NGB Preferred Concept Design - for bidders.pdf
PDF 15 MB Posted
- Attached to
- Design/Build ANG ACS Weapons Facility
- Solicitation number
- FA850122R0011
View the file
Other files
| File | Type | Posted |
|---|---|---|
| ANG Site Visit Sign in.jpg | JPG image | |
| Solicitation Amendment FA850122R00110002 SF 30.pdf | ||
| Atch Blank Sample AF Form 3052.xls | XLS spreadsheet | |
| Atch BLANK SAMPLE AF Form 3064.xlsx | XLSX spreadsheet | |
| Atch BLANK SAMPLE AF Form 3065.xlsx | XLSX spreadsheet | |
| QA Responses -1 of 2 165 CES.pdf | ||
| Bid QA Responses 2 of 2 - 165 CES.pdf | ||
| XDQU172001 Site 2 Utilities.pptx | PPTX presentation | |
| XDQU172001 Site 1 Utilities.pdf | ||
| RFIs with answers 81622.docx | DOCX document | |
| QA Responses - 165 CES.pdf | ||
| Bid Schedule.docx | DOCX document | |
| Chatham Co wage rates.pdf | ||
| RFIs with Answers updated 27 July 2022.docx | DOCX document | |
| Solicitation Amendment - FA850122R00110001 updated.pdf | ||
| Location Map-image.png | PNG image | |
| wage determination.pdf | ||
| Solicitation Final - FA850122R0011.pdf | ||
| XDQU172001 - SOW Revised 22 Final.docx | DOCX document |
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project No. SKXJ162001
100% COMPLETION SET - 10/3/2017
103rd AIR CONTROL SQUADRON
ORANGE AIR NATIONAL GUARD STATION
ORANGE, CONNECTICUT
CONSTRUCT ACS WEAPONS SYSTEM FACILITY
"CONCEPT ONLY"
CONNECTICUT BLDG CODES
NOT FOR CONSTRUCTION
"CONCEPT ONLY"
C
B
B
B
SITE PLAN
D N
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD File:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
40234
AS NOTED
NB
10/03/17
STA
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987
Fax (860)549-2572 www.aztecheng.com
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
C-1
SITE PLAN
"CONCEPT ONLY"
CONNECTICUT BLDG CODES
NOT FOR CONSTRUCTION
AutoCAD SHX Text
EXISTING UTILITY TROUGH
AutoCAD SHX Text
6" PVC STORM DRAINAGEPIPE AT (TYP).
AutoCAD SHX Text
NEW CONCRETE PAD
AutoCAD SHX Text
ELEC HH
AutoCAD SHX Text T
AutoCAD SHX Text
AutoCAD SHX Text
GATE #1
AutoCAD SHX Text
GATE #3
AutoCAD SHX Text
GATE #4
AutoCAD SHX Text
COMM
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
GROUND
AutoCAD SHX Text
WALL LIGHTS
AutoCAD SHX Text
TEMP BLDG
AutoCAD SHX Text
GRASSED SLOPE
AutoCAD SHX Text
2" COND., 8" DEEP
AutoCAD SHX Text
2" COND., 10" DEEP
AutoCAD SHX Text
EXISTING CONC. PAD
AutoCAD SHX Text
EXISTING CONC. PAD
AutoCAD SHX Text
EXISTING CONC. PAD
AutoCAD SHX Text
EXISTING CONC. PAD
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
CHAIN LINK FENCE
AutoCAD SHX Text
CONNECT TO EXISTING CATCH BASIN
AutoCAD SHX Text
PROVIDE AND MAINTAIN INLET PROTECTION
AutoCAD SHX Text
LOAM AND SEED DISTURBED GRASS
AutoCAD SHX Text
SILT FENCE
AutoCAD SHX Text
SCALE: 1"=10'-0"
AutoCAD SHX Text F
AutoCAD SHX Text
ANTENNA FOUNDATION TO REMAIN
AutoCAD SHX Text
ANTENNA FOUNDATION
AutoCAD SHX Text
GRASSED SLOPE
AutoCAD SHX Text
GRASSED SLOPE
AutoCAD SHX Text
EXISTING ANTENNA FOUNDATION TO BE REMOVED
AutoCAD SHX Text
STAIR
AutoCAD SHX Text A
AutoCAD SHX Text
LGKS
AutoCAD SHX Text
AutoCAD SHX Text
DN
AutoCAD SHX Text
LGK
AutoCAD SHX Text
CHIEF OF MAINT.
AutoCAD SHX Text
LGK
AutoCAD SHX Text
CONF. RM.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FEC
AutoCAD SHX Text
SLOPE
AutoCAD SHX Text
SLOPE 0.5%%%
AutoCAD SHX Text
CRUSHED STONE PAVEMENT
AutoCAD SHX Text
CONNECT UNDERGROUND ELECTRIC TO EXISTING SWITCHBOARD
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
1-2" PVC CONDUITS IN SAND
AutoCAD SHX Text
NEW CONCRETE PAD
AutoCAD SHX Text
BOLLARD 6" SEE DETAIL DRAWING S1
AutoCAD SHX Text
TOP OF CONCRETE SLAB ELEVATION 0'-0"
AutoCAD SHX Text
ELEVATION 0'-0"
AutoCAD SHX Text NEW 5'-0"x7'-0" CONCRETE PAD CENTERED ON DOOR OPENING. TOP OF CONCRETE PAD ELEVATION SHALL MATCH TOP OF ACCESS FLOOR.
AutoCAD SHX Text VERIFY LOCATION OF EXISTING CONDUITS & REROUTE CONDUITS AS REQUIRED TO CLEAR NEW COLUMN FOOTING
AutoCAD SHX Text
SLOPE 0.5%
AutoCAD SHX Text
3-4" CONDUITS FROM TROUGHTHRU BUILDING FOUNDATION WALL AND UP THRU SLAB.
AutoCAD SHX Text TOP OF EXISTING CONCRETE PAD ELEVATION TO BE ASSUMED DATUM ELEVATION 0'-0". ALL ELEVATION RELATIVE TO TOP OF THIS CONCRETE PAD.
AutoCAD SHX Text
PORTABLE A/C UNITS BY OWNER (TYP.)
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
GRASSED SLOPE
AutoCAD SHX Text
GRASSED SLOPE
AutoCAD SHX Text
SILT FENCE AT GRASSED SLOPE
AutoCAD SHX Text
6" BOLLARD EACH SIDE ROLL UP DOOR (TYP.)SEE DETAIL DRAWING S1
AutoCAD SHX Text
6" PVC STORM DRAINAGEPIPE AT (TYP).
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SF
AutoCAD SHX Text
SLOPE 0.5%%%
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text NEW 4'-0"x8'-0" CONCRETE PAD CENTERED ON DOOR OPENING.
