This Request for Quotation solicits commercial services for maintenance and repair of fire protection systems at Aviano Air Base and Ghedi Air Base in Italy. The requirement is set aside for Italian vendors in accordance with FAR 5.202(a)(12). A site visit will be held on 22 June 2023 at 08:00 local time at LVIS GATE Via Loc. Tornielli 18 Roveredo in Piano, PN AREA F - Flightline Aviano AB, Italy. Offerors must RSVP for the site visit by 20 June 2023. Any other requests for information must be submitted by 26 June 2023. The performance work statement details the required services and includes appendices on inspection addendums and fire protection systems. The solicitation is being conducted by the Department of the Air Force United States Air Forces in Europe - Air Forces Africa.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bldg# 43 – November 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

Standpipe and Hose Systems

1. Point 13.8.1 (3) of NFPA 25 ed. 2020: The Fire department connection does not have a cap. – Providing of a FDC cup:

#1 EMME ANTINCENDIO UNI 70 FDC CUP

0831 Total of: €

2. Point 13.8.1 (5) of NFPA 25 ed. 2020: The Fire department connection does not have identification sign. – Providing and installing of a proper FDC Sign:

#1 450 x 300 FIRE DEPARTMENT CONNECTION sign

Total of: €

3. Hose Cabinets show a little rust and damaged – It is advisable to replace the hose cabinets:

#4 EMME ANTINCENDIO UNI 45 Hose cabinet red 375X600HX200 1149A #4 EMME ANTINCENDIO Safe window 217X120 COD. 2155 #5 Duty hours labor

Appendix A “Addendum - RFQ FA568223Q0022”

Bldg# 110 – October 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#7 EMME ANTINCENDIO sign for Manual call points CAR1006 #1 Duty hour

Total : €

2. The activation matrix is incorrect, when the tampers are activated no audible or visual indicator of the supervision signal is generated, and the FACP display does not change status.

3. The activation of the mass notification system is indicated as an input and not as an output, according to the matrix moreover, it should activate an audible or visual indicator of the supervision signal, and should transmit the fire supervision signal to the firefighters of the base.

– Software reconfiguration of the 2 input modules that interface the tampers to the FACP and Production of a new and correct activation matrix

#1 documentation on electronic media #2 hour labor

Total of: €

4. Once activated, the module connected to the sprinkler system trim circuit pressure switch gives a fault and not an alarm signal. – Informational comment - If the sprinkler system is activated, the alarm signal is generated by a flow switch installed on the riser.

5. Once the backflow preventer isolation valves tamper are activated, no signal or notification is reproduced by the FACP, a silent alarm is activated which sends a "supervisor" alarm signal to the Monaco transceiver. – See point 2

6. The FACP does not have the ability to download the status of the detector chamber values. No smoke detectors with chamber values greater than 49% were found. – It is recommended to install a serial communication card (RS-232 or RS-485) for the new AM2000, AM4000 and AM6000 control panels.

#1 Notifier RS232/485 serial output interface board with CEI ABI protocol SIB600-OEM #1 duty hour

Total of : €

Wet Pipe Fire Sprinkler Systems

7. The automatic drain valve is not installed in correct position, (it should be installed at the lowest point of the pipes to drain the residual water). – “The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve in areas subject to freezing”.

Relocation of the automatic drip valve:

Various fittings for horizontal installation #4 hour labor

Total : €

8. Since the last six-monthly inspection, changes have been made to the system with the implementation of the automatic drain valve on the pipeline arriving from FDC and related drain piping. However, since no valves have been installed to seal the drains, and since the diameter of the pipes is not sufficient to discharge the entire water flow during the Main Drain Test, its execution is not an easy operation, moreover the water that escapes abundantly risks damaging the heating system. – (to be carried out only after point 7) It is recommended to modify the drain pipes by adjusting the diameters to the valves/drains, and to install ball valves to allow the normal execution of the main drain test.

