Vendor Questions and Government Responses 3.docx

DOCX document 13 KB Posted

Attached to
Procurement of 37 each Link-16 Mobile Racks - Amendment 6 Federal contract opportunity
Solicitation number
FA8224-20-Q-RCK2
Issued by
Department of the Air Force Materiel Command Air Force Sustainment Center

About this file

This solicitation requests offers for the procurement of 37 Link-16 MIDS JTRS Mobile Racks. Offers are due by September 15, 2020 and shall be submitted electronically to David Padgett at the listed email address. Award will be made to the offeror representing the best value based on technical capability, price, and past performance using the Past Performance Information Retrieval System. The period of performance is 52 weeks after receipt of order. The required items and specifications are detailed in the attached purchase description. The contracting agency is the Department of the Air Force Materiel Command Air Force Sustainment Center.

View the file

Other files for this federal contract opportunity

Other files attached to Procurement of 37 each Link-16 Mobile Racks - Amendment 6, newest first.
File Type Posted
Vendor Questions and Government Responses - Revised.docx DOCX document
Vendor Questions and Government Responses 5.docx DOCX document
Vendor Questions and Government Responses 4.docx DOCX document
Combined Synopsis Solicitation - Link-16 Mobile Racks - FA8224-20-R-RCK2 Amendment 2.docx DOCX document
Vendor Questions and Government Responses 2.docx DOCX document
Vendor Questions and Government Responses.docx DOCX document
PURCHASE DESCRIPTION -Link 16 Mobile Rack.doc DOC document
Combined Synopsis Solicitation - Link-16 Mobile Racks - FA8224-20-R-RCK2.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. Are they trying to create a 280 VDC (140 to -140) to run this voltage directly into a set vicor bricks? If that is the case, what VDC are they trying to get out of the vicors?

The UPS input must operate from a 120VAC power source. The output must nominally be 120VAC, pure sine wave, when in battery mode. The equipment powered from the UPS requires 120VAC power.

2. Please confirm that (2) DC Outputs are required.

DC power outputs are not required from the UPS. If a system with DC output is quoted at no extra cost, this is acceptable. (Voltage/current ratings should be identified.)