AutoCAD SHX Text
GM2 ASSOCIATES, INC. 115 GLASTONBURY BLVD. GLASTONBURY, CT (860) 659-1416
TYPICAL SLIT FENCE EROSION
PROTECTION DETAIL
ELECTRIC AND DATA CONDUIT UNDER EARTH DETAIL
TYPICAL CATCH BASIN SILTSACK DETAIL
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD File:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
40234
AS NOTED
NB
10/03/17
STA
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987
Fax (860)549-2572 www.aztecheng.com
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
C-2
NTS
SITE DETAILS
"CONCEPT ONLY"
CONNECTICUT BLDG CODES
NOT FOR CONSTRUCTION
AutoCAD SHX Text
CONSTRUCTION NOTES:
AutoCAD SHX Text
INSTALL FENCE TO BETWEEN 70° & 80°
AutoCAD SHX Text 1 "X1 "X48" WOOD STAKE 12"X1 "X48" WOOD STAKE 12"X48" WOOD STAKE AT A MAXIMUM SPACING OF 10'-0" ON CENTER
AutoCAD SHX Text FILTER FABRIC WITH WOVEN WIRE FENCE, INDUSTRIAL NETTING, OR SNOW FENCE FOR SUPPORT
AutoCAD SHX Text
6"X6" COMPACTED BACKFILLED TRENCH
AutoCAD SHX Text
FLOW
AutoCAD SHX Text
NATIVE SOIL
AutoCAD SHX Text
1. SILT FENCE FILTER CLOTH TO BE SECURELY FASTENED TO GRADE SILT FENCE FILTER CLOTH TO BE SECURELY FASTENED TO GRADE STAKE WITH STAPLES, 6" ON CENTER. 2. WHEN TWO SECTIONS OF FILTER CLOTH ADJOIN ONE ANOTHER THEY WHEN TWO SECTIONS OF FILTER CLOTH ADJOIN ONE ANOTHER THEY SHALL OVERLAP AT STAKE BY 6" AND BE FOLDED.
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
CONDUIT TRENCH WIDTH
AutoCAD SHX Text
4" CRUSHED STONE
AutoCAD SHX Text
GENERAL BACKFILL PASSING 3" SCREEN
AutoCAD SHX Text
UNDERGROUND WARNING TAPES "CAUTION-CABLE BURIED BELOW".
AutoCAD SHX Text
COMPACTED SAND FILL
AutoCAD SHX Text
SCHEDULE 40 PVC CONDUITS WITH GLUED JOINTS SEE PLAN FOR SIZE & NUMBER
AutoCAD SHX Text
6" MIN., (TYP.)
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
OPTIONAL OVERFLOW
AutoCAD SHX Text
INSERT 1" REBAR FOR BAG REMOVAL FROM INLET
AutoCAD SHX Text
SILT SACK
AutoCAD SHX Text
DUMP LOOPS
AutoCAD SHX Text
EXPANSION RESTRAINT
AutoCAD SHX Text
NOT TO SCALE
DN
A
B
C
A
B
C
FOUNDATION PLAN
SECTION
TYPICAL BOLLARD DETAIL
S-1
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD File:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
40234
AS NOTED
NB
10/03/17
STA
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987
Fax (860)549-2572 www.aztecheng.com
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
FOUNDATION PLAN
"CONCEPT ONLY"
CONNECTICUT BLDG CODES
NOT FOR CONSTRUCTION
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
AutoCAD SHX Text S-1
AutoCAD SHX Text
AutoCAD SHX Text S-1
AutoCAD SHX Text
CONCRETE PIER, (TYP.)
AutoCAD SHX Text
4" CONCRETE SLAB-ON-GRADE
AutoCAD SHX Text
PIER FOUNDATION, (TYP.)
AutoCAD SHX Text
WALL FOUNDATION, (TYP.)
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
(SIM.)
AutoCAD SHX Text
TYP.
AutoCAD SHX Text
SCALE: "=1'-0"14"=1'-0"=1'-0"
AutoCAD SHX Text
6" CONCRETE SLAB-ON-GRADE
AutoCAD SHX Text VERIFY LOCATION OF EXISTING CONDUITS & REROUTE CONDUIITS AS REQUIRED TO CLEAR NEW COLUMN FOOTING
AutoCAD SHX Text P1 F4-5.5
AutoCAD SHX Text P3 F3
AutoCAD SHX Text P1 F4-5.5
AutoCAD SHX Text P3 F3
AutoCAD SHX Text F3 P3
AutoCAD SHX Text P1 F4-5.5
AutoCAD SHX Text P1 F4-5.5
AutoCAD SHX Text F3 P3
AutoCAD SHX Text F3 P2
AutoCAD SHX Text F3 P2
AutoCAD SHX Text
NEW CONCRETE PAD
AutoCAD SHX Text
NEW CONCRETE PAD
AutoCAD SHX Text
CAST-IN-PLACE CONCRETE CURB
AutoCAD SHX Text
6" CONCRETE FILLED PIPE BOLLARD TYP. SEE DETAIL DWG ON S3
AutoCAD SHX Text
EXISTING CONCRETE PAD TO REMAIN
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text
6" CONCRETE FILLED PIPE BOLLARD TYP. SEE TYP. DETAIL/S1
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text
TOP OF CONCRETE SLAB ELEV. 0'-0"
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-3")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-3")
AutoCAD SHX Text (-4'-3")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-3")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text C.J.
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text (-4'-0")
AutoCAD SHX Text C.J.
AutoCAD SHX Text
RAMP DOWN
AutoCAD SHX Text
EXISTING UTILITY TROUGH
AutoCAD SHX Text C.J.
AutoCAD SHX Text
EXISTING CONCRETE PAD TO REMAIN
AutoCAD SHX Text TOP OF EXISTING CONCRETE PAD ELEVATION TO BE ASSUMED DATUM ELEVATION 0'-0". ALL ELEVATION RELATIVE TO TOP OF THIS CONCRETE PAD
AutoCAD SHX Text
NOTES
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FOR PIER DETAILS, SEE DRAWING S-2
AutoCAD SHX Text
FOR GENERAL NOTES AND TYPICAL DETAILS, SEE DRAWING S-2
AutoCAD SHX Text
TOP OF CONCRETE SLAB ELEV. 0'-0"
AutoCAD SHX Text
NEW CONCRETE PAD
AutoCAD SHX Text REINFORCED W/W.W.F.6X6-W2.9xW2.9
AutoCAD SHX Text REINFORCED W/W.W.F.6X6-W2.9xW2.9
AutoCAD SHX Text
6" CONCRETE SLAB-ON-GRADE
AutoCAD SHX Text REINFORCED W/W.W.F.6X6-W2.9xW2.9
AutoCAD SHX Text
6" CONCRETE SLAB-ON-GRADE
AutoCAD SHX Text REINFORCED W/W.W.F.6X6-W2.9xW2.9
AutoCAD SHX Text
NOTCH INTERIOR OF CONCRETE STEM AT COLUMNS, (TYP.)
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
(SIM.,TYP.)