Various fittings and assorted materials #3 VIKING 2" DN50 Ball Valve R850D0200 #8 hour labor

Total : €

Bldg# 113 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#2 Notifier Plexiglass sign for Manual call points MCP-PLEX #1 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

Bldg# 147 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#7 Notifier Plexiglass sign for Manual call points MCP-PLEX #1 1/2 Duty hour

Total : €

DRY STANDPIPE AND HOSE SYSTEM:

1. 5 hoses 20 meters DN45mm to replace, 5 saddle to put – Standpipe hoses not compliant with UNI 804, To be replace with:

#5 EMME ANTINCENDIO UNI 45 20 MT. Stand pipe hose 0614 #5 EMME ANTINCENDIO UNI 45-70 Stand pipe hose saddle 1060-1 #1 Normal Duty Hours Labor

Total of : €

2. There isn't the automatic drain valve as per point 8.17.2.6 of NFPA 13 Ed 2013 – “The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve in areas subject to freezing”.

Installation of a automatic drip valve:

#1 Viking Automatic Ball Drip Valve, ½” Model B-1 Various fittings for horizontal installation #4 hour labor

Total : €

WET PIPE SPRINKLER SYSTEMS:

3. There isn't the automatic drain valve as per point 8.17.2.6 of NFPA 13 Ed 2013 – See point “2”

4. During main drain test some water gushes out of the PVC funnel located under the backflow preventer and connected to the PVC drain pipe, the room floods completely. – The leaking water seeps through the wall and floods the electrical room. It is advisable to seal the pipes:

#1 Assorted material #2 hour labor

Total of:

Bldg# 149 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#11 Notifier Plexiglass sign for Manual call points MCP-PLEX #2 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

2. The FACP does not have the ability to download the status of the detector chamber values. – It is recommended to install a serial communication card (RS-232 or RS-485) for the new AM2000, AM4000 and AM6000 control panels.

#1 Notifier RS232/485 serial output interface board with CEI ABI protocol SIB600-OEM #1 duty hour

Total of : €

WET PIPE SPRINKLER SYSTEMS:

3. The electric heater doesn't respond to the termostat and runs continuously – Informational comment

4. There isn't the automatic drain valve as per point 8.17.2.6 of NFPA 13 Ed 2013 and per point

16.12.7 of NFPA 13 Ed 2019. – “The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve in areas subject to freezing”.

Installation of a automatic drip valve:

Viking Automatic Ball Drip Valve, ½” Model B-1 Various fittings for horizontal installation #4 hour labour

Total : €

Standpipe and Hose System:

5. There isn't the automatic drain valve as per point 8.17.2.6 of NFPA 13 Ed 2013 and per point

16.12.7 of NFPA 13 Ed 2019. – See point “4”

Bldg# 170 – April 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time:

DETECTION SYSTEM

1. In case of a device disabled, the FACP is not able to send any signal of out of service to the F.D.

as required at par. 5.5.3.2. of UNI 9795 - Ed. 1999, Ed. 2005, Ed. 2010 and Ed. 2013. – Installation of a Box containing the output modules necessary to signal exclusions (one for each programmed zone) And programming of the FACP. Programming of a new "supervisory" ZID in the ECC Monaco computer.

#1 metal electrical box CEB CBSPD4.30.16 400x300x160 #2 Notifier CMX-10RME 10 RELAY OUTPUTS MODULE #3 Notifier M701 single output Addressable module M701E #3 DIN rail mounting clip for M7xx series modules. Notifier M200E-DIN Various materials for electrical wiring and short piping.

#8 hour labor

Total of : €

2. Duct Detector in corridor 46 without repeater as required at par. 5.4.4.6 of UNI 9795 Ed. 2013.

- Installation of a Optic repeater:

#1 NOTIFIER VISUAL/ACOUSTIC REPEATER INDICATOR

#2 Teaflex Metal flexible conduit. 20mm TEAL20G #2 Teaflex Fixed Male thread. Brass fittings with metallic continuity 20mm

TEAEXCMMFG020

#1 Legrand Metal Box. 192X168X80 ALU VERNIC LEG387743 #3 Berica Cavi Fire Cable 2x1 mm² BECB5602100FRM #2 hour labor

Total of : €

3. The FACP does not have the ability to download the status of the detector chamber values. No smoke detectors with chamber values greater than 49% were found. – It is recommended to install a serial communication card (RS-232 or RS-485) for the new AM2000, AM4000 and AM6000 control panels.

