Fayette County Justice Center Sprinkler Repor.pdf

PDF 816 KB Posted

Attached to
26008-A Fire Sprinkler Inspections
Solicitation number
PE-65600-NONST-2026-000000185
Issued by
Douglas County, Georgia

About this file

This is an Annual Inspection Report for the fire sprinkler systems at Fayette County Justice Center located at 1 Center Drive, Fayetteville, Georgia 30214, conducted by Acom Fire Solutions on March 4, 2025. The inspection was performed by Cody Cook, a certified technician holding NICET Level II credentials in Fire Alarm Systems (NFPA 72) and ACE Level II credentials in Water-Based Systems (NFPA 25), along with certifications in Portable Fire Extinguishers (NFPA 10), Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96), Emergency Lights/Exit Signs, and Backflow Prevention (NFPA 13 & 25). The report documents the inspection of seven wet sprinkler systems across multiple floors and the main riser, with all systems tagged as operational with deficiencies (Yellow Tag). A total of one general system was inspected and one failed, along with seven butterfly valve systems and thirteen ITV systems, all passing inspection. Main drain flow tests were conducted on all seven systems, with initial static pressures of 160-195 FP and return times ranging from 4-5 seconds, all with positive waterflow alarm operations and comparable results to previous tests.

The inspection revealed two critical deficiencies requiring corrective action: system gauges are out of date and do not meet current standards for showing normal water supply pressure, and a 5-year internal investigation of the piping system is overdue and must be conducted by removing a flushing connection and sprinkler near the end of a branch line. All other inspection components passed, including inspector's test connections at multiple locations with alarm response times ranging from 20-42 seconds, valve exercises and lubrication, and flow and tamper seals on all butterfly valves. The facility remains occupied with standard occupancy classification and hazard contents, and all fire protection systems remain in service without modification since the last inspection with no reported actuations or alarms.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Annual Inspection Report

Completed on: 2025-03-04 for

Fayette County Justice Center

1 Center Dr

Fayetteville, GA 30214

Conducted By:

Cody Cook

NICET ll ITM Fire Alarm Systems (NFPA 72)

ACE ll ITM Water-Based Systems (NFPA 25)

Portable Fire Extinguishers (NFPA 10)

Pre-Engineered Kitchen Suppression Systems (NFPA 17A & 96)

Emergency Lights / Exit Signs

Backflow Prevention (NFPA 13 & 25)

Acom Fire Solutions

7521 Veterans Parkway

Columbus, Georgia 31909

Inspection Summary

This is to certify that our representative has inspected the equipment noted below and that he has left the equipment in operating condition. There is available in our file, a complete record of conditions as found and all repairs made and recommended.

Tag Color

☐ (Green Tag) Sprinkler Operational ☑ (Yellow Tag) Sprinkler Operational with Deficiencies

☐ (Red Tag) Sprinkler Inoperable ☐ 5-Year Sprinkler Inspection

☐ Kitchen Suppression Compliant ☐ (Red Tag)Kitchen Suppression Non Compliant

SPRINKLER SUMMARY

SYSTEM TECHNICIAN TAG COLOR QTY INSPECTED QTY FAILED DATE INSPECTED

General Cody Cook 1 1 2025-03-04

General Wet Cody Cook 1 0 2025-03-04

Wet Cody Cook (Yellow Tag) Sprinkler Operational with Deficiencies

7 0 2025-03-04

Butterfly Cody Cook 7 0 2025-03-04

ITV Cody Cook 13 0 2025-03-04

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Copyright 2025 Inspect Point

Report of Inspection / Test General Questions

OWNER SECTION

Is the building occupied? Yes

No

NA

Has the occupancy classification and hazard of contents remained the same since the last inspection?

Yes

No

NA

Are all fire protection systems in service? Yes

No

NA

Has the system remained in service without modification since the last inspection?

Yes

No

NA

Was the system free of actuations of devices or alarms since the last inspection?

Yes

No

NA

FIRE DEPARTMENT CONNECTION

Is the FDC plainly visible? Yes

No

NA

Is the FDC easily accessible? Yes

No

NA

Is the FDC swivels and couplings not damaged? Yes

No

NA

Are the FDC caps and plugs in place? Yes

No

NA

Are the FDC gaskets in place and in good condition? Yes

No

NA

Is the FDC check valve drip free? Yes

No

NA

Is the clapper and automatic drain valve in place and properly operating?