AutoCAD SHX Text
NEW CONCRETE PAD
AutoCAD SHX Text
CONSTRUCTION JOINT THRU SLAB
AutoCAD SHX Text
OVER 8" COMPACTED PROCESSED AGGREGATE
AutoCAD SHX Text 12" x 8"EMBEDMENT 'J'-BOLTS, (TYP. DOOR JAMB LOCATIONS)
AutoCAD SHX Text 3'-0" x 3'-0"
AutoCAD SHX Text
MARK
AutoCAD SHX Text
PLAN SIZE
AutoCAD SHX Text F3
AutoCAD SHX Text
FOOTING SCHEDULE
AutoCAD SHX Text
REINFORCEMENT
AutoCAD SHX Text
THICKNESS
AutoCAD SHX Text
4-#5 EACH WAY, BOTTOM
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 4'-0" x 5'-6"
AutoCAD SHX Text F4-5.5
AutoCAD SHX Text 1'-3"
AutoCAD SHX Text
4-#6 TOP, EACH WAY
AutoCAD SHX Text
6-#6 BOTTOM, EACH WAY
AutoCAD SHX Text
SCALE: 3" = 1'-0"
AutoCAD SHX Text
6" METAL STUD WALL. SEE ARCH. DWGS
AutoCAD SHX Text
CAST-IN-PLACE CONCRETE CURB
AutoCAD SHX Text
TOOLED EDGE, TYP. EACH SIDE
AutoCAD SHX Text
ACCESS FLOOR SEE ARCH DWGS
AutoCAD SHX Text HYDROPHYLIC WATERSTOP 1"x " (CONT. 34" (CONT. RETURN UP FOUNDATION WALLS, EACH END)
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text 2"
AutoCAD SHX Text
#4 ADHESIVE ANCHOR @18"O.C.
AutoCAD SHX Text
ELEV. 0'-0"
AutoCAD SHX Text
4" PROCESSED AGGREGATE BASE
AutoCAD SHX Text
16" CONTROLLED FILL
AutoCAD SHX Text
10 MIL POLYETHYLENE VAPOR BARRIER
AutoCAD SHX Text
CONCRETE SLAB-ON-GRADE.
AutoCAD SHX Text
SUBGRADE
AutoCAD SHX Text
UNDISTURBED
AutoCAD SHX Text
NOTE: CONCRETE SHALL HAVE A COMPRESSIVE STRENGTH OF 4,000 PSI AT 28 DAYS.
AutoCAD SHX Text N.T.S.
AutoCAD SHX Text 6" DIA. STANDARD STEEL PIPE BOLLARD & HOT DIPPED GALVANIZED FILLED SOLID WITH CONCRETE. PAINT BOLLARD
AutoCAD SHX Text CAST-IN-PLACE CONCRETE BOLLARD FOUNDATION SHALL BE PLACED IN CARDBOARD "SONOTUBE" TYPE FORM.
AutoCAD SHX Text
TOP OF DOME CONCRETE FILL.
AutoCAD SHX Text
FINISH GRADE/FINISH FLOOR
AutoCAD SHX Text
AT EXTERIOR BOLLARDS SLOPE TOP OF CONCRETE BOLLARD FOUNDATION
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text 1'-6"
AutoCAD SHX Text AT INTERIOR BOLLARDS CONCRETE BOLLARD FOUNDATION SHALL BE HELD LOW AND SLAB-ON-GRADE SHALL EXTEND TO BOLLARD
TYPICAL SLAB-ON-GRADE DETAIL
TYPICAL SECTION AT DOOR OPENING
SECTION
SECTION
PIER DETAIL - P1
PIER DETAIL - P2
PIER DETAIL - P3
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD File:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
40234
AS NOTED
NB
10/03/17
STA
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987
Fax (860)549-2572 www.aztecheng.com
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
S-2
AS_NOTED
FOUNDATION SECTIONS
& GENERAL NOTES
"CONCEPT ONLY"
CONNECTICUT BLDG CODES
NOT FOR CONSTRUCTION
AutoCAD SHX Text BUILDING CODE: 2016 CONNECTICUT BUILDING CODE REFERENCED STANDARD: CONCRETE: ACI, 318-11 MASONRY: ACI 530-11 DESIGN LOADS: A. LIVE LOADS: 100 PSF 100 PSF PSF MATERIAL PROPERTIES CONCRETE: FOOTINGS: f'c = 3,000 PSI AT 28 DAYS FOOTINGS: f'c = 3,000 PSI AT 28 DAYS f'c = 3,000 PSI AT 28 DAYS FOUNDATION WALLS: f'c = 4,500 PSI AT 28 DAYS f'c = 4,500 PSI AT 28 DAYS INTERIOR CONCRETE SLABS: f'c = 4,000 PSI AT 28 DAYS f'c = 4,000 PSI AT 28 DAYS EXTERIOR CONCRETE SLABS: f'C = 4,500 PSI AT 28 DAYS WITH 6% AIR ENTRAINMENT, A f'C = 4,500 PSI AT 28 DAYS WITH 6% AIR ENTRAINMENT, A MAXIMUM WATER TO CEMENTIUOUS MATERIAL RATIO OF 0.45, AND LIMITS ON CEMENTITOUS MATERIALS PER ACI 318-08, SECTION 4.4.2. REINFORCEMENT STEEL: ASTM A615, GRADE 60 ASTM A615, GRADE 60 WELDED WIRE FABRIC: ASTM A185 ASTM A185 GEOTEXTILE FABRIC: SHALL BE ONE OF THE FOLLOWING: SHALL BE ONE OF THE FOLLOWING: TC MIRAFI FW500 SYNTHETIC INDISTRIES GEOTEX 701 EVERGREEN TECHNOLOGIES TG650
AutoCAD SHX Text FOUNDATION NOTES: 1. ALL EARTHWORK FOR BUILDING FOUNDATIONS SHOWN ON CONTRACT DOCUMENTS IS IN ACCORDANCE WITH THE ALL EARTHWORK FOR BUILDING FOUNDATIONS SHOWN ON CONTRACT DOCUMENTS IS IN ACCORDANCE WITH THE "GEOTECHNICAL STUDY" DATED NOVEMBER 14, 2016 PREPARED BY DR. CLEARANCE WELTI, P.E., P.C. THIS REPORT IS AVAILABLE FOR CONTRACTOR'S USE. 2. ALL FILL AND BACKFILL FOR FOOTINGS, SLABS AND WALLS SHALL BE CONTROLLED FILL, CONFORMING TO THE ALL FILL AND BACKFILL FOR FOOTINGS, SLABS AND WALLS SHALL BE CONTROLLED FILL, CONFORMING TO THE GEOTECHNICAL STUDY REFERENCED ABOVE. 3. SEE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR EXACT SIZE OF SLAB AND WALL PENETRATIONS. SEE MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR EXACT SIZE OF SLAB AND WALL PENETRATIONS. CONCRETE NOTES: 1. ALL CONCRETE WORK SHALL CONFORM TO ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR ALL CONCRETE WORK SHALL CONFORM TO ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS" 2. REINFORCING SHALL BE DETAILED IN ACCORDANCE WITH ACI 315 "MANUAL OF STANDARD PRACTICE FOR REINFORCING SHALL BE DETAILED IN ACCORDANCE WITH ACI 315 "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES". 