Appendix_A-1(Equipment_List)_Serv_19-008-R-0045_Reverse_Osmosis.xlsx
XLSX spreadsheet 20 KB Posted
- Attached to
- CSS for Reverse Osmosis System Preventative Maintenance and Remedial Maintenance Federal contract opportunity
- Solicitation number
- FA813219R1908
About this file
Appendix A/Equipment List for Reverse Osmosis PM/RM
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Response_to_Question_2_Combined_Synopsis_Solicitation_FA8132-19-Q-1908_Amdt_01.pdf | ||
| FA813219R1908_Amndt_Question.docx | DOCX document | |
| FA813219R1908_Amendment_01_CSS.docx | DOCX document | |
| FA813219R1908_Amendment_01-_Rev_Appendix_A-1(Equipment_List).xlsx | XLSX spreadsheet | |
| PWS_Reverse_Osmosis.pdf | ||
| RevOs_FO_Wage_Determination.pdf | ||
| CSS_Reverse_Osmosis_PMRM.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Cover Page
| Revised Appendix A1-RO PMXG Maintenance Contract | |
| FA8125-15-M-0045 | |
| Tabs | |
| Tab: | RO Plating |
| Tab: | Main Line RO |
| Tab: | 095 RO |
Plating RO
| LOCATION | OC-Number | NUMBER | NAME | Manufacturer | Model No./Serial No. | MAINTENANCE REQUIRED |
| Building 3001, Post H-53 | ALL EQUIPMENT | - Check for proper function on all equipment, i.e. check each system for errors. Verify systems are operating to designed set points. Initiate RM as required. | ||||
| Building 3001, Post H-53 | OC23392 | RAW WATER BOOSTER PUMP 1 | MARLO INCORPORATED OF RACINE | BOOSTER PUMP SKID MTD / EP-170287-001-3020 | - (Standard pump/motor maintenance) | |
| Building 3001, Post H-53 | RAW WATER BOOSTER PUMP 2 | - (Standard pump/motor maintenance) | ||||
| Building 3001, Post H-53 | OC23390 | MMF-1 | MULTIMEDIA FILTRATION SYSTEM | MARLO INCORPORATED OF RACINE | MZA-63G DUPLEX/PARALLEL MEDI / EP-160275-001-1441 | - Replace multimedia if required. Expected media life is 10-15 years (expected replacement 2028-2033). |
| Building 3001, Post H-53 | OC23387 | CCF-1 | CARBON FILTRATION SYSTEM | MARLO INCORPORATED OF RACINE | ACA-48G DUPLEX PARALLEL CARB / EP-160275-002-1442 | - Replace carbon media if required. Expected carbon life is 2-5 years (expected replacement 2020-2023, based on ORP). |
| Building 3001, Post H-53 | OC23391 | WS-1 | WATER SOFTENER SYSTEM | MARLO INCORPORATED OF RACINE | MRG-1200-3 DUPLEX ALT WATER S / EP-160275-003-1443 | - Replace 2 consumable bottles for hardness monitor as required (expected replacement every ~2 months). Use: |
Hach SP 510 Hardness Monitor Buffer Solution for 20 mg/L Hardness, 500 mL container Hach SP 510 Hardness Monitor Indicator Solution for 5 to 100 mg/L Hardness, 500 mL container
- Hardness monitor 2-point standardization whenever reagent is replaced or when optical system component is replaced. Use:
Hach TitraVer (EDTA) Hardness Titrant 0.200N, 0.100M, 29 mL container Hach Magnesium Sulfate Solution 10,000 ±1000 mg/L, 29 mL container
- Replace water softener resin if required. Expected resin life is very long, 15+ years (expected replacement 2033 or later).
- Replace hardness monitor pump tubes every 3 months Building 3001, Post H-53 BRINE TANK - Clean out brine tank to maintain cleanliness. Minimum yearly.
- Check function on automatic water fill equipment for proper function.
- Provide salt (A-A-694, Type II, Form 1, 40 lb bag) in brine tank to support water softener regenerations.
