Questions Answers - Generator Replacement.xlsx

XLSX spreadsheet 19 KB Posted

Attached to
Generator Replacement Federal contract opportunity
Solicitation number
FA670325B0006
Issued by
Department of the Air Force Reserve Command

About this file

This document is a Questions and Answers spreadsheet for a Generator Replacement project at Dobbins Air Reserve Base in Georgia. The project involves replacing generators at multiple facilities, including removing existing generators and installing new Cummins 150kW mobile generators with specific technical requirements such as EPA Tier 4 Final Certified emissions, 208-480V variable voltage, and integral 24-hour runtime fuel tanks. The contract (Solicitation FA670325B0006) will be awarded on a Lowest Responsive/Responsible Bid basis, with work to commence upon Notice to Proceed.

Key technical and operational details include: only one site on the flightline may be offline simultaneously, contractors must provide backup generators during changeovers, all surge protection devices must be from the same manufacturer, and O&M manuals must be submitted in both hard copy and electronic formats. Contractors will need to obtain airfield operation waivers, which typically take approximately two months, and must have qualified personnel for superintendent, safety, and quality control roles. The project requires a contract-specific QA/QC and Safety Plan, with badging and site access to be coordinated after award.

View the file

Other files for this federal contract opportunity

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

No.Document TitleAttachment/ParagraphPage NumberSoliciation StatementQuestion/CommentAnswerJA Review
1Specifications - 828_2012_2125_2313.pdf1.3.2“150kW - Cummins C150D2RE Mobile Generator - Portable Generator Only”.Which CLIN will this generator be priced under?CLIN 1 with Gen 828
2Specifications - 828_2012_2125_2313.pdf1.3.2“150kW - Cummins C150D2RE Mobile Generator - Portable Generator Only”.Will this mobile generator be turned over to the government at the completion of the contract?Yes
3Specifications - 828_2012_2125_2313.pdf1.3.2“150kW - Cummins C150D2RE Mobile Generator - Portable Generator Only”.Can the mobile generator be used as the temporary generator during the construction period?Yes – Generator must be maintained by the contractor during the duration of the project. If the generator is damaged, it must be repaired prior to turning over to the Government. It must be fully operational with no significant damage (like new condition). The government does expect hours of usage on the generator and the warranty will start at the time of start-up. Diesel will be provided by the government for all government owned generators; however, DEF if required will be the contractor’s responsibility to provide during construction for all generators used. The contractor must schedule diesel fueling with government as soon as possible prefer a week’s notice.
4Specifications - 550_1001_2021_2300.pdf1.3.2“550 - Medical - Remove generator - Manual transfer with mobile generator”.What are the specs for the mobile generator?150kW - Cummins C150D2RE Mobile Generator - Portable Generator Only – See Attachment

Generator set, diesel engine, including battery, charger, heater C150D2RE Diesel Genset, 50/60HZ, 150KW, Standby Rental U.S. EPA, Nonroad (Portable) Application 1 C50D2RE, Diesel Genset, 50/60 Hz, 150kW, Standby-Rental 1 Duty Rating - Prime Power (PRP) 1 Emissions - Compliance EPA Tier 4 Final Certified 1 Voltage 208 - 480 Variable 1 Alternator - 60Hz, 208/416 - 240/480 Volt, 125/80C Standby/Prime 1 Electric Brake Trailer 1 Pintle Hitch - 3 inch 1 UN31A Certified Fuel Tank 1 Generator Set Control - PowerCommand 3.3, Paralleling with MLD 1 Distribution Panel - Rental Bus Bar Connection 1 Packaging - Cummins Power Generation 1 Genset Warranty - Industrial Mobile Base, Prime 3 Years/3000 hours 1 Battery Charger - Rental 1 Engine Coolant - 60% Antifreeze, 40% Water Mixture 1 Cam Lock Distribution Panel - U.S. Rental 1 Quick Fit Kit 1 Harness, Paralleling 1 Auxiliary DEF Connections

