Rev - 0.pdf
PDF 91 KB Posted
- Solicitation number
- FA820126R0015
About this file
This document is a preliminary field redlines SCADA (Supervisory Control and Data Acquisition) input/output (I/O) point list for the Hill Air Force Base Integrated Water Treatment Plant (IWTP).
The document provides a detailed technical specification of all digital input (DI), digital output (DO), analog input (AI), and analog output (AO) points configured in the PLC control system. It lists approximately 200+ I/O points organized by function, including flow switches, level switches, handstations for manual control, pump motors, mixer controls, solenoid valve commands, and sensor inputs for pH, oxidation-reduction potential (ORP), temperature, and flow measurements. Each entry specifies the tag identification, loop letter designation, I/O module type (1756-IA32, 1756-IB32, 1756-OA16, 1756-OB32, 1756-IF16, 1756-OF8), rack and slot locations, field device connections, signal type, operating voltage (120VAC or 24VDC), and panel terminal wiring designations. The I/O points support control and monitoring of treatment tanks (T-1 through T-10), chemical injection systems (SO2, polymer), transfer and recirculation pumps, sludge handling, and various process instrumentation throughout the water treatment facility. This document appears to be an internal technical reference for PLC programming and field wiring configuration, marked as preliminary and subject to redline revisions.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hill AFB IWTP SCADA
Ta g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State Comments
FI ‐ 3‐1 AC DI 1756‐IA32 0 ‐ : 0 / 00 1 ‐ 1 ‐ 0 T1 ‐ A1 T1 ‐ B1 CHROME REACTION FLOW SWITCH FS‐3‐1 120VAC PLC
FI ‐ 4‐1 AC DI 1756‐IA32 0 ‐ : 0 / 01 1 ‐ 1 ‐ 1 T1 ‐ A2 T1 ‐ B2 FLOW SWITCH FS‐4‐1 120VAC PLC
FSL 10 1A AC DI 1756‐IA32 0 ‐ : 0 / 02 1 ‐ 1 ‐ 2 PLC
FSL 10 1B AC DI 1756‐IA32 0 ‐ : 0 / 03 1 ‐ 1 ‐ 3 PLC
FSL 5 1 AC DI 1756‐IA32 0 ‐ : 0 / 04 1 ‐ 1 ‐ 4 PLC
Panel Terminals
FSL 5 2 AC DI 1756‐IA32 0 ‐ : 0 / 05 1 ‐ 1 ‐ 5 PLC
HS ‐ 1‐5 AUTO AC DI 1756‐IA32 0 ‐ : 0 / 06 1 ‐ 1 ‐ 6 T1 ‐ A7 T1 ‐ B7 HANDSTATION AUTO T‐5 VALVE HS‐1‐5A 120VAC PLC AUTO POS Relay #1
AC DI 1756‐IA32 0 ‐ : 0 / 07 1 ‐ 1 ‐ 7 120VAC PLC
HS ‐ 3‐1 AUTO AC DI 1756‐IA32 0 ‐ : 0 / 10 1 ‐ 1 ‐ 8 T1 ‐ A9 T1 ‐ B9 HANDSTATION AUTO T‐3 INFL HS‐3‐1A 120VAC PLC AUTO POS Relay #3
AC DI 1756‐IA32 0 ‐ : 0 / 11 1 ‐ 1 ‐ 9 120VAC PLC
HS ‐ 3‐2 AUTO AC DI 1756‐IA32 0 ‐ : 0 / 12 1 ‐ 1 ‐ 10 T1 ‐ A11 T1 ‐ B11 HANDSTATION AUTO T‐3 EFFL HS‐3‐2A 120VAC PLC AUTO POS Relay #4
AC DI 1756‐IA32 0 ‐ : 0 / 13 1 ‐ 1 ‐ 11 120VAC PLC
HS ‐ 4‐1 AUTO AC DI 1756‐IA32 0 ‐ : 0 / 14 1 ‐ 1 ‐ 12 T1 ‐ A13 T1 ‐ B13 HANDSTATION AUTO T‐4 INFL HS‐4‐1A 120VAC PLC AUTO POS Relay #5
AC DI 1756‐IA32 0 ‐ : 0 / 15 1 ‐ 1 ‐ 13 120VAC PLC
HS ‐ 4‐2 AUTO AC DI 1756‐IA32 0 ‐ : 0 / 16 1 ‐ 1 ‐ 14 T1 ‐ A15 T1 ‐ B15 HANDSTATION AUTO T‐4 EFFL HS‐4‐2A 120VAC PLC AUTO POS Relay #6
AC DI 1756‐IA32 0 ‐ : 0 / 17 1 ‐ 1 ‐ 15 120VAC PLC
HS ‐ M03A AUTO AC DI 1756‐IA32 0 ‐ : 1 / 00 1 ‐ 1 ‐ 16 T1 ‐ A17 T1 ‐ B17 HANDSTATION AUTO MIXER T‐3 HS‐M03AA 120VAC PLC AUTO POS
HS ‐ M03A HAND AC DI 1756‐IA32 0 ‐ : 1 / 01 1 ‐ 1 ‐ 17 T1 ‐ B18 HANDSTATION HAND MIXER T‐3 HS‐M03AH 120VAC PLC HAND POS L1 ‐ Same as Auto
HS ‐ M03B AUTO AC DI 1756‐IA32 0 ‐ : 1 / 02 1 ‐ 1 ‐ 18 T1 ‐ A19 T1 ‐ B19 HANDSTATION AUTO MIXER T‐3 HS‐M03BA 120VAC PLC AUTO POS
