Fayette County Justice Center Sprinkler Repor.pdf
PDF 816 KB Posted
- Attached to
- 26008-A Fire Sprinkler Inspections
- Solicitation number
- PE-65600-NONST-2026-000000185
- Issued by
- Douglas County, Georgia
About this file
This is an Annual Inspection Report for the fire sprinkler systems at Fayette County Justice Center located at 1 Center Drive, Fayetteville, Georgia 30214, conducted by Acom Fire Solutions on March 4, 2025. The inspection was performed by Cody Cook, a certified technician holding NICET Level II credentials in Fire Alarm Systems (NFPA 72) and ACE Level II credentials in Water-Based Systems (NFPA 25), along with certifications in Portable Fire Extinguishers (NFPA 10), Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96), Emergency Lights/Exit Signs, and Backflow Prevention (NFPA 13 & 25). The report documents the inspection of seven wet sprinkler systems across multiple floors and the main riser, with all systems tagged as operational with deficiencies (Yellow Tag). A total of one general system was inspected and one failed, along with seven butterfly valve systems and thirteen ITV systems, all passing inspection. Main drain flow tests were conducted on all seven systems, with initial static pressures of 160-195 FP and return times ranging from 4-5 seconds, all with positive waterflow alarm operations and comparable results to previous tests.
The inspection revealed two critical deficiencies requiring corrective action: system gauges are out of date and do not meet current standards for showing normal water supply pressure, and a 5-year internal investigation of the piping system is overdue and must be conducted by removing a flushing connection and sprinkler near the end of a branch line. All other inspection components passed, including inspector's test connections at multiple locations with alarm response times ranging from 20-42 seconds, valve exercises and lubrication, and flow and tamper seals on all butterfly valves. The facility remains occupied with standard occupancy classification and hazard contents, and all fire protection systems remain in service without modification since the last inspection with no reported actuations or alarms.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Annual Inspection Report
Completed on: 2025-03-04 for
Fayette County Justice Center
1 Center Dr
Fayetteville, GA 30214
Conducted By:
Cody Cook
NICET ll ITM Fire Alarm Systems (NFPA 72)
ACE ll ITM Water-Based Systems (NFPA 25)
Portable Fire Extinguishers (NFPA 10)
Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96)
Emergency Lights / Exit Signs
Backflow Prevention (NFPA 13 & 25)
Acom Fire Solutions
7521 Veterans Parkway
Columbus, Georgia 31909
Inspection Summary
This is to certify that our representative has inspected the equipment noted below and that he has left the equipment in operating condition. There is available in our file, a complete record of conditions as found and all repairs made and recommended.
Tag Color
☐ (Green Tag) Sprinkler Operational ☑ (Yellow Tag) Sprinkler Operational with Deficiencies
☐ (Red Tag) Sprinkler Inoperable ☐ 5-Year Sprinkler Inspection
☐ Kitchen Suppression Compliant ☐ (Red Tag)Kitchen Suppression Non Compliant
SPRINKLER SUMMARY
SYSTEM TECHNICIAN TAG COLOR QTY INSPECTED QTY FAILED DATE INSPECTED
General Cody Cook 1 1 2025-03-04
General Wet Cody Cook 1 0 2025-03-04
Wet Cody Cook (Yellow Tag) Sprinkler Operational with Deficiencies
7 0 2025-03-04
Butterfly Cody Cook 7 0 2025-03-04
ITV Cody Cook 13 0 2025-03-04
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Copyright 2025 Inspect Point
Report of Inspection / Test General Questions
OWNER SECTION
Is the building occupied? Yes
No
NA
Has the occupancy classification and hazard of contents remained the same since the last inspection?
Yes
No
NA
Are all fire protection systems in service? Yes
No
NA
Has the system remained in service without modification since the last inspection?
Yes
No
NA
Was the system free of actuations of devices or alarms since the last inspection?
Yes
No
NA
FIRE DEPARTMENT CONNECTION
Is the FDC plainly visible? Yes
No
NA
Is the FDC easily accessible? Yes
No
NA
Is the FDC swivels and couplings not damaged? Yes
No
NA
Are the FDC caps and plugs in place? Yes
No
NA
Are the FDC gaskets in place and in good condition? Yes
No
NA
Is the FDC check valve drip free? Yes
No
NA
Is the clapper and automatic drain valve in place and properly operating?
