Attach 2 - Drawings - 550_ 1001_ 2021_ 2300.pdf
PDF 27 MB Posted
- Attached to
- Generator Replacement Federal contract opportunity
- Solicitation number
- FA670325B0006
About this file
These are electrical design drawings for the replacement of generators at multiple locations on Dobbins Air Reserve Base in Georgia. The project involves studying, replacing, and adding generators at eight specific facilities: Medical Building 550, Transmitter Receiver 1001, ILS/Glideslope 2021, TACAN 2300, and others. The design documents detail electrical specifications, grounding requirements, conduit installation, and phasing plans for generator replacements.
Key technical details include installing new 25kW diesel generators with integral fuel tanks, new automatic transfer switches (ATS), manual transfer switches (MTS), and associated electrical infrastructure. The project requires removing existing generators, modifying electrical panels, installing new conduits and feeders, and ensuring proper grounding and connection methods. The electrical design follows 2017 National Electrical Code standards and Unified Facilities Criteria, with specific attention to generator connections, concrete pad installations, and electrical system integration across multiple base buildings.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attendance Roster.pdf | ||
| Solicitation Amendment FA670325B00060001 SF 30.pdf | ||
| Questions Answers - Generator Replacement.xlsx | XLSX spreadsheet | |
| Attach 1 - Specifications -550_1001_ 2021_ 2300.pdf | ||
| Attach 4 - Drawings - 828_ 2012_ 2125_ 2313.pdf | ||
| Solicitation - FA670325B0006.pdf | ||
| Attach 3 - Specifications - 828_ 2012_ 2125_ 2313.pdf | ||
| Attach 5 - Wage Determination.pdf | ||
| Attach 6 - Financial Institution Reference Sheet.pdf | ||
| Attach 7 - Submittal Register.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATIONS
G-001
C O
V E
R
S
H E
E T
2018-201
MMM
JKM
REV. DATE/BY DESCRIPTION
Croft & Associates
3400 Blue Springs Road, Suite 200
Kennesaw, GA 30144
770.529.7714 (p)
770.529.7716 (f) www.croftae.com
CONSTRUCTION DOCS.
C I V
I L
E
N G
I N
E E
R I N
G t h
A
I R
L I F
T
W
I N
G
D O
B B
I N
S
A
I R
E S
E R
V
B
A S
E
G
E O
R G
I A
P R
O J E
C T
L O
C A
T I O
N
D R
A W
I N
G
C O
N T
A C
T
PROJECT No.
PROJ. OFFICER
DESIGNED
CHECKED
DATE
DRAWING OF
P R
O J E
C T
O N
T A
C T
R O
B E
N
S
D
N r o b e r t e r n s t u s a f m i l
S T
U D
Y R
E P
L A
C E
G E
N E
R A
T O
R S
F G
W
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
J. MORGAN
A 2019-02-19 35% DESIGN
B 2019-05-24 65% DESIGN
C 2019-08-21 REVISED 65% DESIGN
D 2020-07-01 100% DESIGN
2020-07-24
E 2020-07-24
FINAL DESIGN
DRAWING INDEX
NUMBER
S H
E E
F
S
H E
E T
S
SHEET NAME
I S
U B
M I T
T A
L
GENERAL
G-001 1 COVER SHEET X
ELECTRICAL DRAWINGS
E-100 2 X
3 X
4 X
Dobbins Study/Replace/Add
Generators at Facilities
FGWB 25-0011
DOBBINS AIR RESERVE BASE, GA
N.T.S.
G-001
VICINITY MAP
N.T.S.
G-001
PROJECT LOCATIONS
PLAN
NORTH
PLAN
NORTH
ELECTRICAL GENERAL NOTES
5 X
MEDICAL BLDG - 550
E-104
TRANSMITTER RCVR - 1001
E-117
E-119 ILS/GLIDESLOPE 2021 & TACAN 2300
TRANSMITTER RCVR 1001
TACAN 2300
ILS/GLIDESLOPE 2021
MEDICAL 550
Grand total: 8
E-601
E-602
I S
B
M I T
T A
L
X
X
X
X
X
X
X
NOTE:
SEE SHEETS E-601 AND E-602 FOR ELECTRICAL DETAILS FOR ALL SITES.
ELECTRICAL DETAILS
ELECTRICAL DETAILS
I S
R
B
M I T
T A
L
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
I S
S
U B
M I T
T A
L
EP-101
PHASING PLANS
X
X
X
X
X
X
X
X
I S
F
I N
L
S
I G
N
Attach 2 FA670325B0006
Jeff Morgan GA Stamp - JKM - Simple
ELECTRICAL ABBREVIATIONS:
SINGLE POLE SWITCH.
3-WAY SINGLE POLE SWITCH.
4-WAY SINGLE POLE SWITCH.
DIMMER SWITCH, 0-10V, LEVITON RENOIR II
# AWSMT-7DW, OR EQUIVALENT.
D
OS
CEILING-MOUNTED OCCUPANCY SENSOR, DUAL
TECHNOLOGY.
120V DUPLEX RECEPTACLE, WALL MOUNTED, 18" AFF UNO.
ELECTRICAL SYMBOL LEGEND
PX
ELECTRICAL PANELBOARD, SEE PANEL SCHEDULE FOR
DETAILS - SURFACE MOUNTED
PX
ELECTRICAL PANELBOARD, SEE PANEL SCHEDULE FOR
DETAILS - FLUSH MOUNTED
SAFETY SWITCH
1'X4' WALL MOUNTED LIGHT FIXTURE (SEE LIGHT
FIXTURE SCHEDULE)
STRIP LIGHT FIXTURE, SURFACE OR SUSPENDED. (SEE
LIGHT FIXTURE SCHEDULE)
2'X4' RECESSED MOUNTED LIGHT FIXTURE. (SEE
LIGHT FIXTURE SCHEDULE)
2'X4' RECESSED MOUNTED LIGHT FIXTURE. EMERGENCY
BATTERY BACKUP (SEE LIGHT FIXTURE SCHEDULE)
SURFACE OR RECESSED LIGHT FIXTURE.
( SEE LIGHT FIXTURE SCHEDULE)
WALL MOUNTED LIGHT FIXTURE.
( SEE LIGHT FIXTURE SCHEDULE)
SURFACE OR RECESSED LIGHT FIXTURE. EMERGENCY
BATTERY BACKUP ( SEE LIGHT FIXTURE SCHEDULE)
3D
DIMMER SWITCH, 0-10V, LEVITON RENOIR II
# AWSMT-7DW, OR EQUIVALENT.
A AMPS, AMPERES
AB AS-BUILT
AC ALTERNATING CURRENT
AFCI ARC FAULT CIRCUIT INTERRUPTOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AL ALARM
AM AMMETER
AT ASTRONOMIC TIMER
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CLR CLEARANCE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPVC CLORINATED POLYVINYL CLORIDE
CT CURRENT TRANSFORMER
CTR COUNTER
CU COPPER
DC DIRECT CURRENT
DIA DIAMETER
DS DISCONNECT SWITCH
EA EACH
ELEC ELECTRICAL
EMER EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ES EMERGENCY STOP
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FC FULLY CLOSED
FLA FULL LOAD AMPS
FO FULLY OPEN
FU FUSE
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT
INTERRUPTOR
GND GROUND
HP HORSEPOWER
HZ HERTZ
IDC INITIATING DEVICE CIRCUIT
IMC INTERMEDIATE METAL CONDUIT
JB JUNCTION BOX
KVA KILO-VOLT AMP(S)
KW KILO-WATT
KWH KILO-WATT HOUR(S)
LTG LIGHTING
LTS LIGHTS
LO LOCKOUT
MC METAL-CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTR METER
MTS MANUAL TRANSFER SWITCH
N NEUTRAL
NAC NOTIFICATION APPLIANCE CIRCUIT
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMANATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATED
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OC OVERCURRENT
OCPD OVERCURRENT PROTECTION DEVICE
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PB PUSHBUTTON
PH PHASE
PNL PANELBOARD
PVC POLYVINYL CLORIDE
QTY QUANTITY
RA REMOTE ANNUNCIATOR
RCC RELAY CONTROL CABINET
REF REFERENCE
REQD REQUIRED
RMC RIGID METAL CONDUIT
SLC SIGNALING LINE CIRCUIT
SPD SURGE PROTECTION DEVICE
SW SWITCH
SWB SWITCHBOARD
SWGRSWITCHGEAR
UC UNDER COUNTER
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
V VOLT(S)
VA VOLT-AMPERE(S)
VFD VARIABLE FREQUENCY DRIVE
VSD VARIABLE SPEED DRIVE
W WATT(S)
WP WATER PROOF
XFMR TRANSFORMER
ONE 3/4"X10' COPPERCLAD GROUND ROD WITH ULTRAWELD
CONNECTIONS
DATA/PHONE OUTLET WALL MOUNTED 18" AFF UNO, WITH
3/4" CONDUIT STUBBED UP TO ABOVE ACCESSIBLE CEILING
W/PULL STRING.
QUAD DATA/PHONE OUTLET WALL MOUNTED 18" AFF UNO,
WITH 3/4" CONDUIT STUBBED UP TO ABOVE ACCESSIBLE
CEILING W/PULL STRING.
EQUIPMENT JUNCTION BOX, WALL MOUNTED.J
EXIT SIGN LIGHT FIXTURE, CEILING/WALL MOUNTED,
ARROWS AS REQUIRED. (SEE LIGHT FIXTURE SCHEDULE)
EXIT SIGN LIGHT FIXTURE WITH EMERGENCY HEADS, WALL
MOUNTED, ARROWS AS REQUIRED. (SEE LIGHT FIXTURE
SCHEDULE)
DATA OUTLET CEILING MOUNTED, WITH 3/4" CONDUIT
STUBBED TO ACCESSIBLE CEILING W/PULL STRING.
CEILING / WALL MOUNTED HEAT DETECTOR
SINGLE STATION 110V COMBINATION CARBON
MONOXIDE/SMOKE DETECTOR WITH BATTERY BACKUP,
CEILING /WALL MOUNTED
SINGLE STATION 110V COMBINATION CARBON
MONOXIDE/SMOKE DETECTOR WITH BATTERY BACKUP, AND
ADA STROBE, CEILING MOUNTED
CEILING / WALL MOUNTED SYSTEM SMOKE DETECTOR
SMOKE DETECTOR AIR DUCT MOUNTED
FIRE ALARM ADA APPROVED VISUAL STROBE DEVICE, 80" AFF
P
FIRE ALARM ADA APPROVED PULLSTATION, 48" AFF
S
S
S
FIRE ALARM ADA APPROVED HORN/STROBE DEVICE, 80" AFF
R AHU SHUTDOWN
'EX' SUBSCRIPT DENOTES EXISTING POWER RECEPTACLE
EX
120V QUAD RECEPTACLE, WALL MOUNTED, 18" AFF UNO.
