FC Sprinkler Inspection Reports.pdf

PDF 7 MB Posted

Attached to
26008-A Fire Sprinkler Inspections
Solicitation number
PE-65600-NONST-2026-000000185
Issued by
Douglas County, Georgia

About this file

This document comprises annual fire protection system inspection reports for multiple Fayette County, Georgia facilities conducted by Acom Fire Solutions between March 3-5, 2025. The inspections cover sprinkler systems, fire alarm systems, and related suppression equipment at ten fire stations, the Administration Complex, Justice Center, Old Courthouse, Public Works facility, and Senior Center locations. The inspections were conducted in accordance with NFPA 25 (water-based fire protection systems) and NFPA 72 (fire alarm systems) standards by certified technician Cody Cook, who holds NICET Level II certifications in fire alarm systems, water-based systems, portable fire extinguishers, pre-engineered kitchen suppression systems, emergency lights/exit signs, and backflow prevention.

The inspection reports document the operational status of fire protection equipment across all facilities, with most systems receiving yellow tags indicating operational status with minor deficiencies. Common deficiencies identified across multiple properties include outdated pressure gauges, overdue internal pipe investigations (due within 5 years per NFPA standards), and missing or faded fire department connection identification signage. Notable findings include broken sprinkler cover plates at Fire Station 10, a cracked main drain at the Senior Center wet system, and out-of-date batteries in the Senior Center's fire alarm booster panel. The Old Courthouse demonstrated the most compliant performance with all systems receiving green tags and no deficiencies noted, while the Senior Center's dry sprinkler system and fire alarm system failed air leakage and battery condition tests respectively, requiring remedial action and scheduled testing within specified timeframes.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Annual Inspection Report

Completed on: 2025-03-04 for

Fayette County Administration Complex

140 Stonewall Ave W

Fayetteville, GA 30214-1520

Conducted By:

Cody Cook

NICET ll ITM Fire Alarm Systems (NFPA 72)

ACE ll ITM Water-Based Systems (NFPA 25)

Portable Fire Extinguishers (NFPA 10)

Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96)

Emergency Lights / Exit Signs

Backflow Prevention (NFPA 13 & 25)

Acom Fire Solutions

7521 Veterans Parkway

Columbus, Georgia 31909

Inspection Summary

This is to certify that our representative has inspected the equipment noted below and that he has left the equipment in operating condition. There is available in our file, a complete record of conditions as found and all repairs made and recommended.

Tag Color

☐ (Green Tag) Sprinkler Operational ☑ (Yellow Tag) Sprinkler Operational with Deficiencies

☐ (Red Tag) Sprinkler Inoperable ☐ 5-Year Sprinkler Inspection

☐ Kitchen Suppression Compliant ☐ (Red Tag)Kitchen Suppression Non Compliant

SPRINKLER SUMMARY

SYSTEM TECHNICIAN TAG COLOR QTY INSPECTED QTY FAILED DATE INSPECTED

General Cody Cook 1 1 2025-03-04

General Wet Cody Cook 1 0 2025-03-04

Wet Cody Cook (Yellow Tag) Sprinkler Operational with Deficiencies

1 0 2025-03-04

Butterfly Cody Cook 3 0 2025-03-04

ITV Cody Cook 1 0 2025-03-04

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Copyright 2025 Inspect Point

Report of Inspection / Test General Questions

OWNER SECTION

Is the building occupied? Yes

No

NA

Has the occupancy classification and hazard of contents remained the same since the last inspection?

Yes

No

NA

Are all fire protection systems in service? Yes

No

NA

Has the system remained in service without modification since the last inspection?

Yes

No

NA

Was the system free of actuations of devices or alarms since the last inspection?

Yes

No

NA

FIRE DEPARTMENT CONNECTION

Is the FDC plainly visible? Yes

No

NA

Is the FDC easily accessible? Yes

No

NA

Is the FDC swivels and couplings not damaged? Yes

No

NA

Are the FDC caps and plugs in place? Yes

No

NA

Are the FDC gaskets in place and in good condition? Yes

No

NA

Is the FDC check valve drip free? Yes

No

NA

Is the clapper and automatic drain valve in place and properly operating?

Yes

No

NA

Is the FDC identification sign(s) in place? Yes

No

NA

SPRINKLER HEADS

Are there the proper number and type of spare sprinklers? Yes

No

NA

Are visible sprinklers in the proper position: upright, pendent, sidewall?