5Specifications - 550_1001_2021_2300.pdf1.3.2“550 - Medical - Remove generator - Manual transfer with mobile generator”.Is this an additional mobile generator that will stay at B550?Building 550 will be set-up to take a quick disconnect connection for a mobile generator. The government already has a mobile generator that will be used there after the project is com-pleted.
6General QuestionN/AN/ABesides the standard O&M manuals that come with the generator and transfer switches, will there be additional manuals required for submission at closeout? If so, can the Government provide a list of the required manuals?The contractor will be required to provide all manuals available for the generator, ATS, 3-way switches and load bank connection. This would include the engine, ser-vice, overhaul, O&M, controllers, and parts manuals. How will the government know all the manuals required when we do not know the exact generators that would be ordered. See attached example of manuals required both hard bound and elec-tronic.
7General QuestionN/AN/AN/AIs it acceptable to provide the O&M's files only electronically or will hard copies need to be provided.Both hard bound and electronic.
8General QuestionN/AN/AN/ACLIN 0009 requests pricing for the Generator and Transfer Switch but drawing sheet E-104 does not show the installation of a new generator and automatic transfer switch. Please confirm that a new generator and automatic transfer switch is not to be installed.A new generator or ATS will not be installed at building 550. This site will be set-up for a future mobile generator.
9Drawings - 550_1001_2021_2300.pdfAttachment 2N/A"MTS switch sized is base upon generator size."Drawing sheet E-104 General sheet note in top right corner states "MTS switch sized is base upon generator size". Please confirm size stated in sheet E-104 new work keynote #1 is correct.Used detail 6/E-104 for size. The MTS must have cam-lock connections. That was the designer note for the size chosen.
10Solicitiation - FA670325B0006.pdfSection B - Page 4(3 WAY SWITCHES, LOAD BANK

CONNECTIONS, SURGE PROTECTION, SIOH

0.257)CLIN 0004 and CLIN 0012 reference SIOH 0.257, please clarify what this is.That is a misprint and should not be referenced.
11Specifications - 828_2012_2125_2313.pdfAttachment 3
2.22 Surge Protection"Total Protection
Solutions is one manufacturer who meets the UFC requirement."Spec. Section 26 32 14.00 10 / 2.22 Surge Protection references Total Protection Solutions as one manufacturer that meets UFC requirements. It is our understanding that Total Protection Solutions is the only manufacturer that meets the UFC requirement because of the language that it provides unlimited free replacements of the unit if destroyed by lightning or other transient during the warranty period. Please confirm if this is correct.All SPD’s must be by the same manufacturer. If another SPD company is found that meets all the UFC requirements we would approve. I have reviewed multiple differ-ent companies SPD’s, and I find that their warranties or their construction or specs do not meet all the requirements.
12General QuestionN/AN/AN/AWill night shift or weekend work be required to accommodate flight line activities?Normally we work during duty hours. We cannot have more than one system down at the same time on the flightline. If more than one site is being worked on then one must not be on the flightline. Airfield systems work in pairs this why we cannot have more than one down.
13Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 1 Table of Contents DIVISION 02 - Existing Conditions

Attachment 3 Table of Contents

DIVISION 02 - Existing Conditions02 82 00 ASBESTOS REMEDIATION
02 83 00 LEAD REMEDIATIONSpecification Project Table of Contents Division 02 calls for Asbestos and Lead Remediation. Drawings do not indicate any areas that have lead or asbestos. Please clarify that no asbestos or lead is present at any project site locations, and if there is, please provide exact locations of asbestos and lead.There is no known asbestos in these locations.
14General QuestionN/AN/AN/AWill new equipment and concrete installed on the airfield require Airfield Operation waivers or FAA waivers? Please provide information on how long waivers will take and if this can be accomplished during procurement?Yes, waivers will be required and not just on the airfield. If a crane is used a waiver must be done if it causes an airfield obstruction. This process will be explained dur-ing the pre-construction meeting. Normally about two months depending on the re-quirements and equipment used.
15General QuestionN/AN/AN/AIn executing this project, can one superintendent fulfill the supervision, safety, and QAQC roles?Normally it is better to have more than one. This also depends on how many sites are planning to be done. We can have one person fulfill this as long as they are qualified to do all parts and they are on site during construction.
16General QuestionN/AN/AN/AAre contractors required to issue a contract specific QA/QC Plan?Yes
17General QuestionN/AN/AN/AAre contractors required to issue a contract specific Safety Plan?Yes
18General QuestionN/AN/AN/AIs this project tax exempt?N/A
19General QuestionN/AN/AN/ACan the site visit sign in sheet be provided to contractors?Sign in sheet is attached
20Solicitiation - FA670325B0006.pdfSection B - Page 5"...complete all

requirements/work in accordance with Specifications (Attachment 3 and Drawings (Attachment 4) for