SPECIAL POWER RECEPTACLE, TYPE NOTED IN SHEET
SPECIFIC KEY NOTE, WALL MOUNTED, 18" AFF UNO.
TV
COAXIAL RECEPTACLE, 18" AFF UNO
AV
AUDIO/VISUAL RECEPTACLE, TYPE NOTED IN SHEET
SPECIFIC KEY NOTE, WALL MOUNTED, 18" AFF UNO.
COORDINATION:
1. ELECTRICAL CONTRACTOR SHALL COORDINATE
LOCATIONS AND ELECTRICAL REQUIREMENTS OF
MECHANICAL/PLUMBING EQUIPMENT WITH THE
MECHANICAL/PLUMBING CONTRACTORS PRIOR TO
ORDERING ANY MATERIAL OR PERFORMING ANY WORK
ASSOCIATED WITH SUCH EQUIPMENT.
MATERIALS:
1. CONDUIT
1.1 RIGID METALLIC CONDUIT (RMC): HOT DIPPED
GALVANIZED STEEL CONFORMING TO (FS)
WW-C581E AND UL 6.
1.2 ELECTRICAL METALLIC TUBING (EMT): GALVANIZED
STEEL CONFORMING TO ASA C80.3, (FS) WW-C563
AND ULF 797.
1.3 FLEXIBLE METAL CONDUIT (FMC): SPIRAL WOUND,
SQUARE LOCKED, HOT DIPPED GALVANIZED STEEL
CONFORMING TO UL 1
2. CONDUIT FITTINGS
2.1 RMC: HOT DIPPED GALVANIZED OR CADMIUM
PLATED. FITTINGS USED WITH COATED RMC SHALL
HAVE A SIMILAR COATING.
2.2 EMT: COMPRESSION OR SET SCREW TYPE, MADE OF
CADMIUM PLATED STEEL OR HOT DIPPED
GALVANIZED MALLEABLE IRON.
2.3 FMC: TWO SCREW, DOUBLE CLAMP MALLEABLE
IRON, HOT DIPPED GALVANIZED OR CADMIUM
PLATED.
3. WIRING
3.1 ALL WIRING SHALL BE COPPER UNLESS NOTED
OTHERWISE.
3.2 INSULATION: HEAT AND MOISTURE RESISTANT WITH
A TEMPERATURE RATING OF AT LEAST 75 DEGREES
THERMAL HIGH HEAT NYLON (THHN), THERMAL HIGH
WATER RESISTANT NYLON (THWN) AND A 600 VOLT
RATING UNLESS OTHERWISE INDICATED.
3.3 USE STRANDED CONDUCTOR ON ALL WIRING #8
AWG AND LARGER. ALL OTHER WIRING MAY BE
SOLID.
4. USE ANCHORS AND FASTENERS OF A TYPE DESIGNED
AND INTENDED FOR USE IN THE BASE MATERIAL TO
WHICH THE MATERIAL OR SUPPORT IS TO BE ATTACHED,
AND CAPABLE OF SUPPORTING THE INTENDED LOAD AND
WITHSTANDING ANY ASSOCIATED STRESSES AND
VIBRATIONS. DO NOT USE WOODEN PLUGS FOR
FASTENING.
5. ALL MATERIALS USED FOR CONSTRUCTION SHALL BE
INSTALLED IN A NEAT AND WORK-LIKE MANNER.
6. ALL WIRING DEVICES SHALL BE SPECIFICATION GRADE
AND MATCH BASE BUILDING STANDARD DEVICE STYLE,
COLOR, AND MOUNTING HEIGHT UNLESS REQUIRED TO
BE IN COMPLIANCE WITH ADA.
7. ALL MATERIALS AND EQUIPMENT FURNISHED AND
INSTALLED BY THE ELECTRICAL CONTRACTOR SHALL BE
NEW, UL LISTED OR LABELED, AND CONFORM TO NEMA
ANS/ANSI STANDARDS WHERE APPLICABLE.
8. FURNISH AND INSTALL PULL BOXES, JUNCTION BOXES,
AND DEVICE BOXES OF SUITABLE GAUGE AND SIZE AS
NECESSARY TO PROVIDE A FULLY FUNCTIONAL AND
CODE COMPLIANT SYSTEM.
9. ANY WIRE OR CONTROL WIRE TO BE REUSED MUST BE
VERIFIED TO CONTAIN THE PROPER AMOUNT OF WIRES.
INSTALL ADDITIONAL WIRES IF MORE WIRING IS NEEDED
TO MAKE EQUIPMENT OPERATIONAL.
EXECUTION:
1. ALL EQUIPMENT SHALL BE INSTALLED PER
MANUFACTURES INSTALLATION INSTRUCTIONS.
2. MAINTAIN THE INTEGRITY OF ALL EXISTING CIRCUITS IN
SERVICE THAT MAY BE AFFECTED BY THIS WORK.
IDENTIFY ALL SOURCES OF POWER AND DE-ENERGIZE
REQUIRED CIRCUITS BEFORE BEGINNING WORK.
3. PERFORM ALL CUTTING AND DRILLING TO PROVIDE
PENETRATIONS THROUGH WALLS AND FLOORS FOR
ELECTRICAL INSTALLATION WORK.
4. WHERE CONDUITS PASS THROUGH FIRE RATED OR
SMOKE RATED ASSEMBLIES, CONTRACTOR SHALL
FOLLOW UL GUIDELINES FOR SEALING/STOPPING
PENETRATIONS TO MAINTAIN FIRE AND/OR SMOKE
RATING OF WALL ASSEMBLY.
5. ALL DEVICES AND JUNCTION BOXES SHALL BE
ACCESSIBLE. PROVIDE ACCESS PANELS AS REQUIRED TO
ENSURE ACCESS TO DEVICES. COORDINATE ACCESS
PANEL LOCATIONS AND TYPES WITH COR AND GENERAL
CONTRACTOR PRIOR TO ORDERING AND INSTALLATION.
6. DISCONNECT SWITCHES SHALL BE MOUNTED ON
INDIVIDUAL STRUCTURAL SUPPORTS, OR OTHERWISE
DIRECTLY ON EQUIPMENT, PROVIDED NO MODIFICATION
TO EQUIPMENT IS NECESSARY. ALL STRUCTURAL
SUPPORTS FOR ELECTRICAL EQUIPMENT SHALL BE
PROVIDED AND INSTALLED BY ELECTRICAL
CONTRACTOR.
7. ALL ELECTRICAL DEVICE CONNECTIONS SHALL BE
TIGHTENED TO THE TORQUE VALUES RECOMMENDED BY
THE DEVICE MANUFACTURER. IF THESE VALUES ARE NOT
LISTED, TIGHTEN TO POUND INCH OR POUND FOOT
VALUES RECOMMENDED BY UL STANDARD 486A-B.
7. GROUNDING
7.1 ALL ELECTRICAL EQUIPMENT, WIRING, CONDUITS,
AND BUILDING ELEMENTS SHALL BE GROUNDED PER
THE REQUIREMENTS OF NFPA 70, 2017.
7.2 THE BUILDING GROUNDING ELECTRODE SYSTEM
SHALL BE INSTALLED TO MAINTAIN A RESISTANCE TO
EARTH OF 25 OHMS OR LESS. IF A SINGLE
GROUNDING ELECTRODE CAN NOT MEET THIS
REQUIREMENT, THE CONTRACTOR IS REQUIRED TO
INSTALL SUPPLEMENTAL ELECTRODES PER SECTION
250.53 OF NFPA 70, 2017.
7.3 PROVIDE AN EQUIPMENT CONDUCTOR IN ALL
RACEWAYS SIZED IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 70, 2017. CONDUITS ARE
NOT PERMITTED TO BE USED IN LIEU OF A GROUND
WIRE.
7.4 BOND ALL BRANCH CIRCUIT DEVICES TO THE
BUILDING GROUND SYSTEM BY MEANS OF THE
GROUNDING CONDUCTOR INSTALLED IN EACH
RACEWAY.
8. CABLE INSTALLED OUTSIDE OF RACEWAYS SHALL BE
SUPPORTED INDEPENDENTLY AND NOT FROM OTHER
SYSTEMS. SECURING CABLES TO OR FROM WATERLINES,
ELECTRICAL RACEWAYS, OR ANY OTHER MECHANICAL
SYSTEM IS NOT ACCEPTABLE. CABLES SHALL BE
SUPPORTED FROM BAR JOISTS, CABLE TRAYS,
UNI-STRUT TRAPEZE HANGERS, OR OTHER HANGERS
INSTALLED AND APPROVED FOR THIS PURPOSE.
MAXIMUM SPACING SHALL BE 10' ON CENTER WITH A
MAXIMUM 8” SAG. CABLES SHALL MAINTAIN A MINIMUM 6”
CLEARANCE FROM ELECTRICAL EQUIPMENT.
10. H-FRAME (UNI-STRUT MOUNTING FRAME)
10.1 PROVIDE NEW H-FRAME UNI-STRUT STRUCTURE IF
EXISTING FRAME THAT IS TO BE REUSED CANNOT BE
REUSED.
11. IDENTIFICATION
11.1 PROVIDE 1/8” SELF-STICK LABELS WITH BLOCK
LETTERING PROTECTED WITH CLEAR TAPE TO
IDENTIFY PANEL AND CIRCUIT NUMBER AT
RECEPTACLES, SWITCHES, CONTROL CABINETS, ETC.
ADDITIONALLY, PROVIDE 1-1/2” HIGH ENGRAVED
LAMINATED NAMEPLATES TO IDENTIFY CABINETS,
PANELBOARDS, MOTOR STARTERS, ETC.
11.2 ALL OUTDOOR IDENTIFICATION SHALL BE WITH
PROVIDE 1-1/2” HIGH ENGRAVED LAMINATED
NAMEPLATES.
11.3 IDENTIFY ALL JUNCTION BOXES USING BLACK
LETTERS TO IDENTIFY THE PANEL AND CIRCUIT
NUMBER OR SYSTEM WIRING
11.4 CONTRACTOR SHALL PROVIDE IDENTIFICATION FOR
WIRING SYSTEMS AND EQUIPMENT.
11.5 POWER WIRING SHALL HAVE CONDUCTORS COLOR
BANDED IN EACH JUNCTION AND PULL BOX.
11.6 CONTROL CIRCUIT WIRING SHALL BE IDENTIFIED
WITH WIRE NUMBERS AT EACH TERMINATION.
11.7 ON PANELBOARD NAMEPLATES, LIST THE PANEL
DESIGNATION, AMPERAGE, VOLTAGE, AND PHASE.