Yes

No

NA

Is the FDC identification sign(s) in place? Yes

No

NA

SPRINKLER HEADS

Are there the proper number and type of spare sprinklers? Yes

No

NA

Are visible sprinklers in the proper position: upright, pendent, sidewall?

Yes

No

NA

Are visible sprinklers free of corrosion and physical damage?

Yes

No

NA

Is there proper clearance below the sprinklers? Yes

No

NA

Are visible sprinklers free of foreign materials including paint?

Yes

No

NA

Is there liquid in all visible glass bulb sprinklers? Yes

No

NA

Are there spare sprinklers and a sprinkler wrench? Yes

No

NA

Is the information sign attached and legible? Yes

No

NA

Are all the sprinklers dated 1920 or later? Yes

No

NA

Fast response sprinklers 20 or more years old replaced or successfully sample tested within last 10 years?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Standard response sprinklers 50 or more years old replaced or successfully sample tested within last 10 years?

Yes

No

NA

Standard response sprinklers 75 or more years old replaced or successfully sample tested within last 5 years?

Yes

No

NA

Dry-type sprinklers replaced or successfully sample tested within last 10 years?

Yes

No

NA

Have sprinklers subject to harsh environments been replaced or successfully sample tested in the last 5 years?

Yes

No

NA

PIPES

Is the visible pipe in good condition with no external corrosion?

Yes

No

NA

Does visible pipe have no mechanical damage or leaks? Yes

No

NA

Does visible pipe have no external loads? Yes

No

NA

Are visible pipe hangers and seismic braces not damaged or loose?

Yes

No

NA

Is the pipe through freezers free if any ice blockage? Yes

No

NA

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation)

Yes

No

NA

VALVE AREA

Are the control valves (including backflow preventer isolation valves) supervised with seals in correct (open or closed) position?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals locked or is supervision in place?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals accessible?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals free from leaks?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals have appropriate wrenches?

Yes

No

NA

Are the control valves (including backflow preventer isolation valves) supervised with seals properly identified?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision in correct (open or closed) position?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision locked or is supervision in place?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision accessible?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision free from any leaks?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision have the appropriate wrenches?

Yes

No

NA

Are the control valves (including valves on backflow preventers) with locks or electrical supervision properly identified?

Yes

No

NA

Are all check valves externally inspected, operating properly, and are in good condition?

Yes

No

NA

Are the gauges on system in good condition and showing normal water supply pressure?

Yes

No

NA

Is the hydraulic name plate (calculated systems) attached securely to the riser and legible?

Yes

No

NA

Are Pressure reducing valves in open position and not leaking?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Are Pressure reducing valves with downstream pressure per the design?

Yes

No

NA

Are Pressure reducing valves in good condition including no handwheels broken?

Yes

No

NA

Have the mechanical waterflow alarm devices passed tests by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Do valve supervisory switches indicate movement? Yes

No

NA

The electrical waterflow alarm devices passed test by opening inspector's test connection/bypass connection with alarms actuating and flow observed?

Yes

No

NA

Have post indicating valves been opened until spring or torsion felt in the rod and then closed back 1/4 turn?

Yes

No

NA

All control valves operated through full range and returned to normal position?

Yes

No

NA

Have pressure reducing valves passed partial flow test? Yes

No

NA

BACKFLOW PREVENTERS

Is relief port on RPZ device not discharging? Yes

No

NA

Have backflow devices passed forward flow test? Yes

No

NA

ALARMS

Is the alarm valve free from physical damage? Yes

No

NA

Is the trim in correct (open or closed) position? Yes

No

NA

Is there no leakage in the retarding chamber or drains? Yes

No

NA

Are alarms and supervisory devices not damaged? Yes

No

NA

Do low temperature alarms look ok? Yes

No

NA

MAINTENANCE

Perform an obstruction investigation if any of the following were found: defective intake screen on pump supplied from open sources, obstructive material discharged during flow tests, foreign material in dry-type valves, foreign material in water during drain test or plugging of inspector's test connection, plugging of pipe or sprinklers found, failure to flush yard piping or surrounding mains following new installation or repairs, record of broken mains in the vicinity, abnormal frequent false-tripping of dry valves, system has just been returned to service after more than 1 year, there is a reason to think the system contains sodium silicate or its derivatives or highly corrosive fluxes in copper pipe, raw water was pumped into the fire department connection, pinhole leaks

Yes

No

NA

If a sprinkler failed a sample test were all the sprinklers represented by that sample replaced?

