Text version

AutoCAD SHX Text

SWITCHGEAR PAD PLAN

AutoCAD SHX Text

SCALE: NONE

AutoCAD SHX Text PROVIDE ADDITIONAL GROUND RODS AS REQUIRED FOR 5 OHM MAXIMUM MEASURED GROUND RESISTANCE

AutoCAD SHX Text 1'-0"

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text 2'-6"

AutoCAD SHX Text

(TYP.)

AutoCAD SHX Text 12"

AutoCAD SHX Text SWITCHGEAR PAD 3500 PSI CONCRETE AT 28 DAYS 1'-0" BEYOND SWITCHGEAR ON ALL SIDES BY 6" THICK (PROVIDE #4 BARS AT 12" O.C. EACH DIRECTION AND 2-#4 BARS ALL AROUND PERIMETER)

AutoCAD SHX Text

#2 BARE STRANDED COPPER RING GROUND LOOP AT 18" BELOW GRADE

AutoCAD SHX Text GROUND ROD 5/8" DIA. x 8'-0" LONG (TYPICAL FOR 4)

AutoCAD SHX Text #2 CRUSHED STONE AT 12" DEEP INSTALL IN 6" LAYERS AND COMPACT WITH MOTORIZED TAMPER

AutoCAD SHX Text

SWITCHGEAR GROUND BUS (CONNECT GROUNDS AT BOTH ENDS)

AutoCAD SHX Text

(TYPICAL FOR PRIMARY SWITCH PS-1 AND PS-2)

AutoCAD SHX Text

PROVIDE CONDUIT OPENINGS PER MANUFACTURER'S LITERATURE

AutoCAD SHX Text

EXOTHERMIC WELD (TYPICAL)

AutoCAD SHX Text

SWITCHGEAR OUTLINE

Sheets and Views