Yes
No
NA
Is the FDC identification sign(s) in place? Yes
No
NA
SPRINKLER HEADS
Are there the proper number and type of spare sprinklers? Yes
No
NA
Are visible sprinklers in the proper position: upright, pendent, sidewall?
Yes
No
NA
Are visible sprinklers free of corrosion and physical damage?
Yes
No
NA
Is there proper clearance below the sprinklers? Yes
No
NA
Are visible sprinklers free of foreign materials including paint?
Yes
No
NA
Is there liquid in all visible glass bulb sprinklers? Yes
No
NA
Are there spare sprinklers and a sprinkler wrench? Yes
No
NA
Is the information sign attached and legible? Yes
No
NA
Are all the sprinklers dated 1920 or later? Yes
No
NA
Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?
Yes
No
NA
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?
Yes
No
NA
Standard response sprinklers 75 or more years old replaced or successfully sample tested within last 5 years?
Yes
No
NA
Dry-type sprinklers replaced or successfully sample tested within last 10 years?
Yes
No
NA
Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?
Yes
No
NA
PIPES
Is the visible pipe in good condition with no external corrosion?
Yes
No
NA
Does visible pipe have no mechanical damage or leaks? Yes
No
NA
Does visible pipe have no external loads? Yes
No
NA
Are visible pipe hangers and seismic braces not damaged or loose?
Yes
No
NA
Is the pipe through freezers free if any ice blockage? Yes
No
NA
Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation)
Yes
No
NA
VALVE AREA
Are the control valves (including backflow preventer isolation valves) supervised with seals in correct (open or closed) position?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals accessible?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals free from leaks?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals have appropriate wrenches?
Yes
No
NA
Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision in correct (open or closed) position?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision locked or is supervision in place?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision accessible?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision free from any leaks?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision have the appropriate wrenches?
Yes
No
NA
Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified?
Yes
No
NA
Are all check valves externally inspected, operating properly, and are in good condition?
Yes
No
NA
Are the gauges on system in good condition and showing normal water supply pressure?
Yes
No
NA
Is the hydraulic name plate (calculated systems) attached securely to the riser and legible?
Yes
No
NA
Are Pressure reducing valves in open position and not leaking?
Yes
No
NA
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Are Pressure reducing valves with downstream pressure per the design?
Yes
No
NA
Are Pressure reducing valves in good condition including no handwheels broken?
Yes
No
NA
Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?
Yes
No
NA
Do valve supervisory switches indicate movement? Yes
No
NA
The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?
Yes
No
NA
Have post indicating valves been opened until spring or torsion felt in the rod and then closed back 1/4 turn?
Yes
No
NA
All control valves operated through full range and returned to normal position?
Yes
No
NA
Have pressure reducing valves passed partial flow test? Yes
No
NA
BACKFLOW PREVENTERS
Is relief port on RPZ device not discharging? Yes
No
NA
Have backflow devices passed forward flow test? Yes
No
NA
ALARMS
Is the alarm valve free from physical damage? Yes
No
NA
Is the trim in correct (open or closed) position? Yes
No
NA
Is there no leakage in the retarding chamber or drains? Yes
No
NA
Are alarms and supervisory devices not damaged? Yes
No
NA
Do low temperature alarms look ok? Yes
No
NA
MAINTENANCE
Perform an obstruction investigation if any of the following were found: defective intake screen on pump supplied from open sources, obstructive material discharged during flow tests, foreign material in dry-type valves, foreign material in water during drain test or plugging of inspector's test connection, plugging of pipe or sprinklers found, failure to flush yard piping or surrounding mains following new installation or repairs, record of broken mains in the vicinity, abnormal frequent false-tripping of dry valves, system has just been returned to service after more than 1 year, there is a reason to think the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe, raw water was pumped into the fire department connection, pinhole leaks
Yes
No
NA
If a sprinkler failed a sample test were all the sprinklers represented by that sample replaced?