Yes

No

NA

Are visible sprinklers free of corrosion and physical damage?

Yes

No

NA

Is there proper clearance below the sprinklers? Yes

No

NA

Are visible sprinklers free of foreign materials including paint?

Yes

No

NA

Is there liquid in all visible glass bulb sprinklers? Yes

No

NA

Are there spare sprinklers and a sprinkler wrench? Yes

No

NA

Is the information sign attached and legible? Yes

No

NA

Are all the sprinklers dated 1920 or later? Yes

No

NA

Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?

Yes

No

NA

Standard response sprinklers 75 or more years old replaced or successfully sample tested within last 5 years?

Yes

No

NA

Dry-type sprinklers replaced or successfully sample tested within last 10 years?

Yes

No

NA

Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?

Yes

No

NA

PIPES

Is the visible pipe in good condition with no external corrosion?

Yes

No

NA

Does visible pipe have no mechanical damage or leaks? Yes

No

NA

Does visible pipe have no external loads? Yes

No

NA

Are visible pipe hangers and seismic braces not damaged or loose?

Yes

No

NA

Is the pipe through freezers free if any ice blockage? Yes

No

NA

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation)

Yes

No

NA

VALVE AREA

Are the control valves (including backflow preventer isolation valves) supervised with seals in correct (open or closed) position?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals accessible?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals free from leaks?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals have appropriate wrenches?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision in correct (open or closed) position?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision locked or is supervision in place?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision accessible?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision free from any leaks?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision have the appropriate wrenches?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified?

Yes

No

NA

Are all check valves externally inspected, operating properly, and are in good condition?

Yes

No

NA

Are the gauges on system in good condition and showing normal water supply pressure?

Yes

No

NA

Is the hydraulic name plate (calculated systems) attached securely to the riser and legible?

Yes

No

NA

Are Pressure reducing valves in open position and not leaking?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Are Pressure reducing valves with downstream pressure per the design?

Yes

No

NA

Are Pressure reducing valves in good condition including no handwheels broken?

Yes

No

NA

Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Do valve supervisory switches indicate movement? Yes

No

NA

The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Have post indicating valves been opened until spring or torsion felt in the rod and then closed back 1/4 turn?

Yes

No

NA

All control valves operated through full range and returned to normal position?

Yes

No

NA

Have pressure reducing valves passed partial flow test? Yes

No

NA

BACKFLOW PREVENTERS

Is relief port on RPZ device not discharging? Yes

No

NA

Have backflow devices passed forward flow test? Yes

No

NA

ALARMS

Is the alarm valve free from physical damage? Yes

No

NA

Is the trim in correct (open or closed) position? Yes

No

NA

Is there no leakage in the retarding chamber or drains? Yes

No

NA

Are alarms and supervisory devices not damaged? Yes

No

NA

Do low temperature alarms look ok? Yes

No

NA

MAINTENANCE

Perform an obstruction investigation if any of the following were found: defective intake screen on pump supplied from open sources, obstructive material discharged during flow tests, foreign material in dry-type valves, foreign material in water during drain test or plugging of inspector's test connection, plugging of pipe or sprinklers found, failure to flush yard piping or surrounding mains following new installation or repairs, record of broken mains in the vicinity, abnormal frequent false-tripping of dry valves, system has just been returned to service after more than 1 year, there is a reason to think the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe, raw water was pumped into the fire department connection, pinhole leaks

Yes

No

NA

If a sprinkler failed a sample test were all the sprinklers represented by that sample replaced?

Yes

No

NA

If sprinklers have been replaced, were they proper replacements?

Yes

No

NA

Were marine systems normally having fresh water drained and refilled twice if raw water got into the system?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Was heat tape inspected per the manufacturer's instructions?

Yes

No

NA

If conditions were found that required flushing, was flushing of the system conducted?

Yes

No

NA

Have adjusted, repaired, reconditioned, or replaced components had proper tests/inspections performed?

Yes

No

NA

Was a drain test conducted after opening any closed valve? Yes

No

NA

Operating stem of all OS&Y valves lubricated, completely closed and reopened?

Yes

No

NA

Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Report of Inspection / Test for System - Wet Sprinkler

Tag Color

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

MAIN DRAIN FLOW TESTS

System Initial Static Residual Static Seconds to Return to

Initial Static

Flow Observed?

