REVIEWED WITH THE OWNER IN

ADVANCE OF SUCH WORK AS THE MORGUE WILL

CONTINUE OPERATION THROUGHOUT THE

ACCOMPLISHMENT OF THE WORK.

5. CONTRACTOR TO REVIEW ALL EXISTING CONDITIONS

AND ADVISE ARCHITECT/ENGINEER OF ALL DESIGN

DOCUMENT DISCREPANCIES.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR

VERIFYING ALL DIMENSIONS AND EXISTING

CONDITIONS. ANY DISCREPANCIES WHICH WILL

PREVENT THE ACCOMPLISHMENT OF INTENT SHOWN

ON DRAWINGS SHALL BE BROUGHT TO THE

IMMEDIATE ATTENTION OF THE ARCHITECT.

7. WHERE A CONDITION IS NOTED 'TYPICAL' (TYP.), IT IS

UNDERSTOOD THAT ALL SIMILAR CONDITIONS BE

CONSTRUCTED OF THE SAME MATERIALS AND/OR

DIMENSIONS.

8. LIFE SAFETY SYSTEMS INCLUDING, BUT NOT LIMITED

TO FIRE SUPPRESSION SYSTEMS, EXIT SIGNS,

EMERGENCY LIGHTING, ETC... SHALL REMAIN IN

SERVICE THROUGHOUT CONSTRUCTION. IF SYSTEM

SHUT DOWN IS NECESSARY, CONTRACTOR SHALL

COORDINATE WITH OWNER.

9. DURING PHASE 3, CONTRACTOR SHALL PROVIDE

REFRIDGERATED TRUCK & FREEZER FOR KITCHEN

ITEMS

10. WHERE "EXIT" IS NOTED, CONTRACTOR TO LEAVE

UNOBSTRUCTED DURING CONSTRUCTION.

11. ALL TEMPORRY WALLS MUST BE CONSTRUCTED AS

A 1HR RATED ASSEMBLY. OPENINGS WITHIN THE

RATED ASSEMBLY MUST HAVE A FIRE RESISTANCE

RATING OF 3/4HR

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

G1.01

PHASING - KITCHEN

05 / 06 /2022 RK

1/8" = 1'-0"F3 PHASING - KITCHEN

KEY PLANPLAN

NORTH

E X

IT

EXIT

EXIT

No Description Date

K

J H

0 4' 8'2'

PHASE 1

COOLER TO REMAIN IN

SERVICE DURING

CONSTRUCTION. VA

REQUIRES 48 HR NOTICE

BEFORE INTERRUPTION

OF SERVICES

PHASE 2

PHASE 3

AUTOPSY RM TO REMAIN

IN SERVICE DURING

CONSTRUCTION. VA

REQUIRES 48 HR NOTICE

BEFORE INTERRUPTION

OF SERVICES

AUTOPSY

D031

COOLER

D030

STORAGE

D028

CORRIDOR

CBD5

CUST.

D029

RR

D027

E X

IT

PHASING LEGEND:

PHASE 1

PHASE 2

PHASE 3

TEMPORARY WALLS

SHALL BE CONSTRUCTED TO BE A

1HR PARTITION. DOOR ASSEMBLIES

TO BE 45 MIN RATED

PHASING NOTES:

1. THE PHASING PLANS ARE INTENDED TO PROVIDE A

GUIDE FOR THE ACCOMPLISHMENT OF THE WORK

TO BE COMPLETED & ARE GENERAL IN NATURE.

REVIEW DETAILED PHASING WORK WITH THE

OWNER IN ADVANCE OF ALL WORK.

2. THE EXISTING FACILITIES ARE TO BE OCCUPIED

THROUGHOUT THE CONSTRUCTION TIME PERIOD.

COORDINATE ALL WORK WITH THE OWNER DURING

THE ACCOMPLISHMENT OF THE WORK.

3. UPDATE THE OWNER WITH ALL ENVISIONED

CHANGES FOR PHASING THE WORK; NO CHANGES

ARE TO BE MADE WITHOUT FIST CLEARING SUCH

CHANGES WITH THE OWNER IN ADVANCE OF SUCH

CHANGES.

4. ALL DEMOLITION AND CONSTRUCTION WORK IN THE

MORGUE IS TO BE REVIEWED WITH THE OWNER IN

ADVANCE OF SUCH WORK AS THE MORGUE WILL

CONTINUE OPERATION THROUGHOUT THE

ACCOMPLISHMENT OF THE WORK.

5. CONTRACTOR TO REVIEW ALL EXISTING CONDITIONS

AND ADVISE ARCHITECT/ENGINEER OF ALL DESIGN

DOCUMENT DISCREPANCIES.

6. CONTRACTOR SHALL BE RESPONSIBLE FOR

VERIFYING ALL DIMENSIONS AND EXISTING

CONDITIONS. ANY DISCREPANCIES WHICH WILL

PREVENT THE ACCOMPLISHMENT OF INTENT SHOWN

ON DRAWINGS SHALL BE BROUGHT TO THE

IMMEDIATE ATTENTION OF THE ARCHITECT.

7. WHERE A CONDITION IS NOTED 'TYPICAL' (TYP.), IT IS

UNDERSTOOD THAT ALL SIMILAR CONDITIONS BE

CONSTRUCTED OF THE SAME MATERIALS AND/OR

DIMENSIONS.

8. LIFE SAFETY SYSTEMS INCLUDING, BUT NOT LIMITED

TO FIRE SUPPRESSION SYSTEMS, EXIT SIGNS,

EMERGENCY LIGHTING, ETC... SHALL REMAIN IN

SERVICE THROUGHOUT CONSTRUCTION. IF SYSTEM

SHUT DOWN IS NECESSARY, CONTRACTOR SHALL

COORDINATE WITH OWNER.

9. DURING PHASE 3, CONTRACTOR SHALL PROVIDE

REFRIDGERATED TRUCK & FREEZER FOR KITCHEN

ITEMS

10. WHERE "EXIT" IS NOTED, CONTRACTOR TO LEAVE

UNOBSTRUCTED DURING CONSTRUCTION.

11. ALL TEMPORRY WALLS MUST BE CONSTRUCTED AS

A 1HR RATED ASSEMBLY. OPENINGS WITHIN THE

RATED ASSEMBLY MUST HAVE A FIRE RESISTANCE

RATING OF 3/4HR

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

G1.02

PHASING - MORGUE

05 / 06 /2022 RK

1/4" = 1'-0"F2 PHASING - MORGUE

PLAN

NORTH

KEY PLAN

TD = 192'-6"

R E

F

R Q P N.2B Na N M.2 M La L K

6.2

6.7

11.5

J H

F-1 OCC

B OCC

EXIT

E X

IT

E X

IT

CLASS K

CLASS K

F.E.

F.E.

F.E.

CLASS K

F.E.

C008

C002

C002A C002B

WALK-IN COOLER

C009E

WALK-IN

FREEZER

C009D

MECHANICAL

ROOM

C010

MOW

C009B

C A

N T

E E

N

C C

TRAY MAKE LINE

B001I

CART WASH

C009M

M O

W P

R E

P

C A

WAREWASH

C009K

COOKLINE

C009L

FOOD PREP

B001 C

O R

R

ID

O R

C

H O

U S

E K

E E

P

B

FMEN'S

B001C

WOMEN'S

B001D

LOCKER ROOM

B001E

TRAINING

B001G

CORRIDOR

B001B

STORAGE

C009F

ORDERING

C009H

DIRECTOR

C009I

SUPERVISORS

C009J S

T O

R A

G E

B H

CHEM. CLST.

