Questions and Answers Set 5 McLaughlin B017.docx.pdf

PDF 94 KB Posted

Attached to
FA8604 Materials Handling System/McLaughlin Air National Guard Base, West Virginia MMHS
Solicitation number
FA860424RB017
Issued by

About this file

This document is a set of Questions and Answers related to a federal contract opportunity for a Materials Handling System at McLaughlin Air National Guard Base in West Virginia.

The contract opportunity is solicitation FA8604-24-R-B017, a Request for Proposal (RFP) issued by the Department of the Air Force Materiel Command Lifecycle Management Center at Wright Patterson Air Force Base. The RFP is a 100% small business set-aside with a NAICS code of 333922. It requires the performance, design, fabrication, installation, and testing of a Materials Handling System, with a 300-day completion period from date of award. Evaluation will be based on Lowest Price Technically Acceptable. Key details include information on handrail design, load capacities for modular cabinets, pallet racks, and rack-supported mezzanines. The RFP has 22 line items and all specifications/drawings are posted on SAM.gov. Proposals are due by 4:00 PM EDT on 16 August 2024.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA8604-22-R-B017

McLaughlin ANGB

Question Set #5

8 August 2024

Question/Answer Response:

Q: It appears engineer has handrail terminating in the middle of the 1st section of P3 rack on upper level. Is this what is intended? Should design be altered to use a shorter section in that 1st section?

A: Yes, that is what is intended.

Q: Please advise if engineer is wanting handrail on top / mezzanine side of section P4. It appears it will be fairly close to a wall. If so – will rack beams be acceptable?

A: handrail on the “top/mezzanine side of section P4” is not required. That area is as such to allow personnel access to the other mezzanine/platform. The current mezzanine allows a similar access between mezzanine sections using a step up/down ladder. The rack section P4 should be fairly close to the a wall as mentioned and the catwalk should cover the top of the P4 as shown on AF Drawing NCH801-02, SIDE VIEW P4 section.

Load Capacity Questions for the following:

Appendix A - Modular Cabinets Mini-Mezz

Q: How are you (the government) determining the maximum static load capacity of the Modular Drawer cabinet?

A: Modular drawer will be verified in accordance with paragraph 4.1 and cabinets will be load tested per paragraph 4.2. The max static load specified has been used in multiple or past projects.

Q/Statement: You have a request for certification of a minimum cabinet static load capacity of 24,000lbs.

A: Yes, that is correct.

Appendix C - Pallet Racking

Q: Load capacities: You only provided 125# per sq ft

A: For each type pallet rack, capacities are specified in Appendix B, Paragraph 3.2.2.

Appendix F – Rack Supported Mezzanine

Q: Load capacities: You only provided 125# per sq ft

A: Yes, the decking/catwalk capacity is as specified in paragraph 3.2.4.1. Rack capacities are specified in Appendix B

KirkN2 Pencil

handrail question_Question Set 5
Questions and Answers Set 5 McLaughlin B017