Did waterflow alarm operate?

Are results comparable to previous test?

Wet Sprinkler 55 45 55 4 Yes Yes Yes

INSPECTORS TEST CONNECTION

Wet Sprinkler (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

2nd Floor Suite 214 Breakroom

1" Test Valve 75 Yes Yes Yes Yes Yes

VALVES

Wet Sprinkler (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tam per

Pass

6" Butterfly 1st Floor Mechanical Room Butterfly 6 " Not Secured Yes Yes Yes Yes Yes Pass Pass

6" butterfly vave 2nd floor mechanical room Butterfly 6 " Locked Yes Yes Yes Yes Yes Pass Pass

4" butterfly valve 1st Floor Mechanical Room Butterfly 4 " Locked Yes Yes Yes Yes Yes Pass Pass

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Questions with Photos and Notes

Wet Sprinkler - Tag Color (Yellow Tag) Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Deficiencies - General Questions

Deficiency #1

Are the gauges on system in good condition and showing normal water supply pressure?: No

Notes: Gauges out of date

Deficiency #2

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation): No

Notes: Due for 5 year internal investigation

Deficiencies - General Wet System Questions

None

Deficiencies - Wet Sprinkler

None

Deficiencies - FDC

None

Deficiencies - Inspectors Test Connection

None

Deficiencies - Valves

None

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention

(NFPA 13 & 25)

2025-03-04

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Completed on: 2025-03-05 for

Fayette County Fire Station 1

450 GA-279

Fayetteville, GA 30214-3420

Conducted By:

Cody Cook

NICET ll ITM Fire Alarm Systems (NFPA 72)

ACE ll ITM Water-Based Systems (NFPA 25)

Portable Fire Extinguishers (NFPA 10)

Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96)

Emergency Lights / Exit Signs

Backflow Prevention (NFPA 13 & 25)

Acom Fire Solutions left the equipment in operating condition. There is available in our file, a complete record of conditions as found and all repairs made and recommended.

Tag Color

☐ (Green Tag) Sprinkler Operational ☑ (Yellow Tag) Sprinkler Operational with Deficiencies

☐ (Red Tag) Sprinkler Inoperable ☐ 5-Year Sprinkler Inspection

☐ Kitchen Suppression Compliant ☐ (Red Tag)Kitchen Suppression Non Compliant

SPRINKLER SUMMARY

SYSTEM TECHNICIAN TAG COLOR QTY INSPECTED QTY FAILED DATE INSPECTED

General Cody Cook 1 1 2025-03-05

General Wet Cody Cook 1 0 2025-03-05

Wet Cody Cook (Yellow Tag) Sprinkler Operational with Deficiencies

1 0 2025-03-05

Butterfly Cody Cook 1 0 2025-03-05

ITV Cody Cook 1 0 2025-03-05

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs

Is the building occupied? Yes

No

NA

Has the occupancy classification and hazard of contents remained the same since the last inspection?

Yes

No

NA

Are all fire protection systems in service? Yes

No

NA

Has the system remained in service without modification since the last inspection?

Yes

No

NA

Was the system free of actuations of devices or alarms since the last inspection?

Yes

No

NA

FIRE DEPARTMENT CONNECTION

Is the FDC plainly visible? Yes

No

NA

Is the FDC easily accessible? Yes

No

NA

Is the FDC swivels and couplings not damaged? Yes

No

NA

Are the FDC caps and plugs in place? Yes

No

NA

Are the FDC gaskets in place and in good condition? Yes

No

NA

Is the FDC check valve drip free? Yes

No

NA

Is the clapper and automatic drain valve in place and properly operating?

Yes

No

NA

Is the FDC identification sign(s) in place? Yes

No

NA

SPRINKLER HEADS

Are there the proper number and type of spare sprinklers? Yes

No

NA

Are visible sprinklers in the proper position: upright, pendent, sidewall?

Yes

No

NA

Are visible sprinklers free of corrosion and physical damage?

Yes

No

NA

Is there proper clearance below the sprinklers? Yes

No

NA

Are visible sprinklers free of foreign materials including paint?

Yes

No

NA

Is there liquid in all visible glass bulb sprinklers? Yes

No

NA

Are there spare sprinklers and a sprinkler wrench? Yes

No

NA

Is the information sign attached and legible? Yes

No

NA

Are all the sprinklers dated 1920 or later? Yes

No

NA

Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25) years?