Yes

No

NA

If sprinklers have been replaced, were they proper replacements?

Yes

No

NA

Were marine systems normally having fresh water drained and refilled twice if raw water got into the system?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Was heat tape inspected per the manufacturer's instructions?

Yes

No

NA

If conditions were found that required flushing, was flushing of the system conducted?

Yes

No

NA

Have adjusted, repaired, reconditioned, or replaced components had proper tests/inspections performed?

Yes

No

NA

Was a drain test conducted after opening any closed valve? Yes

No

NA

Operating stem of all OS&Y valves lubricated, completely closed and reopened?

Yes

No

NA

Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulb-type which show no signs of grease buildup?

Yes

No

NA

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Report of Inspection / Test for System - Wet Sprinkler 1st Floor Stairwell 1

Tag Color

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

Report of Inspection / Test for System - Wet Sprinkler 2nd Floor Stairwell 1

Tag Color

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

Report of Inspection / Test for System - Wet Sprinkler 3rd Floor Stairwell 1

Tag Color

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

Report of Inspection / Test for System - Wet Sprinkler 3rd Floor Stairwell 6

Tag Color

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

Report of Inspection / Test for System - Wet Sprinkler 2nd Floor Stairwell 6

Tag Color

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

Report of Inspection / Test for System - Wet Sprinkler 1st floor Stairwell 6

Tag Color

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

Report of Inspection / Test for System - Wet Sprinkler Main Riser

Tag Color

Tag Color (Yellow Tag) Sprinkler Operational with Deficiencies

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

MAIN DRAIN FLOW TESTS

System Initial Static Residual Static Seconds to Return to

Initial Static

Flow Observed?

Did waterflow alarm operate?

Are results comparable to previous test?

Wet Sprinkler 1st Floor Stairwell 1

195 FP 195 5 Yes Yes Yes

Wet Sprinkler 2nd Floor Stairwell 1

195 FP 195 4 Yes Yes Yes

Wet Sprinkler 3rd Floor Stairwell 1

195 FP 195 5 Yes Yes Yes

Wet Sprinkler 3rd Floor Stairwell 6

195 FP 195 5 Yes Yes Yes

Wet Sprinkler 2nd Floor Stairwell 6

195 FP 195 4 Yes Yes Yes

Wet Sprinkler 1st floor Stairwell 6

195 FP 195 4 Yes Yes Yes

Wet Sprinkler Main Riser

160 FP 165 4 Yes Yes Yes

INSPECTORS TEST CONNECTION

Wet Sprinkler 1st Floor Stairwell 1 (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

1st floor stairwell 1 1" Auxiliary Drain 21 Yes Yes Yes Yes Yes

1st floor stairwell 1 1" Auxiliary Drain Yes Yes Yes Yes Yes

1st Floor Janitors closet

1" Auxiliary Drain Yes Yes Yes Yes Yes

1st floor janitors closet 1" Auxiliary Drain Yes Yes Yes Yes Yes

Wet Sprinkler 2nd Floor Stairwell 1 (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

2nd floor stairwell 1 1" test valve 20 Yes Yes Yes Yes Yes

2nd floor janitors closet by room 205

Auxiliary Drain Yes Yes Yes Yes Yes

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Wet Sprinkler 3rd Floor Stairwell 1 (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

3rd Floor Stairwell 1 1" test valve 42 Yes Yes Yes Yes Yes

3rd floor mechanical room

Auxiliary drain Yes Yes Yes Yes Yes

3rd floor mechanical room

Auxiliary Drain Yes Yes Yes Yes Yes

Wet Sprinkler 3rd Floor Stairwell 6 (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

3rd Floor Stairwell 6 1" test drain 31 Yes Yes Yes Yes Yes

Wet Sprinkler 2nd Floor Stairwell 6 (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

2nd floor stairwell 6 1" test valve 20 Yes Yes Yes Yes Yes

Wet Sprinkler 1st floor Stairwell 6 (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

1st floor stairwell 6 1" test valve 31 Yes Yes Yes Yes Yes

Wet Sprinkler Main Riser (Wet)

Location Description Time to

Alarm (seconds)

Reported? Smooth Orifice

Easily Accessible

Signs? Pass?