#1 Notifier RS232/485 serial output interface board with CEI ABI protocol SIB600-OEM

WET PIPE SPRINKLER SYSTEMS:

4. There are not the correct number of Spare sprinkler heads as per point 5.4.1.5 of NFPA 25-20 Ed 2019. Missing 2 Sprinkler heads. – Provide of a correct number of spare sprinkler heads:

#2 VIKING Standard Response pendent Sprinkler 68° 12987FB

Total : €

5. There isn't the automatic drain valve as per point 8.17.2.6 of NFPA 13 Ed 2013 and per point

16.12.7 of NFPA 13 Ed 2019. – “The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve in areas subject to freezing”.

Installation of a automatic drip valve:

#1 Viking Automatic Ball Drip Valve, ½” 04292B Various fittings for horizontal installation #4 hour labor

Bldg# 172 – November 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of proper signs in accordance with ISO 7010 and UNI 9795.

#20 EMME ANTINCENDIO sign for Manual call points CAR1006 #2 Duty hour

Total :

2. All warning devices are controlled by two output modules, but from the floor plan, a module is installed for each device. - The system installer claims to have removed all output modules to remedy the synchronization problem of the strobe lights warning devices. One solution is the installation of synchronizable warning devices:

#18 Notifier Optical and acoustic fire alarm device for indoor installation. Synchronizable

DSE3-23 HW

#8 normal duty hour Labor

Total of : €

3. The FACP does not have the ability to download the status of the detector chamber values. No smoke detectors with chamber values greater than 49% were found. – It is recommended to install a serial communication card (RS-232 or RS-485) for the new AM2000, AM4000 and AM6000 control panels.

#1 Notifier RS232/485 serial output interface board with CEI ABI protocol SIB600-OEM #1 duty hour

Total of : €

WET PIPE SPRINKLER SYSTEMS:

4. Gaskets are damaged and one is missing – Provide and installing of the gaskets

Total of : €

5. Missing the Fire Dept Connection signs and the two caps. – Providing and installing of proper FDC sign and two FDC caps.

#1 “FIRE DEPARTMENT CONNECTION” sign

#2 EMME ANTINCENDIO UNI 70 FDC CUP 0831

#1 normal duty hour Labor

6. Point 13.8.1 (7) of NFPA 25 ed. 2020: The Fire department connection does not have an automatic drain valve. – “The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve in areas subject to freezing”.

Installation of a automatic drip valve:

#1 Viking Automatic Ball Drip Valve, ½” Model B-1 Various fittings for horizontal installation

Bldg# 176 – October 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#8 EMME ANTINCENDIO sign for Manual call points CAR1006 #1 Duty hour

Total : €

2. The FACP does not have the ability to download the status of the detector chamber values. – It is recommended to install a serial communication card (RS-232 or RS-485) for the new AM2000, AM4000 and AM6000 control panels.

#1 Notifier RS232/485 serial output interface board with CEI ABI protocol SIB600-OEM #1 hour labor

Bldg# 176-B – August 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#3 Notifier Plexiglass sign for Manual call points MCP-PLEX #1 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

2. The FACP does not have the ability to download the status of the detector chamber values. - Installation and programming of the appropriate additional module in the FACP

#1 Notifier RS232/485 serial output interface board with CEI ABI protocol SIB600-OEM

Bldg# 178-11 – August 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#5 Notifier Plexiglass sign for Manual call points MCP-PLEX #1 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57%

Bldg# 179 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

WET PIPE SPRINKLER SYSTEM

1. There are not the correct number of Spare sprinkler heads as per point 5.4.1.5 of NFPA 25-20 Ed 2019. present 10 spare heads out of 12. – Missing one pendant Sprinkler heads and 2 upright Sprinkler heads. Providing 2 sprinkler heads