Yes

No

NA

Standard response sprinklers 75 or more years old replaced or successfully sample tested within last 5 years?

Yes

No

NA

Dry-type sprinklers replaced or successfully sample tested within last 10 years?

Yes

No

NA

Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?

Yes

No

NA

PIPES

Is the visible pipe in good condition with no external corrosion?

Yes

No

NA

Does visible pipe have no mechanical damage or leaks? Yes

No

NA

Does visible pipe have no external loads? Yes

No

NA

Are visible pipe hangers and seismic braces not damaged or loose?

Yes

No

NA

Is the pipe through freezers free if any ice blockage? Yes

No

NA

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation)

Yes

No

NA

VALVE AREA

Are the control valves (including backflow preventer isolation valves) supervised with seals in correct (open or closed) position?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals accessible?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals free from leaks?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals have appropriate wrenches?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision in correct (open or closed) position?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision locked or is supervision in place?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision accessible?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision free from any leaks?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision have the appropriate wrenches?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified?

Yes

No

NA

Are all check valves externally inspected, operating properly, and are in good condition?

Yes

No

NA

Are the gauges on system in good condition and showing normal water supply pressure?

Yes

No

NA

Is the hydraulic name plate (calculated systems) attached securely to the riser and legible?

Yes

No

NA

Are Pressure reducing valves in open position and not leaking?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Yes

No

NA

Are Pressure reducing valves in good condition including no handwheels broken?

Yes

No

NA

Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Do valve supervisory switches indicate movement? Yes

No

NA

The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Have post indicating valves been opened until spring or torsion felt in the rod and then closed back 1/4 turn?

Yes

No

NA

All control valves operated through full range and returned to normal position?

Yes

No

NA

Have pressure reducing valves passed partial flow test? Yes

No

NA

BACKFLOW PREVENTERS

Is relief port on RPZ device not discharging? Yes

No

NA

Have backflow devices passed forward flow test? Yes

No

NA

ALARMS

Is the alarm valve free from physical damage? Yes

No

NA

Is the trim in correct (open or closed) position? Yes

No

NA

Is there no leakage in the retarding chamber or drains? Yes

No

NA

Are alarms and supervisory devices not damaged? Yes

No

NA

Do low temperature alarms look ok? Yes

No

NA

MAINTENANCE

Perform an obstruction investigation if any of the following were found: defective intake screen on pump supplied from open sources, obstructive material discharged during flow tests, foreign material in dry-type valves, foreign material in water during drain test or plugging of inspector's test connection, plugging of pipe or sprinklers found, failure to flush yard piping or surrounding mains following new installation or repairs, record of broken mains in the vicinity, abnormal frequent false-tripping of dry valves, system has just been returned to service after more than 1 year, there is a reason to think the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe, raw water was pumped into the fire department connection, pinhole leaks

Yes

No

NA

If a sprinkler failed a sample test were all the sprinklers represented by that sample replaced?

Yes

No

NA

If sprinklers have been replaced, were they proper replacements?

Yes

No

NA

Were marine systems normally having fresh water drained and refilled twice if raw water got into the system?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Yes

No

NA

If conditions were found that required flushing, was flushing of the system conducted?

Yes

No

NA

Have adjusted, repaired, reconditioned, or replaced components had proper tests/inspections performed?

Yes

No

NA

Was a drain test conducted after opening any closed valve? Yes

No

NA

Operating stem of all OS&Y valves lubricated, completely closed and reopened?

Yes

No

NA

Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

MAIN DRAIN FLOW TESTS

System Initial Static Residual Static Seconds to Return to

Initial Static

Flow Observed?

Did waterflow alarm operate?

Are results comparable to previous test?

