Request_for_Information_21May2018.docx
DOCX document 12 KB Posted
- Attached to
- Replace Generators Federal contract opportunity
- Solicitation number
- FA6606-18-R-0009
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Responses_to_RFI_18May2018.docx | DOCX document | |
| Responses_to_RFI_051518.docx | DOCX document | |
| 2017_Generator_Replacement_Project__-_SOW_(Revised_15_May_2018).docx | DOCX document | |
| Site_Visit_Sign_In_Sheet.pdf | ||
| Revised_Generator_Replacement_Project-SOW.docx | DOCX document | |
| Responses_to_RFI_051018_(with_TBD).docx | DOCX document | |
| Generators_SOW.pdf | ||
| B1800_Electrical_-_Legend,_Schedules_and_Power_Plan_Demo.pdf | ||
| B7070_As-Build_One_Line_Diagram_new_work_and_demo.pdf | ||
| B2450_Electrical_Panel_Schedules_and_Riser_Diagram.pdf | ||
| B7707_As-Build_One_Line_Diagram.pdf | ||
| Wage_Rates_12Apl2018.pdf | ||
| Bid_Schedule.pdf | ||
| B7070_Panel_Schedules_and_One_Line_Diagram.pdf | ||
| FA660618R0009_Solicitation_for_Generators.pdf | ||
| B2450-_As-build_Riser_Diagrams_and_Luminaire_Details.pdf | ||
| Generators_General_Requirement.pdf |
Show all 17
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Request for Information – 21 May 2018
Question 1:
1 - Scope of Work for Building 2450 says "If existing branch wiring, connections and conduit in good condition re-use them otherwise replace and install new in accordance to the latest NEC." Since this generator is an outdoor unit, is it your intention to excavate for new conduits if necessary or may we assume that existing conduits are intact for bidding purposes? If new, please provide distance or scaled drawing of distance of underground conduits to be replaced.
Response: The existing conduits are to be considered intact and available for re-use.
Question 2:
2- Is the bypass function of the transfer switch, which can be integral to the ATS or separate, the same double-throw switch selector that is indicated on the one-line diagram or is there a requirement for a bypass feature separate from this selector switch?
Response: The requirement is for a by-pass for the ATS. The double-throw switch shown on the one-line diagram is not intended to function as an ATS by-pass.