Project FGWB 25-0011…"Option Line Item 0009 does not match the drawings for building #550. Should the power scheme be modified or should the generator be replaced for building # 550?The generator and ATS are being removed and converting this site to a quick disconnect mobile generator connection.
21General QuestionN/AN/AN/AWhat’s the process for contractor badging and how long does it typically take to get issued?This depends upon the personnel working. If they clear the background check, we should be able to badge them the same day. We will provide a form to get your personnel checked upon award/selection.
22General QuestionN/AN/AN/ADuring the site visit, we entered “controlled areas”: Will contractors be issued badges for these areas or will contractors be escorted by government staff?The flightline area you will have to get trained on driving that area once trained you will have access to the work locations. The only other area is building 1001 which we will work out with the employees working there to get you access to the work site.
23General QuestionN/AN/AN/AWhen will the period of performance (POP) officially start?Upon issuance of Notice to Proceed
24Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 1

2.1 Manufacturers

Attachment 3

2.1 Manufacturers"Cummins is the only allowed manufacturers for this generator project."The government specifies “Cummins” as the preferred OEM, will any others be considered?No
25General QuestionN/AN/AN/AIs this selection LPTA or “best value”?Lowest Responsive/Responsible Bid
26General QuestionN/AN/AN/APlease confirm whether the Superintendent, SSHO, and QC Manager must be three separate individuals, or if dual roles may be accepted if qualifications are met.Normally it is better to have more than one. This also depends on how many sites are planned to be worked on at the same time. We can have one person fulfill this if they are qualified to do all parts and they are on site during construction.
27Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 2 Drawing Index

(EP-101)

Attachment 4 Drawing Index

(EP-102)Phasing PlansDrawings (EP-101, EP-102) show phasing plans. Please confirm: (a) May multiple facilities be taken offline at the same time, or is only one outage permitted? (b) Will the Government provide temporary mobile generator coverage during ATS/generator changeovers, or must contractor include this?Only one site on the flightline may be taken offline at a time. Only two sites can be down at the same time. One can be on the flightline while the other can be off the flightline. The contractor must provide back-up generator and ATS to these sites. The 150kW mobile generator purchased can be one of the mobile generators used to back-up the facility.
28General QuestionN/AN/AN/AIf the buildings remain occupied during construction, please confirm the anticipated occupancy levels (number of personnel).The only facility that will be occupied is 1001 which have no more than 10 personnel.
29General QuestionN/AN/AN/AAre any temporary heating or cooling requirements expected for occupied buildings during outages?There is no temporary heating or cooling requirement. The ex-pected outage should be minimal to connect and disconnect the temporary ATS. This outage must be scheduled prior.
30General QuestionN/AN/AN/ACan the period of performance be extended post-award to accommodate long-lead equipment procurement (e.g., generators, ATS)?If extension is warranted, yes
31General QuestionN/AN/AN/AAre soil boring reports available for the project sites? If not, please confirm excava-tion may be assumed free of rock/obstructions.There are no soil samples availa-ble. There is no possible way to assume free of rocks or obstructions. We expect grounding to meet the 25 ohms or less. A dig permit must be performed prior to any earthwork.
32Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 1 1.3.2

Attachment 3

1.3.2 1001 - ATCALS - Use integral fuel tank - Return convault tank to government 2021 – ILS Glidescope East - Use integral fuel tank 2300 – TACAN - Use integral fuel tank 828 - Lift Station - Use integral fuel tank 2012 - ILS Glideslope West - Use integral fuel tank 2125 – ILS Localizer East - Use integral fuel tank

2313 – Lift Station - Use integral fuel tankPlease confirm whether the integral fuel tanks specified for Facilities 1001, 2021, 2300, 828, 2012, 2125, and 2313 are sized to provide 24-hour runtime at full load, or if external double-walled tanks are required.When you purchase these fuel tanks as part of the generator, you must specify 24-hour run-time tanks per full load calcu-lations. No external tanks will be used, only integral.
33Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 1 2.1

Attachment 3

2.1 "I hereby certify the information provided herein is accurate and that the requisition/procurement of all materials listed on this form comply with

current EPA standards for recycled/recovered materials content."Specs require compliance with “latest EPA standards.” Please confirm whether generators must meet Tier 3 or Tier 4 Final.This is a manufacturer requirement.
34Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 1 1.3.2

Attachment 3

1.3.2 " Cam‐lock connectors will be installed for all 3-Way MTS installation to connect portable generators.