Wet Sprinkler 75 45 75 3 Yes Yes Yes

INSPECTORS TEST CONNECTION

Wet Sprinkler (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

Tested at Riser . 32 Yes Yes Yes Yes Yes

VALVES

Wet Sprinkler (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tamp er

Pass

1-1/2" Butterfly Milwaukee Laundry Room Butterfly 1-1/2 " Supervision Yes Yes Yes Yes Yes Pass Pass

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Tag) Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Are the gauges on system in good condition and showing normal water supply pressure?: No

Notes: Gauges out of date

Deficiency #2

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation): No

Notes: Due for 5 year internal investigation

Deficiencies - General Wet System Questions

None

Deficiencies - Wet Sprinkler

None

Deficiencies - FDC

None

Deficiencies - Inspectors Test Connection

None

Deficiencies - Valves

None

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention

(NFPA 13 & 25)

2025-03-05

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 1

450 GA-279

Fayetteville GA 30214-3420

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25) for

Fayette County Fire Station 2

1330 Hwy 92

Fayetteville, GA 30214-3376

Conducted By:

Cody Cook

NICET ll ITM Fire Alarm Systems (NFPA 72)

ACE ll ITM Water-Based Systems (NFPA 25)

Portable Fire Extinguishers (NFPA 10)

Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96)

Emergency Lights / Exit Signs

Backflow Prevention (NFPA 13 & 25)

Acom Fire Solutions left the equipment in operating condition. There is available in our file, a complete record of conditions as found and all repairs made and recommended.

Tag Color

☐ (Green Tag) Sprinkler Operational ☑ (Yellow Tag) Sprinkler Operational with Deficiencies

☐ (Red Tag) Sprinkler Inoperable ☐ 5-Year Sprinkler Inspection

☐ Kitchen Suppression Compliant ☐ (Red Tag)Kitchen Suppression Non Compliant

SPRINKLER SUMMARY

SYSTEM TECHNICIAN TAG COLOR QTY INSPECTED QTY FAILED DATE INSPECTED

General Cody Cook 1 1 2025-03-05

General Wet Cody Cook 1 0 2025-03-05

Wet Cody Cook (Yellow Tag) Sprinkler Operational with Deficiencies

1 0 2025-03-05

Butterfly Cody Cook 1 0 2025-03-05

Post Indicator Cody Cook 1 0 2025-03-05

ITV Cody Cook 1 0 2025-03-05

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs

Is the building occupied? Yes

No

NA

Has the occupancy classification and hazard of contents remained the same since the last inspection?

Yes

No

NA

Are all fire protection systems in service? Yes

No

NA

Has the system remained in service without modification since the last inspection?

Yes

No

NA

Was the system free of actuations of devices or alarms since the last inspection?

Yes

No

NA

FIRE DEPARTMENT CONNECTION

Is the FDC plainly visible? Yes

No

NA

Is the FDC easily accessible? Yes

No

NA

Is the FDC swivels and couplings not damaged? Yes

No

NA

Are the FDC caps and plugs in place? Yes

No

NA

Are the FDC gaskets in place and in good condition? Yes

No

NA

Is the FDC check valve drip free? Yes

No

NA

Is the clapper and automatic drain valve in place and properly operating?

Yes

No

NA

Is the FDC identification sign(s) in place? Yes

No

NA

SPRINKLER HEADS

Are there the proper number and type of spare sprinklers? Yes

No

NA

Are visible sprinklers in the proper position: upright, pendent, sidewall?

Yes

No

NA

Are visible sprinklers free of corrosion and physical damage?

Yes

No

NA

Is there proper clearance below the sprinklers? Yes

No

NA

Are visible sprinklers free of foreign materials including paint?

Yes

No

NA

Is there liquid in all visible glass bulb sprinklers? Yes

No

NA

Are there spare sprinklers and a sprinkler wrench? Yes

No

NA

Is the information sign attached and legible? Yes

No

NA

Are all the sprinklers dated 1920 or later? Yes

No

NA

Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25) years?

Yes

No

NA

Standard response sprinklers 75 or more years old replaced or successfully sample tested within last 5 years?

Yes

No

NA

Dry-type sprinklers replaced or successfully sample tested within last 10 years?

Yes

No

NA

Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?

Yes

No

NA

PIPES

Is the visible pipe in good condition with no external corrosion?

Yes

No

NA

Does visible pipe have no mechanical damage or leaks? Yes

No

NA

Does visible pipe have no external loads? Yes

No

NA

Are visible pipe hangers and seismic braces not damaged or loose?

Yes

No

NA

Is the pipe through freezers free if any ice blockage? Yes

No

NA

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation)

Yes

No

NA

VALVE AREA

Are the control valves (including backflow preventer isolation valves) supervised with seals in correct (open or closed) position?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals accessible?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals free from leaks?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals have appropriate wrenches?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision in correct (open or closed) position?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision locked or is supervision in place?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision accessible?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision free from any leaks?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision have the appropriate wrenches?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified?