11.8 PROVIDE TYPEWRITTEN PANELBOARD CIRCUIT
DIRECTORY IN PANELBOARD DOOR IDENTIFYING ALL
ACTIVE CIRCUITS AND SPARES. ACTIVE CIRCUITS
SHALL DESIGNATE EQUIPMENT SERVED. DIRECTORY
SHALL REFLECT ACTUAL CIRCUITRY, AND SHALL NOT
BE A REPRODUCTION OF DESIGN DRAWING PANEL
SCHEDULES IF DEVIATIONS WERE MADE DURING
CONSTRUCTION.
11.9 PROVIDE A PERMANENT PLACARD ATTACHED WITH
SHEET METAL SCREWS OR RIVETS ON LOAD BANK
CONNECTION BOXES RATED LOWER THAN 100
PERCENT OF GENERATOR:
LOAD BANK CONNECTION BOX IS RATED FOR 50% OF
GENERATOR CAPABILITY
12. WIRING
12.1 ALL WIRING SHALL BE INSTALLED IN APPROVED
CONDUITS OR RACEWAYS UNLESS NOTED
OTHERWISE.
12.2 ALL BRANCH CIRCUITS SHALL HAVE DEDICATED
NEUTRAL CONDUCTORS UNLESS NOTED OTHERWISE.
12.3 WIRES SHALL BE A MINIMUM #12 AWG IN SIZE.
12.4 COLOR CODE WIRING AS FOLLOWS:
12.4.1 120/240V, 1 PHASE: NEUTRAL - WHITE, PHASE A -
BLACK, PHASE B - RED, GROUND - GREEN
12.4.2 120/208V, 3 PHASE: NEUTRAL - WHITE, PHASE A -
BLACK, PHASE B - RED, PHASE C - BLUE, GROUND
- GREEN
12.4.3 277/480V, 3 PHASE: NEUTRAL - GREY, PHASE A -
BROWN, PHASE B - ORANGE, PHASE C - YELLOW,
GROUND - GREEN
13. CONDUIT
13.1 ALL CONDUITS SHALL BE INSTALLED IN A
CONCEALED LOCATION WHERE POSSIBLE, WITH THE
EXCEPTION OF DEDICATED MECHANICAL AND
ELECTRICAL SPACES. IN THOSE AREAS OUTSIDE OF
THE EXCEPTION WHERE IT IS NOT POSSIBLE TO
INSTALL CONDUITS IN A CONCEALED MANNER,
ELECTRICAL CONTRACTOR SHALL INSTALL EXPOSED
CONDUITS PARALLEL AND AT RIGHT ANGLES TO THE
NEARBY SURFACES AND STRUCTURAL MEMBERS. IN
THESE AREAS, GROUP RACEWAYS IN MINIMUM
GROUPS OF THREE RACEWAYS ON A COMMON
SUPPORT SYSTEM.
13.2 PROVIDE PULL ROPE IN ALL EMPTY CONDUITS.
13.3 EXTERIOR LOCATIONS: USE RMC CONDUIT.
13.4 INTERIOR LOCATIONS, WHERE SUBJECT TO DAMAGE
BELOW 8' AFF: USE RMC OR EMT CONDUIT.
13.5 INTERIOR LOCATIONS, WHERE NOT SUBJECT TO
DAMAGE, ABOVE 8' AFF, OR IN CONCEALED
LOCATIONS: USE RMC OR EMT CONDUIT.
13.6 TYPE NM CABLE IS NOT PERMITTED TO BE USED
WITHOUT CONDUIT IN ANY LOCATIONS EXCEPT BY
WRITTEN APPROVAL BY THE COR.
13.7 FMC IS PERMITTED TO BE USED IN FOR RUNOUTS
FOR EQUIPMENT SUBJECT TO VIBRATION (MOTORS,
HVAC EQUIP, ETC.). RUNOUT LENGTHS FOR FMC
MUST BE 6'0” FEET OR LESS.
13.8 CONDUIT REQUIREMENTS IN THIS SECTION ARE
PROVIDED FOR GENERAL PRICING AND INSTALLATION
GUIDANCE. CONTRACTOR IS RESPONSIBLE FOR
FOLLOWING NFPA 70 REQUIREMENTS.
13.9 IF EXISTING CONDUIT OR WIRE IS REUSED BUT IS
FOUND DAMAGED, WRONG SIZE, OR TOO SHORT TO
REATTACH, INSTALL NEW CONDUIT OR WIRE IN ITS
PLACE. CONTRACTOR SHOULD PROVIDE A
FUNCTIONING SYSTEM WHEN COMPLETED.
13.10 CONDUIT PLACEMENT SHALL NOT CAUSE OR
CONTRIBUTE TO A TRIPPING OR SAFETY HAZARD.
GENERAL ELECTRICAL NOTES:
GENERAL REQUIREMENTS:
1. ALL WORK SHALL BE DONE IN CONFORMANCE WITH THE
FOLLOWING STANDARDS.
1.1. 2015 INTERNATIONAL BUILDING CODE WITH UFC
1-200-01 AMENDMENTS.
1.2. 2017 NATIONAL ELECTRICAL CODE.
1.3. UNIFIED FACILITIES CRITERIA (UFC) CODES,
INCLUDING BUT NOT LIMITED TO:
1.3.1. UFC 3-501-01 ELECTRICAL ENGINEERING
1.3.2. UFC 3-540-01 ENGINE DRIVEN GENERATOR
SYSTEMS FOR BACKUP POWER APPLICATIONS,
WITH CHANGE 1
2. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FEES,
PERMITS, AND LICENSES FOR THE COMPLETE
INSTALLATION OF THE WORK OUTLINED IN THESE
CONTRACT DOCUMENTS.
3. THE CONTRACT DOCUMENTS ARE DIAGRAMMATIC IN
NATURE AND NOT EVERY DETAIL OR EXACT LOCATION
OF EQUIPMENT AND/OR CONDUIT IS SHOWN. VERIFY ALL
CONDITIONS AND DIMENSIONS PRIOR TO ORDERING ANY
MATERIAL OR PERFORMING ANY WORK. NOTIFY THE
COR OF ANY CONDITIONS OR DIMENSIONS WHICH
WOULD AFFECT PERFORMANCE OF WORK IN
ACCORDANCE WITH THE CONTRACT DRAWINGS AND/OR
SPECIFICATIONS.
4. THE ELECTRICAL CONTRACTOR SHALL SUBMIT SHOP
DRAWINGS WITH CATALOG SHEETS TO THE COR PRIOR
TO ORDERING ANY ELECTRICAL EQUIPMENT. SHOP
DRAWINGS AND CATALOG SHEETS SHALL BE SUBMITTED
AS A COMPREHENSIVE COMPLETE SET, AND PARTIAL
EQUIPMENT SUBMITTALS WILL NOT BE ACCEPTED.
5. IF WIRING INDICATED ON DRAWINGS ARE NOT THE
CORRECT SIZE, IT IS THE CONTRACTORS
RESPONSIBILITY TO PROVIDE CORRECTLY SIZED WIRING
AND CONDUIT PER NEC.
14. GENERATOR CONNECTIONS
GENERATOR FACILITY CONNECTIONS MUST EITHER BE
HARDWIRED OR UTILIZE CONNECTIONS METHODS AS
NOTED BELOW.
14.1 HEAVY-DUTY CYLINDRICAL. MIL-C-22992, CLASS L,
QWLD-RATED CONNECTORS (CANNON PLUG) WITH
APPROPRIATELY RATED DISCONNECT SWITCH
SELECTED IN ACCORDANCE WITH NFPA 70 ARE
PERMITTED AS FOLLOWS:
14.1.1 UP TO THREE (3) CONNECTIONS PER
GENERATOR ARE PERMITTED. THE MAXIMUM
SINGLE CONNECTOR RATING MUST BE 200
AMPERES.
14.1.2 THE COMBINED LOADS FROM MULTIPLE
CONNECTIONS MUST NOT EXCEEDED THE
RATED CAPACITY OF THE STANDBY
GENERATOR.
14.1.3 THE SINGLE CONDUCTOR SIZE USED IN ANY
CONNECTOR MUST NOT EXCEED #4/0 AMERICAN
WIRE GAUGE (AWG).
14.1.4 UNUSED CONNECTOR RECEPTACLE MUST BE
CAPPED WITH MANUFACUTRER-RECOMMENDED
COVERS TO PREVENT EXPOSURE TO LIVE
ELECTRICAL CONTACTS. PLASTIC DUST CAPS
ARE NOT ACCEPTABLE.
14.1.5 A DATA PLATE STYLE PLACARD MUST BE
PERMANENTLY ATTACHED, USING SHEET METAL
SCREWS OR RIVETS, ADJACENT TO THE
CONNECTION(S), WITH READ:
DANGER
UNUSED CONNECTOR RECEPTACLES ARE ENERGIZED
DURING GENERATOR OPERATION.
EXERCISE EXTREME CAUTION.
PROPER PPE REQUIRED WHEN MAKING CONNECTIONS.
14.1.6 CABLE ASSEMBLIES CONNECTED IN PARALLEL
MUST COMPLY WITH ALL OF THE FOLLOWING:
14.1.6.a BE THE SAME LENGTH
14.1.6.b HAVE THE SAME CONDUCTOR MATERIAL
14.1.6.c BE THE SAME SIZE IN CIRCULAR MIL AREA
14.1.6.d HAVE THE SAME INSULATION TYPE, INCLUDING CABLE ASSEMBLY SHEATHING
14.1.6.e BE TERMINATED IN THE SAME MANNER
AND BE OF THE SAME RATING.
14.2 GENERATOR AND ATS SHALL BE PROVIDED
WITH ADDITIONAL CONTACTS FOR SCADA OR
ADDITIONAL MONITORING CAPABILITY.
14.3 ATS THAT ARE SUPPLYING BUILDINGS WITH A
UPS SHALL HAVE 4-POLES (TOTAL POLES
REQUIRED FOR NEUTRAL SWITCHING)
SWITCHES .
9. REPAIR ANY DAMAGED CONCRETE PADS FROM THE
CONSTRUCTION PROCESS AT NO COST TO THE
GOVERNMENT.
E-100
E L
E C
T R
I C
G
N
E R
T
E S
2018-201
MMM
JKM
REV. DATE/BY DESCRIPTION
Croft & Associates
3400 Blue Springs Road, Suite 200
Kennesaw, GA 30144
770.529.7714 (p)
770.529.7716 (f) www.croftae.com
CONSTRUCTION DOCS.
C I V
I L
E
N G
I N
E E
R I N
G t h
A
I R
L I F
T
W
I N
G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
P R
O J E
C T
L O
C A
T I O
N
D R
A W
I N
G
C O
N T
A C
T
PROJECT No.