3. ALL REINFORCING FOR WALLS AND FOOTINGS SHALL BE CONTINUOUS AND LAPPED 48 BAR DIAMETERS AT ALL ALL REINFORCING FOR WALLS AND FOOTINGS SHALL BE CONTINUOUS AND LAPPED 48 BAR DIAMETERS AT ALL SPLICES, CORNERS AND INTERSECTIONS. U.N.O. 4. REINFORCING BARS SHALL BE PROTECTED BY THE FOLLOWING THICKNESS OF CONCRETE COVER: REINFORCING BARS SHALL BE PROTECTED BY THE FOLLOWING THICKNESS OF CONCRETE COVER: A. CONCRETE PLACED AGAINST EARTH....................................................................... 3" 3" B. CONCRETE PLACED IN FORMS BUT EXPOSED TO EARTH OR WATER.................... 2" 2" (EXCEPT FOR NO. 5 BARS OR SMALLER, 1 "). 12"). C. SLAB AND WALLS NOT EXPOSED TO THE GROUND OR WEATHER......................... " 34" D. IN ALL CASES THE THICKNESS OF CONCRETE OVER THE REINFORCEMENT SHALL BE AT LEAST EQUAL TO THE DIAMETER OF THE REINFORCEMENT. 5. CONTRACTOR SHALL COORDINATE LOCATIONS AND DETAILS OF ALL OPENINGS AND EMBEDDED ITEMS WITH THE CONTRACTOR SHALL COORDINATE LOCATIONS AND DETAILS OF ALL OPENINGS AND EMBEDDED ITEMS WITH THE VARIOUS TRADES. 6. CONSTRUCTION JOINTS SHALL BE DETAILED AND LOCATED ON SHOP DRAWINGS AND APPROVED BY ENGINEER. CONSTRUCTION JOINTS SHALL BE DETAILED AND LOCATED ON SHOP DRAWINGS AND APPROVED BY ENGINEER. UNLESS SHOWN OTHERWISE, CONSTRUCTION JOINTS ARE TO BE KEYED AND PROVIDE FOR CONTINUITY OF REINFORCING STEEL. CONSTRUCTION JOINTS ARE TO BE LOCATED WHERE CONSTRUCTION OPERATIONS ARE SUSPENDED FOR 30 MINUTES OR MORE. 7. CONTROL JOINTS FOR INTERIOR SLABS ON GRADE SHALL GENERALLY BE LOCATED ALONG BUILDING GRID CONTROL JOINTS FOR INTERIOR SLABS ON GRADE SHALL GENERALLY BE LOCATED ALONG BUILDING GRID LINES. CONTROL JOINTS FOR OTHER LOCATIONS SHALL FORM UNIFORM PANELS NOT EXCEEDING 400 S.F. TYPICAL CONTROL JOINT PATTERNS ARE INDICATED ON FOUNDATION PLANS.
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
CONTROL JOINT - " X 1" DEEP 14" X 1" DEEP SAWCUT AND FILL W/ SEALANT
AutoCAD SHX Text
CUT EVERY OTHER WIRE BELOW SAWCUT JOINT
AutoCAD SHX Text
ONE LAYER OF WELDED WIRE FABRIC- 6X6 - W2.9X2.9
AutoCAD SHX Text
10 MIL POLYETHYLENE SHEET VAPOR BARRIER
AutoCAD SHX Text NOTE: 1. CONTROL JOINTS MUST BE SAWCUT WITHIN 4 TO 12 HOURS CONTROL JOINTS MUST BE SAWCUT WITHIN 4 TO 12 HOURS AFTER SLAB HAS BEEN PLACED AND FINISHED.
AutoCAD SHX Text
VARIES SEE FOUNDATION PLAN
AutoCAD SHX Text
4" PROCESSED AGGREGATE BASE
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
16" CONTROLLED FILL
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
#5 @ 24" O.C. ALTERNATE SIDES
AutoCAD SHX Text
6" -3/8" CRUSHED STONE
AutoCAD SHX Text
CONCRETE RAMP
AutoCAD SHX Text
CONSTRUCTION JOINT
AutoCAD SHX Text
4" PROCESSED AGGREGATE BASE
AutoCAD SHX Text
10 MIL POLYETHYLENE VAPOR BARRIER
AutoCAD SHX Text W.W.F.
AutoCAD SHX Text STOP SLAB 2" SHORT AT OVERHEAD DOORS FOR CONCRETE APRON TO OVERLAP ON TO FOUNDATION WALL
AutoCAD SHX Text
CONTROLLED FILL
AutoCAD SHX Text
SCALE: " = 1'-0"34" = 1'-0"
AutoCAD SHX Text
8" PROCESSED AGGREGATE BASE
AutoCAD SHX Text #4X4'-0" @ 12" O.C.
AutoCAD SHX Text
SLAB-ON-GRADE
AutoCAD SHX Text
16" CONTROLLED FILL
AutoCAD SHX Text
THICKNESS VARIES SEE FOUNDATION PLAN
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
WWF
AutoCAD SHX Text
METAL BUILDING SIDING
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
#5@24"O.C. ALTERNATE SIDES
AutoCAD SHX Text
6" -3/8" CRUSHED STONE
AutoCAD SHX Text
4" PROCESSED AGGREGATE BASE
AutoCAD SHX Text
10 MIL POLYETHYLENE VAPOR BARRIER
AutoCAD SHX Text W.W.F.
AutoCAD SHX Text
SCALE: 1" = 1'-0"
AutoCAD SHX Text 1" RIGID INSULATION w/ 45°CHAMFER@ TOP, (CONT.)
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
THICKNESS VARIES SEE FOUNDATION PLAN
AutoCAD SHX Text
16" CONTROLLED FILL
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text
6" -3/8" CRUSHED STONE
AutoCAD SHX Text W.W.F.
AutoCAD SHX Text
SCALE: 1" = 1'-0"
AutoCAD SHX Text 1" RIGID INSULATION w/ 45°CHAMFER@ TOP, (CONT.)
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text 3'-6"
AutoCAD SHX Text
FINISHED GRADE
AutoCAD SHX Text
6-#6 VERT.
AutoCAD SHX Text
CONCRETE SLAB-ON-GRADE
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text
AutoCAD SHX Text S-2
AutoCAD SHX Text
4" PROCESSED AGGREGATE BASE
AutoCAD SHX Text
16" CONTROLLED FILL
AutoCAD SHX Text
10 MIL POLYETHYLENE VAPOR BARRIER
AutoCAD SHX Text
THICKNESS VARIES SEE FOUNDATION PLAN
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text 6"
AutoCAD SHX Text
NOTCH CONCRETE STEM TO CLEAR COLUMNS, (TYP.)
AutoCAD SHX Text 4-3/4" ANCHOR RODS (A307) THREADED TOP &BOTTOM (SEE METAL BUILDING DRAWINGS FOR ANCHOR ROD LOCATIONS AND PROJECTION)
AutoCAD SHX Text
NUT TACK WELDED, (TYP.)
