FHPS-Structured Cabling RFP-APP B-Thornapple (1).pdf

PDF 2 MB Posted

Attached to
Request for Structured Cabling System
Solicitation number
RFP FHP 210000000025 2
Issued by
Kent County, Grand Rapids City, Michigan

About this file

This file is a technical specifications document for the Thornapple structured cabling project, part of the FHPS (presumably a school district) RFP. The document provides detailed infrastructure requirements for a technology installation space, including specifications for wireless access points, data locations, A/V capabilities, and teacher station connections throughout multiple rooms. The project requires the installation of grounding busbars, electrical receptacles (L5-20R, 120V), four 4-inch conduits for horizontal pathways, 12-inch by 4-inch cable trays, and 3/4-inch fire-treated plywood backboards standing 8 feet high. Environmental controls must maintain room temperatures between 64°F and 75°F with relative humidity levels between 37% and 55% non-condensing, supported by a dedicated A/C unit. The specifications indicate no suspended ceilings are required or desired, and all grounding infrastructure must connect to the main building ground system.

The document does not contain information regarding pricing terms, set-asides, incumbent contractors, funding sources, or contract award dates. The technical specifications provided are primarily focused on infrastructure requirements and installation standards necessary to support the structured cabling network across the identified facility spaces.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Legend

General Data

A/V Location

Wireless AP

Teacher StationT

A/V Rack

T

T

TT

T

I

4" Slv

4TGB

For future use

For future use

For future use

A/V Location

Wireless AP

Teacher StationT

T

T T

T T

T ex ex

A/V Location

Wireless AP

Teacher StationT

A/V Rack ex ex ex ex ex ex ex ex ex ex

To be removed

A/V Location

Wireless AP

Teacher StationT

Legend

General Data

A/V Location

Wireless AP

Teacher StationT

T

T

T

T

T

T

T

T ex ex ex ex ex ex ex

M

TGB

4" S lv

General Notes:

1. Suspended ceilings are not required or desired.

2. The space should be environmentally controlled to maintain a room temperature range of 64F to 75F (18°C to 24°C) with a relative humidity level between 37% to 55% non-condensing.

Space should have a dedicated A/C unit.

3. Grounding busbars shall be provided and grounded to the main building ground. Mount and secure to backboard at 80" AFF.

Detailed Notes:

1. L5-20R, 120V. Receptacles should be mounted inside of the technology cabinet provided by others.

2. Four 4" conduits should be provided for horizontal pathway from the hallway.

3. 12"x4" cable tray should be provided to support cabling from sleeve locations to provided equipment rack location.

4. 3/4" A/C fire treated plywood backboards to be installed, 8’ high, mounted so the bottom is 6" AFF, painted with two coats of fire retardant white paint.

x