Janitors closet ITV 41 Yes Yes Yes Yes Yes

VALVES

Wet Sprinkler 1st Floor Stairwell 1 (Wet)

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tamp er

Pass

4" Buttery Valve 1st Floor Stairwell1 Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass

Wet Sprinkler 2nd Floor Stairwell 1 (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tamp er

Pass

4" butterfly valve 2nd floor stairwell Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass

Wet Sprinkler 3rd Floor Stairwell 1 (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tamp er

Pass

2.5" Butterly Valve 3rd Floor Stairwell 1 Butterfly 2-1/2 " Supervision Yes Yes Yes Yes Yes Pass Pass

Wet Sprinkler 3rd Floor Stairwell 6 (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tamp er

Pass

2.5" butterfly valve 3rd floor stairwell 6 Butterfly 2-1/2 " Supervision Yes Yes Yes Yes Yes Pass Pass

Wet Sprinkler 2nd Floor Stairwell 6 (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tamp er

Pass

4" Butterfly valve 2nd floor stairwell 6 Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass

Wet Sprinkler 1st floor Stairwell 6 (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tamp er

Pass

4" Butterfly valve 1st Floor Stairwell 6 Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass

Wet Sprinkler Main Riser (Wet)

Description Location Valve Type Size Secured Open

Easily Accessible Signs Exercised

Stems Lubricated

Flow Pass

Tamp er

Pass

4" Butterfly Valve Outside Riser Room Butterfly 4 " Supervision Yes Yes Yes Yes Yes Pass Pass

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Questions with Photos and Notes

Wet Sprinkler Main Riser - Tag Color (Yellow Tag) Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Wet Sprinkler 1st floor Stairwell 6 - Tag Color (Yellow Tag) Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Wet Sprinkler 2nd Floor Stairwell 6 - Tag Color (Yellow

Sprinkle r Operatio nal with Deficien cies

Notes:

Wet Sprinkler 3rd Floor Stairwell 6 - Tag Color (Yellow Tag) Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Wet Sprinkler 3rd Floor Stairwell 1 - Tag Color (Yellow

Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Wet Sprinkler 2nd Floor Stairwell 1 - Tag Color (Yellow

Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Wet Sprinkler 1st Floor Stairwell 1 - Tag Color (Yellow

Sprinkle r Operatio nal with Deficien cies

Notes:

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Deficiencies - General Questions

Deficiency #1

Are the gauges on system in good condition and showing normal water supply pressure?: No

Notes: Gauges out of date

Deficiency #2

Has an internal investigation of the pipe (remove a flushing connection and a sprinkler near the end of a branch line) been performed in the last 5 years? (If no conduct investigation): No

Notes: Due for 5 year internal investigation

Deficiencies - General Wet System Questions

None

Deficiencies - Wet Sprinkler 1st Floor Stairwell 1

None

Deficiencies - Wet Sprinkler 2nd Floor Stairwell 1

None

Deficiencies - Wet Sprinkler 3rd Floor Stairwell 1

None

Deficiencies - Wet Sprinkler 3rd Floor Stairwell 6

None

Deficiencies - Wet Sprinkler 2nd Floor Stairwell 6

None

Deficiencies - Wet Sprinkler 1st floor Stairwell 6

None

Deficiencies - Wet Sprinkler Main Riser

None

Deficiencies - Inspectors Test Connection

None

Deficiencies - Valves

None

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

Inspector Signature

I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.

Inspector Name Signature Date Completed

Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention

(NFPA 13 & 25)

2025-03-04

Report of Inspection / Test Annual NFPA 25

2025-03-04 Property Fayette County Justice Center 1 Center Dr Fayetteville GA 30214

Print Date: 2025-03-04

Conducted by: Cody Cook NICET ll ITM Fire Alarm Systems (NFPA 72) ACE ll ITM Water-Based Systems (NFPA 25) Portable Fire Extinguishers (NFPA 10) Pre-Engineered Kitchen Suppression Systems

(NFPA 17A & 96)

Emergency Lights / Exit Signs Backflow Prevention (NFPA 13 & 25)

File details come from the government source that posted it. Updated .