AutoCAD SHX Text A
AutoCAD SHX Text C
AutoCAD SHX Text
SCALE: 1" = 1'-0"
AutoCAD SHX Text
3-#5 WALL REINF. CONT. THRU PIER
AutoCAD SHX Text
CONCRETE PIER
AutoCAD SHX Text
#3 TIES
AutoCAD SHX Text
CONCRETE FOUNDATION WALL
AutoCAD SHX Text
SCALE: 1" = 1'-0"
AutoCAD SHX Text
3-#5 WALL REINF. CONT. THRU PIER
AutoCAD SHX Text
CONCRETE PIER
AutoCAD SHX Text
#3 TIES @ 12" O.C.
AutoCAD SHX Text
CONCRETE FOUNDATION WALL
AutoCAD SHX Text
SCALE: 1" = 1'-0"
AutoCAD SHX Text
3-#5 WALL REINF. CONT. THRU PIER
AutoCAD SHX Text
#3 TIES @ 12" O.C.
AutoCAD SHX Text
ARCHITECTURAL ABBREVIATION AND SYMBOLS
AutoCAD SHX Text @ ARCH C = X" CANT. C.J. CMU CONT. DWGS EA. E.J. EL. EXP. EXT. F.F. GALV. HI HSS K L.L.V. LO MAX. MIN. O.C. P.L.F. P.S.F. SIM. S.J. S.L.V. TYP. T.O.S. T.O.W. T.S.E. U.N.O. V.I.F.
AutoCAD SHX Text AT ARCHITECTURAL CAMBER CANTILEVERED CONTROL JOINT CENTERLINE CONCRETE MASONRY UNIT CONTINUOUS DRAWINGS EACH EXPANSION JOINT ELEVATION EXPANSION EXTERIOR FINISH FLOOR HOT DIPPED GALVANIZED INDICATES BEAM AT HIGHER ELEVATION WITH RESPECT TO OTHER BEAM SHOWN AT SAME LOCATION HOLLOW STRUCTURAL SECTION KIPS LONG LEG VERTICAL INDICATES BEAM AT LOWER ELEVATION WITH RESPECT TO OTHER BEAM SHOWN AT SAME LOCATION MAXIMUM MINIMUM ON CENTER POUNDS PER LINEAR FOOT PLATE POUNDS PER SQUARE FOOT SIMILAR SEISMIC JOINT SHORT LEG VERTICAL TYPICAL-INDICATES MATERIAL OR REQUIREMENT NOTED SHALL BE CONSIDERED AS CALLED FOR AT ALL SIMILAR LOCATIONS TOP OF STEEL TOP OF WALL TOP OF SHELF ELEVATION UNLESS NOTED OTHERWISE VERIFY IN THE FIELD
CR
CR
CR
CTV
E L E C T / V O I C E / D A T A K E Y
Mixed Voice and Data Cable as required from computer rack.
Floor mounted outlet (direct to concrete slab under access floor).
Quadruplex Receptacle
Switch
A300
A301
A300
A3011
A400
A401
A400
/8
5'
1"
STORAGE
2A
OFFICE
1A
CA
B
6' - 10"
Computer Racks by CT ANG.
Security Panel Electrical Panel FIber demarcation panel
Exist concrete pad.
Bulkhead connectors @ 42" A.F.F.
Typ. Coordinate with girt locations.
Bulkhead connectors @ 42" A.F.F.
coordinate with girt locations.
35' - 0"
213 Van by
CT ANG.
OM Van by
CT ANG.
78910
New Concrete Ramp.
ECU ECU
ECU
A403
A402
A403
A402
Existing Temp. Building
Portable A/C units by CT ANG (Typ.)
6" Concrete filled pipe bollard Typ. See structural dwg's
Furniture to be provided by CT ANG.
18 Desks & 18 Chairs.
10'-0" x10'-0" Heavy duty Overhead Door corp. #625 Stormtite series overhead insulated rolling steel door.
10'-0" x10'-0" Heavy duty Overhead Door corp. #625 Stormtite series overhead insulated rolling steel door.
Exist utility trench to remain.
Corner cut tile for floor mount duplex under access floor. (Typ.)
A.1 B.9
1.1
3.9
6" Wide ladder tray to cable tray above.
1'
0"
1'
0"
EQ EQ
Painted FR Plywood wall surface. by CT ANG.
3' - 7" 3' - 0" 4' - 3" 6' - 0" 2' - 0" 5' - 0" 1' - 0" 6' - 0" 4' - 6" (+/-)
3' - 10" 3' - 0" 2' - 6" 5' - 0" 8' - 10" 5' - 0" 7' - 2"
Concrete Ramp.
Existing concrete pad to remain.
6' - 2" 26' - 10"
ECUECU
1'
6"
1'
1'
6"
6'
5"
1'
5"
6' - 0"
2' - 5" 3' - 0"
Card reader access.
Portable A/C units by CT ANG (Typ.)
Enclosed supply and return. Refer to Mechanical dwg's.Concrete ramp down
6" to concrete pad.
Downspout shown thus, typical.
6" Step up at door threshold.
Paint face of curb saftey yellow.
6' - 0"
1'
5"FE
FE2A:10BC Fire extinguisher.
2A:10BC Fire extinguisher.
6'
6"
CONSTRUCTION KEY
"x-xx"
"x-xx"
Window Tag, refer to window schedule for further information.
Door opening tag, refer to door elevations and schedule for further information.
Denotes dimension from face of framing to face of framing or face of existing surface unless specifically noted otherwise
Denotes dimension between two centerlines.
Spot elevation indicated thus.
Dimensions in parenthesis are negative numbers.
New partition construction shown thus, typical. All interior walls shall be Wall Type 'C' unless specifically noted otherwise. All exterior walls type 'A' unless otherwise noted.
New door shown thus typical.
Interior elevation flag
Wall type indicator x'-xx"
A
A000
W-?
A
C
BD
Detail No.
Sheet No.
CONSTRUCTION N O T E S:
Refer to Specifications for further information regarding materials and methods prior to beginning any work.
CON. 1
Numbered note refer to this sheef only unless specifically noted otherwise.
CON. 2
New access flooring by contractor. Refer to specification section 10270 for further information. Povide 18 tiles with 3" x 3" cut at one corner to feed cable through floor space below. Provide 20 attic stock floor tiles to CT ANG. Refer to specifications for further information.
CON. 3
F I N I S H N O T E S:
Refer to Specifications for further information regarding materials and methods.
FIN 4 All walls (except where specifically noted otherwise) shall be finished with two coats of premium latex enamel eggshell paint. Paint colors to be determined by Owner, paint brand to be as specified. Contractor shall include all costs necessary to complete painting in Base Bid.
FIN. 1 FIN 5 All door faces shall be painted with two coats of alkyd enamel semi-gloss exterior trim paint, color to be determined by Owner.
FIN 6 Access floor finish: High pressure laminate as specified, color and pattern to be determined by Owner.
Numbered note refer to this sheef only unless specifically noted otherwise.
FIN. 2
See Finish Schedule for additional information and description of finishes.
