This document is a division of responsibilities diagram for a Door Access Control (DAC) System Request for Quotation (RFQ) for Forest Hills Public Schools. The detailed schematic outlines the specific installation responsibilities for various components of a door access control system, delineating which elements will be provided and installed by the school district or construction trades (gray), and which will be the responsibility of the DAC vendor to provide and install (blue and green). The diagram comprehensively maps out infrastructure requirements including network equipment, electrical connections, cabling pathways, door hardware, sensors, intercoms, and related technological components necessary for a comprehensive access control system implementation.

The diagram specifies technical details such as J-hook cable supports every 5 feet, 10-foot service loops, pathway routing through drop ceilings and interior walls, and specific mounting locations for devices like card readers, keypads, handicap push buttons, and door release mechanisms. Notable technical components include network switches, patch panels, rack equipment, ground bars, addressable fire relays, and various door-related hardware like electrified strikes, transfer hinges, and door contact sensors. The diagram includes a note that ancillary components may also be required to be provided by the vendor when possible, suggesting flexibility in the implementation approach and potential for vendor-driven solutions to meet the school district's access control infrastructure needs.

View the file

Other files

File Type Posted
FHPS DAC RFP Addendum 1.pdf PDF
FHPS DAC RFQ APP D.pdf PDF
FHPS DAC RFP APP C (1).pdf PDF
FHPS DAC RFP APP C.pdf PDF
FHPS Door Access Control System RFP (1).pdf PDF
FHPS DAC RFP APP A (1).xlsx XLSX spreadsheet
FHPS DAC RFP APP A.xlsx XLSX spreadsheet
FHPS Door Access Control System RFP.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DAC panel

Equipment room wall fireproofing sleeve

J-hooks every 5 feet

Interior wall

Drop ceiling

10 feet service loop door frame

Provided and installed by the District or construction trades

DAC vendor to provide and install.

DAC vendor to reuse when possible, or alternatively replace or add new as needed

Forest Hills Public Schools – Door Access Control System RFQ – Appendix D Division of responsibilities for door access control (DAC) installation metal conduit and box electrical power backing board in equipment room

Door

Electrified hardware

(whether strike or door bar + transfer hinge, the connection point is on the frame side) pathways

1-gang box for card reader or keypad handicap push button Door release button / panic button pathway

Drop ceiling

Intercom master station handicap controller/ power supply/ maglock

1-gang box for intercom door station

To patch panel

To patch panel rack ladder core

Interior ceiling plenum space UTP addressable fire relay

Note: Additionally ancillary components may be required to be provided by the vendor when possible.

Ground bar in equipment room

Network switch

Patch panel

REX and door contact sensors

Rack in equipment room

Slide Number 1