HS ‐ M03B HAND AC DI 1756‐IA32 0 ‐ : 1 / 03 1 ‐ 1 ‐ 19 T1 ‐ 20B HANDSTATION HAND MIXER T‐3 HS‐M03BH 120VAC PLC HAND POS L1 ‐ Same as Auto
Bowen Collins & Associates Tetra Tech Preliminary Field Redlines Page 1 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
HS ‐ 04AB AUTO AC DI 1756‐IA32 0 ‐ : 1 / 04 1 ‐ 1 ‐ 20 T1 ‐ A21 T1 ‐ B21 HANDSTATION AUTO MIXER T‐4 HS‐04BA 120VAC PLC AUTO POS
HS ‐ 04B HAND AC DI 1756‐IA32 0 ‐ : 1 / 05 1 ‐ 1 ‐ 21 T1 ‐ B22 HANDSTATION HAND MIXER T‐4 HS‐04BH 120VAC PLC HAND POS L1 ‐ Same as Auto
HS ‐ 04B AUTO AC DI 1756‐IA32 0 ‐ : 1 / 06 1 ‐ 1 ‐ 22 T1 ‐ A23 T1 ‐ B23 HANDSTATION AUTO MIXER T‐4 HS‐04AA 120VAC PLC AUTO POS
HS ‐ 04B HAND AC DI 1756‐IA32 0 ‐ : 1 / 07 1 ‐ 1 ‐ 23 T1 ‐ B24 HANDSTATION HAND MIXER T‐4 HS‐04AH 120VAC PLC HAND POS L1 ‐ Same as Auto
HS ‐ 06 AUTO AC DI 1756‐IA32 0 ‐ : 1 / 10 1 ‐ 1 ‐ 24 T1 ‐ A25 T1 ‐ B25 HANDSTATION AUTO MIXER T‐6 HS‐06A 120VAC PLC AUTO POS
HS ‐ 06 HAND AC DI
1756‐IA32
0 ‐ : 1 / 11 1 ‐ 1 ‐ 25 T1 ‐ B26 HANDSTATION HAND MIXER T‐6 HS‐06H 120VAC PLC HAND POS L1 ‐ Same as Auto
HS ‐ M02A AUTO AC DI 1756‐IA32 0 ‐ : 1 / 12 1 ‐ 1 ‐ 26 T1 ‐ A27 T1 ‐ B27 HANDSTATION AUTO HS‐M02AA 120VAC PLC AUTO POS
HS ‐ M02A HAND AC DI 1756‐IA32 0 ‐ : 1 / 13 1 ‐ 1 ‐ 27 T1 ‐ B28 HANDSTATION HAND HS‐M02AH 120VAC PLC HAND POS L1 ‐ Same as Auto
HS ‐ M07D AUTO AC DI 1756‐IA32 0 ‐ : 1 / 14 1 ‐ 1 ‐ 28 T1 ‐ A29 T1 ‐ B29 HANDSTATION AUTO MIXER T‐7 HS‐M07DA 120VAC PLC AUTO POS
HS
HS
M07 M07
DH
DH
AC DI 1756‐IA32 0 ‐ : 1 / 15 1 ‐ 1 ‐ 29 T1 ‐ B30 120VAC PLC L1 ‐ Same as Auto
Hs M07 BA AC DI 1756‐IA32 0 ‐ : 1 / 16 1 ‐ 1 ‐ 30 T1 ‐ A31 T1 ‐ B31 120VAC PLC
HS M07 BH AC DI 1756‐IA32 0 ‐ : 1 / 17 1 ‐ 1 ‐ 31 T1 ‐ B32 120VAC PLC L1 ‐ Same as Auto
HS ‐ M07B AUTO AC DI 1756‐IA32 0 ‐ : 2 / 00 1 ‐ 2 ‐ 0 CLARIFIER ‐ RUNNING STATUS 120VAC PLC RUNNING
HS ‐ M07B HAND AC DI 1756‐IA32 0 ‐ : 2 / 01 1 ‐ 2 ‐ 1 FLASH MIXER ‐ RUNNING STATUS 120VAC PLC RUNNING
HS
HS
M M
10C 10A
AC DI 1756‐IA32 0 ‐ : 2 / 02 1 ‐ 2 ‐ 2 120VAC PLC
HS ‐ M 10H AC DI 1756‐IA32 0 ‐ : 2 / 03 1 ‐ 2 ‐ 3 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 2 / 04 1 ‐ 2 ‐ 4 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 2 / 05 1 ‐ 2 ‐ 5 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 2 / 06 1 ‐ 2 ‐ 6 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 2 / 07 1 ‐ 2 ‐ 7 120VAC PLC
Tetra Tech Preliminary Field Redlines Page 2 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
HS ‐ P03 AUTO AC DI 1756‐IA32 0 ‐ : 2 / 10 1 ‐ 2 ‐ 8 T2 ‐ A9 T2 ‐ B9 HANDSTATION AUTO PROCESS PMP HS‐P03A 120VAC PLC AUTO POS
HS ‐ P03 HAND AC DI 1756‐IA32 0 ‐ : 2 / 11 1 ‐ 2 ‐ 9 T2 ‐ No L T3 ‐ B10
HANDSTATION HAND PROCESS
PMP
HS‐P03H 120VAC PLC HAND POS
HS ‐ P04 AUTO AC DI 1756‐IA32 0 ‐ : 2 / 12 1 ‐ 2 ‐ 10 T2 ‐ A11 T2 ‐ B11 HANDSTATION AUTO PROCESS PMP HS‐P04A 120VAC PLC AUTO POS
HS ‐ P04 HAND AC DI 1756‐IA32 0 ‐ : 2 / 13 1 ‐ 2 ‐ 11 T2 ‐ No L T2 ‐ B12
HANDSTATION HAND PROCESS
PMP
HS‐P04H 120VAC PLC HAND POS
HS ‐ P05A AUTO AC DI 1756‐IA32 0 ‐ : 2 / 14 1 ‐ 2 ‐ 12 T2 ‐ A13 T2 ‐ B13 HANDSTATION AUTO T‐5 RECIRC HS‐P05AA 120VAC PLC AUTO POS
HS P05 AH AC DI 1756‐IA32 0 ‐ : 2 / 15 1 ‐ 2 ‐ 13 120VAC PLC
HS ‐ P05B AUTO AC DI 1756‐IA32 0 ‐ : 2 / 16 1 ‐ 2 ‐ 14 T2 A‐15 T2 ‐ B15 HANDSTATION AUTO T‐5 RECIRC HS‐P05BA 120VAC PLC AUTO POS
HS P0? BH AC DI 1756‐IA32 0 ‐ : 2 / 17 1 ‐ 2 ‐ 15 120VAC PLC