B001A

C O

R R

C B

D

CLASS A

F.E.

LEGEND

F.E. FIRE EXTINGUISHER & BRACKET W/ REQ. SIGN

F.E.C. FIRE EXTINGUISHER CABINET & EXTINGUISHER

W/ REQ. SIGN

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

G1.03

LIFE SAFETY PLAN

05 / 06 /2022 RK

1/8" = 1'-0"F1 LIFE SAFETY PLAN

FIBERGLASS BATT

INSULATION

MINERAL WOOL BATT

INSULATION

EXPANDED POLYSTYRENE

RIGID INSULATION (EPS)

EXTRUDED POLYSTYRENE

RIGID INSULATION (XPS)

CLOSED-CELL SPRAY FOAM

INSULATION

POLYISOCYANURATE RIGID

INSULATION

INSULATION:

FIBER CEMENT PANELS, SIDING & TRIM

(PLAN & SECTION)

BRICK

CONCRETE MASONRY UNITS (CMU)

GROUT / MORTAR

STEEL

ALUMINUM

MATERIAL LEGEND:

STANDING SEAM METAL

ROOFING

METAL WALL PANEL

WOOD

GYPSUM WALLBOARD

PLYWOOD

COMPRESSIBLE FILLER

ABBREVIATIONS / ACRONYMS:

ACT ACOUSTICAL CEILING TILE

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

ALUM ALUMINUM

ALT ALTERNATE

ARCH ARCHITECT / ARCHITECTURAL

APX APPROXIMATE

BDRM BEDROOM

BLDG BUILDING

B.O. BOTTOM OF

BSMT BASEMENT

CJ CONTROL JOINT

CLG CEILING

CLR CLEAR

CORR CORRIDOR

CMU CONCRETE MASONRY UNIT

CONC. CONCRETE

CONT. CONTINUOUS

CPT. CARPET

DEG. DEGREES

DIA DIAMETER

DTL DETAIL

DS DOWNSPOUT

EJ EXPANSION JOINT

ELEV ELEVATOR

EPDM ETHYLENE PROPYLENE DIENE

MONOMER

EW EACH WAY

EST ESTIMATE

EQ EQUAL

EXST EXISTING

FD FLOOR DRAIN

FE FIRE EXTINGUISHER

FF&E FIXTURES, FURNISHINGS &

EQUIPMENT

FLR. FLOOR

FP FIREPLACE

FT FOOT / FEET

GA GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GFCI GROUND FAULT CIRCUIT

INTERRUPTED

GYP GYPSUM

GYP BD GYPSUM BOARD

HEX HEXAGONAL

HM HOLLOW METAL

INSUL INSULATION

INT INTERIOR

JC JANITOR'S CLOSET

JT JOINT

KIT KITCHEN

MAT MATERIAL

MAX MAXIMUM

MECH MECHANICAL / MECHANICAL

ENGINEER

MEMB MEMBRANE

MEZZ MEZZANINE

MFR MANUFACTURER / MANUFACTURING

MIN MINIMUM

MO MASONRY OPENING

MTL METAL / MATERIAL

N NORTH

NOM NOMINAL

NTS NOT TO SCALE

O.C. ON CENTER

OHD OVERHEAD DOOR

OFF OFFICE

OPP OPPOSITE

PERIM PERIMETER

PERP PERPENDICULAR

PFN PREFINISHED

PL PROPERTY LINE

PLAM PLASTIC LAMINATE

PNL PANEL

PRCST PRECAST

PREFAB PREFABRICATED

PT PAINT

PTN PARTITION

PVMT PAVEMENT

PVT PRIVATE

PWR POWER

QTR QUARTER

QTY QUANTITY

R RISER

RAD RADIUS

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RE REFER / REFERENCE

REF REFRIGERATOR

REINF. REINFORCE / REINFORCEMENT

RES RESILIENT

REQ REQUIRED

RO ROUGH OPENING

RM ROOM

ROW RIGHT OF WAY

RR RESTROOM

S SOUTH

SF SQUARE FEET

SCHED SCHEDULE

SCWD SOLID CORE WOOD DOOR

SEAL SEALANT

SHT SHEET

SHWR SHOWER

SIM SIMILAR

SPECS SPECIFICATIONS

SQ SQUARE

SPLR SPRINKLER

SS STAINLESS STEEL

STC SOUND TRANSMISSION CLASS

STL STEEL

STOR STORAGE

STRUCT STRUCTURAL / STRUCTURAL

ENGINEER

T TREAD

T&B TOP & BOTTOM

T&G TONGUE & GROOVE

TAN TANGENT

TC TOP OF CURB

TD TRENCH DRAIN

TEL TELEPHONE

TEMP TEMPORARY / TEMPERATURE

THK THICK / THICKNESS

THRU THROUGH

TLT TOILET

T.O. TOP OF

TYP. TYPICAL

UNO UNLESS NOTED OTHERWISE

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

W WEST

W/ WITH

W/O WITHOUT

WC WATERCLOSET

WD WOOD

WRB WEATHER RESISTIVE BARRIER

EARTH - UNDISTURBED / COMPACTED

EARTH - FILL

CONCRETE (PLAN)

CONCRETE (SECTION)

CRUSHED ROCK (PLAN & SECTION)

DECORATIVE GRAVEL (PLAN &

SECTION)

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

AE0.01

GENERAL NOTES

05 / 06 /2022 RK

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

AE0.02

UL RATINGS

05 / 06 /2022 RK

F.E.

F.E.

F.E.

F.E.

F.E.

E STADIUM BLVD

PARKING LOT

HARRY S. TRUMAN MEMORIAL VETERANS' HOSPITAL (VA)

PLAN

NORTH

0 40' 80'20'

TRASH

SITE LOGISTICS NOTES:

1. THE INTENT OF THE PARTIAL SITE PLAN IS TO

PROVIDE A VERY GENERAL OVERVIEW OF THE

FACILITY LAYOUT AND SITE USE FUNCTION. USE

OF THE SITE FOR THE CONTRACTOR'S PURPOSES

SHALL BE REVIEWED WITH THE OWNER PRIOR

TO MOBLIZATION.

2. REFER TO THE PROJECT MANUAL FOR ALL

REQUIREMENTS ASSOCIATED WITH SITE USE AS

WELL AS THE DRAWINGS.

3. PATIENT, VISITOR AND STAFF SAFETY AND

SECURITY IS A PRORITY OF THE OWNER. USE OF

THE SITE SHALL, AT ALL TIMES, ASSURE FOR THIS

PRIORITY.

4. THE PHASING PLANS ARE GENERAL IN NATURE.

REVIEW DETAILED PHASING WORK WITH THE

OWNER IN ADVANCE OF ALL WORK.

5. ALL DEMOLITION AND CONSTRUCTION WORK

IN THE MORGUE IS TO BE REVIEWED WITH THE

OWNER IN ADVANCE OF SUCH WORK AS THE

MORGUE WILL CONTINUE OPERATION

THROUGHOUT THE ACCOMPLISHMENT OF THE

WORK.

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

AE1.00

SITE PLAN

05 / 06 /2022 RK

1" = 40'-0"F4 Site Plan

5.7

6.2

6.7

B002D

B002G

B002F

B002K

B002E

C009D C009

C009B

C009C

C009A

B001E B001B

B001D B001F

B C

C009E

C009F

C009G

C J

C009I

C009K

C008

C010

C009M

C009H

C009N

B002

B001A

B002A

5 5

DEMOLITION SCHEDULE:

WALL TO BE DEMOLISHED

WALL TO REMAIN

4" SLAB DEPRESSION.