FIN. 3
1FIRST FLOOR CONSTRUCTION PLAN
SCALE: 1/4"=1'-0" 0' 2' 5' 8' 10'
FINISH SCHEDULE
Number Name Finishes
Area CommentsBase Floor Wall Ceiling
1A OFFICE 4" Vinyl HPDL Laminate Paint Paint 1405 SF See finish note #6 2A STORAGE 4" Vinyl Sealed concrete Paint Paint 476 SF
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987 Fax (860)549-2572 www.aztecheng.com
GM2 ASSOCIATES, INC.
115 GLASTONBURY BLVD.
GLASTONBURY, CT
(860) 659-1416
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD file:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
As indicated
ABP DBA
2017.065 10/03/17
FIRST FLOOR
CONSTRUCTION
PLAN
ACS_BASE.rvt
A101
"CONCEPT ONLY"
A300
A301
A300
A3011
A400
A401
A400
CA
B
4" / 1'-0" 4" / 1'-0" 61
35' - 6"
1'
0"
4' - 7"
4' - 7"
5" 24 gauge Kynar finished galvanized steel box gutter. Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building. Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping.
Provide clean out at connection to PVC boot.
A.1 B.9
1.1
3.9
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports. Canopy color to be determined by Architect. Center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F. Verify height clears light fixture. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports. Canopy color to be determined by Architect. Center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F. Verify height clears light fixture.Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
5" 24 gauge Kynar finished galvanized steel box gutter. Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building. Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping. Provide clean out at connection to PVC boot.
1'
0"
1'
0"
Security light Type C at each corner. Typ.
Security light Type C at each corner. Typ.
35' - 0"
16' - 7" 16' - 7"
4'
0"
Security light Type C at each corner. Typ.
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987 Fax (860)549-2572 www.aztecheng.com
GM2 ASSOCIATES, INC.
115 GLASTONBURY BLVD.
GLASTONBURY, CT
(860) 659-1416
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD file:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
1/4" = 1'-0"
ABP DBA
2017.065 10/03/17
ROOF PLAN
ACS_BASE.rvt
A102 10' 2' 5' 8' 10'
ROOF PLAN
SCALE: 1/4"=1'-0"
"CONCEPT ONLY"
A300
A301
A300
A3011
A400
A401
A400
CA
B
A403
STORAGE
2A
OFFICE
1A
Security Panel
EPB P.1
FIber demarcation panel
6" x 48" Pendant mounted utility light fixture. Hang from froof structure.
B/Fixtures at 10'-6" A.F.F.
A.1 B.9
1.1
3.9
16" Cablofil wire mesh overhead cable tray with wall mounted tray between computer racks with sweep.
Bottom of tray 10'-6" A.F.F.
Computer Racks by CT ANG.
Wiremold "Flamestopper" through wall fitting at cable tray.
Provide 2 evenly distributed along cable tray width.
1'
4"
1'
4"
Center cable tray on door as shown.
EQ
EQ
Wall light with integral emergency light.
Emergency light fixture. See Electrical dwg's.
10'-0" x10'-0" Heavy duty Overhead Coor corp #625 Stormtite series overhead insulated rolling steel door.
6" x 48" Pendant mounted utility light fixture. Hang from roof structure, provide unistrut as necessary to span.
B/Fixtures at 10'-6" A.F.F.
10'-0" x10'-0" Heavy duty Overhead Coor corp #625 Stormtite series overhead insulated rolling steel door.
5'
4"
Enclosed supply and return. Refer to Mechanical dwg's.
Security light Type C at each corner. Typ.
Security light Type C at each corner. Typ.
Security light Type C at each corner. Typ.
Security light Type C at each corner. Typ.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building. Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping. Provide clean out at connection to PVC boot.
Ductwork. Refer to Mechanical dwg's
Ductwork. Refer to Mechanical dwg's.
Coordinate final location with cable tray.
16" Cablofil wire mesh overhead cable tray with wall mounted tray between computer racks with sweep. Bottom of tray 10'-0" A.F.F.
Wall light with integral emergency light.
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports.
Canopy color to be determined by Architect. Center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F. Verify height clears light fixture.
Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports. Canopy color to be determined by Architect. Center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F. Verify height clears light fixture.Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
8'
9"
5'
3"
3' - 11"7' - 1"10' - 11"7' - 1"3' - 11"
EXIT
EXIT
8' - 6"16' - 0"8' - 6"
Unistrut trapeze at lights under cable tray. Typ.
5'
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987 Fax (860)549-2572 www.aztecheng.com
GM2 ASSOCIATES, INC.
115 GLASTONBURY BLVD.
GLASTONBURY, CT
(860) 659-1416
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD file:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
1/4" = 1'-0"
ABP DBA
2017.065 10/03/17
FIRST FLOOR
REFLECTED CEILING
PLAN
ACS_BASE.rvt
A201
1FIRST FLOOR REFLECTED CEILING PLAN
SCALE: 1/4"=1'-0" 0' 2' 5' 8' 10'
"CONCEPT ONLY"
12"
4"
Roof 21' - 0"
Top of GWB 8' - 10"
Storage Finish Floor 0' - 0"
A402
Exterior walls to be prefinished insulated metal panels with painted interior and exterior faces.
Light colored standing seam metal roof, with metal roof panels with a 18 gauge steel min.
Card reader color to be selected by Architect.
Bulkhead connectors @ 42" A.F.F. (Typ.)
Portable A/C units by CT ANG.Entrance concrete pad w/ ramp down to existing concrete pad.
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports. Canopy color to be determined by Architect center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F.
Verify height clears light fixture.Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
12"
4"
Security light Type C at each corner. Typ.
Exterior 6-1/2"x 13" wall light with integral emergency light feature.
5" 24 gauge Kynar finished galvanized steel box gutter. Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building. Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping. Provide clean out at connection to PVC boot. Typ.
A600
8'
0"
Security light Type C at each corner. Typ.
3'
0"
Office Finish Floor 0' - 6"
12"
4"
12"
4"
Roof 21' - 0"
Top of GWB 8' - 10"
Storage Finish Floor 0' - 0"
A403
A402
Bulkhead connectors @ 42" A.F.F. (Typ.)
Portable A/C units by CT ANG.
6" Concrete filled pipe bollard Typ. See structural dwg's
6" Concrete filled pipe bollard Typ.
See structural dwg's
Exterior walls to be prefinished insulated metal panels with painted interior and exterior faces.
Light colored standing seam metal roof, with metal roof panels with a 18 gauge steel min. Color to be selected by Architect.
Card reader color to be selected by Architect.
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports.
Canopy color to be determined by Architect center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F. Verify height clears light fixture.
Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
Security light Type C at each corner. Typ.
Exterior 6-1/2"x 13" wall light with integral emergency light feature.
A600
Exterior walls to be prefinished insulated metal panels with painted interior and exterior faces.
5" 24 gauge Kynar finished galvanized steel box gutter. Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building.
Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping.
Provide clean out at connection to PVC boot. Typ.
3'
0"
8'
0"
Office Finish Floor 0' - 6"
1SOUTH ELEVATION
SCALE: 1/4"=1'-0"
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987 Fax (860)549-2572 www.aztecheng.com
GM2 ASSOCIATES, INC.