Yes

No

NA

Are all check valves externally inspected, operating properly, and are in good condition?

Yes

No

NA

Are the gauges on system in good condition and showing normal water supply pressure?

Yes

No

NA

Is the hydraulic name plate (calculated systems) attached securely to the riser and legible?

Yes

No

NA

Are Pressure reducing valves in open position and not leaking?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Yes

No

NA

Are Pressure reducing valves in good condition including no handwheels broken?

Yes

No

NA

Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Do valve supervisory switches indicate movement? Yes

No

NA

The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Have post indicating valves been opened until spring or torsion felt in the rod and then closed back 1/4 turn?

Yes

No

NA

All control valves operated through full range and returned to normal position?

Yes

No

NA

Have pressure reducing valves passed partial flow test? Yes

No

NA

BACKFLOW PREVENTERS

Is relief port on RPZ device not discharging? Yes

No

NA

Have backflow devices passed forward flow test? Yes

No

NA

ALARMS

Is the alarm valve free from physical damage? Yes

No

NA

Is the trim in correct (open or closed) position? Yes

No

NA

Is there no leakage in the retarding chamber or drains? Yes

No

NA

Are alarms and supervisory devices not damaged? Yes

No

NA

Do low temperature alarms look ok? Yes

No

NA

MAINTENANCE

Perform an obstruction investigation if any of the following were found: defective intake screen on pump supplied from open sources, obstructive material discharged during flow tests, foreign material in dry-type valves, foreign material in water during drain test or plugging of inspector's test connection, plugging of pipe or sprinklers found, failure to flush yard piping or surrounding mains following new installation or repairs, record of broken mains in the vicinity, abnormal frequent false-tripping of dry valves, system has just been returned to service after more than 1 year, there is a reason to think the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe, raw water was pumped into the fire department connection, pinhole leaks

Yes

No

NA

If a sprinkler failed a sample test were all the sprinklers represented by that sample replaced?

Yes

No

NA

If sprinklers have been replaced, were they proper replacements?

Yes

No

NA

Were marine systems normally having fresh water drained and refilled twice if raw water got into the system?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Yes

No

NA

If conditions were found that required flushing, was flushing of the system conducted?

Yes

No

NA

Have adjusted, repaired, reconditioned, or replaced components had proper tests/inspections performed?

Yes

No

NA

Was a drain test conducted after opening any closed valve? Yes

No

NA

Operating stem of all OS&Y valves lubricated, completely closed and reopened?

Yes

No

NA

Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

MAIN DRAIN FLOW TESTS

System Initial Static Residual Static Seconds to Return to

Initial Static

Flow Observed?

Did waterflow alarm operate?

Are results comparable to previous test?

Wet Sprinkler 48 45 48 4 Yes Yes Yes

INSPECTORS TEST CONNECTION

Wet Sprinkler (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

At riser A riser 59 Yes Yes Yes Yes Yes

VALVES

Wet Sprinkler (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tam per

Pass

6" Lansdale Butterfly valve

Storage room in truck bay

Butterfly 6 " Supervision Yes Yes Yes Yes Yes Pass Pass

Outside PIV Outside PIV Post Indicator 6 " Monitored And Locked

Yes Yes Yes Yes Yes Pass Pass

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Tag) Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Are the gauges on system in good condition and showing normal water supply pressure?: No

Notes: Gauges out of date

Deficiency #2

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation): No

Notes: Due for 5 year internal investigation

Deficiencies - General Wet System Questions

None

Deficiencies - Wet Sprinkler

None

Deficiencies - FDC

None

Deficiencies - Inspectors Test Connection

None

Deficiencies - Valves

None

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention

(NFPA 13 & 25)

2025-03-05

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 2 1330 Hwy 92 Fayetteville GA 30214-3376

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25) for

Fayette County Fire Station 3

420 Jenkins Rd

Tyrone, GA 30290

Conducted By:

Cody Cook

NICET ll ITM Fire Alarm Systems (NFPA 72)

ACE ll ITM Water-Based Systems (NFPA 25)

Portable Fire Extinguishers (NFPA 10)

Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96)

Emergency Lights / Exit Signs

Backflow Prevention (NFPA 13 & 25)

Acom Fire Solutions left the equipment in operating condition. There is available in our file, a complete record of conditions as found and all repairs made and recommended.