#1 VIKING Standard Response Upright Sprinkler 68° 13001AB #1 VIKING Standard Response pendent Sprinkler 68° 12987FB

TOTAL OF: €

2. There isn't a Fire Dept Connection sign as per point 8.17.2.4.7.1 of NFPA 13 Ed 2013 and Ed 2016, and as per Table A.16.17 (Sprinkler System Signage Summary) of NFPA 13 Ed 2019. – Providing and installing of a proper FDC Sign:

#1 450 x 300 FIRE DEPARTMENT CONNECTION sign

Total of: €

3. There isn't the automatic drain valve as per point 8.17.2.6 of NFPA 13 Ed 2013 – “The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve in areas subject to freezing”.

Installation of a automatic drip valve:

#1 Viking Automatic Ball Drip Valve, ½” Model B-1 Various fittings for horizontal installation #4 hour labor

Total : €

4. The two FDC caps are missing and Gaskets are damaged. – Installation of a FDC cup and Providing and installation of 2 2 ½” gaskets:

#2 EMME ANTINCENDIO UNI 70 FDC CUP 0831

Total: €

5. Main drain test cannot be performed because the drain pipe, immediately after the drain valve, makes the water flow into a funnel and enters in a smaller pipe without watertight closure. All the water gushes from the funnel into the sprinkler room. – Seal the Drain valve with the water drain.

Various pipe fittings and hangers #2 hours labour

Bldg# 264 – August 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#3 Notifier Plexiglass sign for Manual call points MCP-PLEX #1 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57%

Bldg# 265 – November 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

FIRE PUMP SYSTEM

1. The priming pressure of FP-2 pump is calibrated too low, the calibration is feasible by accessing the "programming" level from the control panel which however requires an unknown password, the Water shop staff could not help Sias. When turned on, it produces abnormal noises and vibrations, debris leaked from the engine cooling fan, apparently pieces of gasket. It is not possible to further adjust the glands.

The FP-1 pump has a problem that appears to be motor-impeller alignment, the gland does not remain in place and damages the motor shaft, despite this, the pump group is free from friction and the rotation of motor and impeller turns regularly in the absence of abnormal noises or vibrations. - For the overhaul of the pumps, (at least necessary for the FP-2), the cost should be (it is only an estimate, the precise calculation will be possible only after the specialized company has received and inspected the pump) of € 3000,00.

However, there is the big problem of handling it, being installed inside a pit, and not being able to lift it with an overhead crane or a mobile crane. An inspection to understand if an alternative solution is possible, for example by removing the ventilation grilles installed in the south wall of the building, with our staff, and a representative of the Water shop and C.E..

2. The two 10” butterfly valves of the test circuit no longer close properly and need to be replaced.

– To be replace with:

#2 La T.I.S. Butterfly Valve Wafer DN250 PN16 Latis ART D102 #6 Normal Duty Hours labor

TOTAL OF: €

Bldg# 407 – December 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of proper signs in accordance with ISO 7010 and UNI 9795.

#20 EMME ANTINCENDIO sign for Manual call points CAR1006 2 Duty hour

Total : €

2. The warning device located at the exit of the south stairs on the first floor has the acoustic component non-functioning – Replacement of the warning device

#1 Notifier Optic acoustic warning device PAN1-EU #1 hour labor

Total of : €

3. In the event of a fire alarm, there is no longer the HVAC shutdown (even if the related L2M16 module is working correctly) – Reconnection of the trip coil

#1 hour labor

Total of : €

4. The FACP does not have the ability to download the status of the detector chamber values. No smoke detectors with chamber values greater than 49% were found. – It is recommended to install a serial communication card (RS-232 or RS-485) for the new AM2000, AM4000 and AM6000 control panels.