CONTRACTOR SHALL

REMOVE ALL FLOORING

AND MATERIAL BUILDUP

DOWN TO STRUCTURAL

CONCRETE SLAB.

6" SLAB DEPRESSION.

CONTRACTOR SHALL

REMOVE ALL FLOORING

AND MATERIAL BUILDUP

DOWN TO STRUCTURAL

CONCRETE SLAB.

PLAN NOTES:

1 ELECTRICAL PANELS TO BE REMOVED. RE ELEC

FOR MORE INFORMATION.

COOLER WALLS TO BE DEMOLISHED

REMOVE PLUMBING FIXTURES

PNEUMATIC TUBE SYSTEM TO REMAIN. RE.

ELECTRICAL FOR MORE INFORMATION

REMOVE EXISTING SHEET VINYL FLOORING AND

WALL BASE TO EXTENTS SHOWN, PREP FLOOR

TO RECEIVE NEW FINISH.

REMOVE EXISTING VINYL TILE IN ITS ENTIRETY

EXISTING FLOORING AND FINISHES TO REMAIN

REMOVE EXISTING DUMBWAITER CABS AND

SYSTEM IN THEIR ENTIRETY AT BASEMENT

LEVEL ONLY.

TEMPORARY WALL FOR DUST AND DEBRIS

PROTECTION. TO BE CONSTRUCTED AS A 1HR

FIRE RATED ASSEMBLY. OPENINGS TO BE

CONSTRUCTED WITH 3/4HR RATING.

QUARRY TILE TO REMAIN

SALVAGE LIKE MASONRY BLOCK FOR INFILL

GENERAL NOTES:

1. THIS DRAWING REPRESENTS THE GENERAL SCOPE OF

CONTRACTOR REQUIRED DEMOLITION FOR THE

REFERENCED AREA. REFER TO NEW CONSTRUCTION

DRAWINGS FOR REQUIRED WORK THAT MAY NOT BE

REPRESENTED IN THIS DRAWING.

2. REFERENCE PHASING SHEETS, G1.01 & G1.02 FOR

GENERAL OUTLINE OF SEQUENCE OF WORK.

3. CONTRACTOR TO REVIEW ALL EXISTING CONDITIONS

AND ADVISE ARCHITECT/ENGINEER OF ALL DESIGN

DOCUMENT DISCREPANCIES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING

ALL DIMENSIONS AND EXISTING CONDITIONS. ANY

DISCREPANCIES WHICH WILL PREVENT THE

ACCOMPLISHMENT OF INTENT SHOWN ON DRAWINGS

SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE ARCHITECT.

5. WHERE A CONDITION IS NOTED 'TYPICAL' (TYP.), IT IS

UNDERSTOOD THAT ALL SIMILAR CONDITIONS BE

CONSTRUCTED OF THE SAME MATERIALS AND/OR

DIMENSIONS.

6. ALL DIMENSIONS ARE TO FACE OF STUD, FACE OF

CMU, FACE OF CONCRETE FOUNDATION WALL, OR

CENTER OF STL. STRUCTURE, UNLESS NOTED

OTHERWISE.

7. DAMAGE TO WALLS, FLOORS & CEILINGS NOT MARKED

FOR DEMO, SHALL BE REPAIRED

8. FIRE PROTECTION TO BE UPDATED. SPRINKLER HEADS

TO BE MOVED PER RENOVATION WORK.

9. KNOWN HAZARDOUS MATERIAL IN AREAS OF WORK.

CONTRACTOR SHALL REVIEW ASBESTOS SURVEY

FROM VA FOR AREAS OF ABATEMENT.

10. THE LOGISTICS OF ACCESS TO AND FROM THE AREA

OF WORK ARE TO BE REVIEWED WITH THE OWNER

PRIOR TO INITIATION OF ALL WORK.

11. THE CONTRACTOR IS REMINDED THAT THE EXISTING

FACILITY IS TO BE OCCUPIED THROUGHOUT THE

ACCOMPLISHMENT OF THE WORK AND THAT CRITICAL

SERVICES ARE TO BE MAINTAINED THROUGHOUT THE

DEMOLITION AND CONSTRUCTION OF THE WORK.

12. ALL WORK WHICH WILL RESULT IN STRUCTURE

INDUCED NOISE AND/OR VIBRATION ARE TO BE

REVIEWED WITH THE OWNER PRIOR TO

ACCOMPLISHING SUCH WORK. FINAL WORK AND

SCHEDULE FOR DEMOLITION TO BE APPROVED BY THE

OWNER.

13. NO WORK SHALL BE STARTED WITHOUT TEMPORARY

DUST CONTROL MEASURES IN PLACE. DUST CONTROL

MEASURES SHALL REMAIN IN PLACE UNTIL ALL WORK

HAS BEEN ACCOMPLISHED AND THE OWNER AGREES

TO REMOVAL.

14. ALL WORK THAT WILL INFRINGE OR OTHERWISE

ENCUMBER COMMON AREA USE (I.E. CORRIDORS)

SHALL ACCOMPLISHED SUCH AS TO MINIMIZE IMPACT

ONGOING OPERATIONS.

15. LIFE SAFETY SYSTEMS INCLUDING, BUT NOT LIMITED

TO FIRE SUPPRESSION SYSTEMS, EXIT SIGNS,

EMERGENCY LIGHTING, ETC... SHALL REMAIN IN

SERVICE THROUGHOUT CONSTRUCTION. IF SYSTEM

SHUT DOWN IS NECESSARY, CONTRACTOR SHALL

COORDINATE WITH OWNER.

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

AD1.01

KITCHEN DEMOLITION

PLAN

05 / 06 /2022 RK

1/8" = 1'-0"E2 KITCHEN DEMO PLAN

KEY PLAN

PLAN

NORTH 0 8' 16'4'

J H

D028 D029

D031

D030

CBD5

D027

B8

AE1.02

PLAN NOTES:

REMOVE WALL MOUNTED MTL SHELVING UNIT;

SALVAGE FOR REINSTALLATION

REMOVE X-RAY FILM VIEWER

REMOVE AND SALVAGE FOR REINSTALLATION

NOT USED

AREA OF DEPRESSED SLAB. RE STRUCTURAL FOR

INFILL DETAILS

TEMPORARY WALL FOR DUST & DEBRIS

PROTECTION

DEMOLITION SCHEDULE:

WALL TO BE DEMOLISHED

WALL TO REMAIN

4" SLAB DEPRESSION.

CONTRACTOR SHALL

REMOVE ALL FLOORING

AND MATERIAL BUILDUP

DOWN TO STRUCTURAL

CONCRETE SLAB.

6" SLAB DEPRESSION.

CONTRACTOR SHALL

REMOVE ALL FLOORING

AND MATERIAL BUILDUP

DOWN TO STRUCTURAL

CONCRETE SLAB.

GENERAL NOTES:

1. THIS DRAWING REPRESENTS THE GENERAL SCOPE OF

CONTRACTOR REQUIRED DEMOLITION FOR THE

REFERENCED AREA. REFER TO NEW CONSTRUCTION

DRAWINGS FOR REQUIRED WORK THAT MAY NOT BE

REPRESENTED IN THIS DRAWING.

2. REFERENCE PHASING SHEETS, G1.01 & G1.02 FOR

GENERAL OUTLINE OF SEQUENCE OF WORK.