Yes
No
NA
If sprinklers have been replaced, were they proper replacements?
Yes
No
NA
Were marine systems normally having fresh water drained and refilled twice if raw water got into the system?
Yes
No
NA
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Was heat tape inspected per the manufacturer's instructions?
Yes
No
NA
If conditions were found that required flushing, was flushing of the system conducted?
Yes
No
NA
Have adjusted, repaired, reconditioned, or replaced components had proper tests/inspections performed?
Yes
No
NA
Was a drain test conducted after opening any closed valve? Yes
No
NA
Operating stem of all OS&Y valves lubricated, completely closed and reopened?
Yes
No
NA
Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup?
Yes
No
NA
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Report of Inspection / Test for System - Wet Sprinkler 1st Floor Stairwell 1
Tag Color
Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies
Report of Inspection / Test for System - Wet Sprinkler 2nd Floor Stairwell 1
Tag Color
Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies
Report of Inspection / Test for System - Wet Sprinkler 3rd Floor Stairwell 1
Tag Color
Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies
Report of Inspection / Test for System - Wet Sprinkler 3rd Floor Stairwell 6
Tag Color
Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies
Report of Inspection / Test for System - Wet Sprinkler 2nd Floor Stairwell 6
Tag Color
Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies
Report of Inspection / Test for System - Wet Sprinkler 1st floor Stairwell 6
Tag Color
Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies
Report of Inspection / Test for System - Wet Sprinkler Main Riser
Tag Color
Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
MAIN DRAIN FLOW TESTS
System Initial Static Residual Static Seconds to Return to
Initial Static
Flow Observed?
Did waterflow alarm operate?
Are results comparable to previous test?
Wet Sprinkler 1st Floor Stairwell 1
195 FP 195 5 Yes Yes Yes
Wet Sprinkler 2nd Floor Stairwell 1
195 FP 195 4 Yes Yes Yes
Wet Sprinkler 3rd Floor Stairwell 1
195 FP 195 5 Yes Yes Yes
Wet Sprinkler 3rd Floor Stairwell 6
195 FP 195 5 Yes Yes Yes
Wet Sprinkler 2nd Floor Stairwell 6
195 FP 195 4 Yes Yes Yes
Wet Sprinkler 1st floor Stairwell 6
195 FP 195 4 Yes Yes Yes
Wet Sprinkler Main Riser
160 FP 165 4 Yes Yes Yes
INSPECTORS TEST CONNECTION
Wet Sprinkler 1st Floor Stairwell 1 (Wet)
Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
1st floor stairwell 1 1" Auxiliary Drain 21 Yes Yes Yes Yes Yes
1st floor stairwell 1 1" Auxiliary Drain Yes Yes Yes Yes Yes
1st Floor Janitors closet
1" Auxiliary Drain Yes Yes Yes Yes Yes
1st floor janitors closet 1" Auxiliary Drain Yes Yes Yes Yes Yes
Wet Sprinkler 2nd Floor Stairwell 1 (Wet)
Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
2nd floor stairwell 1 1" test valve 20 Yes Yes Yes Yes Yes
2nd floor janitors closet by room 205
Auxiliary Drain Yes Yes Yes Yes Yes
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Wet Sprinkler 3rd Floor Stairwell 1 (Wet)
Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
3rd Floor Stairwell 1 1" test valve 42 Yes Yes Yes Yes Yes
3rd floor mechanical room
Auxiliary drain Yes Yes Yes Yes Yes
3rd floor mechanical room
Auxiliary Drain Yes Yes Yes Yes Yes
Wet Sprinkler 3rd Floor Stairwell 6 (Wet)
Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
3rd Floor Stairwell 6 1" test drain 31 Yes Yes Yes Yes Yes
Wet Sprinkler 2nd Floor Stairwell 6 (Wet)
Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
2nd floor stairwell 6 1" test valve 20 Yes Yes Yes Yes Yes
Wet Sprinkler 1st floor Stairwell 6 (Wet)
Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
1st floor stairwell 6 1" test valve 31 Yes Yes Yes Yes Yes
Wet Sprinkler Main Riser (Wet)
Location Description Time to
Alarm (seconds)
Reported? Smooth Orifice
Easily Accessible
Signs? Pass?
