ATTACHMENT 5 - BLADE INSPECTION REPORT
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Attachment_9_-_Past_Performance.doc | DOC document | |
| Attachment_2_-__Evaluation_Criteria_and_Instruction_to_offerors_TURBINE.doc | DOC document | |
| Attachment_4-_Offeror_Information.xlsx | XLSX spreadsheet | |
| Attahcment_8_-_GFP_Available_0115.xlsx | XLSX spreadsheet | |
| Attachment_7_-__Base_Support_Letter.pdf | ||
| Attachment_1_-__PWS_31_May_2013.doc | DOC document | |
| FA8903-13-R-0115_SYNOPSIS_ _SOLICITATION.docx | DOCX document | |
| Attachment_3_-__CDRLs_31_May_2013.doc | DOC document | |
| Attachment_6_-_Transformer_inspection_report.pdf | ||
| Attachment_2_-__Evaluation_Criteria_and_Instruction_to_offerors_TURBINE.doc | DOC document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Report 11/26/12
Attach 5
FA8903-13-R-0115
On the inspection of the Rotor Blades on a wind turbine Type FUHERLANDER 1500 KW Wind turbine-no. 1 Rotor Blade type. LM 40 m Pitch
Customer:
Robert Desharnais
Lumus Construction
1 Jewel Dr. Suite 321
Wilmington, Massachusetts Customer P.O. number:
46RD30-170
Wind farm:
Massachusetts Military Reservation Report by:
BS Rotor Technic USA LLC
2200 E. Winston Road
Anaheim, CA 92806
Tel.: (888) 44-ROTOR
Fax: (714) 758-7000 Table of content
General information 1.1 Order
1.2 Directives for the inspection
1.3.
Working extent 1.4 Remarks on implementation of the inspection 1.5.
Main data of the inspected wind turbine Inspection of the rotor blades
2.1 Location diagram of the damage Result of inspection 3.1 Result 3.1.1 Blade interior 3.1.2 Blade exterior 3.2 Conclusions and recommendations
Pictures of the inspection
The photographs are available on the pages following each blade diagram.
1. General Information
1.1. Order
BS Rotor Technic USA, LLC inspected on behalf of Lumus Construction, the rotor blades for the on page 4 mentioned wind turbine of the type: FUHRLANDER 1500 KW. The work included the inspection, generation of this report and the condition of the rotor blades during the inspection.
1.2. Directives for the inspection
The inspection was carried out according to:
· The standards for regular inspection of wind turbines from the Germanischer Lloyd,
· The standards for regular inspection of wind turbines from the specialist commission of the BWE,
· The standards of the TÜV Berlin Brandenburg, from the course “Service technician for Rotor Blade repair and service“
· As well as National / international standard.
1.3. Working extent
The rotor blade where inspected by our technicians using rope access. Identified damage has been documented with photos. They are displayed in the location diagram of the damage under section 2.1.
1.4. Remarks on implementation of the inspection
The implementation of the inspected Rotor Blades starts from the hub of the blade approach toward the blade tip. The distance data from blade flange to the body damage is measured in meters specified. R=0 is the start of the blade (flange).
Names and abbreviations in the following segment:
l = length
Ø = diameter ps = pressure side ss = suction side rc = rear chamber mb = main beam fc = front chamber le = leading edge te = trailing edge
1.5. Main data of the inspected wind turbine
Wind farm: Massachusetts Military Reservation
Customer:
Lumus Construction WT-No.: 70224
Inspection period: 11/15/12
Blade type:
LM 40 m pitch
Aerodynamic installations:
Manufacturer:
LM
none exist Material:
Epoxy reinforced fiberglass
Type: Fuhrlander Hub height 80 m
Rated power:
1.5 mw
Wind speed [m/s]:
2 - 12
Surroundings temperature °F]:
40 to 48
2.1 Inspection of the exterior of the Rotor Blade type: LM 40m ss 0 ps
Blade-no.: 1
| Radius in Meters |
| Damage |
| Picture |
| 40 |
| Small lighting strike that has bubbled the leading edge tape. |
| 1-1 |
Photo 1-1
2.1 Inspection of the interior of the Rotor Blade type LM 40m
Blade-no.: 1
| Radius in Meters |
| Damage |
| Picture |
Not inspected
2.1 Inspection of the exterior of the Rotor Blade type: LM 40m
Blade-no.: 2
| Radius in Meters |
| Damage |
| Picture |
| 39 |
| Small lighting strike that has bubbled the leading edge tape. |
| 2-1 |
Photo 2-1
2.1 Inspection of the interior of the Rotor Blade type: LM 40m
Blade-no.: 2
| Radius in Meters |
| Damage |
| Picture |
Not inspected
2.1 Inspection of the exterior of the Rotor Blade type: LM 40m
Blade-no: 3
| Radius in Meters |
| Damage |
| Picture |
| 40 |
| Small lighting strike that has bubbled the leading edge tape. |
| 3-1 |
Photo 3-1
2.1 Inspection of the interior of the Rotor Blade type: LM 40m
Blade-no.: 3
| Radius in Meters |
| Damage |
| Picture |
Not inspected
Result of the inspection
3.1 Result
Here the most important types of damage are summarized in groups with their likely causes at the time of the inspection
3.1.1 Blade interior
Blade 1
Not inspected Blade 2
Blade 3
3.1.2 Blade exterior
Cracks The surface of the rotor blades are in good condition and no cracks where found at the time of inspection.
Surface and Lunker No surface lunker or holes where found during the inspection.
Aerodynamic installations None exist on this LM Rotor Blade design.
Other Each of the three blades had a black area typical to small lighting strikes. The areas seen in the photos are at the leading edge protective tape. The result of the small lighting strikes had caused the leading edge tape to bubble. The laminate at these locations was not compromised, and the top coat seemed to be in good condition aside from the discoloration. Our Technicians cut back the leading edge tape to mitigate the noise that is made during normal operation caused from loose leading edge tape.
3.2 Conclusions and recommendations
With regard to operational safety we suggest that the Rotor Blades have the existing leading edge tape removed while the rotor is on the ground during the gear box repairs, or replacement.
For manufacturing and design defects, we assume no liability.
After the repairs these Rotor Blades should be inspected periodically so that any future problems can be addressed as needed.
For the future we recommend that the blades will be:
· Checked visual by rope access and, if necessary, repair them based on the actual condition, yearly.
We recommend that the next check be scheduled for October 2013.
11/26/12
BS Rotor Technic USA, LLC
Steven Elrod General Manager
BS Rotor Technic USA, LLC WF: Massachusetts Military Reservation
WT: 1
Type: FUHRLANDER 1500 KW 11/26/12