Cam‐Lock connectors shall not be rated greater than 200 amps per connector."Cam-lock connectors are required for 3-Way MTS installations, limited to 200A per connector. Please confirm if multiple connectors are acceptable for generators rated >200A.Yes. I know some 3-way switch manufacturers use 400 Amp.
35Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 1

2.22 Surge Protection

Attachment 3

2.22 Surge Protection "Electrical and electronic components shall be protected from, or designed to withstand the effects of surges from switching and lightning. Surge protection devices shall meet the requirements of UFC 3-520-01, section 3-4.

All surge protection devices must be from same manufacturer."Please clarify whether surge protection devices (SPD) must be integral to the ATS or installed as separate devices.These will be exterior to the ATS.
36Specifications - 550_1001_2021_2300.pdf1.3.2“550 - Medical - Remove generator - Manual transfer with mobile generator”.Scope for Facility 550 references removal of generator and provision of manual transfer. Please confirm whether a new permanent generator is included at this facility.No generator or ATS will be installed back into the location. This will be a manual transfer site.
37Specifications

Drawings Attachments 1 and 3

SECTION 01 35 26

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

Attachments 2 and 4 General Electrical Notes

8.1 "NFPA 70 --- 2017"

"All electrical equipment, wiring, conduits, and building elements shall be grounded per the requirements of NFPA 70, 2023."Specs reference NFPA 70 (2017, 25-ohm requirement) while drawings reference NFPA 70 (2023). Please confirm which edition governs and required resistance-to-earth value.At the time of these original drawings 2017 was in effect. Use current NFPA 70.
38Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 1 Table of Contents DIVISION 02 - Existing Conditions

Attachment 3 Table of Contents

DIVISION 02 - Existing Conditions02 82 00 ASBESTOS REMEDIATION
02 83 00 LEAD REMEDIATIONDivision 02 includes asbestos/lead remediation. Please confirm whether the Government will provide ACM/LCM survey reports, or if contractor must carry an allowance.There is no known asbestos in these locations.
39Solicitiation - FA670325B0006.pdfSection E - Inspection and Acceptance"Instructions: See Statement of Work (SOW) or Performance Work Statement (PWS) for Acceptance/inspection criteria."Please confirm whether generator/ATS acceptance testing (e.g., load bank testing) must be witnessed by Government representatives, and required notice period.Yes it must be witnessed by the government. Prefer a minimum of 14 working days prior notification.
40General QuestionN/AN/AN/APlease provide: (a) Site visit sign-in sheet, (b) Photos of existing job site conditions, (c) Contact info for building controls contractor, (d) Contact info for building fire alarm contractor.A )Sign in Sheet attached B) None C) NA - Upon award D) N/A – Upon Award
41General QuestionN/AN/AN/APlease confirm whether this project is tax exempt.I would say no. I do not know the answer – Contracting should answer.
42General QuestionN/AN/AN/AWill the deadline for questions/RFI be extended to allow for proper review post site-visit?No
43Specifications - 550_1001_2021_2300.pdf

Specifications - 828_2012_2125_2313.pdf Attachment 1 Section 01 30 00 Administrative Requirements

Attachment 3 Section 01 30 00 Administrative Requirements "Submit with the monthly invoice two sets of digital photographs, each set on a separate compact disc (CD) or data versatile disc (DVD), cumulative of all photos to date. Indicate photographs demonstrating environmental procedures. Provide photographs for each month in a separate monthly directory and name each file to indicate its location on the view location sketch. Also provide the view location sketch on the CD or DVD as a digital file." Will the Government accept electronic submittals of bid documents, shop drawings and O&M manuals, or are hard copies required? Bid Documents shall be submitted in accordance with Solicitation Instructions Shop drawings can be electronic unless it is required to be a hard copy. Red lines are normally both. Manuals will be both hard bound and electronic. Each piece of equipment will require one hard and one electronic copy per different type of manual.

44 General Question N/A N/A N/A Will there be a virtual option to attend the bid opening (Bid opening will be conducted at Building 812, Dobbins ARB)? No