APPENDIX D.docx

DOCX document 35 KB Posted

Attached to
Storage Aid System (SAS) - Fairchild AFB, WA
Solicitation number
FA8604-12-R-7955
Issued by

About this file

Appendix D

View the file

Other files

File Type Posted
ADD_I.docx DOCX document
ADD_I.docx DOCX document
FA8604-12-R-7955_0001.pdf PDF
DI DRPR 81003.pdf PDF
DI MGMT 80909 T.pdf PDF
BFR1B0-01.dwg DWG drawing
a002.doc DOC document
DI TMSS 80527.pdf PDF
APPENDIX A.docx DOCX document
APPENDIX B.docx DOCX document
Notification_of_Compliance_with_Contract_Insurance_Requirements_(Sols).docx DOCX document
DI MGMT 80227 T.pdf PDF
Contractor Information —
BFR1B0-03.dwg DWG drawing
BFR1B0-02.dwg DWG drawing
a003.doc DOC document
APPENDIX C.docx DOCX document
a004.doc DOC document
A001.doc DOC document
FA860412R7955_RFP.pdf PDF
a006.doc DOC document
Cover PD.docx DOCX document
a007.doc DOC document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNICAL PROPOSAL QUESTIONNAIRE

FOR

Offeror: _ Solicitation No. F33600- -R- _

Offeror:

Solicitation Number:
FA8604-

-R-

APPENDIX D

FOR

WIDE-SPAN SHELVING

AT

FAIRCHILD AIR FORCE BASE, OH

BUILDING 2163

CSN: BFR1B0

DATE: 31 August 2011

PREPARED BY:

SHANE M. LEGGE

PROJECT ENGINEER

403 SCMS/GUEC

DONNA L. HARTMAN

REVIEWER

403 SCMS/GUEC

Table of Contents

1. SCOPE1
2. APPLICABLE DOCUMENTS1
3. REQUIREMENTS1
3.1. System description1
3.2. Performance and Physical Characteristics1
3.2.1. Configuration requirements1
3.2.2. Upright frames1
3.2.2.1. Columns2
3.2.2.2. bearing plates2
3.2.2.3. Diagonal/horizontal bracing2
3.2.3. Shelf beams2
3.2.3.1. Connectors3
3.2.4. wire mesh Decking3
3.2.5. Leveling shims4
3.2.6. Anchoring the structure4
3.2.7. Assembly4
4. QUALITY ASSURANCE PROVISIONS4
4.1. Inspection4
4.2. Tests4
4.3. CERTIFICATIONS5

Fairchild AFB App D - Page i

SCOPE

This appendix establishes the minimum performance, design, fabrication, installation, and test requirements for a wide-span shelving system in Bldg. 2163,at Fairchild Air Force Base (AFB), WA. The work shall be completed in accordance with this appendix, the Cover Purchase Description (PD), and Air Force (AF) Drawings BFR1B0-01 and BFR1B0-02. This appendix covers all equipment, materials, and labor necessary to complete installation of the system.

APPLICABLE DOCUMENTS

Applicable documents shall be in accordance with Section 2 of the Cover PD.

REQUIREMENTS

System description The wide-span shelving will be used to store medium sized loads (i.e., hand-liftable boxes and parts) in such a manner as to permit placement and removal of any individual item. The wide-span shelving system shall interface with the wall section display shelving specified in the Cover PD. The wide-span shelving system shall be designed for use in seismic zone 3. The wide-span shelving shall conform to the requirements of the Rack Manufacturers Institute (RMI) June 1990 Specification for the Design, Testing, and Utilization of Industrial Steel Storage Racks.

Performance and Physical Characteristics Configuration requirements The rows of wide-span shelving shall be located as shown on AF Drawing BFR1B0-01. The shelving shall be capable of being assembled sidebyside, in a row, using common uprights to support the shelf beams.

Upright frames The upright frames shall be made of all welded steel construction consisting of two columns, diagonal and horizontal braces, and floor bearing plates. Each upright frame shall be capable of being fully loaded to capacity without permanent deformation. The upright frames of like units shall be interchangeable. Upright frames shall meet the following requirements, as a minimum:

Capacity:2,200 pounds
Safety factor:1.92 to 1

Columns The columns shall be a continuous channel, box channel, rectangular, square or other formation approved by the Contracting Officer or technical representative (COTR). The width of the column, facing the aisle, shall be nominal 2 inches. Each column shall have openings to readily accommodate beam connectors, end-to-end, at corresponding heights throughout the height range of the column openings. The openings at the bottom shall allow for the tops of shelf beams to be installed at six inches above the ground and shall continue upward to the top of the column by 2 or 3 inch increments. All openings of each column shall be identical to each other and identical to the openings of all other columns. The position of all corresponding openings of the columns shall not vary more than 3/32-inch as measured from the bottom of the bearing plates. The arrangement of the openings and the fastening devices of the beams shall be such that the tops of the beams are flush, within 3/8-inch, with the top of the column.

bearing plates The bottom of each column shall have a load bearing plate securely attached. Each bearing plate shall be sufficiently sized to disperse the maximum load imposed by the column.

Diagonal/horizontal bracing The columns shall be braced by horizontal and diagonal braces. Each end of all braces shall be securely welded to the columns. The braces shall not protrude beyond the sides of the columns or obstruct the attachment of the shelf beams to the columns, at any height on the columns. The centerline of the bottom horizontal brace shall not be located more than 12 inches from the bottom of the upright frame, and the centerline of the top horizontal brace shall be located not farther than 12 inches from the top of the upright frame. Other diagonal and horizontal braces shall be uniformly spaced between the top and bottom horizontal braces.

Shelf beams Shelf beams shall be the closed box or step type. Any openings in the shelf beam construction shall face inward, they shall not face the aisle. Shelf beamtocolumn connection shall be of the locking type. Each pair of shelf beams shall provide a bay width of 96 inches. With a uniformly distributed load of 1,100 pounds per bay, there shall be no permanent deflections, and elastic deformations shall not exceed 0.70 percent of the unsupported span, measured with respect to the two ends of the beam. Shelf beams shall be designed with a safety factor of 1.65 to 1.

Connectors Each end of the shelf beams shall have a multiple prong slipfit or slipjoint type shelf beamtocolumn connector. Separate shelf beams and connectors are unacceptable. The connectors shall allow shelf beams to be moved with no more than the use of a soft hammer. The connector shall be capable of transferring all loads and external forces of the shelf beam to the column without failure of the connection, or damage to the column or connector. The prongs shall be of sufficient number, size, and strength to withstand repeated loading and unloading of the rack, and to continually sustain the rated shelf beam load. The prongs shall engage with the openings of the columns in such a manner to prevent lateral rotation of the beam, with each prong contributing to the support of the beam. The prongs shall engage with the openings of the columns to ensure a snug metaltometal fit between the horizontal and vertical load carrying members. The prongs shall be of the same type design as the opening. The connector shall not be welded to the column.

wire mesh Decking Wire mesh decking shall be installed in between all parallel shelf beams and uprights. The decking shall have a nominal 2-inch by 2-inch grid. The decking shall be heavy duty welded steel wire with integral support channels capable of supporting a uniformly distributed load of 1,100 pounds per bay. The decking shall be designed with a safety factor of 1.65 to 1. The decking shall not exhibit permanent deformation and elastic deformations shall not exceed 0.70 percent of the unsupported span. The decking shall be plated or galvanized to protect against corrosion in accordance with 3.3.3 of the Cover PD. Decking shall be the appropriate type to interface with the type shelf beam being provided. The ends of the wire mesh decking shall bend over the shelf beam to provide a secure load supporting deck and keep the decking from accidentally disengaging from the shelf beams. Where building columns are located within the wide-span shelving units the Contractor shall provide a useful bay by cutting the decking to fit around the building column.

Leveling shims Leveling shims shall be installed with the shelving units where necessary. The shims shall have holes corresponding to the holes in the bearing plate, and shall anchor or lock with the bearing plate when the shelving is erected. Shims shall be equal in width and length to the bearing plate under which it is installed. Shims shall be of varying thickness so no more than five shims are installed at any point. Slotted shims shall be unacceptable.

Anchoring the structure The shelving shall be anchored to resist all design shear and uplift forces. The shelving units shall be designed to be a rigid freestanding structure and shall not be connected to any existing building structure except the floor. Each bearing plate shall be securely anchored to the floor with minimum one 3/8-inch diameter anchor bolt. The minimum embedment of the anchor shall be in accordance with 3.3.2.3 of the Cover PD.

Assembly The assembled wide-span shelving system shall be rigid, stable, and without deformation or skewing when each wide-span shelving unit is loaded to the capacity of the design loads. The wide-span shelving system shall assemble so that the columns are perpendicular to the beams and parallel to each other. Shelf frames shall be straight and square. All horizontal members shall be level to within 1/8-inch per 10 feet measured over any distance in the shelving system.