115 GLASTONBURY BLVD.
GLASTONBURY, CT
(860) 659-1416
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD file:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
1/4" = 1'-0"
DLD DBA
2017.065 10/03/17
EXTERIOR
ELEVATIONS
ACS_BASE.rvt
A300
2NORTH ELEVATION
SCALE: 1/4"= 0' 2' 5' 8' 10'
0' 2' 5' 8' 10'
"CONCEPT ONLY"
A400
A400
Roof 21' - 0"
Top of GWB 8' - 10"
Storage Finish Floor 0' - 0"
1' - 0"
Portable A/C units by CT ANG.
6" Concrete filled pipe bollard Typ.
See structural dwg's
Light colored standing seam metal roof, by metal building manufacturer.
Security light Type C at each corner. Typ.
Exterior walls to be prefinished insulated metal panels with painted interior and exterior faces.
5" 24 gauge Kynar finished galvanized steel box gutter. Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building.
Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping.
Provide clean out at connection to PVC boot. Typ.
Security light Type C at each corner. Typ.
10'-0" x10'-0" Heavy duty 625 Stormtite series overhead insulated rolling steel door.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building. Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping. Provide clean out at connection to PVC boot. Typ.
10' - 0"
Office Finish Floor 0' - 6"
A400
A400
Roof 21' - 0"
Top of GWB 8' - 10"
Storage Finish Floor 0' - 0"
A403
Portable A/C units by CT ANG.
6" Concrete filled pipe bollard Typ.
See structural dwg's
Light colored standing seam metal roof, with metal roof panels with a 18 gauge steel min.
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports.
Canopy color to be determined by Architect center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F. Verify height clears light fixture.
Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
Security light Type C at each corner. Typ.
Exterior. wall light with emergency light fixture.
Exterior walls to be prefinished insulated metal panels with painted interior and exterior faces.
5" 24 gauge Kynar finished galvanized steel box gutter.
Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building.
Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping.
Provide clean out at connection to PVC boot. Typ.
10'-0" x10'-0" Heavy duty 625 Stormtite series overhead insulated rolling steel door.
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports. Canopy color to be determined by Architect center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F. Verify height clears light fixture. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
Portable A/C units by CT ANG.
Security light Type C at each corner. Typ.
10' - 0"
Office Finish Floor 0' - 6"
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987 Fax (860)549-2572 www.aztecheng.com
GM2 ASSOCIATES, INC.
115 GLASTONBURY BLVD.
GLASTONBURY, CT
(860) 659-1416
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD file:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
1/4" = 1'-0"
ABP DBA
2017.065 10/03/17
EXTERIOR
ELEVATIONS
ACS_BASE.rvt
A301
1EAST ELEVATION
SCALE: 1/4"=1'-0"
2WEST ELEVATION
SCALE: 1/4"= 0' 2' 5' 8' 10'
0' 2' 5' 8' 10'
"CONCEPT ONLY"
Top of Footing -3' - 0"
A401
Roof 21' - 0"
Top of GWB 8' - 10"
Storage Finish Floor 0' - 0"
6" Concrete filled pipe bollard Typ. Refer to structural dwg's
6" Concrete filled pipe bollard Typ.
Refer to structural dwg's
Light colored standing seam metal roof,by metal building manufacturer.
Card reader access.
5" 24 gauge Kynar finished galvanized steel box gutter.
Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
10'-0" x10'-0" Heavy duty Overhead Door corp. #625 Stormtite series overhead insulated rolling steel door.10'-0" x10'-0" Heavy duty 625 Stormtite series overhead insulated rolling steel door.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building. Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping. Provide clean out at connection to PVC boot. Typ.
6" x 48" Pendant mounted utility light fixture.
Hang from roof structure, provide unistrut as necessary to span. B/Fixtures at 10'-6" A.F.F.
Ducts. Refer to Mechanical dwg's.
Horizontal Plywood sheets.
Cable tray.
Structual columns and footings. Refer to structural dwg's
Structural purlins. Refer to metal building Structual dwg's.
Office Finish Floor 0' - 6"
STORAGE
2A 10
First Floor 0' - 0"
Top of Footing -3' - 0"
A401
Roof 21' - 0"
Top of GWB 8' - 10"
8'
9"
Exterior walls to be prefinished insulated metal panels with painted interior and exterior faces.
Light colored standing seam metal roof, by metal building manufacturer.
Security light Type C at each corner. Typ.
5" 24 gauge Kynar finished galvanized steel box gutter.
Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant. Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
3" x 4" 22 gauge Kynar finished galvanized steel plain square downsprout typical at each corner of building. Provide all elbows and accessories as necessary and tie down spout into perimeter storm drain piping. Provide clean out at connection to PVC boot. Typ.
6" x 48" Pendant mounted utility light fixture. Typ.
Ducts. Refer to Mechanical dwg's.
GWB wall 8'-10" high A.F.F.
Duct. Refer to Mechanical dwg's.
Structual columns and footings. Refer to structural dwg's
Structural purlins. Refer to metal building Structual dwg's.
Furniture to be provided by CT ANG.
Office Finish Floor
0' - 6"
OFFICE
1A
6" high computer access floor, typical throughout office.
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987 Fax (860)549-2572 www.aztecheng.com
GM2 ASSOCIATES, INC.
115 GLASTONBURY BLVD.
GLASTONBURY, CT
(860) 659-1416
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD file:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
1/4" = 1'-0"
ABP DBA
2017.065 10/03/17
BUILDING SECTIONS
ACS_BASE.rvt
A400
1BUILDING SECTION 1
SCALE: 1/4"=1'-0" 0' 2' 5' 8' 10'
2BUILDING SECTION 3
SCALE: 1/4"=1'-0" 0' 2' 5' 8' 10'
"CONCEPT ONLY"
First Floor 0' - 0"
Top of Footing -3' - 0"
A400
A400
Roof 21' - 0"
Top of GWB 8' - 10"
Storage Finish Floor 0' - 0"
Access Floor 0' - 6"
Light colored standing seam metal roof, by metal building manufacturer.
Security light at each corner. Typ.
6" x 48" Pendant mounted utility light. Typ.
Ducts. Refer to Mechanical dwg's.
GWB wall 8'-10" high A.F.F.
B/Duct AT 14' A.F.F. Refer to Mechanical dwg's.
Structual columns and footings. Refer to structural dwg's
Structural purlins. Refer to metal building Structual dwg's.
Furniture to be provided by CT ANG.
Ladder tray to cable tray above. Cable tray bottom at 10'-6" A.F.F.
Global Building Products single color, Kynar finished 24 gauge heavy duty door canopy with supports.
Canopy color to be determined by Architect center canopy above door, lowest projection of canopy shall be 8'-0" A.F.F. Verify height clears light fixture.
Connect canopy gutter to perimeter storm drain with appropiate size 22 gauge Kynar finished galvanized steel plain square down spouts, typ.
Computer racks.
6" Concrete filled pipe bollard Typ.