HS ‐ P08A AUTO AC DI 1756‐IA32 0 ‐ : 3 / 00 1 ‐ 2 ‐ 16 T2 ‐ A17 T2 ‐ B17
HANDSTATION AUTO SLUDGE PMP
A
HS‐P08AA 120VAC PLC AUTO POS
HS ‐ P08A HAND AC DI 1756‐IA32 0 ‐ : 3 / 01 1 ‐ 2 ‐ 17 T2 ‐ No L T2 ‐ B18
HANDSTATION HAND SLUDGE PMP
A
HS‐P08AH 120VAC PLC HAND POS
AC DI 1756‐IA32 0 ‐ : 3 / 02 1 ‐ 2 ‐ 18 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 3 / 03 1 ‐ 2 ‐ 19 120VAC PLC
HS
HS
P10 P10
AC
AA
AC DI 1756‐IA32 0 ‐ : 3 / 04 1 ‐ 2 ‐ 20 120VAC PLC
HS P10 AH AC DI 1756‐IA32 0 ‐ : 3 / 05 1 ‐ 2 ‐ 21 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 3 / 06 1 ‐ 2 ‐ 22 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 3 / 07 1 ‐ 2 ‐ 23 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 3 / 10 1 ‐ 2 ‐ 24 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 3 / 11 1 ‐ 2 ‐ 25 120VAC PLC
HS
HS
P10 P10
BC
BA
AC DI 1756‐IA32 0 ‐ : 3 / 12 1 ‐ 2 ‐ 26 120VAC PLC
HS P10 BH AC DI 1756‐IA32 0 ‐ : 3 / 13 1 ‐ 2 ‐ 27 120VAC PLC
Tetra Tech Preliminary Field Redlines Page 3 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
HS ‐ P13 AC DI 1756‐IA32 0 ‐ : 3 / 14 1 ‐ 2 ‐ 28 T2 ‐ A29 T2 ‐ B29 HANDSTATION, SUMP PUMP HS‐P13 120VAC PLC
LI ‐ 14 AC DI 1756‐IA32 0 ‐ : 3 / 15 1 ‐ 2 ‐ 29 T2 ‐ A30 T2 ‐ B30 LEVEL SWITCH, SUMP PUMP LS‐14 120VAC PLC
LI ‐ 15 AC DI 1756‐IA32 0 ‐ : 3 / 16 1 ‐ 2 ‐ 30 T2 ‐ A31 T2 ‐ B31 LEVEL SWITCH, SUMP PUMP LS‐15 120VAC PLC
LI ‐ 16 AC DI 1756‐IA32 0 ‐ : 3 / 17 1 ‐ 2 ‐ 31 T2 ‐ A32 T2 ‐ B32 LEVEL SWITCH, SUMP PUMP LS‐16 120VAC PLC
LI ‐ P17 AC DI 1756‐IA32 0 ‐ : 4 / 00 1 ‐ 3 ‐ 0 T3 ‐ A1 T3 ‐ B1 LEVEL SWITCH, SUMP PUMP LS‐P17 120VAC PLC
LI ‐ P18 AC DI 1756‐IA32 0 ‐ : 4 / 01 1 ‐ 3 ‐ 1 T3 ‐ A2 T3 ‐ B2 LEVEL SWITCH, SUMP PUMP LS‐P18 120VAC PLC
YI ‐ 2‐1 A AC DI 1756‐IA32 0 ‐ : 4 / 02 1 ‐ 3 ‐ 2 T3 ‐ No L T3 ‐ B3 STATUS (splice block PLCT‐12) YS‐2‐1A 120VAC PLC
YI ‐ 2‐1 B AC DI 1756‐IA32 0 ‐ : 4 / 03 1 ‐ 3 ‐ 3 T3 ‐ No L T3 ‐ B4 STATUS (splice block PLCT‐12) YS‐2‐1B 120VAC PLC
YS
YS
2‐1 2‐1
AC DI 1756‐IA32 0 ‐ : 4 / 04 1 ‐ 3 ‐ 4 120VAC PLC
YI ‐ 4‐1 0 AC DI 1756‐IA32 0 ‐ : 4 / 05 1 ‐ 3 ‐ 5 T3 ‐ No L T3 ‐ B6 STATUS T‐3 INF OPEN YS‐3‐1A 120VAC PLC
YI ‐ 4‐1 C AC DI 1756‐IA32 0 ‐ : 4 / 06 1 ‐ 3 ‐ 6 T3 ‐ No L T3 ‐ B7 STATUS T‐3 INF CLOSED YS‐3‐1B 120VAC PLC
YI ‐ 3‐2 A AC DI 1756‐IA32 0 ‐ : 4 / 07 1 ‐ 3 ‐ 7 T3 ‐ No L T3 ‐ B8 STATUS T‐3 EFF OPEN YS‐3‐2A 120VAC PLC
YI ‐ 3‐2 B AC DI 1756‐IA32 0 ‐ : 4 / 10 1 ‐ 3 ‐ 8 T3 ‐ No L T3 ‐ B9 STATUS T‐3 EFF CLOSED YS‐3‐2B 120VAC PLC
YI ‐ 4‐1 A AC DI 1756‐IA32 0 ‐ : 4 / 11 1 ‐ 3 ‐ 9 T3 ‐ No L T3 B10 STATUS T‐4 INF OPEN YS‐4‐1A 120VAC PLC
YI ‐ 4‐1 B AC DI 1756‐IA32 0 ‐ : 4 / 12 1 ‐ 3 ‐ 10 T3 ‐ No L T3 ‐ B11 STATUS T‐4 INF CLOSED YS‐4‐1B 120VAC PLC
YI ‐ 3‐1 A AC DI 1756‐IA32 0 ‐ : 4 / 13 1 ‐ 3 ‐ 11 T3 ‐No L T3 ‐ B12 STATUS T‐4 EFF OPEN YS‐4‐2A 120VAC PLC
YI ‐ 3‐1 B AC DI 1756‐IA32 0 ‐ : 4 / 14 1 ‐ 3 ‐ 12 T3 ‐ No L T3 ‐ B13 STATUS T‐4 EFF CLOSED YS‐4‐2B 120VAC PLC
YI ‐ M03 A AC DI 1756‐IA32 0 ‐ : 4 / 15 1 ‐ 3 ‐ 13 T3 ‐ A14 T3 ‐ B14 STATUS T‐3 MIXER ON YS‐M03A 120VAC PLC
YI ‐ M03 B AC DI 1756‐IA32 0 ‐ : 4 / 16 1 ‐ 3 ‐ 14 T3 ‐ A15 T3 ‐ B15 STATUS T‐3 MIXER ON YS‐M03B 120VAC PLC
YI ‐ M04 A AC DI 1756‐IA32 0 ‐ : 4 / 17 1 ‐ 3 ‐ 15 T3 ‐ A16 T3 ‐ B16 STATUS T‐4 MIXER ON YS‐M04A 120VAC PLC
Tetra Tech Preliminary Field Redlines Page 4 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
YI ‐ M04 B AC DI 1756‐IA32 0 ‐ : 5 / 00 1 ‐ 3 ‐ 16 T3 ‐ A17 T3 ‐ B17 STATUS T‐4 MIXER ON YS‐M04B 120VAC PLC
