Fayette County Administration Complex Sprinkl.pdf
PDF 384 KB Posted
- Attached to
- 26008-A Fire Sprinkler Inspections
- Solicitation number
- PE-65600-NONST-2026-000000185
- Issued by
- Douglas County, Georgia
About this file
This is an Annual Inspection Report for fire sprinkler systems at the Fayette County Administration Complex located at 140 Stonewall Avenue W, Fayetteville, GA 30214, conducted by Acom Fire Solutions on March 4, 2025. The inspection was performed by Cody Cook, a NICET II certified technician with expertise in fire alarm systems (NFPA 72), water-based systems (NFPA 25), portable fire extinguishers (NFPA 10), pre-engineered kitchen suppression systems (NFPA 17A & 96), emergency lights and exit signs, and backflow prevention systems. The facility's sprinkler systems included a General system, General Wet system, Wet system with one yellow tag designation (operational with deficiencies), three Butterfly systems, and one ITV system. All systems passed inspection except for one General system that was tagged red as inoperable. The comprehensive inspection evaluated multiple components including fire department connections, sprinkler heads, pipes, valves, backflow preventers, alarms, and maintenance protocols in accordance with NFPA 25 standards.
Two deficiencies were identified during the inspection: the system's gauges were found to be out of date and therefore not showing accurate water supply pressure, and a five-year internal investigation of the pipe system was due but had not been conducted. All other inspection categories, including the fire department connection, inspector's test connection, and valve operations, passed without noted deficiencies. The wet sprinkler main drain flow test demonstrated proper operation with initial and residual static pressures of 55 and 45 PSI respectively, waterflow alarm operation confirmed, and results comparable to previous tests. Butterfly valves located in the first and second-floor mechanical rooms were exercised and verified as operational with stems properly lubricated and secured where required.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Annual Inspection Report
Completed on: 2025-03-04 for
Fayette County Administration Complex
140 Stonewall Ave W
Fayetteville, GA 30214-1520
Conducted By:
Cody Cook
NICET ll ITM Fire Alarm Systems (NFPA 72)
ACE ll ITM Water-Based Systems (NFPA 25)
Portable Fire Extinguishers (NFPA 10)
Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96)
Emergency Lights / Exit Signs
Backflow Prevention (NFPA 13 & 25)
Acom Fire Solutions
7521 Veterans Parkway
Columbus, Georgia 31909
Inspection Summary
This is to certify that our representative has inspected the equipment noted below and that he has left the equipment in operating condition. There is available in our file, a complete record of conditions as found and all repairs made and recommended.
Tag Color
☐ (Green Tag) Sprinkler Operational ☑ (Yellow Tag) Sprinkler Operational with Deficiencies
☐ (Red Tag) Sprinkler Inoperable ☐ 5-Year Sprinkler Inspection
☐ Kitchen Suppression Compliant ☐ (Red Tag)Kitchen Suppression Non Compliant
SPRINKLER SUMMARY
SYSTEM TECHNICIAN TAG COLOR QTY INSPECTED QTY FAILED DATE INSPECTED
General Cody Cook 1 1 2025-03-04
General Wet Cody Cook 1 0 2025-03-04
Wet Cody Cook (Yellow Tag) Sprinkler Operational with Deficiencies
1 0 2025-03-04
Butterfly Cody Cook 3 0 2025-03-04
ITV Cody Cook 1 0 2025-03-04
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Copyright 2025 Inspect Point
Report of Inspection / Test General Questions
OWNER SECTION
Is the building occupied? Yes
No
NA
Has the occupancy classification and hazard of contents remained the same since the last inspection?
Yes
No
NA
Are all fire protection systems in service? Yes
No
NA
Has the system remained in service without modification since the last inspection?
Yes
No
NA
Was the system free of actuations of devices or alarms since the last inspection?
Yes
No
NA
FIRE DEPARTMENT CONNECTION
Is the FDC plainly visible? Yes
No
NA
Is the FDC easily accessible? Yes
No
NA
Is the FDC swivels and couplings not damaged? Yes
No
NA
Are the FDC caps and plugs in place? Yes
No
NA
Are the FDC gaskets in place and in good condition? Yes
No
NA
Is the FDC check valve drip free? Yes
No
NA
Is the clapper and automatic drain valve in place and properly operating?
Yes
No
NA
Is the FDC identification sign(s) in place? Yes
No
NA
SPRINKLER HEADS
Are there the proper number and type of spare sprinklers? Yes
No
NA
Are visible sprinklers in the proper position: upright, pendent, sidewall?
Yes
No
NA
Are visible sprinklers free of corrosion and physical damage?
Yes
No
NA
Is there proper clearance below the sprinklers? Yes
No
NA
Are visible sprinklers free of foreign materials including paint?
Yes
No
NA
Is there liquid in all visible glass bulb sprinklers? Yes
No
NA
Are there spare sprinklers and a sprinkler wrench? Yes
No
NA
Is the information sign attached and legible? Yes
No
NA
Are all the sprinklers dated 1920 or later? Yes
No
NA
Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?
Yes
No
NA
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?
Yes
No
NA
Standard response sprinklers 75 or more years old replaced or successfully sample tested within last 5 years?
Yes
No
NA
Dry-type sprinklers replaced or successfully sample tested within last 10 years?