PROJ. OFFICER
DESIGNED
CHECKED
DATE
DRAWING OF
P R
O J E
N
T A
C T
R O
B E
N r o b e r t e r n s t u s a f m i l
S T
U D
Y R
E P
L A
C E
G E
N E
R A
T O
R S
F G
-0
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
J. MORGAN
A 2019-02-19 35% DESIGN
B 2019-05-24 65% DESIGN
C 2019-08-21 REVISED 65% DESIGN
D 2020-07-01 100% DESIGN
2020-07-24
E 2020-07-24
FINAL DESIGN
Attach 2 FA670325B0006
EXISTING
208/120V, 130KW, 3P
GENERATOR
EXISTING
CHILLER
EXISTING
UTILITY
TRANSFOMER
BUILDING
MAIN
"MDP"
EXISTING
ATS
EXISTING
TVSS
NATURAL GAS LINE
EXISTING
SERVICE
MAIN PANEL
"MDP"
208V, 3P, 2000A
EXISTING
ATS 208V,
400AMP
3-POLE
N
E
EXISTING
208V, 3P, 130KW
GENERATOR
EXISTING
UTILITY
208/120V, 3P, 500KVA
TRANSFORMER
EXISTING
PANEL "E"
208/120V, 3P, 400A
ELECTRICAL ROOM AEXTERIOR
EXISTING
TVSS
TVSS
EXISTING
ATS
EXISTING
SERVICE MAIN
PANEL "MDP"
208V, 3P, 2000A
EXISTING
CONDUITS
TO REMAIN
TVSS
NEW
MTS
EXISTING
SERVICE MAIN
PANEL "MDP"
208V, 3P, 2000A
NEW WEATHERPROOF
JUNCTION BOX TO PANEL "E"
EXISTING
CONDUITS
TO REMAIN
EXISTING
CHILLER
EXISTING
UTILITY
TRANSFOMER
BUILDING
MAIN
"MDP"
NEW
MTS
RELOCATED
TVSS
CAPPED
NATURAL GAS
LINE
EXISTING
SERVICE
MAIN PANEL
"MDP"
208V, 3P, 2000A
N
E
EXISTING
UTILITY
208/120V, 3P, 500KVA
TRANSFORMER
EXISTING
PANEL
"E"
208/120V, 3P, 400A
ELECTRICAL ROOM AEXTERIOR
CAMLOCK
CONNECTIONS
NEW WEATHERPROOF JUNCTION
BOX: 2'X2'X10" MIN SIZE
NEW 200A, 208V,
3-POLE, MTS
NEMA 3R
NEW
SPD
E-104
M E
D I C
2018-201
MMM
JKM
REV. DATE/BY DESCRIPTION
Croft & Associates
3400 Blue Springs Road, Suite 200
Kennesaw, GA 30144
770.529.7714 (p)
770.529.7716 (f) www.croftae.com
CONSTRUCTION DOCS.
C I V
I L
E
N G
I N
E E
R I N
G t h
A
I R
L I F
T
W
I N
G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
P R
O J E
C T
L O
C A
T I O
N
D R
A W
I N
G
C O
N T
A C
T
PROJECT No.
PROJ. OFFICER
DESIGNED
CHECKED
DATE
DRAWING OF
P R
O J E
N
T A
C T
R O
B E
N r o b e r t e r n s t u s a f m i l
S T
U D
Y R
E P
L A
C E
G E
N E
R A
T O
R S
F G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
J. MORGAN
A 2019-02-19 35% DESIGN
B 2019-05-24 65% DESIGN
C 2019-08-21 REVISED 65% DESIGN
D 2020-07-01 100% DESIGN
2020-07-24
E 2020-07-24
FINAL DESIGN
E-104
EXISTING 550-MEDICAL ELECTRICAL SERVICE ELEVATION
NOT TO SCALE
E-104
EXISTING 550-MEDICAL PARTIAL POWER LAYOUT
1/8" = 1'-0"
PLAN
NORTH
X DEMOLITION KEY NOTES:
1. REMOVE EXISTING GENERATOR AND ASSOCIATED CONDUITS,
FEEDERS, WIRES, AND GROUNDING.
2. REMOVE EXPOSED CONDUIT IN MECHANICAL YARD ASSOCIATED
WITH THE GENERATOR BACK TO THE POINT IT TURNS
UNDERGROUND. CAP CONDUITS AND PERMANENTLY MARK
CONDUITS AS ABANDONED.
3. MARK CIRCUITS FOR GENERATOR BLOCK HEATER AND BATTERY
CHARGER AS SPARES IN SOURCE PANEL. REMOVE CIRCUITS AND
EXPOSED CONDUITS. EXISTING UNDERGROUND CONDUITS WILL BE
CAPPED AND PERMANENTLY MARKED AS ABANDONED.
4. REMOVE NATURAL GAS PIPING BACK TO REGULATOR. CAP AND
SEAL GAS PIPING.
5. REMOVE EXISTING ATS ON EXTERIOR WALL.
6. REMOVE CONDUIT AND FEEDER FROM EXISTING ATS TO "MDP".
7. REMOVE CONDUIT FROM EXISTING ATS TO CONDUIT/LB THAT
PENETRATES INTO THE BUILDING. LEAVE FEEDER CABLES FOR
RE-USE TO CONNECT TO AND EXTEND FEEDER TO PANEL "E".
8.
9.
CUT CONDUIT FROM GENERATOR THAT CONNECTS TO ATS ABOVE
GROUND, CAP AND PERMANENTLY MARK AS ABANDONED.
REMOVE CONDUIT AND WIRES FOR EXISTING TVSS. REMOVE TVSS.
E-104
EXISTING 550-MEDICAL PARTIAL RISER DIAGRAM
NOT TO SCALE
E-104
NEW 550-MEDICAL ELECTRICAL SERVICE ELEVATION
NOT TO SCALE
E-104
NEW 550-MEDICAL PARTIAL POWER LAYOUT
1/8" = 1'-0"
PLAN
NORTH
E-104
NEW 550-MEDICAL PARTIAL RISER DIAGRAM
NOT TO SCALE
X NEW WORK KEY NOTES:
1. PROVIDE AND INSTALL NEW 200AMP, 3-POLE, 208V, NEMA 3R, MTS
(SSDX-200C-200C-208-311-S-C, OR EQUAL) WITH 200AMP RATED
CAM-LOCK CONNECTIONS.
2. PROVIDE NEW CONDUIT AND FEEDER (4#3/0, #6G - 2"C) WITH
WEATHERPROOF JUNCTION BOX TO CONNECTION TO EXISTING
LARGER FEEDERS TO PANEL "E".
3. PROVIDE NEW CONDUIT AND FEEDER (4#3/0, #6G - 2"C) FROM PANEL
"MDP" TO NEW MTS. UTILIZE EXISTING PENETRATION IN PANEL
"MDP". PROVIDE NEW 200AMP, 3P CIRCUIT BREAKER TO REPLACE
EXISTING 400AMP, 3P CIRCUIT BREAKER.
4. PROVIDE AND INSTALL NEW SPD (TK-ST160-SY208-L NEMA 4 OR
EQUAL) ON EXTERIOR WALL TO THE RIGHT SIDE OF PANEL "MDP".
PROVIDE NEW CONDUIT AND FEEDERS (4#1, #8G-1"C). USE EXISTING
PENETRATION. IF UNABLE, PROVIDE A WATERTIGHT SEAL FOR
EXISTING HOLE. CONNECT BACK TO EXISTING CIRCUIT BREAKER.
PROVIDE SEALS TO ANY HOLES THAT ARE NOT WEATHER TIGHT.
PAINT TO MATCH EXISTING PANEL DOOR.
GENERAL SHEET NOTES:
1. MTS SWITCH SIZED IS BASE UPON GENERATOR
SIZE.
Attach 2 FA670325B0006
EXISTING 240V,
1P, 53KW
GENERATOR
EXISTING
ATS
EXISTING
PANEL
"C"
EXISTING
PANEL
"B"
EXISTING
PANEL
"MDP"
METER
SERVICE
DISCONNECT
EXISTING
500GAL
CONVAULT
FUEL TANK
EXISTING
CONCRETE
PAD
EXISTING
SERVICE
DISCONNECT
208, 1P, 600A
EXISTING
ATS 208V,
400AMP
3-POLE
E
N
EXISTING
208V, 1P, 53KW
GENERATOR
METER
CABINET
EXISTING
500GAL
CONVAULT
FUEL TANK
EXISTING WIRE
TROUGH
UTILITY SERVICE
EXISTING
400A, 3-POLE,
240V
ATS
EXISTING
600A, 240V, 1P
DISCONNECT
EXISTING
METER
CABINET
WIRE TROUGH
EXISTING
SERVICE
DISCONNECT
240V, 1P, 600A
NEW 3-WAY
MTS 240V,
150AMP
3-POLE
N
E
NEW 240V, 1P,
25KW GENERATOR,
WITH INTEGRAL
FUEL TANK
METER
CABINET
UTILITY SERVICE
NEW BYPASS
ISOLATION
ATS 240V,
600AMP
3-POLE
E
N
AUX
CAMLOCK
CONNECTIONS
NEW 240V, 1P,
25KW
GENERATOR
NEW
3-WAY
MTS
EXISTING
PANEL
"C"
EXISTING
PANEL
"B"
EXISTING
PANEL
"MDP"
METER
SERVICE
DISCONNECT
NEW
ATS
EXISTING CONCRETE
PAD - EXTEND PAD
TO FIT NEW
GENERATOR
NEW 3-WAY,
3-POLE, 240V, 1P,
150A MTS
EXISTING
600A, 240V, 1P
DISCONNECT
EXISTING
METER
CABINET
NEW 600A,
3-POLE, 240V
BY-PASS
ISOLATION
ATS
E-117
T R
A N
S M
I T
T E
R
R
C V
R
2018-201
MMM
JKM
REV. DATE/BY DESCRIPTION
Croft & Associates
3400 Blue Springs Road, Suite 200
Kennesaw, GA 30144
770.529.7714 (p)
770.529.7716 (f) www.croftae.com
CONSTRUCTION DOCS.
C I V
I L
E
N G
I N
E E
R I N
G t h
A
I R
L I F
T
W
I N
G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
P R
O J E
C T
L O
C A
T I O
N
D R
A W
I N
G
C O
N T
A C
T
PROJECT No.
PROJ. OFFICER
DESIGNED
CHECKED
DATE
DRAWING OF
P R
O J E
N
T A
C T
R O
B E
N r o b e r t e r n s t u s a f m i l
S T
U D
Y R
E P
L A
C E
G E
N E
R A
T O
R S
F G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
J. MORGAN
A 2019-02-19 35% DESIGN
B 2019-05-24 65% DESIGN
C 2019-08-21 REVISED 65% DESIGN
D 2020-07-01 100% DESIGN
2020-07-24
E 2020-07-24
FINAL DESIGN
E-117
EXISTING 1001-TRANSMITTER RCVR EXTERIOR ELEVATION
NOT TO SCALE
E-117
EXISTING 1001-TRANSMITTER RCVR PARTIAL POWER LAYOUT PLAN
1/4" = 1'-0"
PLAN
NORTH
X NEW WORK KEY NOTES:
1. PROVIDE AND INSTALL NEW 150AMP, 3-POLE, 240V, NEMA 3R, 3-WAY MTS
WITH 200AMP RATED CAM-LOCK CONNECTIONS. REFER TO DETAIL 3/E-601
AND 4/E-601 FOR CONNECTION AND OPERATION DIAGRAM.
2. PROVIDE NEW 600AMP, 3-POLE, 240V, NEMA 3R BYPASS ISOLATION ATS.
3. PROVIDE NEW CONDUIT AND FEEDERS (3#1/0, #6G-2"C) FROM NEW 3-WAY
MTS TO NEW ATS.
4. PROVIDE NEW CONDUIT AND FEEDERS [(2) SETS - (3#350KCMIL, #4G-3"C)]
FROM EXISTING SERVICE DISCONNECT TO NEW ATS.
5. PROVIDE NEW CONDUIT AND FEEDERS [(2) SETS - (3#350KCMIL, #4G-2-1/2"C)]
FROM NEW ATS TO EXISTING PANEL "MDP". CONNECT TO AND RE-USE
SLEEVES THRU EXTERIOR WALL INTO PANEL "MDP".
6. PROVIDE NEW GENERATOR:
6.1. GENERATOR TO BE 240V, 1P, 25KW RATED.
6.2. PROVIDE NEW CONTROLS WIRING FROM NEW ATS SWITCH.
6.3. PROVIDE AND EXTEND EXISTING BRANCH CIRCUITRY FOR BLOCK
HEATER AND BATTERY CHARGER FROM EXISTING SOURCE PANEL.
[(2)-2#12, #12G - 3/4"C]
6.4. PROVIDE WITH INTEGRAL DIESEL TANK.
6.5. PROVIDE NEW GROUNDING AND BONDING PER NEC 70, REFER TO DETAIL
1/E-601 FOR FURTHER INFORMATION.
7. CONNECT EXISTING CONDUIT STUB-UPS TO NEW 3-WAY MTS.
8. PROVIDE NEW FEEDERS (3#1/0, #6G) IN EXISTING CONDUITS AND CONNECT
TO NEW GENERATOR.
X DEMOLITION KEY NOTES:
1. REMOVE EXISTING GENERATOR AND ASSOCIATED FEEDERS, WIRES,
AND GROUNDING.
2. LEAVE CONDUITS FROM EXISTING ATS TO EXISTING GENERATOR
FOR REUSE.
3. LEAVE CIRCUITS FOR GENERATOR BLOCK HEATER AND BATTERY
CHARGER IN FOR RE-USE.
4. REMOVE EXISTING ATS ON EXTERIOR WALL OF BLDG 1001.
5. REMOVE CONDUIT AND FEEDERS FROM SERVICE DISCONNECT TO
EXISTING ATS.
6. REMOVE CONDUIT AND FEEDERS FROM EXISTING ATS TO EXISTING
PANEL "MDP". LEAVE IN PLACE SLEEVED CONDUITS FROM WIRE
TROUGH THRU BUILDING WALL FOR RE-USE.
7. REMOVE WIRE TROUGH ON EXTERIOR WALL.
8. REMOVE EXISTING CONVAULT FUEL TANK AND ALL FUEL LINES TO
AND FROM TANK TO EXISTING GENERATOR. SALVAGE TANK FOR
POSSIBLE REUSE AT BLDG 700. REMOVE EXISTING CONCRETE PAD
AND PROVIDE MATCHING GRAVEL TO BE LEVEL WITH
SURROUNDING GRADE.
9. SAW CUT GENERATOR CONCRETE PAD REMOVE CONCRETE
MATERIAL TO ALLOW FOR CONDUIT MODIFICATION FOR NEW
SELECTED GENERATOR WITH INTEGRAL FUEL TANK. PATCH
REMOVED CONCRETE SECTION EVEN WITH EXISTING SLAB.
E-117
EXISTING 1001-TRANSMITTER RCVR PARTIAL RISER DIAGRAM
NOT TO SCALE
E-117
NEW 1001-TRANSMITTER RCVR EXTERIOR ELEVATION
NOT TO SCALE
E-117
NEW 1001-TRANSMITTER RCVR PARTIAL POWER LAYOUT PLAN
1/4" = 1'-0"
PLAN
NORTH
E-117
NEW 1001-TRANSMITTER RCVR PARTIAL RISER DIAGRAM
NOT TO SCALE
GENERAL SHEET NOTES:
1.
SPD - MDP
SPDSPD
2.
SIZING FOR ATS SWITCH IS BASED ON FULL BUILDING SERVICE SIZE. 3-WAY
MTS SWITCH SIZE IS BASED UPON GENERATOR SIZE.
PROVIDE SURGE PROTECTION DEVICES FOR THE UTILITY SERVICE
GENERATOR, ATS, AND LOAD DISTRIBUTION.
Attach 2 FA670325B0006
NEW
GENERATOR
EXISTING
UTILITY
TRANSFORMER
EXISTING PANEL
"DP-1"
NEW
ATS
STEP-UP
TRANSFORMER
EXISTING PANEL
"A-2021"
NEW
GENERATOR
SERVICE DISCONNECT
RELOCATED TRANSFORMER
NEW ATS
NEW
3-WAY MTS
NEW 3-WAY MTS
NEW JUNCTION BOX
NEW HOUSEKEEPING PAD
4'
8'
EXISTING
GENERATOR
EXISTING
UTILITY
TRANSFORMER
EXISTING PANEL
"DP-1"
EXISTING ATS
SERVICE
DISCONNECT
480V/208V, 1P
TRANSFORMER
SERVICE
DISCONNECT
EXISTING PANEL
"A-2021"
EXISTING
STEP-UP 15kVA
TRANSFORMER
EXISTING 2kVA
TRANSFORMER
JUNCTION BOX
EXISTING
ATS 208V,
100AMP
(3) POLE
NEMA 1
N
E
EXISTING GENERATOR
208V, 3P, 35KW, DIESEL
POWERED
#8AWG
EXISTING UTILITY
TRANSFORMER
SERVICE
DISCONNECT
100AMP,
208V, 3P
EXISTING
PANEL DP-1
208V, 3P, 125AMP
MCB
EXISTING
STEP-UP
TRANSFORMER
208/480V, 1P, 15KVA
80A,2P
BLDG
EXISTING 2kVA
TRANSFORMER
JUNCTION BOX
NEW BYPASS
ISOLATION ATS
208V, 150AMP
(4) POLE NEMA 3R
N
E
NEW GENERATOR
208V, 3P, 25KW,
DIESEL POWERED
#8AWG
EXISTING UTILITY
TRANSFORMER
NEW
JUNCTION
BOX
EXISTING
PANEL DP-1
208V, 3P, 125AMP
MCB
EXISTING
STEP-UP
TRANSFORMER
208/480V, 1P, 15KVA
NEW
SERVICE
DISCONNECT
60AMP
FUSED,
208V, 2P, NEMA 3R
EXISTING
FEEDER TO
BLDG 2021
NEW 3-WAY
MTS 208V,
150AMP
(3) POLE
NEMA 3R
E
AUX
SERVICE
DISCONNECT
100AMP,
480V, 1P
EXISTING
PANEL
A-2021
240V, 1P, 60AMP
MCB
EXISTING
480V/208V, 1P
TRANSFOMER
FROM 2300
NEW BYPASS
ISOLATION
ATS 240V,
150AMP
(3) POLE
NEMA 3R
N
E
NEW GENERATOR
240V, 1P, 25KW,
DIESEL POWERED
#8AWG
SERVICE
DISCONNECT
100AMP,
480V, 1P
EXISTING
PANEL
A-2021
240V, 1P, 60AMP
MCB
EXISTING
480V/240V, 1P
TRANSFOMER
EXISTING
FEEDER
FROM 2300
NEW 3-WAY
MTS 240V,
150AMP
(3) POLE
NEMA 3R
AUX
E
E-119
I L
S G
L I D
E S
L O
P
C
2018-201
MMM
JKM
REV. DATE/BY DESCRIPTION
Croft & Associates
3400 Blue Springs Road, Suite 200
Kennesaw, GA 30144
770.529.7714 (p)
770.529.7716 (f) www.croftae.com
CONSTRUCTION DOCS.
C I V
I L
E
N G
I N
E E
R I N
G t h
A
I R
L I F
T
W
I N
G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
P R
O J E
C T
L O
C A
T I O
N
D R
A W
I N
G
C O
N T
A C
T
PROJECT No.
PROJ. OFFICER
DESIGNED
CHECKED
DATE
DRAWING OF
P R
O J E
N
T A
C T
R O
B E
N r o b e r t e r n s t u s a f m i l
S T
U D
Y R
E P
L A
C E
G E
N E
R A
T O
R S
F G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
J. MORGAN
A 2019-02-19 35% DESIGN
B 2019-05-24 65% DESIGN
C 2019-08-21 REVISED 65% DESIGN
D 2020-07-01 100% DESIGN
2020-07-24
E 2020-07-24
FINAL DESIGN
E-119
EXISTING 2021 AND 2300 POWER LAYOUT
1/8" = 1'-0"
PLAN
NORTH
X NEW WORK KEY NOTES:
1. PROVIDE AND INSTALL NEW NEMA 3R, 208V, 4-POLE, 150A BYPASS
ISOLATION ATS SWITCH. PROVIDE A NEW CONCRETE PAD,
ENSURE PAD IS 6" FROM EDGE OF SELECTED EQUIPMENT TO
EDGE OF SLAB FOR NEW ATS, 3-WAY MTS, AND DISCONNECT.
REFER TO DETAIL 4/E-601 AND 5/E-601 FOR OPERATION AND
CONCRETE PAD DETAIL. PROVIDE 100A NEMA 3R, SERVICE RATED
DISCONNECT. PROVIDE NEW FEEDERS (4#1, #8G - 2"C) FROM
UTILITY TRANSFORMER TO NEW DISCONNECT AND ATS. EXTEND
CONCRETE PADS AS NECCESSARY FOR ALL EQUIPMENT.
2. PROVIDE NEW DIESEL POWER GENERATOR:
2.1.
2.2.
2.3.
2.4.
2.5.
2.6.
2.7.
GENERATOR TO BE 208V, 3P, 25KW RATED.
PROVIDE NEW UNDERGROUND CONDUIT AND PROVIDE NEW
FEEDERS FROM NEW GENERATOR TO CONNECT TO NEW
EXTERIOR ATS.
PROVIDE NEW CONTROLS WIRING FROM NEW ATS SWITCH IN
NEW UNDERGROUND 3/4"C.
PROVIDE NEW BRANCH CIRCUITRY FOR POWER TO BLOCK
HEATER AND BATTERY CHARGER. RECONNECT TO EXISTING
BREAKERS IN PANEL "DP-1".
PROVIDE WITH INTEGRAL DIESEL TANK.
PROVIDE NEW GROUNDING AND BONDING PER NEC 70, REFER
TO DETAIL 1/E-601 FOR FURTHER INFORMATION.
REUSE EXISTING CONCRETE SLAB EXTEND AS NEEDED.
3. PROVIDE AND INSTALL NEW 80AMP, 3-POLE, NEMA 3R 3-WAY MTS.
PROVIDE WITH 200AMP RATED CAM-LOCK CONNECTIONS ON
EXTERIOR OF BUILDING. MOUNT ON LEG KIT AT NEW CONCRETE
PAD LOCATION.
4. PROVIDE NEW 1-1/2" CONDUIT FROM NEW GENERATOR TO NEW
3-WAY MTS LOCATION. PROVIDE NEW FEEDERS (4#1, #8G). PROVIDE
NEW CONTROLS CONDUIT AND WIRES IN (3/4"C) FROM NEW ATS.
5. PROVIDE NEW INTERIOR JUNCTION BOX TO ROUTE CONDUCTORS
FROM NEW ATS TO EXISTING PANEL "DP-1".
6. PROVIDE NEW FEEDERS (4#1, #8G - 2"C) AND REUSE PENETRATION
LOCATION TO ROUTE CONDUIT FROM NEW ATS THRU JUNCTION
BOX TO PANEL "DP-1".
7. PROVIDE NEW 100A FUSED AT 60AMP, 208V, 2P NEMA 3R
DISCONNECT MOUNTED IN SAME LOCATION AS REMOVED 2KVA
TRANSFORMER JUNCTION BOX.
8. PROVIDE NEW UNDERGROUND SERVICE FEEDER (3#1, #8G-1-1/2"C)
FROM EXISTING UTILITY TRANSFORMER TO NEW SERVICE
DISCONNECT.
9. PROVIDE NEW FEEDER (3#1, #8G-1-1/2"C) FROM NEW SERVICE
DISCONNECT TO EXISTING 15KVA TRANSFORMER.
10. NOT USED.
11. PROVIDE NEW DIESEL POWER GENERATOR:
11.1.
11.2.
11.3.
11.4.
11.5.
11.6.
GENERATOR TO BE 240V, 1P, 25KW RATED.
PROVIDE NEW CONTROLS WIRING FROM NEW ATS SWITCH.
PROVIDE NEW BRANCH CIRCUITRY FOR BLOCK HEATER AND
BATTERY CHARGER FROM EXISTING PANEL "A-2021". [(2)-2#12,
#12G - 3/4"C]
PROVIDE WITH INTEGRAL DIESEL TANK.
PROVIDE NEW GROUNDING AND BONDING PER NEC 70, REFER
TO DETAIL 1/E-601 FOR FURTHER INFORMATION.
PROVIDE A NEW CONCRETE SLAB FOR GENERATOR, REFER TO
DETAIL 2/E-601 FOR PAD DETAIL. EXTENDS EQUIPMENT PADS
AS NECCESSAY.
12.
13.
PROVIDE NEW EXTERIOR NEMA 3R 150AMP, 3-POLE BYPASS
ISOLATION ATS SWITCH. PROVIDE NEW CONCRETE PAD 6'X4'X12",
ENSURE PAD IS MINIMUM 6" FORM EDGE OF SELECTED EQUIPMENT
TO EDGE OF CONCRETE SLAB. REFER TO DETAIL 5/E-601 FOR
CONCRETE PAD DETAIL.
RE-USE EXISTING CONDUIT AND FEEDERS FROM H-FRAME INTO
BLDG 2021 TO CONNECT TO THE NEW ATS.
14. PROVIDE A NEW PEDESTAL MOUNTED 100AMP, 3-POLE, NEMA 3R
3-WAY MTS. PROVIDE A NEW CONCRETE PAD TO MOUNTED ON,
ENSURE PAD IS MINIUM 6" FROM EDGE OF SELECTED EQUIPMENT
TO EDGE OF CONCRETE PAD.
15. RE-USE AND RELOCATE EXISTING STEP-DOWN TRANSFORMER.
PROVIDE NEW CONDUIT AND FEEDERS (3#1,1#8G - 1-1/2"C) FROM
DISCONNECT TO NEW TRANSFORMER LOCATION. PROVIDE NEW
GROUNDING PER NEC 70.
X DEMOLITION KEY NOTES:
1. REMOVE EXISTING GENERATOR, LEAVE EXISTING CONCRETE PAD
FOR RE-USE.
2. REMOVE ASSOCIATED CONDUITS AND BLOCK HEATER/BATTERY
CHARGER WIRING TO EXISTING GENERATOR.
3. REMOVE EXISTING ATS SWITCH. REMOVE ASSOCIATED CONDUITS,
FEEDERS AND CONTROL WIRES.
4. REMOVE EXISTING 480V/208V, 1P TRANSFORMER FOR RE-LOCATION.
5. LEAVE EXISTING CONDUITS AND FEEDERS INTO BLDG 2021 FOR
RE-USE.
6. REMOVE FEEDER FROM EXISTING PANEL"DP-1" TO STEP-UP 15kVA
TRANSFORMER THAT FEEDS BLDG 2021.
7. REMOVE EXISTING 2kVA, 1P TRANSFORMER THAT IS BEING USED AS
A JUNCTION BOX.
8. REMOVE SERVICE FEEDER (ABOVE GROUND CONDUIT, FEEDERS)
FROM TRANSFORMER TO SERVICE DISCONNECT. LEAVE IN PLACE
UNDERGROUND CONDUIT TO BE RE-USED AND ROUTED TO NEW
ATS LOCATION.
E-119
NEW 2021 AND 2300 POWER LAYOUT
1/8" = 1'-0"
PLAN
NORTH
E-119
BLDG 2300 PARTIAL RISER DIAGRAM (EXISTING)
NOT TO SCALE
E-119
BLDG 2021 PARTIAL RISER DIAGRAM (EXISTING)
NOT TO SCALE
E-119
BLDG 2300 PARTIAL RISER DIAGRAM (NEW)
NOT TO SCALE
E-119
BLDG 2021 PARTIAL RISER DIAGRAM (NEW)
NOT TO SCALE
16. PROVIDE NEW CONDUIT AND FEEDERS (3#1,1#8G - 1-1/2"C) FROM
TRANSFORMER TO NEW ATS.
17. PROVIDE AND INSTALL NEW CONDUIT AND FEEDERS (3#1,1#8G -
1-1/2"C) FROM NEW 3-WAY MTS TO NEW ATS.
18. PROVIDE AND INSTALL NEW CONDUIT AND FEEDERS (3#1,1#8G -
1-1/4"C) FROM NEW GENERATOR TO NEW 3-WAY MTS. REFER TO
DETAIL 2/E-602 FOR UNDERGROUND CONDUIT INSTALLATION
DETAIL.
19. REFER TO DETAIL 2/E-601 FOR INSTALLATION DETAILS.
20. PROVIDE SURGE PROTECTION DEVICES FOR THE UTILITY SERVICE
GENERATOR, ATS, AND LOAD DISTRIBUTION.
SERVICE
DISCONNECT
100AMP,
208V, 3P
NEW DISCONNECT
Attach 2 FA670325B0006
AutoCAD SHX Text
BLDG 2300
AutoCAD SHX Text
BLDG 2021
AutoCAD SHX Text
BLDG 2300
AutoCAD SHX Text
BLDG 2021
AutoCAD SHX Text
BLDG 2300
AutoCAD SHX Text
BLDG 2300
AutoCAD SHX Text
BLDG 2021
AutoCAD SHX Text
BLDG 2021
Jeff Morgan GA Stamp - JKM - Simple
1036681116C Cross-Out
24"
24"
24" 24"
GENERATOR PAD
3/4" X 10'
COPPER-CLAD
GROUND ROD.
TYPICAL
#1/0 AWG BARE
COPPER
ENGINE-GENERATOR
SET PAD GROUND
BURIED 24" BELOW
GRADE.
#1/0 AWG
BARE
COPPER TO
ENGINE-GENERATOR
SET FRAME.
TO GROUND
ELECTRODE
SYSTEM
#1/0 AWG BARE
COPPER
#1/0 AWG BARE
COPPER TO NEUTRAL
#1/0 AWG BARE
COPPER TO
ENGINE-GENERATOR
SET FRAME.
TEST WELL NOTES:
1. ALL GROUNDING CONNECTIONS SHALL BE IN
CONFORMANCE WITH N.E.C. ARTICLE 250.
2. MAXIMUM GROUND RESISTANCE SHALL NOT
EXCEED 3 OHMS AT THIS POINT.
TEST WELL.
REFER TO
DETAIL
TEST WELL. REFER
TO DETAIL
TEST WELL
3/4" x10'-0"
GROUND ROD
#1/0 AWG COPPER
LOOP (TYPICAL)
GRAVEL BED
POLYMER CONCRETE GROUND
TEST WELL WITH OPEN
BOTTOM CONSTRUCTION
GROUND CLAMP
FINISH GRADE
WEATHERPROOF POLYMER
CONCRETE COVER
MOLDED LETTERING
PLAN
ELEVATION
EXOTHERMIC
WELD
M
I N
12"
PERMANENT
GENERATOR
CONDUIT
1 2
CONDUIT
CABLES CABLES
FEMALE
CONNECTORS
MALE CONNECTORS
BYPASS ISOLATION AUTOMATIC
TRANSFER SWITCH
PG
ATS
LB
EG
3-WAY MTS SWITCH
(ESL POWER OR
APPROVED EQUIVALENT)
1. CONTROLS CONNECTION BETWEEN PERMANENT GENERATOR (PG) AND LOAD BANK (LB). REFER TO
INDIVIDUAL SITE POWER SHEETS FOR CIRCUIT BREAKER SIZING.
2. CONTROLS CONNECTION BETWEEN PERMANENT GENERATOR (PG) AND AUTOMATIC TRANSFER SWITCH
(ATS). REFER TO INDIVIDUAL SITE POWER SHEETS FOR CIRCUIT BREAKER SIZING.
3. CONTROLS CONNECTION BETWEEN AUTOMATIC TRANSFER SWITCH (ATS) AND EMERGENCY GENERATOR
(EG). REFER TO INDIVIDUAL SITE POWER SHEETS FOR CIRCUIT BREAKER SIZING.
4. TAP CONNECTION FROM AUTOMATIC TRANSFER SWITCH (ATS) TO AUGMENTING LOAD BANK. REFER TO
INDIVIDUAL SITE POWER SHEETS FOR CIRCUIT BREAKER SIZING.