YI ‐ M06 AC DI 1756‐IA32 0 ‐ : 5 / 01 1 ‐ 3 ‐ 17 T‐3 A‐18 T3 ‐ B18 STATUS T‐6 MIXER ON YS‐M06 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 5 / 02 1 ‐ 3 ‐ 18 120VAC PLC
YI ‐ M07 A AC DI 1756‐IA32 0 ‐ : 5 / 03 1 ‐ 3 ‐ 19 T3 ‐ A20 T3 ‐ B20 STATUS T‐7 MIXER ON YS‐M07A 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 5 / 04 1 ‐ 3 ‐ 20 120VAC PLC
YI ‐ M07 B AC DI 1756‐IA32 0 ‐ : 5 / 05 1 ‐ 3 ‐ 21 T3 A‐22 T‐3 B22 STATUS T‐7 MIXER ON YS‐M07B 120VAC PLC
YI ‐ M08 A AC DI 1756‐IA32 0 ‐ : 5 / 06 1 ‐ 3 ‐ 22 T3 ‐ A23 T3 ‐ B23 STATUS FLASH MIX ON YS‐M08A 120VAC PLC
YI ‐ M08 B AC DI 1756‐IA32 0 ‐ : 5 / 07 1 ‐ 3 ‐ 23 T3 ‐ A24 T3 ‐ B24 STATUS FLOC MIX ON YS‐M08B 120VAC PLC
YS 11‐10
AC DI 1756‐IA32 0 ‐ : 5 / 10 1 ‐ 3 ‐ 24 120VAC PLC
YI ‐ P03 F AC DI 1756‐IA32 0 ‐ : 5 / 11 1 ‐ 3 ‐ 25 T3 ‐ A26 T3 ‐ B26 FAULT STATUS VFD PROCESS YS‐P03F 120VAC PLC
YI ‐ P03 R AC DI 1756‐IA32 0 ‐ : 5 / 12 1 ‐ 3 ‐ 26 T3 ‐ A27 T3 ‐B27
RUNNING STATUS PROCESS PMP
ON
YS‐P03R 120VAC PLC RUNNING
ON
YI ‐ P04 F AC DI 1756‐IA32 0 ‐ : 5 / 13 1 ‐ 3 ‐ 27 T3 ‐ A28 T3 ‐ B28 FAULT STATUS VFD PROCESS YS‐P04F 120VAC PLC
YI ‐ P04 R AC DI 1756‐IA32 0 ‐ : 5 / 14 1 ‐ 3 ‐ 28 T3 ‐ A29 T3 ‐ B29
RUNNING STATUS PROCESS PMP
ON
YS‐P04R 120VAC PLC RUNNING
YI ‐ P05 A AC DI 1756‐IA32 0 ‐ : 5 / 15 1 ‐ 3 ‐ 29 T3 ‐ A30 T3 ‐ B30 STATUS T‐5 TRANS ON YS‐P05A 120VAC PLC
YI ‐ P05 B AC DI 1756‐IA32 0 ‐ : 5 / 16 1 ‐ 3 ‐ 30 T3 ‐ A31 T3 ‐ B31 STATUS T‐5 TRANS ON YS‐P05B 120VAC PLC
YS P10 A
AC DI 1756‐IA32 0 ‐ : 5 / 17 1 ‐ 3 ‐ 31 120VAC PLC
YS P10 B
AC DI 1756‐IA32 0 ‐ : 6 / 00 1 ‐ 4 ‐ 0 120VAC PLC
YI ‐ P13 AC DI 1756‐IA32 0 ‐ : 6 / 01 1 ‐ 4 ‐ 1 T4 ‐ A2 T4 ‐ B2
STATUS SUMP PUMP ON
(On splice block) PLC T‐12
YS‐P13 120VAC PLC
YI ‐ P14 AC DI 1756‐IA32 0 ‐ : 6 / 02 1 ‐ 4 ‐ 2 T4 ‐ A3 T4 ‐ B3
STATUS SUMP PUMP ON
(On splice block) PLC T‐12
YS‐P14 120VAC PLC
YI ‐ P15 AC DI 1756‐IA32 0 ‐ : 6 / 03 1 ‐ 4 ‐ 3 T4 ‐ A4 T4 ‐ B4 STATUS SUMP PUMP ON YS‐P15 120VAC PLC
Tetra Tech Preliminary Field Redlines Page 5 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
YI ‐ P16 AC DI 1756‐IA32 0 ‐ : 6 / 04 1 ‐ 4 ‐ 4 T4 ‐ A5 T4 ‐ B5 STATUS SUMP PUMP ON YS‐P16 120VAC PLC
YI ‐ P17 AC DI 1756‐IA32 0 ‐ : 6 / 05 1 ‐ 4 ‐ 5 T4 ‐ A6 T4 ‐ B6
STATUS SUMP PUMP ON
(On splice block) PLC T‐12
YS‐P17 120VAC PLC
YI ‐ P18 AC DI 1756‐IA32 0 ‐ : 6 / 06 1 ‐ 4 ‐ 6 T4 ‐ A7 T4 ‐ B7 STATUS SUMP PUMP ON YS‐P18 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 6 / 07 1 ‐ 4 ‐ 7 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 6 / 10 1 ‐ 4 ‐ 8 120VAC PLC
YS T09 A
AC DI 1756‐IA32 0 ‐ : 6 / 11 1 ‐ 4 ‐ 9 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 6 / 12 1 ‐ 4 ‐ 10 120VAC PLC
YS 11E‐1
AC DI 1756‐IA32 0 ‐ : 6 / 13 1 ‐ 4 ‐ 11 120VAC PLC
YI ‐ P01 A AC DI 1756‐IA32 0 ‐ : 6 / 14 1 ‐ 4 ‐ 12 T4 ‐ A13 T4 ‐ B13 STATUS T‐1 PUMP1 YS‐P01A 120VAC PLC
YI ‐ P01 B AC DI 1756‐IA32 0 ‐ : 6 / 15 1 ‐ 4 ‐ 13 T4 ‐ A14 T4 ‐ B14 STATUS T‐1 PUMP2 YS‐P01B 120VAC PLC
YI ‐ P01 C AC DI 1756‐IA32 0 ‐ : 6 / 16 1 ‐ 4 ‐ 14 T4 ‐ A15 T4 ‐ B15 STATUS T‐1 PUMP3 YS‐P01C 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 6 / 17 1 ‐ 4 ‐ 15 120VAC PLC
FI ‐ 6‐1 AC DI 1756‐IA32 0 ‐ : 7 / 00 1 ‐ 4 ‐ 16 T4 ‐ A17 T4 ‐ B17 FLOW SWITCH FS‐6‐1 120VAC PLC JUMPER ‐ ALWAYS ON
FI ‐ 6‐2 AC DI 1756‐IA32 0 ‐ : 7 / 01 1 ‐ 4 ‐ 17 T4 ‐ A18 T4 ‐ B18 FLOW SWITCH FS‐6‐2 120VAC PLC