Yes
No
NA
Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?
Yes
No
NA
PIPES
Is the visible pipe in good condition with no external corrosion?
Yes
No
NA
Does visible pipe have no mechanical damage or leaks? Yes
No
NA
Does visible pipe have no external loads? Yes
No
NA
Are visible pipe hangers and seismic braces not damaged or loose?
Yes
No
NA
Is the pipe through freezers free if any ice blockage? Yes
No
NA
Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation)
Yes
No
NA
VALVE AREA
Are the control valves (including backflow preventer isolation valves) supervised with seals in correct (open or closed) position?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals accessible?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals free from leaks?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals have appropriate wrenches?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision in correct (open or closed) position?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision locked or is supervision in place?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision accessible?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision free from any leaks?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision have the appropriate wrenches?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified?
Yes
No
NA
Are all check valves externally inspected, operating properly, and are in good condition?
Yes
No
NA
Are the gauges on system in good condition and showing normal water supply pressure?
Yes
No
NA
Is the hydraulic name plate (calculated systems) attached securely to the riser and legible?
Yes
No
NA
Are Pressure reducing valves in open position and not leaking?
Yes
No
NA
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Are Pressure reducing valves with downstream pressure per the design?
Yes
No
NA
Are Pressure reducing valves in good condition including no handwheels broken?
Yes
No
NA
Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?
Yes
No
NA
Do valve supervisory switches indicate movement? Yes
No
NA
The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?
Yes
No
NA
Have post indicating valves been opened until spring or torsion felt in the rod and then closed back 1/4 turn?
Yes
No
NA
All control valves operated through full range and returned to normal position?
Yes
No
NA
Have pressure reducing valves passed partial flow test? Yes
No
NA
BACKFLOW PREVENTERS
Is relief port on RPZ device not discharging? Yes
No
NA
Have backflow devices passed forward flow test? Yes
No
NA
ALARMS
Is the alarm valve free from physical damage? Yes
No
NA
Is the trim in correct (open or closed) position? Yes
No
NA
Is there no leakage in the retarding chamber or drains? Yes
No
NA
Are alarms and supervisory devices not damaged? Yes
No
NA
Do low temperature alarms look ok? Yes
No
NA
MAINTENANCE
Perform an obstruction investigation if any of the following were found: defective intake screen on pump supplied from open sources, obstructive material discharged during flow tests, foreign material in dry-type valves, foreign material in water during drain test or plugging of inspector's test connection, plugging of pipe or sprinklers found, failure to flush yard piping or surrounding mains following new installation or repairs, record of broken mains in the vicinity, abnormal frequent false-tripping of dry valves, system has just been returned to service after more than 1 year, there is a reason to think the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe, raw water was pumped into the fire department connection, pinhole leaks
Yes
No
NA
If a sprinkler failed a sample test were all the sprinklers represented by that sample replaced?
Yes
No
NA
If sprinklers have been replaced, were they proper replacements?
Yes
No
NA
Were marine systems normally having fresh water drained and refilled twice if raw water got into the system?
Yes
No
NA
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Was heat tape inspected per the manufacturer's instructions?
Yes
No
NA
If conditions were found that required flushing, was flushing of the system conducted?
Yes
No
NA
Have adjusted, repaired, reconditioned, or replaced components had proper tests/inspections performed?
Yes
No
NA
Was a drain test conducted after opening any closed valve? Yes
No
NA
Operating stem of all OS&Y valves lubricated, completely closed and reopened?
Yes
No
NA
Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup?
Yes
No
NA
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Report of Inspection / Test for System - Wet Sprinkler
Tag Color
Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies
MAIN DRAIN FLOW TESTS
System Initial Static Residual Static Seconds to Return to
Initial Static
Flow Observed?
Did waterflow alarm operate?
Are results comparable to previous test?
Wet Sprinkler 55 45 55 4 Yes Yes Yes
INSPECTORS TEST CONNECTION
Wet Sprinkler (Wet)
Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
2nd Floor Suite 214 Breakroom
1" Test Valve 75 Yes Yes Yes Yes Yes
VALVES
Wet Sprinkler (Wet)
Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
Flow Pass
Tam per
Pass
6" Butterfly 1st Floor Mechanical Room Butterfly 6 " Not Secured Yes Yes Yes Yes Yes Pass Pass
6" butterfly vave 2nd floor mechanical room Butterfly 6 " Locked Yes Yes Yes Yes Yes Pass Pass
4" butterfly valve 1st Floor Mechanical Room Butterfly 4 " Locked Yes Yes Yes Yes Yes Pass Pass
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Questions with Photos and Notes
Wet Sprinkler - Tag Color (Yellow Tag) Sprinkle r Operatio nal with Deficien cies
Notes:
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Deficiencies - General Questions
Deficiency #1
Are the gauges on system in good condition and showing normal water supply pressure?: No
Notes: Gauges out of date
Deficiency #2
Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation): No
Notes: Due for 5 year internal investigation
Deficiencies - General Wet System Questions
None
Deficiencies - Wet Sprinkler
None
Deficiencies - FDC
None
Deficiencies - Inspectors Test Connection
None
Deficiencies - Valves
None
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention
(NFPA 13 & 25)
2025-03-04
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Administration Complex 140 Stonewall Ave W Fayetteville GA 30214-1520
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems