This is a Request for Information (RFI) for a telecommunications cabling project issued by the 910th CONF/PK unit of the US Air Force. The document contains questions and answers about a cable installation project, with key details including cable specifications, installation methods, and site characteristics. The project involves Category 6 (CAT6) cabling, with blue cables and orange RJ45 jacks, and will involve approximately 44 surface-mounted drops due to concrete barriers, while most drops will be routed inside walls. Ceiling heights vary from 8-12 feet in rooms, with some areas reaching up to 15 feet high. The RFI clarifies that existing floor plans showing Cat 3, Navy, Afnet, Coaxial, and Afnet Phone cabling are for reference only, and no NIST SP 800-171 assessment is required. Potential vendors must submit any questions by 10:00 AM Eastern on Friday, 5 September 2025, to the specified contact at joseph.perry.14@us.af.mil.

View the file

Other files

Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA665625Q0015 Attachment 5 Page 1

Request for Information

INSTRUCTIONS: Please complete this form if your firm has questions concerning any aspect of the solicitation. All questions must be submitted to 910th CONF/PK by 10:00 AM Eastern on Friday, 5 September 2025. Late inquiries/questions will not be entertained.

Inquiries may be submitted to the following addresses.

Address: 910th CONF/PK Attn: Joseph Perry 3976 King Graves Rd Vienna OH 44473

E-Mail: joseph.perry.14@us.af.mil

Name & Address of Firm: ___ ___________________

Point of Contact: ___ Phone No. ______ Fax No._________________________

Page Question

Is there a drawing showing existing cable tray/J-hooks runs Answer: There are no existing cable trays / J-hook runs

Is there a preferred Manufacturer for the Category 6 cabling, jacks and patch panels?

Answer: No preferred manufacturer

What is the ceiling height and height above the ceiling to building structure Answer: Ceiling height varies, standard hallways approximately 9 feet, rooms 8 – 12 foot, ceiling height above ranges from 1- 4 feet. Room 132 is approximately 15 high, unknown height above drop ceiling.

4.4.6.3 & Pg 6

States blue for NIPRNET Cabling and Orange for RJ-45. Page 6 Show white outlet in port A and Blue for port B. Please clarify the cable and jack colors for the project.

Answer: CAT6 cable is blue, RJ45 CAT6 jacks are orange.

The 1st and 2nd floor plans list Cat 3, Navy, Afnet, Coxial, and Afnet Phone cabling.

This contradicts the cabling called out in the SOW.

Answer: Those are the old cable drop locations and listings, for government reference.

Will the new drop locations be surface mounted or routed inside the walls?

Answer: Most drops will be routed in walls, approximately 44 drops will be surface mounted due to concrete.

Is NIST SP 800-171 assessment required for this project?

Answer: This assessment is not required.