See structural dwg's
10'-0" x10'-0" Heavy duty Overhead Door corp. #625 Stormtite series overhead insulated rolling steel door.
Office Finish Floor 0' - 6"
6" x 48" Pendant mounted utility light, bottom @ 10'-6" A.F.F. Typ.
STORAGE
2A
OFFICE
1A
6" high computer access floor, typical throughout office.
3'
6"
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987 Fax (860)549-2572 www.aztecheng.com
GM2 ASSOCIATES, INC.
115 GLASTONBURY BLVD.
GLASTONBURY, CT
(860) 659-1416
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD file:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
1/4" = 1'-0"
ABP DBA
2017.065 10/03/17
BUILDING SECTIONS
ACS_BASE.rvt
A401
1BUILDING SECTION
SCALE: 1/4"=1'-0" 0' 2' 5' 8' 10'
"CONCEPT ONLY"
Top of Footing -3' - 0"
Roof 21' - 0"
Top of GWB 8' - 10"
Office Finish Floor 0' - 6"
1" Rigid Insulation w/45 ° chamfer @ top (Cont.).
Volclay Waterstop Concrete footing. See Structural dwg's.
Tate CC1250 Concore panel Access floor system w/ 6" FFH bolted stringer support system. 20 Cutouts for power/data.
Refer to specifications.
Concrete slab-on-grade. Refer to structural dwg's.
4" Processed aggregate base.
16" Controlled fill.
10 Mil polyethylene vapor barrier.
Exterior walls to be prefinished metal panels with painted interior and exterior faces. By metal building manufacturer.
Light colored standing seam metal roof, by metal building manufacturer.
1 layer 5/8" GWB on office side of wall, typ. Fasten GWB to studs with 1-1/4" long type 'W' drywall screws at 12"O.C. in the fields and 8" O.C. at edges.
Insulation by metal building manufacturer.
6 inch 33 mil light gauge steel studs spaced @ a max of 24" O.C.
3 5/8" (33 mil.) flexible metal runners, typical at top and bottom of wall.
4" Vinyl cove base unless noted otherwise.
8" Structural wall girt. Refer to metal building structural dwg's
1'
0"
2' - 0"
Concrete column and footing beyond.
See Structural dwg's
Grade
A600
Roof insulation by metal building manufacturer.
First Floor 0' - 0"
Top of Footing -3' - 0"
Roof 21' - 0"
Top of GWB 8' - 10"
6-3/8" Crushed stone
1" Rigid Insulation w/45 ° chamfer @ top (Cont.).
Volclay Waterstop
2'-0" x 1'-0" Concrete footing.
See Structural dwg's.
Rigid frame column. Refer to metal building structural dwg's
Concrete slab-on-grade. Refer to structural dwg's.
4" Processed aggregate base.
16" Controlled fill.
10 Mil polyethylene vapor barrier.
Exterior walls to be prefinished metal panels with painted interior and exterior faces. By metal building manufacturer.
Wall type 2C @ Equipment area on north, east, west perimeter. Wall height to be 8'-9" A.F.F.
Light colored standing seam metal roof, by metal building manufacturer.
EQUIPMEN EXTERIOR
Seal top of wall to deck with continuous bead of acoustic sealant, Typ.
Hold top of each stud down from deck 1/2" OR provide dual top track to allow for deck deflection.
5'
Office Finish Floor 0' - 6"
Grade
Roof insulation by metal building manufacturer.
Aztech Engineers, Inc.
901 Wethersfield Ave.
Hartford, Ct. 06114
INC.ZTECH ENGINEERS,
Phone (860)548-9987 Fax (860)549-2572 www.aztecheng.com
GM2 ASSOCIATES, INC.
115 GLASTONBURY BLVD.
GLASTONBURY, CT
(860) 659-1416
Revisions:
Project Number:
Scale:
Drawn By:
Issue Date:
CAD file:
Checked By:
Title:
MAIER design group, llc.
architecture & interiors
100 Wells Street, Suite 2i, Hartford, CT 06103 Tel: 860.293.0093 / Fax: 860.293.0094
CONNECTICUT ANG
BOSTON POST ROAD
ORANGE, CT 06477
ORANGE
AIR
NATIONAL
GUARD
STATION
3/4" = 1'-0"
ABP DBA
2017.065 10/03/17
WALL SECTIONS
ACS_BASE.rvt
A402
1WALL SECTION
SCALE: 3/4"=1'-0" 0' 2' 5' 8' 10'2WALL SECTION
SCALE: 3/4"=1'-0" 0' 2' 5' 8' 10'
"CONCEPT ONLY"
Top of Footing -3' - 0"
Top of GWB 8' - 10"
1' - 2"
1" Rigid Insulation w/45 ° chamfer @ top (Cont.).
1'
3"
5' - 6"
0' - 8"
6-3/8" Crushed stone
Volclay Waterstop 4'-0" x 5'-6" x 15" concrete footing @ columns A/2, A/3, C/2 & C/3. See Structural dwg's.
Tate CC1250 Concore panel Access floor system w/ 6" FFH bolted stringer support system. 20 Cutouts for power/data.
Refer to specifications.
Rigid frame column. Refer to metal building structural dwg's
Concrete slab-on-grade. Refer to structural dwg's.
4" Processed aggregate base.
16" Controlled fill.
10 Mil polyethylene vapor barrier.
Exterior walls to be prefinished metal panels with painted interior and exterior faces. By metal building manufacturer.
Wall type @ Office area on south, east, west perimeter. Wall height to be 8'-10" A.F.F.
Roof purlins. Refer to metal building structural dwg's
3'
0" 5'
9"
1 layer 5/8" GWB on office side of wall, typ. Fasten GWB to studs with 1-1/4" long type 'W' drywall screws at 12"O.C. in the fields and 8" O.C. at edges.
6 inch 33 mil light gauge steel studs spaced @ a max of 24" O.C.
Metal floor track set on PT sill, typical.
4" Vinyl cove base unless noted otherwise.
8" Structural wall girt. Refer to metal building structural dwg's
5" 24 gauge Kynar finished galvanized steel box gutter. Provide one expansion joint at center of building. Fasten to fascia with concealed twist strap hangers 24" O.C. Seal all joints with non curing butyl sealant.
A600
Office Finish Floor 0' - 6"
Light colored standing seam metal roof, by metal building manufacturer.
First Floor 0' - 0"
Top of Footing -3' - 0"
Roof 21' - 0"
Top of GWB 8' - 10"
EQUIPMENTOFFICE
0'
4"
0'
6"
Cast-in-place 6" Concrete curb.
See Structural drawings.
Tate CC1250 Concore panel Access floor system w/ 6" FFH bolted stringer support system. 20 Cutouts for power/data. Refer to specifications.
4" Processed aggregate base.
16" Controlled fill.
0'
6"
10 Mil polyethylene vapor barrier.
Concrete slab-on-grade.
Seal top of wall to deck with continuous bead of acoustic sealant, Typ.
Provide dual top track to allow for deck deflection.
Office Finish Floor 0' - 6"
Metal floor track direct to top of…