YI ‐ P06 A AC DI 1756‐IA32 0 ‐ : 7 / 02 1 ‐ 4 ‐ 18 T4 ‐ A19 T4 ‐ B19 STATUS S02 A ON YS‐P06A 120VAC PLC
YI ‐ P06 B AC DI 1756‐IA32 0 ‐ : 7 / 03 1 ‐ 4 ‐ 19 T4 ‐ A20 T‐4 B‐20 STATUS S02 B ON YS‐P06B 120VAC PLC
HS ‐ P06A AUTO AC DI 1756‐IA32 0 ‐ : 7 / 04 1 ‐ 4 ‐ 20 T4 ‐ A21 T4 ‐ B21 HANDSTATION AUTO S02 A HS‐P06AA 120VAC PLC AUTO POS
HS ‐ P06A HAND AC DI 1756‐IA32 0 ‐ : 7 / 05 1 ‐ 4 ‐ 21 T4 ‐ A22 T4 ‐ B22 HANDSTATION HAND S02 A HS‐P06AH 120VAC PLC HAND POS
HS ‐ P06B AUTO AC DI 1756‐IA32 0 ‐ : 7 / 06 1 ‐ 4 ‐ 22 T4 ‐ A23 T4 ‐ B23 HANDSTATION AUTO S02 B HS‐P06BA 120VAC PLC AUTO POS
HS ‐ P06B HAND AC DI 1756‐IA32 0 ‐ : 7 / 07 1 ‐ 4 ‐ 23 T4 ‐ A24 T4 ‐ B24 HANDSTATION HAND S02 B HS‐P06BH 120VAC PLC HAND POS
Tetra Tech Preliminary Field Redlines Page 6 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
HA ‐ 1‐5A AUTO AC DI 1756‐IA32 0 ‐ : 7 / 10 1 ‐ 4 ‐ 24 T4 ‐ A25 T4 ‐ B25 HANDSTATION AUTO HS‐1‐5AA 120VAC PLC AUTO POS Relay #2
AC DI 1756‐IA32 0 ‐ : 7 / 11 1 ‐ 4 ‐ 25 120VAC PLC
YI ‐ 2‐1A C AC DI 1756‐IA32 0 ‐ : 7 / 12 1 ‐ 4 ‐ 26 T4 ‐ No L T4 ‐ B27 CLOSED STATUS, T‐5 DIVERSION YS‐2‐1AC 120VAC PLC CLOSED POS
YI ‐ 2‐1A O AC DI 1756‐IA32 0 ‐ : 7 / 13 1 ‐ 4 ‐ 27 T4 ‐ No L T4 ‐ B28 OPEN STATUS, T‐5 DIVERSION YS‐2‐1AO 120VAC PLC OPEN POS
AC DI 1756‐IA32 0 ‐ : 7 / 14 1 ‐ 4 ‐ 28 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 7 / 15 1 ‐ 4 ‐ 29 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 7 / 16 1 ‐ 4 ‐ 30 120VAC PLC
AC DI 1756‐IA32 0 ‐ : 7 / 17 1 ‐ 4 ‐ 31 120VAC PLC
HS P11 AA
DC DI 1756‐IB32 1 ‐ : 0 / 00 1 ‐ 5 ‐ 0 24VDC PLC
HS P11 AH
DC DI 1756‐IB32 1 ‐ : 0 / 01 1 ‐ 5 ‐ 1 24VDC PLC
HS P11 BA
DC DI 1756‐IB32 1 ‐ : 0 / 02 1 ‐ 5 ‐ 2 24VDC PLC
HS P11 BA
HS P11
BA
DC DI 1756‐IB32 1 ‐ : 0 / 03 1 ‐ 5 ‐ 3 24VDC PLC
YS P11 A
DC DI 1756‐IB32 1 ‐ : 0 / 04 1 ‐ 5 ‐ 4 24VDC PLC
YS P11 B
DC DI 1756‐IB32 1 ‐ : 0 / 05 1 ‐ 5 ‐ 5 24VDC PLC
SP P02 AA
DC DI 1756‐IB32 1 ‐ : 0 / 06 1 ‐ 5 ‐ 6 24VDC PLC
SP P02 AH
DC DI 1756‐IB32 1 ‐ : 0 / 07 1 ‐ 5 ‐ 7 24VDC PLC
SP P02 BA
DC DI 1756‐IB32 1 ‐ : 0 / 10 1 ‐ 5 ‐ 8 24VDC PLC
SP PO2 BH
DC DI 1756‐IB32 1 ‐ : 0 / 11 1 ‐ 5 ‐ 9 24VDC PLC
SP ‐ P08A AUTO DC DI 1756‐IB32 1 ‐ : 0 / 12 1 ‐ 5 ‐ 10 T5 ‐ A11 T5 ‐ B11 HANDSTATION AUTO SLUDGE A SP‐P08AA 24VDC PLC AUTO POS
SP ‐ P08A HAND DC DI 1756‐IB32 1 ‐ : 0 / 13 1 ‐ 5 ‐ 11 T5 ‐ No L T5 ‐ B12 HANDSTATION HAND SLUDGE A SP‐P08AH 24VDC PLC HAND POS
Tetra Tech Preliminary Field Redlines Page 7 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
SP ‐ P08B AUTO DC DI 1756‐IB32 1 ‐ : 0 / 14 1 ‐ 5 ‐ 12 T5 ‐ A13 T5 ‐ B13 HANDSTATION AUTO SLUDGE B SP‐P08BA 24VDC PLC AUTO POS
SP ‐ P08B HAND DC DI 1756‐IB32 1 ‐ : 0 / 15 1 ‐ 5 ‐ 13 T5 ‐ No L T5 ‐ B14 HANDSTATION HAND SLUDGE B SP‐P08BH 24VDC PLC HAND POS
SP ‐ SO2A LO DC DI 1756‐IB32 1 ‐ : 0 / 16 1 ‐ 5 ‐ 14 T5 ‐ A15 T5 ‐ B15 SO2 LOW LEVEL (A) SP‐SO2LO 24VDC PLC
SP ‐ SO2A HI DC DI 1756‐IB32 1 ‐ : 0 / 17 1 ‐ 5 ‐ 15 T5 ‐ A16 T5 ‐ B16 SO2 HIGH LEVEL (A) SP‐SO2HI 24VDC PLC
SP ‐ SO2B LO DC DI 1756‐IB32 1 ‐ : 1 / 00 1 ‐ 5 ‐ 16 T5 ‐ A17 T5 ‐ B17 SO2 LOW LEVEL (B) SP‐SO2LO 24VDC PLC
SP ‐ SO2B HI DC DI 1756‐IB32 1 ‐ : 1 / 01 1 ‐ 5 ‐ 17 T5 ‐ A18 T5 ‐ B18 SO2 HIGH LEVEL (B) SP‐SO2HI 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 02 1 ‐ 5 ‐ 18 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 03 1 ‐ 5 ‐ 19 24VDC PLC
TI ‐ 21A DC DI 1756‐IB32 1 ‐ : 1 / 04 1 ‐ 5 ‐ 20 TEMPERATURE SWITCH TS‐21A 24VDC PLC JUMPER ‐ ALWAYS ON