Tag Color

☐ (Green Tag) Sprinkler Operational ☑ (Yellow Tag) Sprinkler Operational with Deficiencies

☐ (Red Tag) Sprinkler Inoperable ☐ 5-Year Sprinkler Inspection

☐ Kitchen Suppression Compliant ☐ (Red Tag)Kitchen Suppression Non Compliant

SPRINKLER SUMMARY

SYSTEM TECHNICIAN TAG COLOR QTY INSPECTED QTY FAILED DATE INSPECTED

General Cody Cook 1 1 2025-03-05

General Wet Cody Cook 1 0 2025-03-05

Wet Cody Cook (Yellow Tag) Sprinkler Operational with Deficiencies

1 0 2025-03-05

Butterfly Cody Cook 1 0 2025-03-05

ITV Cody Cook 1 0 2025-03-05

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 3 420 Jenkins Rd Tyrone GA 30290

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs

Is the building occupied? Yes

No

NA

Has the occupancy classification and hazard of contents remained the same since the last inspection?

Yes

No

NA

Are all fire protection systems in service? Yes

No

NA

Has the system remained in service without modification since the last inspection?

Yes

No

NA

Was the system free of actuations of devices or alarms since the last inspection?

Yes

No

NA

FIRE DEPARTMENT CONNECTION

Is the FDC plainly visible? Yes

No

NA

Is the FDC easily accessible? Yes

No

NA

Is the FDC swivels and couplings not damaged? Yes

No

NA

Are the FDC caps and plugs in place? Yes

No

NA

Are the FDC gaskets in place and in good condition? Yes

No

NA

Is the FDC check valve drip free? Yes

No

NA

Is the clapper and automatic drain valve in place and properly operating?

Yes

No

NA

Is the FDC identification sign(s) in place? Yes

No

NA

SPRINKLER HEADS

Are there the proper number and type of spare sprinklers? Yes

No

NA

Are visible sprinklers in the proper position: upright, pendent, sidewall?

Yes

No

NA

Are visible sprinklers free of corrosion and physical damage?

Yes

No

NA

Is there proper clearance below the sprinklers? Yes

No

NA

Are visible sprinklers free of foreign materials including paint?

Yes

No

NA

Is there liquid in all visible glass bulb sprinklers? Yes

No

NA

Are there spare sprinklers and a sprinkler wrench? Yes

No

NA

Is the information sign attached and legible? Yes

No

NA

Are all the sprinklers dated 1920 or later? Yes

No

NA

Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 3 420 Jenkins Rd Tyrone GA 30290

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25) years?

Yes

No

NA

Standard response sprinklers 75 or more years old replaced or successfully sample tested within last 5 years?

Yes

No

NA

Dry-type sprinklers replaced or successfully sample tested within last 10 years?

Yes

No

NA

Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?

Yes

No

NA

PIPES

Is the visible pipe in good condition with no external corrosion?

Yes

No

NA

Does visible pipe have no mechanical damage or leaks? Yes

No

NA

Does visible pipe have no external loads? Yes

No

NA

Are visible pipe hangers and seismic braces not damaged or loose?

Yes

No

NA

Is the pipe through freezers free if any ice blockage? Yes

No

NA

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation)

Yes

No

NA

VALVE AREA

Are the control valves (including backflow preventer isolation valves) supervised with seals in correct (open or closed) position?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals accessible?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals free from leaks?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals have appropriate wrenches?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision in correct (open or closed) position?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision locked or is supervision in place?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision accessible?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision free from any leaks?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision have the appropriate wrenches?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified?

Yes

No

NA

Are all check valves externally inspected, operating properly, and are in good condition?

Yes

No

NA

Are the gauges on system in good condition and showing normal water supply pressure?

Yes

No

NA

Is the hydraulic name plate (calculated systems) attached securely to the riser and legible?

Yes

No

NA

Are Pressure reducing valves in open position and not leaking?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-05 Property Fayette County Fire Station 3 420 Jenkins Rd Tyrone GA 30290

Print Date: 2025-03-05

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Yes

No

NA

Are Pressure reducing valves in good condition including no handwheels broken?

Yes

No

NA

Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Do valve supervisory switches indicate movement? Yes

No

NA

The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .