Hangar 7 Compressor-M1 Drawing.pdf

PDF 157 KB Posted

Attached to
TWO AIR COMPRESSORS AND RECEIVER TANK Federal contract opportunity
Solicitation number
FA660626Q0008
Issued by
Department of the Air Force Reserve Command

About this file

This document is a technical specification and schematic for a compressed air system installation. The specification details the complete compressed air piping system, including all required equipment, components, and installation requirements for a facility shop air system.

The compressed air system consists of three primary components specified in detailed schedules: two rotary screw air compressors rated at 95 CFM minimum capacity operating at 240 volts, single-phase, 60 Hz with approximately 977 lbs weight each; one refrigerated air dryer with a 2 PSIG pressure drop, 200 CFM rated flow, designed for 150 PSIG operation, using R513A refrigerant; and one vertical carbon steel compressed air receiver with 400-gallon capacity, designed for 200 PSIG operation, measuring 36 inches diameter by 101 inches height, weighing 662 lbs. The system includes comprehensive filtration with particle removal down to 0.01 micron for coalesced liquid, water, and oil removal at 235 CFM rated capacity. All piping connections must be soldered copper, and the contractor is responsible for providing miscellaneous steel support, mechanical equipment pads, and all equipment as part of the complete compressed air system. The system incorporates automatic tank drain, routing to an oil-water separator, pressure regulators with gauges, automatic drain valves, particulate filters, and a coalescer filter with collection device. Additional specifications require a low-sound enclosure rated at 69 dBA and a minimum system pressure of 145 PSIG.

View the file

Other files for this federal contract opportunity

Other files attached to TWO AIR COMPRESSORS AND RECEIVER TANK, newest first.
File Type Posted
RFI 3 AIR COMPRESSORS.docx DOCX document
Breakers.jpg JPG image
RFI 2 AIR COMPRESSORS.docx DOCX document
PHOTOS OF EXISTING SYSTEM.pdf PDF
Updated Technical Requirements Air Compressors.pdf PDF
RFIs and Answers hangar 7 Air Compressors.pdf PDF
FA660626Q0008 CLAUSE SET.pdf PDF
Salient Features Air Compressors and Receiver Tank.docx DOCX document
Solicitation CLIN Schedule Air Compressors and Receiver Tank.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

4 25

COLLECTION DEVICE

A

AND SIZED

BASED ON CFM AND PRESSURE REQUIREMENTS.

A

IR

R

ES

ER

VE

B

AS

E, M

A

H

AN

G

AR

-N

EW

C

O M

PR

ES

SE

D

A

IR

S

YS

(Min) 95 25 240 977 ,2,3 95 25 240 977 ,2,3

2. LOW SOUND ENCLOSURE (69 dba)

3. MIN PRESSURE 145 PSIG

AMPS

2 200 150 100 513 20 115 1 263 ,2,3

2. FILTRATION: Removal down to 1micron including coalesced liquid, water and oil; 235 CFM rated; 1 ½” FPT connections; Auto drain; Element indicator (PRE-DRYER)

3. FILTRATION: Particle removal down to 0.01micron including coalesced liquid, water, & oil; 235 CFM rated; 1 ½” FPT connections; Auto drain; Element indicator (PRE-DRYER)

200 400 36 101 H 662 ,3

SAFETY VALVE, PRESSURE GAUGE,

3. FILTRATION: Particle removal down to 0.01micron including coalesced liquid, water, & oil; 235 CFM rated; 1 ½” FPT connections; Auto drain; Element indicator (PRE-RECIEVER)

ALL PIPING CONNECTIONS SHALL BE SOLDERD COPPER.