#1 Notifier RS232/485 serial output interface board with CEI ABI protocol SIB600-OEM

Bldg# 410 – October 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#20 EMME ANTINCENDIO sign for Manual call points CAR1006 #2 Duty hour

Total : €

2. The zones partition does not comply with the requirements of paragraph 5.2.6 of the UNI 9795 Ed.2005, Ed.2010 and Ed.2013. ..."5.2.6: The detectors installed in hidden spaces (under raised floors, above false ceilings, in tunnels and in electrical cable ducts, in air conditioning, aeration and ventilation ducts, etc.) must belong to distinct zones. – Reprogramming of the FACP software.

#1 hour labor

Total of: €

3. Manual pull station L01M12 in the rest condition flashes red, while in the alarm condition the green LED lights up steadily. – The pull station sends the alarm signal correctly, if it is requested that the luminous signals must be unique for all the pull stations, replacement is necessary:

#1 Notifier ADDRESSABLE MANUAL CALL POINTS M5A-RP02SG-N026-01 #1/2 hour labor

Total of: €

4. The description of the programmed modules and detectors indicates only a progressive number, without specifying the position of the device or the function. – Reconfigure the FACP by correctly entering the point descriptions.

#5 hour labor

Bldg# 411 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

FIRE PUMP SYSTEM

1. Two butterfly valve DN150 6 inches to replace (One has a broken handle, the other does not close completely). – To be replace with:

#2 La T.I.S. Butterfly Valve Wafer DN150 PN16 Latis ART D102 #2 La T.I.S. Chain with lock KITLOCK #8 Normal Duty Hours Labor

TOTAL OF: €

Bldg# 416 – October 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of proper signs in accordance with ISO 7010 and UNI 9795.

#8 EMME ANTINCENDIO sign for Manual call points CAR1006 #1 Duty hour

Total : €

2. The sirens sound at intervals of about 5 seconds, probably due to abnormal absorption. – The installed sirens have an average absorption of 49Ma, with the simultaneous activation of all, the total average absorption is 392M, higher than the 250M maximum load supported by the sirens output of the FACP. It is therefore recommended to lay a second control line to be connected to the second siren output.

#50 Mt Berica Cavi Fire Cable 2x1 mm² BECB56C02100FRSB (Sonepar) #8 Duty hour

Bldg# 421 – December 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The FACP does not comply UNI EN 54-2 – Panel without certification to be use in fire protection systems, It is recommended to replace the panel with one certified according to the regulations in force:

#1 Fireclass 8 Zone conventional fire alarm control panel J408-8.

#1 Plastic surface mounting enclosure 400X300 X80 SCA639.4080 #2 CSB 12V 7,2Ah Long Life backup battery GPL1272F2 Various materials for electrical wiring and short piping.

#10 Normal Duty Hours Labor.

Total of : €

2. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of proper signs in accordance with ISO 7010 and UNI 9795.

#3 EMME ANTINCENDIO sign for Manual call points CAR1006 ½ Duty hour

Total : €

3. The zones partition does not comply with the requirements of paragraph 5.2.6 of the UNI 9795 Ed.2005, Ed.2010 and Ed.2013 – Zone 2 has been connected together with zone 1, Reconnect zone 2 to the dedicated zone module.

#1 normal duty hour TOTAL OF: €

4. Control lines not supervised (To be carried out following point "1) Laying and wiring of controlled line dedicated to the warning devices, controlled by EOL monitoring.

#Mt 100 Berica Cavi Fire Cable 4x1 mm² BECB56C04100FRSB (Sonepar) #32 Duty hour

Bldg# 422 – December 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#5 EMME ANTINCENDIO sign for Manual call points CAR1006 #1/2 Duty hour

Total : €

2. The manual station in the warehouse east/south side does not work – To be replaced

#1 Notifier Conventional break glass manual call point with rearmable film M3A-R000SF-

STCK-01

#1 hours labor.

Total: €

Bldg# 424 – December 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. Control lines not supervised - Laying and wiring of controlled line dedicated to the warning devices, controlled by EOL monitoring.