5. REFER TO INDIVIDUAL SITE POWER SHEETS FOR CIRCUIT BREAKER SIZING.
6. PROVIDE MULTIPLE LUGS SIZED FOR SERVICE TO ACCOMMODATE CONNECTIONS TO BOTH BUILDING LOAD
AND TO LOAD BANK CONNECTION BOX.
7. PROVIDE CAMLOCK CONNECTIONS SINGLE 200A CONNECTIONS OR IN MULTIPLE IN INCREMENTS OF 200A.
EMERGENCY
PORTABLE
GENERATOR
LOAD
BANK
CABLES
LB
PORTABLE
LOAD BANK
FEMALE CONNECTORS
LOAD BANK CONNECTION
BOX: (ESL POWER TEMP TAP
SERIES OR APPROVED
EQUIVALENT)
NOTE: REQUIRED ONLY FOR
SITES WITH 26kW OR
LARGER GENERATOR.
CONDUIT
TO LOAD
NORMAL UTILITY
POWER
EMERGENCY
POWER
UTILITY
CONDUIT
CONDUIT
LOAD
3-WAY MTS SWITCHES ARE REQUIRED
FOR GENERATORS GREATER THE 25kW.
GENSET PER
ELECTRICAL
DRAWINGS
4000 PSI CONCRETE SLAB ON
GRADE-18" THICK W/#4 AT 12" EACH
WAY TOP AND BOTTOM
STANDBY GENSET
6" MIN,
TYP
4000 PSI CONCRETE SLAB PER PLAN
CONCRETE ANCHOR
FINISH GRADE
1'-0"
TYP
STANDARD HOOK, TYPICAL #4 @
12" O.C
PAD SIZE DETERMINED
BY GENERATOR SIZE.
T
Y P
T Y
P
C L R
3" CLR, TYP UNO
P A
D
S
I Z
E
D
E T
E R
M I N
Y
G
E N
E R
A T
Z
E
CHAMFER EDGE
GENERATOR
GENERATOR
PROVIDE SOIL COMPACTION TO 95%
OF MAXIMUM DENSITY
CB3CB2CB1
ON OFFOFF
PL-LB
PL-GB
CB3CB2CB1
OFF
ONON
PL-LB
PL-GB
NORMAL OPERATION
LOAD BANK TESTING
PERMANENT
GENERATOR
FACILITY ATS
PERMANENT
CONNECTIONS
TEMPORARY
CONNECTIONS
3-WAY SWITCH
EMERGENCY
GENERATOR
LOAD BANK
PERMANENT
GENERATOR
FACILITY ATS
PERMANENT
CONNECTIONS
TEMPORARY
CONNECTIONS
3-WAY SWITCH
EMERGENCY
GENERATOR
LOAD BANK
#4 @ 12" O.C.
ALL EXPOSED EDGES
ALONG TOP OF SLAB
SHALL HAVE A 3/4"
CHAMFER
PROVIDE SOIL
COMPACTION TO 95% OF
MAXIMUM DENSITY
EXISTING
GRADE
NOTE:
4000 PSI CONCRETE PAD WIDTH AND
DEPTH TO BE DETERMINED PER
SELECTED EQUIPMENT (ATS, MTS,
LOAD BANK CONNECTION BOX, FUEL
TANK).
6" MIN,
TYP
ATS, MTS, LOAD BANK CONNECTION
BOX, AND/OR FUEL TANK
MIN.
REV. DATE/BY DESCRIPTION
Croft & Associates
3400 Blue Springs Road, Suite 200
Kennesaw, GA 30144
770.529.7714 (p)
770.529.7716 (f) www.croftae.com
CONSTRUCTION DOCS.
C I V
I L
E
N G
I N
E E
R I N
G t h
A
I R
L I F
T
W
I N
G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
P R
O J E
C T
L O
C A
T I O
N
D R
A W
I N
G
C O
N T
A C
T
PROJECT No.
PROJ. OFFICER
DESIGNED
CHECKED
DATE
DRAWING OF
P R
O J E
N
T A
C T
R O
B E
N r o b e r t e r n s t u s a f m i l
S T
U D
Y R
E P
L A
C E
G E
N E
R A
T O
R S
F G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
J. MORGAN
A 2019-02-19 35% DESIGN
B 2019-05-24 65% DESIGN
C 2019-08-21 REVISED 65% DESIGN
D 2020-07-01 100% DESIGN
2020-07-24
E 2020-07-24
FINAL DESIGN
E-601
E L
E C
T R
I C
T
A I L
S
2018-201
MMM
JKM
N.T.S.
E-601
TYPICAL GENERATOR GROUNDING DETAIL WITH TEST WELL
N.T.S.
E-601
TYPICAL GENERATOR PAD DETAIL
N.T.S.
E-601
3-WAY MTS, ATS, LOAD BANK CONNECTION DIAGRAM
N.T.S.
E-601
GENERAL ATS, MTS, LOAD BANK CONNECTION
BOX, AND FUEL TANK CONCRETE PAD DETAIL
N.T.S.
E-601
3-WAY MTS OPERATION DIAGRAM
Attach 2 FA670325B0006
ADHESIVE 3/4" DOWEL, AT 8"
SPACING ALL AROUND PERIMETER
OF OPENING, DRILL AND EPOXY
INTO EXISTING CONCRETE (3
ANCHORS MINIMUM EACH SIDE OF
OPENING)
SLAB THICKNESS
TO MATCH
EXISTING (6"
MINIMUM)
CURE CONCRETE AS SPECIFIED FOR
PATCHING, DO NOT REMOVE SUPPORTING
FORMS AND DO NOT LOAD UNTIL CONCRETE
ATTAINS FULL 28 DAYS DESIGN STRENGTH,
4000 PSI.
M
I N
C L
R
M
I N
C L
R
SLAB OPENING
#4 @12" TYP.
EXISTING
STRUCTURAL
SLAB
ROUGHEN SURFACE OR EXISTING
SLAB OPENING TO FULL 1/4" MINIMUM
AMPLITUDE, CLEAN AND SOAK PRIOR
TO POURING CONCRETE
NOTES:
1. ROCK AND/OR ADVERSE SOIL CONDITION MAY BE
PRESENT ON SITE.
2. IF 3'-0" MINIMUM COVER REQUIREMENTS CAN NOT BE
MAINTAINED CONTACT CONTRACTING OFFICER.
FINISHED GRADE
CLEAN BACKFILL
DETECTABLE
WARNING TAPE
1'
6"
SCHEDULE 40 PVC
CONDUIT (AS NEEDED)
CONDUIT SUPPORT.
3'
0" M
IN
IM
U M
FINISHED GRADE
EQUAL
EQUAL
MARKING TAPE
DUCTBANK
SPACERS (48") ON
EBR PVC
AT BASE SPACERS AS NEEDED
MASONRY LEVELING BLOCKS
BASE AND INTERMEDIATE
4000 PSI CONCRETE
(TYPICAL)
(3") MINIMUM SEPARATION
(3") MINIMUM SEPARATION
(3") MINIMUM (TYPICAL)
(3") MINIMUM (TYPICAL)
(18") ON CENTER
#4 REBAR (TYPICAL)
#4 REBAR (TYPICAL)
(TYPICAL)
(TYPICAL)
CENTER
(30") MINIMUM
TYPICAL
TYPICAL H-FRAME
SET-UP INSTALLATION.
PROVIDE
BACK-TO-BACK WELDED
1-5/8" CHANNEL.
1-5/8" CHANNEL BOLTED
TO VERTICAL FRAME,
PROVIDED EVERY 2FT
OR AS NEED FOR
SELECTED EQUIPMENT.
6FT
WIDTH AS REQUIRED
2FT
1FT
CONCRETE
FOUNDATION
EQUIPMENT
1-5/8" STEEL
CHANNEL CROSS
SUPPORTS
FEEDER CONDUIT
UNITSTRUT
BRACE
CONDUIT CLAMP
ROOFTOP
CONDUIT
SUPPORT
BLOCKS
(SITTING ON
TOP OF
EXISTING
ROOF)
FINAL GRADE LEVEL
18" MIN.
5' MIN. POLE DEPTH
SLACK
DISCONNECT AND/OR METER
TREATED CLASS 5 POLE,
32FT POLE, MAINTAIN
MINIMUM SECONDARY
CONDUCTORS HEIGHT OF
16FT ABOVE GRADE
2.25"
LATCH
2"
1"
0.5"
APPROX
36"
POST
ABOVE
GROUND
2.25"
STANDARD
HINGE
HINGE
GATE
OPENING
36"
GATE
LATCH
MIN - 6"
24"
GROUND LEVEL
RATED CAULK OR APPROVED
EQUAL, MINIMUM 25mm (1") DEEP
(1/2") MINIMUM
NON-SHRINK OR
PACK BOTH ENDS OF SLEEVE
WITH 3M FIRE DAM 150 3 HOUR
EPOXY GROUT
PACK WITH OAKUM
WALL
AS REQUIRED
CORE DRILL HOLE
STEEL CONDUIT
GALVANIZED RIGID
ADHESIVE 3/4" DOWEL, AT 8"
SPACING ALL AROUND PERIMETER
OF OPENING, DRILL AND EPOXY
INTO EXISTING CONCRETE (3
ANCHORS MINIMUM EACH SIDE OF
OPENING)
SLAB THICKNESS
TO MATCH
EXISTING (6"
MINIMUM)
CURE CONCRETE AS SPECIFIED FOR
PATCHING, DO NOT REMOVE SUPPORTING
FORMS AND DO NOT LOAD UNTIL CONCRETE
ATTAINS FULL 28 DAYS DESIGN STRENGTH,
4000 PSI.
M
I N
C L R
M
I N
C L R
SLAB EXTENSTION
#4 @12" TYP.
EXISTING
STRUCTURAL
SLAB
ROUGHEN SURFACE OR EXISTING
SLAB OPENING TO FULL 1/4" MINIMUM
AMPLITUDE, CLEAN AND SOAK PRIOR
TO POURING CONCRETE
REV. DATE/BY DESCRIPTION
Croft & Associates
3400 Blue Springs Road, Suite 200
Kennesaw, GA 30144
770.529.7714 (p)
770.529.7716 (f) www.croftae.com
CONSTRUCTION DOCS.
C I V
I L
E
N G
I N
E E
R I N
G t h
A
I R
L I F
T
W
I N
G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
P R
O J E
C T
L O
C A
T I O
N
D R
A W
I N
G
C O
N T
A C
T
PROJECT No.
