Vendor Questions and Government Responses.docx

DOCX document 13 KB Posted

Attached to
Procurement of 37 each Link-16 Mobile Racks - Amendment 6 Federal contract opportunity
Solicitation number
FA8224-20-Q-RCK2
Issued by
Department of the Air Force Materiel Command Air Force Sustainment Center

About this file

This solicitation requests offers for the procurement of 37 Link-16 Mobile Racks. Technical capability, price, and past performance will be evaluated. Offers are due by September 15, 2020 and shall be submitted electronically to the contracting officer. The awardee will have 52 weeks to deliver the mobile racks after receipt of order. The solicitation incorporates standard commercial item clauses and provisions. The Department of the Air Force Materiel Command Air Force Sustainment Center is the contracting agency.

View the file

Other files for this federal contract opportunity

Other files attached to Procurement of 37 each Link-16 Mobile Racks - Amendment 6, newest first.
File Type Posted
Vendor Questions and Government Responses - Revised.docx DOCX document
Vendor Questions and Government Responses 5.docx DOCX document
Vendor Questions and Government Responses 4.docx DOCX document
Vendor Questions and Government Responses 3.docx DOCX document
Combined Synopsis Solicitation - Link-16 Mobile Racks - FA8224-20-R-RCK2 Amendment 2.docx DOCX document
Vendor Questions and Government Responses 2.docx DOCX document
PURCHASE DESCRIPTION -Link 16 Mobile Rack.doc DOC document
Combined Synopsis Solicitation - Link-16 Mobile Racks - FA8224-20-R-RCK2.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. What devices and/or systems are being powered?

1. What will the UPS be powered by (generator, grid, vehicle etc.)? Military Prime power and commercial source.

1. Where will the UPS be deployed? (office, shelter, shipboard, transit case, factory etc.) TRANSIT CASE

1. Is there a height and or mechanical size requirements for the UPS? Comply with MIL-STD-1472

1. How much power (in Watts) does your system require? 120V * 20A = 2,400 W minimum

e. Do you have a specific run-time requirement? AT LEAST 10 MINUTES BACKUP TIME

2. Are there any MIL-STD specifications and/or certification(s) the unit needs to meet or be tested to?

Safety Test Standart EN 60950-1 Compliant, Type III Mobility per SAE-AS8090, MIL-STD-1472 compliant

3. What is the Input Voltage level? Into the UPS is 120V +-10% with 60Hz +- 5%. 20A What is the Output Voltage level? +140 VDC and -140 VDC

4. How many AC Outputs are required? 6 How many DC Outputs are required? 2

5. When do they need the UPS’s in hand? Need to come as a KIT to support the MIDS JTRS terminal How many do you need? 37ea.

6. Are any rack mounting hardware required? yes If so, how deep are the transit cases? 6in depth for the covers. Rack is 24in Does the customer required fixed or sliding rail kits? fixed

7. Are any cables required? (If so please specify) all supporting cables

8. What battery type is required? LFP battery type required

9. Is SNMP required? YES

10. Are there any other special requirements? FUNGUS RESISTANT; TEMPEST; NSTISSAM

File details come from the government source that posted it. Updated .