Building 3001, Post H-53 OC23385 RO-1 REVERSE OSMOSIS SYSTEM 1 MARLO INCORPORATED OF RACINE MRO-72K-8H SINGLE PASS RO SKID / EP-160275-004-1113 - Fill antiscallant tank (use PWT SpectraGuard 111, 0.5 gallon container currently authorized)
- Replace 5 micron cartridge filter as required when differential pressure reaches 15 psi.
- Calibrate all gauges and meters based on manufacturer's recommendations. Frequency no less than every 3 months.
- Replace membranes when required
- Grease motor bearings quarterly
- Change metering pump cartridge valves yearly
- (Standard pump/motor maintenance) Building 3001, Post H-53 OC23389 RO-2 REVERSE OSMOSIS SYSTEM 2 MARLO INCORPORATED OF RACINE MRO-72K-8H SINGLE PASS RO SKID / EP-160275-013-1120 - Fill antiscallant tank (use PWT SpectraGuard 111, 0.5 gallon container currently authorized)
- Replace 5 micron cartridge filter as required when differential pressure reaches 15 psi.
- Calibrate all gauges and meters based on manufacturer's recommendations. Frequency no less than every 3 months.
- Replace membranes when required
- Grease motor bearings quarterly
- Change metering pump cartridge valves yearly
- (Standard pump/motor maintenance)
| Building 3001, Post H-53 | RO WATER STORAGE TANK | - Inspect level sensor and high-high level sensor | ||||
| Building 3001, Post H-53 | OC23386 | P-101 | RO SUPPLY PUMP 1 | MARLO INCORPORATED OF RACINE | RECIRCULATION PUMP SKID WITH / EP-160275-006-1502 | - (Standard pump/motor maintenance) |
| Building 3001, Post H-53 | P-102 | RO SUPPLY PUMP 2 | - (Standard pump/motor maintenance) | |||
| Building 3001, Post H-53 | UV FILTER | - Replace UV lamp when required (minimum annually) |
- Inspect and clean or replace UV sleeve as required
- Inspect flow meter sensor periodically Building 3001, Post H-53 OC23388 CIP-1 CLEAN IN PLACE SYSTEM MARLO INCORPORATED OF RACINE MEMBRANE CLEAN-IN-PLACE (CIP) / EP-160275-005-1491 - Run clean in place cycle as required to maintain RO membranes. Use PWT Lavasol 1, 5 gallon containers currently authorized
- Replace filter as required
- (Standard pump/motor maintenance)
Main Line RO
| LOCATION | NUMBER | NAME | Manufacturer | Model No./Serial No. | MAINTENANCE REQUIRED |
| H101 | Side A Filter | Shelco Microguardian | 12F0S4/112739 | Ensure filter is not clogged, replace cartridges as needed. | |
| H101 | Side A Pump | Grundfos | A91129158-P21008003 | Standard Pump/Motor Maintenance | |
| H101 | Side B Filter | Shelco Microguardian | 12F0S4/112739 | Ensure filter is not clogged, replace cartridges as needed. | |
| H101 | Side B Pump | Grundfos | A91129158-P21008003 | Standard Pump/Motor Maintenance | |
| H101 | Sodium Bisulfite Chem Tanks (2) | Fill with Chemical as required. Ensure sensors function properly. Clean out the tank once a year. | |||
| H101 | Pumps Associated with SBS (2) | Pulsatron | LB64SA-VTC1-XX2 | Standard Pump/Motor Maintenance | |
| H101 | Antiscalant Chem Tanks (2) | Fill with Chemical as required. Ensure sensors function properly. Clean out the tank once a year. | |||
| H101 | Pumps Associated with Anticalant (2) | Pulsatron | LB64SA-VTC1-XX2 | Standard Pump/Motor Maintenance | |
| H101 | Cleaner Tank | After use of cleaning out the skid, ensure tank is fully drained. Ensure sensor operates, replace as needed. | |||
| H101 | Cleaner Tank Filter | Shelco Microguardian | 7F0S4/112739 | Ensure filter is not clogged, replace cartridges as needed. | |
| H101 | Cleaner Tank Pump | Leeson Electric Corporation | C184T34FK15D/131583.00 | Standard Pump/Motor Maintenance | |
| H101 | P-3 | Re-Pressure Skid Pump 1 | Leeson Electric Corporation | C215T34FK10AA | Standard Pump/Motor Maintenance |
| H101 | P-4 | Re-Pressure Skid Pump 2 | Leeson Electric Corporation | C215T34FK10AA | Standard Pump/Motor Maintenance |
| H101 | P-5 | Distribution Skid Pump 1 | Leeson Electric Corporation | C215T34FK10AA | Standard Pump/Motor Maintenance |
| H101 | P-6 | Distribution Skid Pump 2 | Leeson Electric Corporation | C215T34FK10AA | Standard Pump/Motor Maintenance |
| H101 | Product Water Holding Tanks | Ensure level sensor is working properly. Replace as needed. | |||
| H101 | UltraViolet Lamp | Aquafine | Replace UV lamps as needed, minimum of once a year. Clean quartz sleeves as needed, and replace once a year. Clean sensor probe window and replace probe once a year. Replace ballast as needed, though it should be infrequent. | ||
| H101 | OC20140 | Main Line Reverse Osmosis System | Hausers Water Systems | Ensure membranes are clear of fouling and there are no leaks on the system as a whole. Clean membranes as needed, minimum once a year. Calibrate, clean, or replace any electrodes/sensors as needed. | |
| H101 | AC Units for Control Panels (3) | Industrial Cooling Equipment | HC12012604XCX | Clean out filters as needed, minimum of once a year. |
O95 RO
| LOCATION | NUMBER | NAME | Manufacturer | Model No./Serial No. | MAINTENANCE REQUIRED |
| S91 | TK-501 | RO Cleaning Tank | Snyder Industries, Inc. | After use of cleaning out the skid, ensure tank is fully drained. Ensure sensor operates, replace as needed. | |
| S91 | TK-502 | Antiscalant Chem Tank | Fill with Chemical as required. Clean out the tank once a year. | ||
| S91 | Antiscalant Tank Agitator | Liquid Metronics | 10590A | Standard Maintenance | |
| S91 | P-501 | Antiscalant Metering Pump | LMI, Milton Roy | P161-468SI/08092663366-2 | Standard Pump/Motor Maintenance |
| S91 | P-502 | Antiscalant Metering Pump | LMI, Milton Roy | P161-468SI/08092663366-1 | Standard Pump/Motor Maintenance |
| S91 | Sodium Metabisulfide Tank | Fill with Chemical as required. Clean out the tank once a year. | |||
| S91 | Sodium Metabisulfide Agitator | LMI, Milton Roy | 6JHX3/71638553 | Standard Maintenance | |
| S91 | Sodium Metabisulfide Metering Pump | Pulsatron, Pulsafeeder | LB03SA-VTC1-XX2/477907 | Standard Pump/Motor Maintenance | |
| S91 | Sodium Metabisulfide Metering Pump | Pulsatron, Pulsafeeder | LB03SA-VTC1-XX2/477905 | Standard Pump/Motor Maintenance | |
| S91 | P-201 | RO A Feed Pump | Grundfos | A96523644-P10838574 | Standard Pump/Motor Maintenance |
| S91 | P-401 | RO B Feed Pump | Grundfos | A96523644-P10838574 | Standard Pump/Motor Maintenance |
| S91 | P-601 | Product Water Feed Pump | Grundfos | A96523641-P10838602 | Standard Pump/Motor Maintenance |
| S91 | TK-602 | Bladder Tank | Well-X-Trol, Amtrol | WX-302 | Ensure proper operation of level sensor and clean as needed. Clean tank once a year. |
| S91 | UV-601 | UltraViolet Lamp | Atlantic Ultraviolet Corp. | S2400C | Replace UV lamps as needed, minimum of once a year. |
| S91 | CF-601 | Post-Treatment Cartridge Filter | Ensure filter is not clogged, replace cartridges as needed. | ||
| S91 | Pre-Treatment Cartridge Filters (2) | Shelco Microguardian | BFS-2SB-2/130857 | Ensure filter is not clogged, replace cartridges as needed. | |
| S91 | TK-601 | Product Water Holding Tank | Clean tank once a year. | ||
| S91 | OC19792 | Automated Cleaning Line RO System | LT Technologies | Ensure membranes are clear of fouling and there are no leaks on the system as a whole. Clean as needed, minimum once a year. Calibrate, clean, or replace any electrodes/sensors as needed. |