TI ‐ 22A DC DI 1756‐IB32 1 ‐ : 1 / 05 1 ‐ 5 ‐ 21 TEMPERATURE SWITCH TS‐22A 24VDC PLC JUMPER ‐ ALWAYS ON
DC DI 1756‐IB32 1 ‐ : 1 / 06 1 ‐ 5 ‐ 22 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 07 1 ‐ 5 ‐ 23 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 10 1 ‐ 5 ‐ 24 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 11 1 ‐ 5 ‐ 25 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 12 1 ‐ 5 ‐ 26 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 13 1 ‐ 5 ‐ 27 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 14 1 ‐ 5 ‐ 28 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 15 1 ‐ 5 ‐ 29 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 16 1 ‐ 5 ‐ 30 24VDC PLC
DC DI 1756‐IB32 1 ‐ : 1 / 17 1 ‐ 5 ‐ 31 24VDC PLC
Tetra Tech Preliminary Field Redlines Page 8 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
MS ‐ P06 B AC DO 1756‐OA16 1 ‐ : 2 / 00 1 ‐ 6 ‐ 0 T6 ‐ A1 T6 ‐ B1 COMMAND START S02 B MS‐P06B 120VAC PLC
YV ‐ 2‐1 B AC DO 1756‐OA16 1 ‐ : 2 / 01 1 ‐ 6 ‐ 1 T6 ‐ No L T6 ‐ A2 COMMAND YV‐2‐1B 120VAC PLC
MS NE‐1 AC DO 1756‐OA16 1 ‐ : 2 / 02 1 ‐ 6 ‐ 2 120VAC PLC
MS ‐ PO8 A AC DO 1756‐OA16 1 ‐ : 2 / 03 1 ‐ 6 ‐ 3 T6 ‐ A4 T6 ‐ B4 COMMAND SLUDGE PUMP A MS‐P08A 120VAC PLC DUPLICATE
AC DO 1756‐OA16 1 ‐ : 2 / 04 1 ‐ 6 ‐ 4 120VAC PLC
MS ‐ M02 A AC DO 1756‐OA16 1 ‐ : 2 / 05 1 ‐ 6 ‐ 5 T6 ‐ A6 T6 ‐ B6 COMMAND MS‐M02A 120VAC PLC
AC DO 1756‐OA16 1 ‐ : 2 / 06 1 ‐ 6 ‐ 6 120VAC PLC
MS ‐ P03 AC DO 1756‐OA16 1 ‐ : 2 / 07 1 ‐ 6 ‐ 7 T6 ‐ A8 T6 ‐ B8 COMMAND CR REAC PUMP A MS‐P03 120VAC PLC
MS ‐ P05 A AC DO 1756‐OA16 1 ‐ : 2 / 10 1 ‐ 6 ‐ 8 T6 ‐ A9 T6 ‐ B9 COMMAND T‐5 TRANS A MS‐P05A 120VAC PLC
MS P10 A AC DO 1756‐OA16 1 ‐ : 2 / 11 1 ‐ 6 ‐ 9 120VAC PLC
MS P10 B AC DO 1756‐OA16 1 ‐ : 2 / 12 1 ‐ 6 ‐ 10 120VAC PLC
MS ‐ P01 A AC DO 1756‐OA16 1 ‐ : 2 / 13 1 ‐ 6 ‐ 11 T6 ‐ A12 T6 ‐ B12 COMMAND T‐1 A MS‐P01A 120VAC PLC
MS ‐ P01 B AC DO 1756‐OA16 1 ‐ : 2 / 14 1 ‐ 6 ‐ 12 T6 ‐ A13 T6 ‐ B13 COMMAND T‐1 B MS‐P01B 120VAC PLC
MS ‐ P01 C AC DO 1756‐OA16 1 ‐ : 2 / 15 1 ‐ 6 ‐ 13 T6 ‐ A14 T6 ‐ B14 COMMAND T‐1 C MS‐P01C 120VAC PLC
MS ‐ P04 AC DO 1756‐OA16 1 ‐ : 2 / 16 1 ‐ 6 ‐ 14 T6 ‐ A15 T6 ‐ B15 COMMAND CR REAC PUMP B MS‐P04 120VAC PLC
MS ‐ P05 B AC DO 1756‐OA16 1 ‐ : 2 / 17 1 ‐ 6 ‐ 15 T6 ‐ A16 T6 ‐ B16 COMMAND T‐5 TRANS B MS‐P05B 120VAC PLC
MS ‐ M03 A AC DO 1756‐OA16 1 ‐ : 3 / 00 1 ‐ 7 ‐ 0 T7 ‐ A1 T7 ‐ B1 COMMAND MIXER T‐3 A MS‐M03A 120VAC PLC
MS ‐ M03 B AC DO 1756‐OA16 1 ‐ : 3 / 01 1 ‐ 7 ‐ 1 T7 ‐ A2 T7 ‐ B2 COMMAND MIXER T‐3 B MS‐M03B 120VAC PLC
MS ‐ M04 A AC DO 1756‐OA16 1 ‐ : 3 / 02 1 ‐ 7 ‐ 2 T7 ‐ A3 T7 ‐ B3 COMMAND MIXER T‐4 A MS‐M04A 120VAC PLC
MS ‐ M04 B AC DO 1756‐OA16 1 ‐ : 3 / 03 1 ‐ 7 ‐ 3 T7 ‐ A4 T7 A‐4 COMMAND MIXER T‐4 B MS‐M04B 120VAC PLC
Tetra Tech Preliminary Field Redlines Page 9 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
MS ‐ M06 AC DO 1756‐OA16 1 ‐ : 3 / 04 1 ‐ 7 ‐ 4 T7 ‐ A5 T7 ‐ B5 COMMAND MIXER T‐6 MS‐M06 120VAC PLC
AC DO 1756‐OA16 1 ‐ : 3 / 05 1 ‐ 7 ‐ 5 120VAC PLC
MS ‐ M07 D AC DO 1756‐OA16 1 ‐ : 3 / 06 1 ‐ 7 ‐ 6 T7 ‐A7 T7 ‐ B7 COMMAND MIXER T‐7 D MS‐M07A 120VAC PLC
MS P02 B AC DO 1756‐OA16 1 ‐ : 3 / 07 1 ‐ 7 ‐ 7 120VAC PLC
MS ‐ M07 B AC DO 1756‐OA16 1 ‐ : 3 / 10 1 ‐ 7 ‐ 8 T7 ‐ A9 T7 ‐ B9 COMMAND MIXER T‐7 D MS‐M07B 120VAC PLC
MS M10 AC DO 1756‐OA16 1 ‐ : 3 / 11 1 ‐ 7 ‐ 9 120VAC PLC
YV ‐ 2‐1 A AC DO 1756‐OA16 1 ‐ : 3 / 12 1 ‐ 7 ‐ 10 T‐7 No L T7 ‐ A11 COMMAND YV‐2‐1A 120VAC PLC Relay #1