3. CONTRACTOR TO REVIEW ALL EXISTING CONDITIONS

AND ADVISE ARCHITECT/ENGINEER OF ALL DESIGN

DOCUMENT DISCREPANCIES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING

ALL DIMENSIONS AND EXISTING CONDITIONS. ANY

DISCREPANCIES WHICH WILL PREVENT THE

ACCOMPLISHMENT OF INTENT SHOWN ON DRAWINGS

SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE ARCHITECT.

5. WHERE A CONDITION IS NOTED 'TYPICAL' (TYP.), IT IS

UNDERSTOOD THAT ALL SIMILAR CONDITIONS BE

CONSTRUCTED OF THE SAME MATERIALS AND/OR

DIMENSIONS.

6. ALL DIMENSIONS ARE TO FACE OF STUD, FACE OF

CMU, FACE OF CONCRETE FOUNDATION WALL, OR

CENTER OF STL. STRUCTURE, UNLESS NOTED

OTHERWISE.

7. DAMAGE TO WALLS, FLOORS & CEILINGS NOT MARKED

FOR DEMO, SHALL BE REPAIRED

8. FIRE PROTECTION TO BE UPDATED. SPRINKLER HEADS

TO BE MOVED PER RENOVATION WORK.

9. KNOWN HAZARDOUS MATERIAL IN AREAS OF WORK.

CONTRACTOR SHALL REVIEW ASBESTOS SURVEY

FROM VA FOR AREAS OF ABATEMENT.

10. THE LOGISTICS OF ACCESS TO AND FROM THE AREA

OF WORK ARE TO BE REVIEWED WITH THE OWNER

PRIOR TO INITIATION OF ALL WORK.

11. THE CONTRACTOR IS REMINDED THAT THE EXISTING

FACILITY IS TO BE OCCUPIED THROUGHOUT THE

ACCOMPLISHMENT OF THE WORK AND THAT CRITICAL

SERVICES ARE TO BE MAINTAINED THROUGHOUT THE

DEMOLITION AND CONSTRUCTION OF THE WORK.

12. ALL WORK WHICH WILL RESULT IN STRUCTURE

INDUCED NOISE AND/OR VIBRATION ARE TO BE

REVIEWED WITH THE OWNER PRIOR TO

ACCOMPLISHING SUCH WORK. FINAL WORK AND

SCHEDULE FOR DEMOLITION TO BE APPROVED BY THE

OWNER.

13. NO WORK SHALL BE STARTED WITHOUT TEMPORARY

DUST CONTROL MEASURES IN PLACE. DUST CONTROL

MEASURES SHALL REMAIN IN PLACE UNTIL ALL WORK

HAS BEEN ACCOMPLISHED AND THE OWNER AGREES

TO REMOVAL.

14. ALL WORK THAT WILL INFRINGE OR OTHERWISE

ENCUMBER COMMON AREA USE (I.E. CORRIDORS)

SHALL ACCOMPLISHED SUCH AS TO MINIMIZE IMPACT

ONGOING OPERATIONS.

15. LIFE SAFETY SYSTEMS INCLUDING, BUT NOT LIMITED

TO FIRE SUPPRESSION SYSTEMS, EXIT SIGNS,

EMERGENCY LIGHTING, ETC... SHALL REMAIN IN

SERVICE THROUGHOUT CONSTRUCTION. IF SYSTEM

SHUT DOWN IS NECESSARY, CONTRACTOR SHALL

COORDINATE WITH OWNER.

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

AD1.02

MORGUE DEMOLITION

PLAN

05 / 06 /2022 RK

1/4" = 1'-0"F2

MORGUE DEMOLITION

PLAN

KEY PLAN

PLAN

NORTH

0 4' 8'2'

R Q P N.2B Na N M.2 M La L

5.7

6.2

6.7

B002D

B002G

B002F

B002K

B002E

C009D C009

C009B

C009C

C009A

B001E B001B

B001D B001F

B

C

C009E

C009F C009G

C J

C009I

C009K

C008

C010

C009M

C009H

C009N

B002

B001A

B002A

DEMOLITION LEGEND:

WALL TO BE DEMOLISHED

WALL TO REMAIN

SPRINKLER SYSTEM & WALL

MOUNTED ENCLOSURE TO BE

REMOVED

REINFORCED CONCRETE

PLASTER CEILING AND ANY

ASSOCIATED STRUCTURE TO

BE REMOVED INCLUDING TIE

WIRES

2x4 CEILING TILES AND GRID

SYSTEM TO BE REMOVED

INCLUDING TIE WIRES

2x2 CEILING TILES AND GRID

SYSTEM TO BE REMOVED

INCLUDING TIE WIRES

COOLER CEILING TO BE

REMOVED ALONG WITH

COOLER WALLS, FLOOR & ANY

ADDITIONAL STRUCTURE AND

EQUIPMENT

PLAN NOTES:

1 HOOD TO BE REMOVED

NOT USED

TEMPORARY WALL FOR DUST & DEBRIS

PRTECTION

GENERAL NOTES:

1. THIS DRAWING REPRESENTS THE GENERAL SCOPE OF

CONTRACTOR REQUIRED DEMOLITION FOR THE

REFERENCED AREA. REFER TO NEW CONSTRUCTION

DRAWINGS FOR REQUIRED WORK THAT MAY NOT BE

REPRESENTED IN THIS DRAWING.

2. REFERENCE PHASING SHEETS, G1.01 & G1.02 FOR

GENERAL OUTLINE OF SEQUENCE OF WORK.

3. CONTRACTOR TO REVIEW ALL EXISTING CONDITIONS

AND ADVISE ARCHITECT/ENGINEER OF ALL DESIGN

DOCUMENT DISCREPANCIES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING

ALL DIMENSIONS AND EXISTING CONDITIONS. ANY

DISCREPANCIES WHICH WILL PREVENT THE

ACCOMPLISHMENT OF INTENT SHOWN ON DRAWINGS

SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE ARCHITECT.

5. WHERE A CONDITION IS NOTED 'TYPICAL' (TYP.), IT IS

UNDERSTOOD THAT ALL SIMILAR CONDITIONS BE

CONSTRUCTED OF THE SAME MATERIALS AND/OR

DIMENSIONS.

6. ALL DIMENSIONS ARE TO FACE OF STUD, FACE OF

CMU, FACE OF CONCRETE FOUNDATION WALL, OR

CENTER OF STL. STRUCTURE, UNLESS NOTED

OTHERWISE.

7. DAMAGE TO WALLS, FLOORS & CEILINGS NOT MARKED

FOR DEMO, SHALL BE REPAIRED

8. FIRE PROTECTION TO BE UPDATED. SPRINKLER HEADS

TO BE MOVED PER RENOVATION WORK.

9. KNOWN HAZARDOUS MATERIAL IN AREAS OF WORK.

CONTRACTOR SHALL REVIEW ASBESTOS SURVEY

FROM VA FOR AREAS OF ABATEMENT.

10. THE LOGISTICS OF ACCESS TO AND FROM THE AREA

OF WORK ARE TO BE REVIEWED WITH THE OWNER

PRIOR TO INITIATION OF ALL WORK.

11. THE CONTRACTOR IS REMINDED THAT THE EXISTING

FACILITY IS TO BE OCCUPIED THROUGHOUT THE

ACCOMPLISHMENT OF THE WORK AND THAT CRITICAL

SERVICES ARE TO BE MAINTAINED THROUGHOUT THE

DEMOLITION AND CONSTRUCTION OF THE WORK.

12. ALL WORK WHICH WILL RESULT IN STRUCTURE

INDUCED NOISE AND/OR VIBRATION ARE TO BE

REVIEWED WITH THE OWNER PRIOR TO

ACCOMPLISHING SUCH WORK. FINAL WORK AND

SCHEDULE FOR DEMOLITION TO BE APPROVED BY THE

OWNER.

13. NO WORK SHALL BE STARTED WITHOUT TEMPORARY

DUST CONTROL MEASURES IN PLACE. DUST CONTROL

MEASURES SHALL REMAIN IN PLACE UNTIL ALL WORK

HAS BEEN ACCOMPLISHED AND THE OWNER AGREES

TO REMOVAL.

14. ALL WORK THAT WILL INFRINGE OR OTHERWISE

ENCUMBER COMMON AREA USE (I.E. CORRIDORS)

SHALL ACCOMPLISHED SUCH AS TO MINIMIZE IMPACT

ONGOING OPERATIONS.

15. LIFE SAFETY SYSTEMS INCLUDING, BUT NOT LIMITED

TO FIRE SUPPRESSION SYSTEMS, EXIT SIGNS,

EMERGENCY LIGHTING, ETC... SHALL REMAIN IN

SERVICE THROUGHOUT CONSTRUCTION. IF SYSTEM

SHUT DOWN IS NECESSARY, CONTRACTOR SHALL

COORDINATE WITH OWNER.

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

Author

AD1.03

KITCHEN REFLECTED

CEILING DEMOLITION PLAN

05 / 06 /2022 Approver

1/8" = 1'-0"F3

KITCHEN REFLECTED

CEILING DEMOLITION

PLAN

KEY PLAN

PLAN

NORTH 0 8' 16'4'

K J H

D31

D28

D29

D30

CBD5

D27

B8

AE1.02

DEMOLITION LEGEND:

WALL TO BE DEMOLISHED

WALL TO REMAIN

SPRINKLER SYSTEM & WALL

MOUNTED ENCLOSURE TO BE

REMOVED

REINFORCED CONCRETE

PLASTER CEILING AND ANY

ASSOCIATED STRUCTURE TO

BE REMOVED INCLUDING TIE

WIRES

2x4 CEILING TILES AND GRID

SYSTEM TO BE REMOVED

INCLUDING TIE WIRES

2x2 CEILING TILES AND GRID

SYSTEM TO BE REMOVED

INCLUDING TIE WIRES

COOLER CEILING TO BE

REMOVED ALONG WITH

COOLER WALLS, FLOOR & ANY

ADDITIONAL STRUCTURE AND

EQUIPMENT

PLAN NOTES:

1 HOOD TO BE REMOVED

NOT USED

TEMPORARY WALL FOR DUST & DEBRIS

PRTECTION

GENERAL NOTES:

1. THIS DRAWING REPRESENTS THE GENERAL SCOPE OF

CONTRACTOR REQUIRED DEMOLITION FOR THE

REFERENCED AREA. REFER TO NEW CONSTRUCTION

DRAWINGS FOR REQUIRED WORK THAT MAY NOT BE

REPRESENTED IN THIS DRAWING.

2. REFERENCE PHASING SHEETS, G1.01 & G1.02 FOR

GENERAL OUTLINE OF SEQUENCE OF WORK.

3. CONTRACTOR TO REVIEW ALL EXISTING CONDITIONS

AND ADVISE ARCHITECT/ENGINEER OF ALL DESIGN

DOCUMENT DISCREPANCIES.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING

ALL DIMENSIONS AND EXISTING CONDITIONS. ANY

DISCREPANCIES WHICH WILL PREVENT THE

ACCOMPLISHMENT OF INTENT SHOWN ON DRAWINGS

SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE ARCHITECT.

5. WHERE A CONDITION IS NOTED 'TYPICAL' (TYP.), IT IS

UNDERSTOOD THAT ALL SIMILAR CONDITIONS BE

CONSTRUCTED OF THE SAME MATERIALS AND/OR

DIMENSIONS.

6. ALL DIMENSIONS ARE TO FACE OF STUD, FACE OF

CMU, FACE OF CONCRETE FOUNDATION WALL, OR

CENTER OF STL. STRUCTURE, UNLESS NOTED

OTHERWISE.

7. DAMAGE TO WALLS, FLOORS & CEILINGS NOT MARKED

FOR DEMO, SHALL BE REPAIRED

8. FIRE PROTECTION TO BE UPDATED. SPRINKLER HEADS

TO BE MOVED PER RENOVATION WORK.

9. KNOWN HAZARDOUS MATERIAL IN AREAS OF WORK.

CONTRACTOR SHALL REVIEW ASBESTOS SURVEY

FROM VA FOR AREAS OF ABATEMENT.

10. THE LOGISTICS OF ACCESS TO AND FROM THE AREA

OF WORK ARE TO BE REVIEWED WITH THE OWNER

PRIOR TO INITIATION OF ALL WORK.

11. THE CONTRACTOR IS REMINDED THAT THE EXISTING

FACILITY IS TO BE OCCUPIED THROUGHOUT THE

ACCOMPLISHMENT OF THE WORK AND THAT CRITICAL

SERVICES ARE TO BE MAINTAINED THROUGHOUT THE

DEMOLITION AND CONSTRUCTION OF THE WORK.

12. ALL WORK WHICH WILL RESULT IN STRUCTURE

INDUCED NOISE AND/OR VIBRATION ARE TO BE

REVIEWED WITH THE OWNER PRIOR TO

ACCOMPLISHING SUCH WORK. FINAL WORK AND

SCHEDULE FOR DEMOLITION TO BE APPROVED BY THE

OWNER.

13. NO WORK SHALL BE STARTED WITHOUT TEMPORARY

DUST CONTROL MEASURES IN PLACE. DUST CONTROL

MEASURES SHALL REMAIN IN PLACE UNTIL ALL WORK

HAS BEEN ACCOMPLISHED AND THE OWNER AGREES

TO REMOVAL.

14. ALL WORK THAT WILL INFRINGE OR OTHERWISE

ENCUMBER COMMON AREA USE (I.E. CORRIDORS)

SHALL ACCOMPLISHED SUCH AS TO MINIMIZE IMPACT

ONGOING OPERATIONS.

15. LIFE SAFETY SYSTEMS INCLUDING, BUT NOT LIMITED

TO FIRE SUPPRESSION SYSTEMS, EXIT SIGNS,

EMERGENCY LIGHTING, ETC... SHALL REMAIN IN

SERVICE THROUGHOUT CONSTRUCTION. IF SYSTEM

SHUT DOWN IS NECESSARY, CONTRACTOR SHALL

COORDINATE WITH OWNER.

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

Author

AD1.04

MORGUE REFLECTED

CEILING DEMOLITION PLAN

05 / 06 /2022 Approver

1/4" = 1'-0"F3

MORGUE REFLECTED

CEILING DEMOLITION

PLAN

PLAN

NORTH

0 8' 16'4'

E

F

R E

F

WALK-IN COOLER

C009E

WALK-IN

FREEZER

C009D

MECHANICAL

ROOM

C010

MOW

C009B

C A

N T

E E

N

C C

/4

/8

TRAY MAKE LINE

B001I

CART WASH

C009M

M O

W P

R E

P

C A

WAREWASH

C009K

COOKLINE

C009L

B A

I4 .0

AE1.01

C1

3'-6" 3'-10"

C010

C J

B001C

B001D

C009K

FOOD PREP

B001

C O

R R

ID

O

R

C

C009G

S3AA.2

S A

A .2 S

A

A

S A

.1

S2A.1

S3AA

S A

A

S3AA

S3AA

S A

A

S A

A .3

.5

S A

S3A

B001I

ALIGN

H O

U S

E K

E E

P

B

FMEN'S

B001C

WOMEN'S

B001D

LOCKER ROOM

B001E

TRAINING

B001G

CORRIDOR

B001B

STORAGE

C009F

R Q P N.2B Na N M.2 M La L K

6.2

6.7

/8

3'-5"

S3AA.2

S3AA.2

S3AA.2

C009B

C I

ORDERING

C009H

DIRECTOR

C009I

SUPERVISORS

C009J

B G

A B

G

B

B F

B5 /AI4.02

S6AA.5

S6AA.5

S T

O R

A G

E

B H

CHEM. CLST.

B001A

B001A

B H

S3AA

C009F

12'-5 3/8"

/4

/2

28'-6 3/4"

C O

R R

C B

D

D A

I4 .0

D5 /AI4.02

A L

IG

N

12'-2"

2'-4" 4'-0" 1'-0" S3A

AE1.01

E1

S A

.1

S A

A .3

.5

S A

A .3

.5

3'-0" 4'-0" 10" 6'-0" 8'-6" 4'-0" 1'-0" 6'-0"

18'-5 1/2"

S A

.1

S3A.1

S A

A .2

S3AA

S A

A

S1A.1

S A

.1

S A

.1

S A

.1

S3A.1

S1A.1

S A

.1

S1A.1

S3A.1 S1A.1

S A

.1

S A

.1

S A

A

S3AA

S A

.1

S2A.1

S A

.1

S2A.1

S2A.1

S2A.1

S A

.1

S A

.1

AE1.06

B1

S6AA.5

S1A.1

S A

.1

S A

.1S2A.1

S A

.1

S2A.1

S A

.1

S2A.1

S A

.1

S A

.1

S A

.1

S1A.1S A

.1

S A

.1

S1A.1

C A

I4 .0

C A

I4 .0

AE1.01

F1

S3AA.2

S2A.1

AE1.01

F1 Sim

AE1.01

F1 Sim

A

A

AE1.01

F1 Sim

S2A.1 S2A.1S1A.1

S A

.1

S A

.1

S A

.1

S1A.1

S1A.1

B B S1A.1

S A

.1

S3A.1

24'-2 1/8"

/1

S1A.1

S A

.1

S1A.1

S A

.1

F7

AE1.01

E A

I4 .0

AE1.06

B1 Sim

AE1.01

F3

5'-2"

S A

A .4

.5

B011A

BASIC MATERIAL:

C CONCRETE (NON-STRUCTURAL WALLS ONLY)

M MASONRY (CMU)

S METAL STUD

W WOOD STUD

NOMINAL SIZE:

0 7/8" FURRING CHANNEL

1 1 5/8" STUD

2 2 1/2" STUD

3 3 5/8" STUD

4 4" CONCRETE, MASONRY OR METAL STUD

6 6" CONCRETE, MASONRY OR METAL STUD

8 8" CONCRETE, MASONRY

APPLIED LAYERS:

A. 1 LAYER 5/8" DRYWALL / TILE BACKING PANEL

B. 2 LAYERS 5/8" DRYWALL / TILE BACKING PANEL

C. 1 LAYER 5/8" DRYWALL ON 7/8" METAL FURRING CHANNEL

D. 1 LAYER 5/8" DRYWALL ON 1 5/8" STUD FURRING

E. 1 LAYER 5/8" DRYWALL ON 3 5/8" STUD FURRING

MODIFYING CONDITIONS:

1. COMPLETE WALL ASSEMBLY EXTENDS TO 6" ABOVE

ADJOINING CEILING. BRACE WALL AS REQUIRED.

2. PROVIDE ACOUSTIC BATT INSULATION; FULL CAVITY

WIDTH AND FULL WALL HEIGHT.

3. SMOKE PARTITION - UNRATED ASSEMBLY, SHALL NOT

ALLOW THE PASSAGE OF SMOKE

4. 2HR RATED WALL ASSEMBLY. RE UL DESIGN NO. W411

5. 16 GAUGE METAL STUDS

GENERAL NOTES:

1. ALL INTERIOR WALL TYPES ARE S3AA UNLESS NOTED

OTHERWISE.

2. COMPLETE WALL ASSEMBLY IS CONTINUOUS TO BOTTOM

OF ROOF DECK OR BOTTOM OF STRUCTURE ABOVE

UNLESS CHANGED BY MODIFYING CONDITION.

3. PROVIDE TILE BACKER BOARD WHERE REQUIRED AS

SUBSTRATE FOR FINISHES. REFER TO FINISH SCHEDULE

FOR WALL FINISH AND SPECIFICATIONS.

4. PROVIDE MOISTURE RESISTANT DRYWALL PER FINISH

SCHEDULE AND SPECIFICATIONS.

5. REFER TO STRUCTURAL DESIGN FOR MASONRY

REQUIREMENTS.

6. THE PARTITION CONSTRUCTION WILL MAINTAIN ITS

DESIGNATION TO THE POINT OF AN INTERSECTING WALL.

IF NO CHANGE IN DESIGNATION IS SHOWN BEYOND THE

INTERSECTION, THE PREVIOUS PARTITION DESIGNATION

APPLIES TO BOTH.

7. ALL CORRIDORS TO RECEIVE ABUSE RESISTANT

DRYWALL TO 4'-0" A.F.F.

8. REFERENCE ENLARGED PLANS FOR ADDITIONAL

PARTITION CALL OUTS.

S3AA.1

BASIC MATERIAL

NOMINAL SIZE

APPLIED LAYERS CODE

MODIFYING CONDITIONS CODE

PARTITION TYPE LEGEND

PARTITION TYPE SYMBOL

FIRE PARTITION; TWO HOUR FIRE RATED -

UL DESIGN NO. W406, EXTEND FROM FLOOR

TO STRUCTURE ABOVE

SMOKE PARTITION; RESIST PASSAGE OF

SMOKE, EXTEND FROM FLOOR TO

STRUCTURE ABOVE

FIRE & SMOKE RATED

PARTITION INDICATION

A3 /AI4.02

A A

I4 .0

A A

I4 .0

12'-5" 5'-3" 6'-8"

/4

1'-9"

S A

A

S6AA.2

S3AA

S A

.1

S A

A

S A

A .2

S A

.1

S2A.1

S1A.1 S

A

.1

S2A.1

R Q

6.2

6.7

B7 /AI4.02

A5 /AI4.02

B8 /AI4.02

B A

I4 .0

B3 /AI4.02

WOMEN'S

B001D

MEN'S

B001C

LOCKER ROOM

B001E

HOUSE KEEP

B001F

S3AA.3.5

S3AA.2

S A

A

S3AA

S3AA.3.5

A7 /AI4.02

A8 /AI4.02

A A

I4 .0

O P

P

A A

I4 .0

O P

P

S A

.1

S1A.1

Q

7/8" HAT CHANNELS @ 16"

O.C.

3-5/8" MTL. STUD @ 16" O.C.

CORNER GUARD PER

FINISH SCHEDULE

EXISTING SMOOTH FACE

TILE UNIT

EXISTING CONCRETE

COLUMN

5/8" GYP. WALLBOARD

COOLER WALL

SS INSIDE CORNER, RE.

FOOD SERVICE

F5

AE1.01

1-5/8" FURRING STUDS @

16" O.C.

SOLID WOOD BLOCKING

PLAN NOTES:

GENERAL NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING

ALL DIMENSIONS AND EXISTING CONDITIONS. ANY

DISCREPANCIES WHICH WILL PREVENT THE

ACCOMPLISHMENT OF INTENT SHOWN ON DRAWINGS

SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE ARCHITECT.

2. WHERE A CONDITION IS NOTED 'TYPICAL' (TYP.), IT IS

UNDERSTOOD THAT ALL SIMILAR CONDITIONS BE

CONSTRUCTED OF THE SAME MATERIALS AND/OR

DIMENSIONS.

3. ALL DIMENSIONS ARE TO FACE OF STUD, FACE OF CMU,

FACE OF CONCRETE FOUNDATION WALL, OR CENTER OF

STL. STRUCTURE, UNLESS NOTED OTHERWISE.

4. ALL DOOR OPENINGS ARE TO BE LOCATED 4" FROM

HINGE SIDE OF ADJACENT WALL UNLESS CENTERED IN

ROOM OR NOTED OTHERWISE.

5. COORDINATE ROOF AND FLOOR PENETRATIONS W/ MEP

AND STRUCTURAL DRAWINGS.

6. SIGNAGE SCHEDULE ON AI7.02 FOR INTERIOR WALL

MOUNTED ADA SIGNAGE AND LOCATIONS.

7. REFER TO ROOM FINISH SCHEDULE ON AI7.02 FOR

INTERIOR FINISHES.

8. REFER TO TYPICAL ADA FIXTURE MOUNTING GUIDE ON

AI7.02.

9. REFER TO ENLARGED FLOOR PLANS FOR FURTHER

INFORMATION ON PARTITION TYPE TAGS, DIMENSIONS,

ETC.

10. KITCHEN EQUIPMENT IS DEPICTED FOR GENERAL

REFERENCE PURPOSES. REFER TO FOOD SERVICE

DESIGN DOCUMENTS FOR FOOD SERVICE

REQUIRMENTS. ALL DESIGN DIFFERENCES NOTED

BETWEEN ARCHITECTURAL AND FOOD SERVICE SHALL

REFER TO FOOD SERVICE DESIGN FOR FINAL DESIGN.

NEW 2HR FLOOR INFILL. RE: UL DESIGN NO. K 913;

REFER TO STRUCTURAL DESIGN

BUILDING EXPANSION JOINT, COORDINATE WITH

WALL FINISH

OUTLINE OF COMMERCIAL KITCHEN HOOD ABOVE;

REFER TO FOOD SERVICE DESIGN

2 HR RATED FLOOR EXPANSION JOINT; RE: SYSTEM

NO. FF-D-0037 ON SHEET AE0.02

SALVAGED MASONRY BLOCK FOR OPENING INFILL;

MATCH EXISTING

DOOR POSITION APPROXIMATE, EXACT LOCATION

TO BE CONFIRMED BY OWNER

EXISTING OPENING IN FLOOR TO REMAIN OPEN

ONLY WITHIN THE CHASE

CLASS K FIRE EXTINGUISHER

CONT. BACKER ROD & SEALANT

CONT. BACKER ROD & SEALANT

EXISTING WALL

5/8" GYP. OR TILE BACKER; RE.

FINISH SCHED.

MTL. STUD @ 16" O.C. (SIZE PER PLAN)

ALIGN

100'-0"

BASEMENT

AI7.03

A3

AI7.03

A5

EXISTING CONC. COLUMN

7/8" HAT CHANNELS

EXISTING SMOOTH FACE TILE UNIT

5/8" GYP WB

REMOVE RADIUS

FIRE TREATED WD BLOCKING

Na N

RE. SYSTEM NO. FF-D-0037

ON SHEET AE0.02

EXPANSION JOINT COVER;

CONT. S.S. PLATE

RESINOUS FLOOR

TERMINATION STRIP

F

IL

L

D E

P R

E S

S

IO

N E

X

IS

IT

N

G S

L A

B

100'-0"

BASEMENT

F.V.

1 1/2"

EXPANSION JOINT

MAINTAIN EXISTING

EXPANSION JOINT

NEW GYP BD;

RE:WALL TYPE

EXISTING MASONRY

COLUMN FURRING

SOLID BLOCKING

TILE

BID SET DOCUMENTS

CONSULTANT

Drawing Title

Approved: Project Director

Project Title

Location

Issue Date Checked Drawn

Design Project Number:

Building Number

Drawing Number

Office of Construction and Facilities Management

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

A

B

C

D

E

F

A

B

C

D

E

F

PhaseARCHITECT/ENGINEER OF RECORD

U.S. Department of Veterans Affairs

MODERNIZE BASEMENT

KITCHEN & MORGUE

589A4-20-157

COLUMBIA, MO VAMC

Revisions Date

Missouri Certificate of Authority #2003011262

110 Armour Road North Kansas City, MO 64116 Tel. 816.300.4101 Fax 816.300.4102

Richard A. Kuhl - Architect

MO # A-2009008321

3 - 60% CONSTRUCTION DOCUMENTS

2 - DESIGN DEVELOPMENT

1 - SCHEMATIC DESIGN

07/23/2021

05/14/2021

01/10/2021

4 - 90% CONSTRUCTION DOCUMENTS 09/17/2021

5 - 100% CONSTRUCTION DOCUMENTS 12/28/2021

6 - BID SET DOCUMENTS 05/06/2022

NM

AE1.01

KITCHEN MODERNIZATION

PLAN

05 / 06 /2022 RK

1/8" = 1'-0"E4 KITCHEN FLOOR PLAN

KEY PLAN

1/4" = 1'-0"C1 ENLARGED PLAN

PLAN

NORTH

0 8' 16'4'

0 4' 8'2'

1 1/2" = 1'-0"E1

COLUMN DETAIL @

COOLER

1 1/2" = 1'-0"F1

NEW WALL @

EXISTING

1 1/2" = 1'-0"F5 TYP. BASE DETAIL

3" = 1'-0"F7 EXPANSION JOINT

1 1/2" = 1'-0"F3

EXPANSION JOINT

WALL

UPUP

SUPPLY STOR.

D030A

RR

D028

H O U S E K

E E P

IN

G

D

AUTOPSY RM

D030

TISSUE STORAGE

D030B

CORRIDOR

CBD5

FOLDING

BENCH

D A

I4 .0

C L R

6'-1" 5 1/2"

1'-3"

AE1.02

F2

B4 /AI4.01

B6 /AI4.01

D3 /AI4.01

D A

I4 .0

WALK-IN LAYOUT

33 BODY STORAGE

BODY STORAGE

D027

D030

7 7

S A

.1

S1A.1

S3AA

S A

A .1

S A

.1

S1A.1

S3A.1

S A

.1

S3A.1

S3AA

D6 /AI4.01

K

J H

2"

T Y

P

F.V.

7'-4"

F .V

5 5

3'-2"

ALIGNEQ EQ

CBD5 S

A

A .2

12'-10"

S1A.1

S A

.1 S

A

.1

AE1.06

D1

E X

IS

T

IN

G

W A

L L

EXISTING WALL

6'-4" 7'-8"

S A

.1

S A

A

S1A.1

S A

.1

S A

.1 S

A

.1 S

A

.1

S A

.1 S

A

.1

S1A.1

5'-0"5'-3"

S1A.1

S3BB.3

S1A.1

S A

.1

S A

A .3

.5

S3AA.3.5 S

A

A .3

.5

S3AA.3.5 S1A.1

D030B

CL CL

S1A.1

S A

.1

S1A.1

S A

.1

S1A.1

S A

.1

4'-9"

D029D028

S1A.1

S A

.1

4'-1" 8'-9"

CL

CL

CL

S A

.1

S A

.1

S2A.1

S3AA.2

S A

.1

AE1.02

C8

B8

AE1.02

F.V.

21'-0"

F .V

/4

F .V

F .V

F .V

/4

CL CL

5'-0"

EQ EQ

2'-0"

EQ EQ

E Q

E Q

CL

F.V.

10'-1 1/2" 3'-9"

F.V.

7'-1 1/2"

3'-1 3/8"

F .V

F .V

F .V

F.V.

1'-4"

F.V.

14'-0"

F .V

F .V

WORKSTATION

CBD5A

F.V.

1'-8"

F.V.

13'-4"

4'-0"

PLAN NOTES:

GENERAL NOTES:

1. CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING

ALL DIMENSIONS AND EXISTING CONDITIONS. ANY

DISCREPANCIES WHICH WILL PREVENT THE

ACCOMPLISHMENT OF INTENT SHOWN ON DRAWINGS

SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF

THE ARCHITECT.

2. WHERE A CONDITION IS NOTED 'TYPICAL' (TYP.), IT IS

UNDERSTOOD THAT ALL SIMILAR CONDITIONS BE

CONSTRUCTED OF THE SAME MATERIALS AND/OR

DIMENSIONS.

3. ALL DIMENSIONS ARE TO FACE OF STUD, FACE OF CMU,

FACE OF CONCRETE FOUNDATION WALL, OR CENTER OF

STL. STRUCTURE, UNLESS NOTED OTHERWISE.

4. ALL DOOR OPENINGS ARE TO BE LOCATED 4" FROM

HINGE SIDE OF ADJACENT WALL UNLESS CENTERED IN

ROOM OR NOTED OTHERWISE.

5. COORDINATE ROOF AND FLOOR PENETRATIONS W/ MEP

AND STRUCTURAL DRAWINGS.

6. SIGNAGE SCHEDULE ON AI7.02 FOR INTERIOR WALL

MOUNTED ADA SIGNAGE AND LOCATIONS.

7. REFER TO ROOM FINISH SCHEDULE ON AI7.02 FOR

INTERIOR FINISHES.

8. REFER TO TYPICAL ADA FIXTURE MOUNTING GUIDE ON

AI7.02.

9. REFER TO ENLARGED FLOOR PLANS FOR FURTHER

INFORMATION ON PARTITION TYPE TAGS, DIMENSIONS,

ETC.

MORGUE COOLER WALL, CONTRACTOR TO FIELD

VERIFY MEASUREMENTS FOR COOLER SUPPLIER.

CONTRACTOR TO SUPPLY FLOOR, WALLS, CEILING,

DOOR, DOOR THRESHOLD, LIGHTING & ELECTRICAL

RECEPTICALS.

27" TRAY WIDTH - 5 TIER RACK, SUPPLIED BY

COOLER MANF.

32" TRAY WIDTH - 4 TIER BARIATRIC RACK, SUPPLIED

BY COOLER MANF.

NEW SCISSOR LIFT SUPPLIED BY COOLER MANF.

NEW FLOOR DRAINS; RE: PLUMBING

18" x 48" EXISTING SHELVES; SALVAGED FOR REUSE

DISSECTION TABLE; SALVAGED FOR REUSE. RE:

MEP DRAWINGS FOR POWER AND WATER

REQUIREMENTS

EXISTING FLOOR DRAINS; CONTRACTOR TO VERIFY

LOCATION AND CONDITION. CONTRACTOR TO

COORD. LOCATION WITH COOLER MANF.

PATCH WALL FINISH AND WALL BASE TO MATCH

EXISTING

EMERGENCY SHOWER AND EYE WASH STATION. RE:

PLUMB

EQUIPMENT, RE: AI7.04

(NOT USED)

NEW 2HR FLOOR INFILL. RE: STRUCTURAL DESIGN

LOCKERS

CLASS A FIRE EXTINGUISHER ON BRACKET

BASIC MATERIAL:

C CONCRETE (NON-STRUCTURAL WALLS ONLY)

M MASONRY (CMU)

S METAL STUD

W WOOD STUD

NOMINAL SIZE:

0 7/8" FURRING CHANNEL

1 1 5/8" STUD

2 2 1/2" STUD

3 3 5/8" STUD

4 4" CONCRETE, MASONRY OR METAL STUD

6 6" CONCRETE, MASONRY OR METAL STUD

8 8" CONCRETE, MASONRY

APPLIED LAYERS:

A. 1 LAYER 5/8" DRYWALL / TILE BACKING PANEL

B. 2 LAYERS 5/8" DRYWALL / TILE BACKING PANEL

C. 1 LAYER 5/8" DRYWALL ON 7/8" METAL FURRING CHANNEL

D. 1 LAYER 5/8" DRYWALL ON 1 5/8" STUD FURRING

E. 1 LAYER 5/8" DRYWALL ON 3 5/8" STUD FURRING

MODIFYING CONDITIONS:

1. COMPLETE WALL ASSEMBLY EXTENDS TO 6" ABOVE

ADJOINING CEILING. BRACE WALL AS REQUIRED.

2. PROVIDE ACOUSTIC BATT INSULATION; FULL CAVITY

WIDTH AND FULL WALL HEIGHT.

3. SMOKE PARTITION - UNRATED ASSEMBLY, SHALL NOT

ALLOW THE PASSAGE OF SMOKE

4. 2HR RATED WALL ASSEMBLY. RE UL DESIGN NO. W411

5. 16 GAUGE METAL STUDS

GENERAL NOTES:

1. ALL INTERIOR WALL TYPES ARE S3AA UNLESS NOTED

OTHERWISE.

2. COMPLETE WALL ASSEMBLY IS CONTINUOUS TO BOTTOM

OF ROOF DECK OR BOTTOM OF STRUCTURE ABOVE

UNLESS CHANGED BY MODIFYING CONDITION.

3. PROVIDE TILE BACKER BOARD WHERE REQUIRED AS

SUBSTRATE FOR FINISHES. REFER TO FINISH SCHEDULE

FOR WALL FINISH AND SPECIFICATIONS.

4. PROVIDE MOISTURE RESISTANT DRYWALL PER FINISH

SCHEDULE AND SPECIFICATIONS.

5. REFER TO STRUCTURAL DESIGN FOR MASONRY

REQUIREMENTS.

6. THE PARTITION CONSTRUCTION WILL MAINTAIN ITS

DESIGNATION TO THE POINT OF AN INTERSECTING WALL.

IF NO CHANGE IN DESIGNATION IS SHOWN BEYOND THE

INTERSECTION, THE PREVIOUS PARTITION DESIGNATION

APPLIES TO BOTH.

7. ALL CORRIDORS TO RECEIVE ABUSE RESISTANT

DRYWALL TO 4'-0" A.F.F.

8. REFERENCE ENLARGED PLANS FOR ADDITIONAL

PARTITION CALL OUTS.

S3AA.1

BASIC MATERIAL

NOMINAL SIZE

APPLIED LAYERS CODE

MODIFYING CONDITIONS CODE

PARTITION…