PROJ. OFFICER
DESIGNED
CHECKED
DATE
DRAWING OF
P R
O J E
N
T A
C T
R O
B E
N r o b e r t e r n s t u s a f m i l
S T
U D
Y R
E P
L A
C E
G E
N E
R A
T O
R S
F G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
J. MORGAN
A 2019-02-19 35% DESIGN
B 2019-05-24 65% DESIGN
C 2019-08-21 REVISED 65% DESIGN
D 2020-07-01 100% DESIGN
2020-07-24
E 2020-07-24
FINAL DESIGN
E-602
E L
E C
T R
I C
T
A I L
S
2018-201
MMM
JKM
N.T.S.
E-602
TYPICAL CONCRETE SLAB REPAIR DETAIL
N.T.S.
E-602
TYPICAL DIRECT BURIED CONDUIT TRENCH
N.T.S.
E-602
TYPICAL CONCRETE ENCASED
DUCT BANK DETAIL
N.T.S.
E-602
TYPICAL H-FRAME DETAIL
N.T.S.
E-602
ROOFTOP CONDUITS SUPPORT DETAIL
N.T.S.
E-602
NEW SERVICE POLE DETAIL
N.T.S.
E-602
NEW PEDESTRIAN GATE DETAIL
N.T.S.
E-602
TYPICAL EXTERIOR WALL PENETRATION DETAIL
N.T.S.
E-602
TYPICAL CONCRETE EXTENSTION REPAIR DETAIL
Attach 2 FA670325B0006
AutoCAD SHX Text
MAX. 60" AFF
AutoCAD SHX Text
WIDTH AS REQ'D
EXISTING 240V,
1P, 53KW
GENERATOR
EXISTING
ATS
EXISTING
PANEL
"C"
EXISTING
PANEL
"B"
EXISTING
PANEL
"MDP"
METER
SERVICE
DISCONNECT
EXISTING
500GAL
CONVAULT
FUEL TANK
T E
M P
O R
A R
Y
G E
N E
R A
T O
R
TEMPORARY WEATHER PROOF
SERVICE DISCONNECT AND ATS
480V/208V, 1P
TRANSFORMER
SERVICE
DISCONNECT
EXISTING PANEL
"A-2021"
TEMPORARY
GENERATOR
TEMPORARY WEATHER PROOF
SERVICE DISCONNECT AND ATS
PHASING NOTES:
1. PROVIDE A TEMPORARY GENERATOR TO MATCH THE SITE
VOLTAGE AND PHASES, SIZED APPROPRIATELY FOR THE SITE
USAGE.
2. PROVIDE A TEMPORARY WEATHERPROOF DISCONNECT AND
WEATHERPROOF ATS TO BY-PASS AND CONNECT UTILITY
POWER TO THE SITE TO ALLOW DEMOLITION AND NEW WORK TO
BE CONDUCTED.
REV. DATE/BY DESCRIPTION
Croft & Associates
3400 Blue Springs Road, Suite 200
Kennesaw, GA 30144
770.529.7714 (p)
770.529.7716 (f) www.croftae.com
CONSTRUCTION DOCS.
C I V
I L
E
N G
I N
E E
R I N
G t h
A
I R
L I F
T
W
I N
G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
P R
O J E
C T
L O
C A
T I O
N
D R
A W
I N
G
C O
N T
A C
T
PROJECT No.
PROJ. OFFICER
DESIGNED
CHECKED
DATE
DRAWING OF
P R
O J E
N
T A
C T
R O
B E
N r o b e r t e r n s t u s a f m i l
S T
U D
Y R
E P
L A
C E
G E
N E
R A
T O
R S
F G
D O
B B
I N
S
A
S
E R
S
E
G
E O
R G
I A
J. MORGAN
A 2019-02-19 35% DESIGN
B 2019-05-24 65% DESIGN
C 2019-08-21 REVISED 65% DESIGN
D 2020-07-01 100% DESIGN
2020-07-24
E 2020-07-24
FINAL DESIGN
EP-101
P H
A S
I N
G
P
L A
N S
2018-201
MMM
JKM
EP-102
1/8" = 1'
BUILDING 1001 PHASING
EP-102
1/8" = 1'
BUILDING 2021 PHASING
EXISTING
GENERATOR
EXISTING
UTILITY
TRANSFORMER
EXISTING PANEL
"DP-1"
EXISTING ATS
SERVICE
DISCONNECT
EXISTING
STEP-UP 15kVA
TRANSFORMER
EXISTING 2kVA
TRANSFORMER
JUNCTION BOX
T E
M P
O R
A R
Y
G E
N E
R A
T O
R
TEMPORARY
WEATHER PROOF
SERVICE
DISCONNECT AND
ATS
EP-103
1/8" = 1'
BUILDING 2300 PHASING
TEMPORARY WEATHER
PROOF SERVICE
DISCONNECT AND ATS
TEMPORARY
GENERATOR
DIESEL FUEL
TANK
MOBILE SKID
EP-103
N.T.S
PROPOSED TEMPORARY GENERATOR SET-UP
X TEMPORARY GENERATOR KEY NOTES:
1. PROVIDE A TEMPORARY GENERATOR MOUNTED TO A MOBILE SKID TO BE
CONNECTED TO THE SITE WHEN THE EXISTING IN PLACE GENERATOR IS
DECOMMISSIONED OR TAKEN OFF LINE FOR THE NEW WORK TO BE CONDUCTED.
1.1.
1.2.
1.3.
GENERATOR VOLTAGE, PHASES AND POWER OUTPUT SHOULD BE COORDINATED
TO MATCH INDIVIDUAL SITE NEEDS AND REQUIREMENTS.
PROVIDE AND INTEGRAL DIESEL FUEL TANK WITH GENERATOR.
PROVIDE THE NECESSARY CABLING FROM GENERATOR TO TEMPORARY ATS
MOUNTED ON THE SAME MOBILE SKID.
2. PROVIDE A SERVICE RATED WEATHERPROOF DISCONNECT MOUNTED ON THE MOBILE
SKID TO TEMPORARY CONNECT UTILITY POWER THRU TO BY-PASS THE SITE SERVICE
ENTRANCE AND ALLOW NEW WORK TO BE CONDUCTED.
2.1.
2.2.
2.3.
SIZE DISCONNECT APPROPRIATELY FOR SITE SERVICE VOLTAGE, PHASE AND
POWER REQUIREMENTS.
PROVIDE CABLING FROM THE UTILITY SERVICE POINT TO TEMPORARY SERVICE
DISCONNECT.
PROVIDE PROPERLY SIZED FEEDER FROM TEMPORARY DISCONNECT TO
TEMPORARY ATS. BOTH MOUNTED ON THE MOBILE SKID.
3. PROVIDE A WEATHER PROOF ATS MOUNTED ON THE MOBILE SKID. CONNECT FROM
THE TEMPORARY GENERATOR AND TEMPORARY SERVICE DISCONNECT. PROVIDE
PROPERLY SIZES FEEDERS.
3.1.
3.2.
PROVIDE CABLING FROM ATS TO FIRST ELECTRICAL EQUIPMENT THAT WILL
ALLOW BY-PASS OF THE MAIN SERVICE.
PROVIDE CONTROL CABLING FROM THE TEMPORARY ATS TO THE TEMPORARY
GENERATOR.
Attach 2 FA670325B0006
AutoCAD SHX Text
AutoCAD SHX Text
BOS COM SIPER AREA
AutoCAD SHX Text
AutoCAD SHX Text
BOS COM RESERVE ADMIN
AutoCAD SHX Text
AutoCAD SHX Text
BOS COM COMM SUPPORT
AutoCAD SHX Text
AutoCAD SHX Text
BOS COM LMR OFFICE
AutoCAD SHX Text
IT UPS ROOM
AutoCAD SHX Text
UPS
AutoCAD SHX Text
BLDG 2021
AutoCAD SHX Text
BLDG 2125
AutoCAD SHX Text
BLDG 2127
AutoCAD SHX Text
DPT
AutoCAD SHX Text
CONVAULT DIESEL FUEL TANK
AutoCAD SHX Text
TGS 4KW 6.6A
AutoCAD SHX Text
PAPI EAST 10KW 6.6A
AutoCAD SHX Text
PAPI WEST 10KW 6.6A
AutoCAD SHX Text
BAY C
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - G-001 - COVER SHEET |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - G-001 - COVER SHEET |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-100 - Electrical General Notes |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-100 - Electrical General Notes |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-101 - HANGAR 5 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-101 - HANGAR 5 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-102 - VEHICLE FUELING STATION 513 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-102 - VEHICLE FUELING STATION 513 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-103 - 531 POL |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-103 - 531 POL |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-104 - MEDICAL 550 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-104 - MEDICAL 550 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-105 - COMM_LIFT STATION 700 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-105 - COMM_LIFT STATION 700 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-106 - 94 SFS - 701 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-106 - 94 SFS - 701 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-107 - LIFT STATION 708, BDLG - 745 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-107 - LIFT STATION 708, BDLG - 745 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-108 - GCA 739 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-108 - GCA 739 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-109 - ATC 740 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-109 - ATC 740 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-110 - LIFT STATION - 805 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-110 - LIFT STATION - 805 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-111 - DINING FACILITY 806 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-111 - DINING FACILITY 806 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-112 - NCC_FINANCE 827 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-112 - NCC_FINANCE 827 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-113 - LIFT STATION - 828 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-113 - LIFT STATION - 828 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-114 -WING HQ 838 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-114 -WING HQ 838 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-115 - ENTRY CONTROL FAC 866 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-115 - ENTRY CONTROL FAC 866 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-116 - LIFT STATION - 955 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-116 - LIFT STATION - 955 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-117 - 1001 TRANSMITTER RCVR |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-117 - 1001 TRANSMITTER RCVR |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-118 - ILS - 2012 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-118 - ILS - 2012 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-119 - ILS 2021 & 2300 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-119 - ILS 2021 & 2300 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-120 - ILS - 2125 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-120 - ILS - 2125 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-121 -ILS - 2127 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-121 -ILS - 2127 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-122 - 2173 MIDFIELD VAULT |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-122 - 2173 MIDFIELD VAULT |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-123 - 2174 LIGHT VAULT WEST END |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-123 - 2174 LIGHT VAULT WEST END |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-124 -2195 LIGHT VAULT EAST END |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-124 -2195 LIGHT VAULT EAST END |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-125 - 2313 LIFT STATION |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-125 - 2313 LIFT STATION |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-126 - BLDG 732 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-126 - BLDG 732 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-127 - BLDG 545 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-127 - BLDG 545 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-128 - BLDG 755 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-128 - BLDG 755 |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-601 - ELECTRICAL DETAILS |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-601 - ELECTRICAL DETAILS |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-602 - ELECTRICAL DETAILS |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - E-602 - ELECTRICAL DETAILS |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - EP-101 -PHASING |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - EP-101 -PHASING |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - EP-102 -PHASING |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - EP-102 -PHASING |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - EP-103 -PHASING |
| 2018-201 - DOBBINS STUDY_REPLACE GENERATORS - EP-103 -PHASING |
File details come from the government source that posted it. Updated .