YV ‐ 4‐2 AC DO 1756‐OA16 1 ‐ : 3 / 13 1 ‐ 7 ‐ 11 T7 ‐ No L T7 ‐ A12 COMMAND T‐3 INF VALVE YV‐3‐1 120VAC PLC Relay #3
YV ‐ 3‐2 AC DO 1756‐OA16 1 ‐ : 3 / 14 1 ‐ 7 ‐ 12 T7 ‐ No L T7 ‐ A13 COMMAND T‐3 EFF VALVE YV‐1‐2 120VAC PLC Re;ay #4
YV ‐ 4‐1 AC DO 1756‐OA16 1 ‐ : 3 / 15 1 ‐ 7 ‐ 13 T7 ‐ No L T7 ‐ A14 COMMAND T‐4 INF VALVE YV‐4‐1 120VAC PLC Relay #5
YV ‐ 3‐1 AC DO 1756‐OA16 1 ‐ : 3 / 16 1 ‐ 7 ‐ 14 T7 ‐ No L T7 ‐ B15 COMMAND T‐4 EFF VALVE YV‐4‐2 120VAC PLC
MS ‐ P06 A AC DO 1756‐OA16 1 ‐ : 3 / 17 1 ‐ 7 ‐ 15 T7 ‐ A16 T7 ‐ B16 COMMAND START S02 PUMPA MS‐P06A 120VAC PLC
MS ‐ P11 A DC DO 1756‐OB32 1 ‐ : 4 / 00 1 ‐ 8 ‐ 0 24VDC PLC
MS P11 B DC DO 1756‐OB32 1 ‐ : 4 / 01 1 ‐ 8 ‐ 1 24VDC PLC
MS ‐ P08 A DC DO 1756‐OB32 1 ‐ : 4 / 02 1 ‐ 8 ‐ 2 T8 ‐ A3 T8 ‐ B3 COMMAND AIR SOL SLUDGE A MSP08A 24VDC PLC DUPLICATE
MS ‐ P08 B DC DO 1756‐OB32 1 ‐ : 4 / 03 1 ‐ 8 ‐ 3 T8 ‐ A4 T8 ‐ B4 COMMAND AIR SOL SLUDGE B MS‐P08B 24VDC PLC
MS PO2 A DC DO 1756‐OB32 1 ‐ : 4 / 04 1 ‐ 8 ‐ 4 24VDC PLC
MS PO2 B DC DO 1756‐OB32 1 ‐ : 4 / 05 1 ‐ 8 ‐ 5 24VDC PLC
MS ‐ POLY DC DO 1756‐OB32 1 ‐ : 4 / 06 1 ‐ 8 ‐ 6 T8 ‐ A7 T8 ‐ B7 COMMAND POLYMER MS‐POLY 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 4 / 07 1 ‐ 8 ‐ 7 T7‐C7 24VDC PLC
Tetra Tech Preliminary Field Redlines Page 10 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
DC DO 1756‐OB32 1 ‐ : 4 / 10 1 ‐ 8 ‐ 8 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 4 / 11 1 ‐ 8 ‐ 9 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 4 / 12 1 ‐ 8 ‐ 10 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 4 / 13 1 ‐ 8 ‐ 11 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 4 / 14 1 ‐ 8 ‐ 12 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 4 / 15 1 ‐ 8 ‐ 13 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 4 / 16 1 ‐ 8 ‐ 14 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 4 / 17 1 ‐ 8 ‐ 15 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 00 1 ‐ 8 ‐ 16 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 01 1 ‐ 8 ‐ 17 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 02 1 ‐ 8 ‐ 18 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 03 1 ‐ 8 ‐ 19 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 04 1 ‐ 8 ‐ 20 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 05 1 ‐ 8 ‐ 21 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 06 1 ‐ 8 ‐ 22 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 07 1 ‐ 8 ‐ 23 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 10 1 ‐ 8 ‐ 24 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 11 1 ‐ 8 ‐ 25 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 12 1 ‐ 8 ‐ 26 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 13 1 ‐ 8 ‐ 27 24VDC PLC
Tetra Tech Preliminary Field Redlines Page 11 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
DC DO 1756‐OB32 1 ‐ : 5 / 14 1 ‐ 8 ‐ 28 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 15 1 ‐ 8 ‐ 29 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 16 1 ‐ 8 ‐ 30 24VDC PLC
DC DO 1756‐OB32 1 ‐ : 5 / 17 1 ‐ 8 ‐ 31 24VDC PLC
AI 1756‐IF16 1 ‐ ‐ 6 ‐ 1 1 ‐ 9 ‐ 0
T 8‐1 D field
4‐20ma LOOP
AI 1756‐IF16 1 ‐ ‐ 6 ‐ 2 1 ‐ 9 ‐ 1
WIRED T8‐2 D
T8‐2 D
4‐20ma LOOP NOT LABELED
AI 1756‐IF16 1 ‐ ‐ 6 ‐ 3 1 ‐ 9 ‐ 2
WIRED T8‐3 D
T8‐3 D
4‐20ma LOOP NOT LABELED
AI 1756‐IF16 1 ‐ ‐ 6 ‐ 4 1 ‐ 9 ‐ 3
WIRED
T8‐4D
4‐20ma LOOP NOT LABELED