QUALITY ASSURANCE PROVISIONS

Inspection The system shall be inspected to verify that it meets all the requirements of sections 1, 2, and 3 of this appendix and the Cover PD. These inspections shall be completed as part of the system checkout test and again as a part of the quality conformance test.

Tests The following tests shall be performed on the system as part of the system checkout test and again as a part of the quality conformance test.

No.
Paragraph
Description
3.2.3.
Three wide-span shelves, picked at random, shall each be loaded with 1,100-pounds to ensure the shelf beams are set in place. The loads shall then be removed. The distance from the top of each designated shelf beam to the top of the shelf beam above it shall be measured and recorded as M1. The 1,100-pounds shall then be put back onto the designated shelves. The loads shall be left for a minimum of four continuous hours. The distance from the designated shelf beams to the top of the next shelf beam shall be measured again and recorded as M2. The following formula shall be used to determine the deflection amount:

Deflection = [(M2 - M1) /96] * 100

If the deflection is greater than 0.70 or if permanent deformation exists on either the shelf beams or decking when the loads are removed, the system shall fail.

CERTIFICATIONS

The Contractor shall provide certification that the following requirements have been met. All certifications shall be provided in accordance with the Contract Data Requirements List.

No.
Paragraph
Certifications
3.1.
The wide-span shelving conforms to the requirements of the Rack Manufacturers Institute (RMI) Specification for the Design, Testing, and Utilization of Industrial Steel Storage Racks.
3.2.2.
Each upright frame shall have a minimum safe load capacity of 2,200 pounds and a safety factor of at least 1.92 to 1.
3.2.2.2.
The bearing plates are of sufficient size to disperse the maximum load imposed on the column.
3.2.3.
All shelf beams are designed for, constructed to, and capable of sustaining the minimum safe load with a safety factor of at least 1.65 to 1.

Fairchild AFB App D - Page 6

WIDE-SPAN SHELVING

Offeror:

Solicitation Number:
FA8604-

-R-

Project Title:
Storage Aid System
Base:
Fairchild AFB WA
CSN:
BFR1B0

Appendix D, Wide-Span Shelving, 31 August 2011

This questionnaire shall be completed by the Offeror. All entries to this questionnaire shall be typed. The questionnaire will be used to determine the Offeror's understanding of the requirements and acceptability of the proposed equipment. Please attach product literature/cut sheets for all equipment detailed in this questionnaire and attach any exceptions to the Purchase Description Appendix or recommendations/design alternatives as detailed below.

Shelving Manufacturer: _______________________________________

Paragraph
Characteristics
3.2.1.
Dimensions:

Width of shelving unit: ______________ inches Depth of shelving unit: ______________ inches Height of shelving unit: _____________ inches

3.2.2.
Upright frame part number: _______________________

Minimum capacity of upright frame: ____________ lbs based on a maximum shelf spacing of: ______ inches

Safety factor of: ____________________________ to 1

3.2.2.1.
Width of column facing the aisle: __________ inches

Center-center spacing of column openings: ___inches

3.2.2.2.
Number of punched holes per bearing plate: _______

Diameter of anchors to be provided: _______ inches

3.2.3.
Shelf beam part number: __________________________

Type of shelf beam: ______________________________ Bay width provided by shelf beam: _________ inches Minimum capacity per bay: _________________ pounds Minimum safety factor: ______________________ to 1 Will shelf deflection meet the criterion as specified? YES NO

3.2.4.
Will the wire decking be provided as specified? YES NO
3.2.5.
Will leveling shims be provided as specified?

YES NO

3.2.6.
Will units be anchored as specified?

YES NO

THIS AREA LEFT BLANK INTENTIONALLY

EXCEPTIONS/RECOMMENDATIONS/DESIGN ALTERNATIVES

Attach any exceptions taken to the Purchase Description Appendix. Please outline those concerns in detail. Your exceptions will be reviewed to determine acceptability.

Are exceptions taken?

Number of pages attached: ____________________________________

Attach any recommendations or design alternatives you feel may enhance operation, maintainability, or reduce system cost. Your recommendations and design alternatives will be reviewed to determine acceptability.

Are recommendations/design alternatives attached?

Number of pages attached: ____________________________________

We have read the requirements of the Purchase Description Appendix and will comply with all paragraphs as written, with exceptions taken only to those items indicated on the attached exception sheet.

_____________________________________________________
Offeror's SignatureDate

TYPED NAME:

COMPANY NAME:

ADDRESS:

PHONE:

FAX:

TPQ, Appendix D - Page 1 of 3

In-Checking Modular Office - Page 1 of TPQ, Appendix D - Page 2 of 3 image1.wmf

File details come from the government source that posted it. Updated .