Janitors closet ITV 41 Yes Yes Yes Yes Yes
VALVES
Wet Sprinkler 1st Floor Stairwell 1 (Wet)
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
Flow Pass
Tamp er
Pass
4" Buttery Valve 1st Floor Stairwell1 Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass
Wet Sprinkler 2nd Floor Stairwell 1 (Wet)
Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
Flow Pass
Tamp er
Pass
4" butterfly valve 2nd floor stairwell Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass
Wet Sprinkler 3rd Floor Stairwell 1 (Wet)
Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
Flow Pass
Tamp er
Pass
2.5" Butterly Valve 3rd Floor Stairwell 1 Butterfly 2-1/2 " Supervision Yes Yes Yes Yes Yes Pass Pass
Wet Sprinkler 3rd Floor Stairwell 6 (Wet)
Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
Flow Pass
Tamp er
Pass
2.5" butterfly valve 3rd floor stairwell 6 Butterfly 2-1/2 " Supervision Yes Yes Yes Yes Yes Pass Pass
Wet Sprinkler 2nd Floor Stairwell 6 (Wet)
Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
Flow Pass
Tamp er
Pass
4" Butterfly valve 2nd floor stairwell 6 Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass
Wet Sprinkler 1st floor Stairwell 6 (Wet)
Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
Flow Pass
Tamp er
Pass
4" Butterfly valve 1st Floor Stairwell 6 Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass
Wet Sprinkler Main Riser (Wet)
Description Location Valve Type Size Secured Open
Easily Accessible Signs Exercised
Stems Lubricated
Flow Pass
Tamp er
Pass
4" Butterfly Valve Outside Riser Room Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Questions with Photos and Notes
Wet Sprinkler Main Riser - Tag Color (Yellow Tag) Sprinkle r Operatio nal with Deficien cies
Notes:
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Wet Sprinkler 1st floor Stairwell 6 - Tag Color (Yellow Tag) Sprinkle r Operatio nal with Deficien cies
Notes:
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Wet Sprinkler 2nd Floor Stairwell 6 - Tag Color (Yellow
Sprinkle r Operatio nal with Deficien cies
Notes:
Wet Sprinkler 3rd Floor Stairwell 6 - Tag Color (Yellow Tag) Sprinkle r Operatio nal with Deficien cies
Notes:
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Wet Sprinkler 3rd Floor Stairwell 1 - Tag Color (Yellow
Sprinkle r Operatio nal with Deficien cies
Notes:
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Wet Sprinkler 2nd Floor Stairwell 1 - Tag Color (Yellow
Sprinkle r Operatio nal with Deficien cies
Notes:
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Wet Sprinkler 1st Floor Stairwell 1 - Tag Color (Yellow
Sprinkle r Operatio nal with Deficien cies
Notes:
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Deficiencies - General Questions
Deficiency #1
Are the gauges on system in good condition and showing normal water supply pressure?: No
Notes: Gauges out of date
Deficiency #2
Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation): No
Notes: Due for 5 year internal investigation
Deficiencies - General Wet System Questions
None
Deficiencies - Wet Sprinkler 1st Floor Stairwell 1
None
Deficiencies - Wet Sprinkler 2nd Floor Stairwell 1
None
Deficiencies - Wet Sprinkler 3rd Floor Stairwell 1
None
Deficiencies - Wet Sprinkler 3rd Floor Stairwell 6
None
Deficiencies - Wet Sprinkler 2nd Floor Stairwell 6
None
Deficiencies - Wet Sprinkler 1st floor Stairwell 6
None
Deficiencies - Wet Sprinkler Main Riser
None
Deficiencies - Inspectors Test Connection
None
Deficiencies - Valves
None
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
Inspector Signature
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Inspector Name Signature Date Completed
Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention
(NFPA 13 & 25)
2025-03-04
Report of Inspection / Test Annual NFPA 25
2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214
Print Date: 2025-03-04
Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems
(NFPA 17A & 96)
Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)
File details come from the government source that posted it. Updated .