AI 1756‐IF16 1 ‐ ‐ 7 ‐ 1 1 ‐ 9 ‐ 4 T9 ‐ 5A T9 ‐5B
WIRED T11‐7 D
T8‐5 D
4‐20ma LOOP NOT LABELED
AI 1756‐IF16 1 ‐ ‐ 7 ‐ 2 1 ‐ 9 ‐ 5 T9 ‐ 6A T9 ‐ 6B T8‐6 D 4‐20ma LOOP
AI 1756‐IF16 1 ‐ ‐ 7 ‐ 3 1 ‐ 9 ‐ 6 T9 ‐ 7A T9 ‐ 7B T8‐7 D 4‐20ma LOOP
Term T11‐7
Term T11‐6
Term T11‐5
AI 1756‐IF16 1 ‐ ‐ 7 ‐ 4 1 ‐ 9 ‐ 7 T9 ‐ 8A T9 ‐ 8B T8‐8 D 4‐20ma LOOP
AI 1756‐IF16 2 ‐ ‐ 0 ‐ 1 1 ‐ 9 ‐ 8 T9 ‐ 9A T9 ‐ 9B T9‐1 D 4‐20ma LOOP
AI 1756‐IF16 2 ‐ ‐ 0 ‐ 2 1 ‐ 9 ‐ 9 T9 ‐ 10A T9 ‐ 10B T9‐2 D 4‐20ma LOOP
T6 ‐ PH 1 AI 1756‐IF16 2 ‐ ‐ 0 ‐ 3 1 ‐ 9 ‐ 10 T9 ‐ 11A T9 ‐ 11B T9‐3D 4‐20ma LOOP
T6 ‐ PH 2 AI 1756‐IF16 2 ‐ ‐ 0 ‐ 4 1 ‐ 9 ‐ 11 T9 ‐ 12A T9 ‐12B T9‐4D 4‐20ma LOOP
T3 PH
T4 PH
T6 ORD
T6 ‐ ORP 2 AI 1756‐IF16 2 ‐ ‐ 1 ‐ 1 1 ‐ 9 ‐ 12 T9 ‐ 13A T9 ‐ 12B T9‐5D 4‐20ma LOOP
T7 ‐ PH 1A AI 1756‐IF16 2 ‐ ‐ 1 ‐ 2 1 ‐ 9 ‐ 13 T9 ‐ 14A T9 ‐ 14B T9‐6D 4‐20ma LOOP
T7 ‐ PH 1B AI 1756‐IF16 2 ‐ ‐ 1 ‐ 3 1 ‐ 9 ‐ 14 T9 ‐ 15A T9 ‐ 15B T9‐7D 4‐20ma LOOP
T7 ‐ PH 2A AI 1756‐IF16 2 ‐ ‐ 1 ‐ 4 1 ‐ 9 ‐ 15 T9 ‐ 16A T9 ‐ 16B T9‐8D 4‐20ma LOOP
Tetra Tech Preliminary Field Redlines Page 12 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
T3 Level AI 2 ‐ ‐ 2 ‐ 1 1 ‐ 10 ‐ 0 T10 ‐ 1A T10 ‐ 1B T10‐1D 4‐20ma LOOP
T4 ‐ Level AI 2 ‐ ‐ 2 ‐ 2 1 ‐ 10 ‐ 1 T10 ‐ 2A T10 ‐ 2B T10‐2D 4‐20ma LOOP
T5 ‐ Level AI 2 ‐ ‐ 2 ‐ 3 1 ‐ 10 ‐ 2 T10 ‐ 3A T10 ‐ 3B T10‐3D 4‐20ma LOOP
T10 ‐ Level AI 2 ‐ ‐ 2 ‐ 4 1 ‐ 10 ‐ 3 T10 ‐ 4A T10 ‐ 4B T10‐4D 4‐20ma LOOP
LI ‐ 1‐2 T‐11‐1 AI 2 ‐ ‐ 3 ‐ 1 1 ‐ 10 ‐ 4 T10 ‐ 5A T10 ‐ 5B
* Blk & Rd Change + ‐ T10‐5D
4‐20ma LOOP
LI ‐ 11‐1 T8‐1 AI 2 ‐ ‐ 3 ‐ 2 1 ‐ 10 ‐ 5 T10 ‐ 6A T10 ‐ 6B
* Blk & Rd Change + ‐ T10‐6D
4‐20ma LOOP
LI ‐
10‐1/ mcpi
T8‐6 AI 2 ‐ ‐ 3 ‐ 3 1 ‐ 10 ‐ 6 T10 ‐ 7A T10 ‐ 7B
* Blk & Rd Change + ‐ T10‐7D
4‐20ma LOOP
T6 ‐
FI
Tank G 3‐1 Flow
AI 2 ‐ ‐ 3 ‐ 4 1 ‐ 10 ‐ 7 T10 ‐ 8A T10 ‐ 8B
T‐11 ‐ 7 D T10‐8D
4‐20ma LOOP
AI 2 ‐ ‐ 4 ‐ 1 1 ‐ 10 ‐ 8 T11‐1D 4‐20ma LOOP
TECM ‐ T 1‐4 AI 2 ‐ ‐ 4 ‐ 2 1 ‐ 10 ‐ 9 T10 ‐ 10A T10 ‐ 10B T11‐2D 4‐20ma LOOP
FT ‐ 3‐1 AI 2 ‐ ‐ 4 ‐ 3 1 ‐ 10 ‐ 10 T10 ‐ 11A T10 ‐ 11B IA‐4D 4‐20ma LOOP
AI
T‐12
Term (splice
T8‐7 block)
AI 2 ‐ ‐ 4 ‐ 4 1 ‐ 10 ‐ 11 T10 ‐ 12A T10 ‐ 12B T11‐4D 4‐20ma LOOP
AI ‐ 8‐1 AI 2 ‐ ‐ 5 ‐ 1 1 ‐ 10 ‐ 12 T10 ‐ 13A T10 ‐ 13B T11‐5D 4‐20ma LOOP
T7 ‐ PH 2‐B AI 2 ‐ ‐ 5 ‐ 2 1 ‐ 10 ‐ 13 T10 ‐ 14A T10 ‐ 14B T11‐6D 4‐20ma LOOP
TI ‐ PH AI 2 ‐ ‐ 5 ‐ 3 1 ‐ 10 ‐ 14 T10 ‐ 15A T10 ‐ 15B T11‐7D 4‐20ma LOOP
TI ‐ ORP AI 2 ‐ ‐ 5 ‐ 4 1 ‐ 10 ‐ 15 T10 ‐ 16A T10 ‐ 16B T11‐8D 4‐20ma LOOP
1 ‐ 11‐0 (unknown) AO 1756‐OF8 2 ‐ ‐ 6 ‐ 1 1 ‐ 11 ‐ 0 T11 ‐ 1A T11 1B T12‐1D 4‐20ma LOOP NOT LABELED
SCP 11A AO 1756‐OF8 2 ‐ ‐ 6 ‐ 2 1 ‐ 11 ‐ 1 T11 ‐ 2A T11 ‐ 2B T12‐2D 4‐20ma LOOP
SCP 11B AO 1756‐OF8 2 ‐ ‐ 7 ‐ 1 1 ‐ 11 ‐ 2 T11 ‐ 3A T11 ‐ 3B T12‐3D 4‐20ma LOOP
SC ‐ P12 AO 1756‐OF8 2 ‐ ‐ 7 ‐ 2 1 ‐ 11 ‐ 3 T11 ‐ 4A T11 ‐ 4B WIRED T12‐4D 4‐20ma LOOP
Tetra Tech Preliminary Field Redlines Page 13 of 14 g
Lo op
Le tt er IO
Type Module Ra ck
Sl ot
Po in t
Description Field Device Signal Type Range Power Closed State CommentsPanel Terminals
SC ‐ P03 AO 1756‐OF8 3 ‐ ‐ 0 ‐ 1 1 ‐ 11 ‐ 4 T11 ‐ 5A T11 ‐ 5B WIRED T13‐1D 4‐20ma LOOP
SC ‐ P04 AO 1756‐OF8 3 ‐ ‐ 0 ‐ 2 1 ‐ 11 ‐ 5 T11 ‐ 6A T11 ‐ 6B WIRED T13‐2D 4‐20ma LOOP
SC ‐ S052 CH3 AO 1756‐OF8 3 ‐ ‐ 1 ‐ 1 1 ‐ 11 ‐ 6 T11 ‐ 7A T11 ‐ 7B WIRED (was T13‐3D) 4‐20ma LOOP
SC ‐ SO2 CH4 AO 1756‐OF8 3 ‐ ‐ 1 ‐ 2 1 ‐ 11 ‐ 7 T11 ‐ 8A T11 ‐ 8B WIRED (was T13‐4D) 4‐20ma LOOP
Tetra Tech Preliminary Field Redlines Page 14 of 14
PAC 1