#Mt 60 Berica Cavi Fire Cable 4x1 mm² BECB56C04100FRSB (Sonepar) #24 Duty hour

Total : €

2. The smoke detector SD 2-3 does not activate, the heat detector HD 1-02 has the thermal probe broken and does not activate, The detector HD 1-06 is torn off with the base broken.. – Replacement of the smoke detector and the 2 heat detectors

#2 Notifier Conventional photoelectric smoke detector SD-851E A #1 Notifier Heat detector max. temperature +rise of temperature FD-851RE A #3 Notifier conventional detector base B401 #3 Normal Duty Hours Labor

Bldg# 428 – November 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of proper signs in accordance with ISO 7010 and UNI 9795.

#2 EMME ANTINCENDIO sign for Manual call points CAR1006 # 1/2h Duty hour

Bldg# 430 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#15 Notifier Plexiglass sign for Manual call points MCP-PLEX #3 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

2. The FACP does not comply UNI EN 54-2 – Panel without certification to be use in fire protection systems, It is recommended to replace the panel with one certified according to the regulations in force:

#1 Fireclass Expandable zone conventional fire alarm control panel J424-8 #1 Fireclass Expander modules J400-EXP8 #1 Plastic surface mounting enclosure 400X300 X80 SCA639.4080 #2 CSB 12V 8Ah Long Life backup battery GPL1272F2 # Various materials for electrical wiring and short piping.

#9 Normal Duty Hours Labor

Total : €

3. A manual station in Bay# 3 is temporary repaired – To be replaced

#1 manual stations Notifier M3A-R000SF-STCK-01 #1 hours labor.

Total: €

Wet Pipe Fire Sprinkler Systems

4. There isn't the automatic drain valve as per point 8.17.2.6 of NFPA 13 Ed 2013 and per point

16.12.7 of NFPA 13 Ed 2019. – “The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve in areas subject to freezing”.

Installation of a automatic drip valve:

#1 Viking Automatic Ball Drip Valve, ½” 04292B Various fittings for horizontal installation

5. During The main drain test the water gushes out and floods the sprinkler room. – Seal the Drain valve with the water drain.

Various pipe fittings

Bldg# 430 Bay #1 – July/October 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#6 EMME ANTINCENDIO sign for Manual call points CAR1006 #1,5 Duty hour

Total : €

2. The auxiliary power supply does not report the trouble status. – The power supply is still functional but to solve the problem it is necessary to replace the entire device:

#1 Fireclass 5 amp switch mode power supply and monitoring board BXM24/50-B #1 Normal Duty Hours Labor

Total : €

3. 2 Repeaters missing under the floor in room 12 as per point 5.4.4.6 of UNI 9795 - Ed. 1999, Ed.

2005, Ed. 2010 & 2013 – Installation of two repeaters.

#2 Repeater Notifier INDICATOR #15 mt of metal conduit Teaflex L20G #2 Legrand Metal Box. 140X115X60 ALU VERNIC LEG387741 #18 mt of fire resistant cable FRS2150100 #2 male thread teaflex CMMFG020

#5 hour labor.

Bldg# 554 – December 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time:

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of proper signs in accordance with ISO 7010 and UNI 9795.

#5 EMME ANTINCENDIO sign for Manual call points CAR1006 ½ Duty hour

Total : €

2. Control lines not supervised - Laying and wiring of controlled line dedicated to the warning devices, controlled by EOL monitoring.

#Mt 70 Berica Cavi Fire Cable 4x1 mm² BECB56C04100FRSB (Sonepar) #24 Duty hour

Bldg# 600 – December 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. Control lines not supervised – Realize new line for the warning devices:

#250 Berica Cavi Fire Cable 4x1,5 mm² BECB56C04150FRSB (Sonepar) #70 hours labor.

Total cost: €

2. The smoke detector SD 10 - 06 does not work. – To be replace with:

#1 Notifier Conventional photoelectric smoke detector SD-851E A #1 Notifier Standard base for 800 Series detectors B401 #1 hours labor

Total cost: €

3. Alarm bells 3, 4, 11 and 21 does not work – To be replace with:

#4 NOTIFIER VISUAL/ACOUSTIC SIGNALLING DEVICE WITH WHITE LED EN 54-3, CWSS-

RW-S5

#3 hours labor

Total cost: €

Bldg# 604 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#4 Notifier Plexiglass sign for Manual call points MCP-PLEX #1 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

2. The FACP does not comply UNI EN 54-2 – Panel without certification to be use in fire protection systems, It is recommended to replace the panel with one certified according to the regulations in force:

#1 Fireclass 8 Zone conventional fire alarm control panel J408-8.

#1 Plastic surface mounting enclosure 400X300 X80 SCA639.4080 #2 CSB 12V 8Ah Long Life backup battery GPL1272F2 Various materials for electrical wiring and short piping.

#8 Normal Duty Hours Labor.

Bldg# 606 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The FACP internal buzzer does not work – Replace the buzzer

#1 MURATA ELECTRONICS 23mm 12V piezo buzzer PKB24SPCH-3601 (ELCO) #1 hour labor

Total : €

2. Control lines not supervised – Realize new line for the warning devices

#100 meters metal pipe Teaflex STD204 #15 meters of metal flexible conduit Teaflex L20G #50 joints Teaflex ARM20 #50 joints Teaflex ARG20 #20 joints Teaflex CMMFG020 #13 Legrand Metal Box. 140X115X60 ALU VERNIC LEG387741 #200 MT Berica Cavi Fire Cable 2x1 mm² BECB56C02100FRSB Assorted materials #80 hours labor.

Total : €

3. It is impossible to test twenty-three heat detectors as they are the melting sensitive element type that, once activated they must be replaced. – Replace the detectors

#23 Notifier Heat detector max. temperature FD-851HTE A #23 Notifier B401 Standard base for 800 Series detectors #13 hours labor.

total :€

4. After the FACP replacement, no one repeater works – Replace the repeaters

# 19 Notifier INDICATOR # 10 hours labor.

Bldg# 620 – July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. Control lines not supervised – It is necessary to realize new line for the warning devices.

#20 meters metal pipe Teaflex STD204 #5 meters of metal flexible conduit Teaflex L20G #8 joints Teaflex ARM20 #8 joints Teaflex ARG20 #8 joints Teaflex CMMFG020 #3 Legrand Metal Box. 140X115X60 ALU VERNIC LEG387741 #30 MT Berica Cavi Fire Cable 2x1 mm² BECB56C02100FRSB Assorted material #32 hours labor.

Bldg# 623 –July 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#8 Notifier Plexiglass sign for Manual call points MCP-PLEX #1,5 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

2. The FACP does not have the ability to download the status of the detector chamber values. - Installation and programming of the appropriate additional module in the FACP

#1 RS232/485 serial output interface board with CEI ABI protocol

Bldg# 627 – December 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of proper signs in accordance with ISO 7010 and UNI 9795.

#3 EMME ANTINCENDIO sign for Manual call points CAR1006 ½ Duty hour

Total : €

2. Control lines not supervised . – Laying a 4 conductors control line:

#70 Mt Berica Cavi Fire Cable 4x1 mm² BECB56C04150FRSB (Sonepar) #24 Duty hour

Total : €

3. The FACP does not react to key presses. – Spare parts no longer available, it is advisable to replace the Facp fo fixing the issue.

#1 Fireclass 8 Zone conventional fire alarm control panel J408-8.

#1 Plastic surface mounting enclosure 400X300 X80 SCA639.4080 #2 CSB 12V 7,2Ah Long Life backup battery GPL1272F2 Various materials for electrical wiring and short piping.

#10 Normal Duty Hours Labor.

Bldg# 898 – November 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of proper signs in accordance with ISO 7010 and UNI 9795.

#3 EMME ANTINCENDIO sign for Manual call points CAR1006 #1/2 Duty hour

Total : €

2. On the same detection line (zone) detectors sensitive to different phenomena are installed, but the respective signals are not uniquely identifiable to the C.C.S. as per point 5.2.7 of UNI 9795.

Ed. 2013. – To discriminate between the two signals, it is necessary to connect the manual call point of the boiler room with the "manual call point zone" of the building.

#20Mt Berica Cavi Fire Cable 2x1 mm² BECB56C02100FRSB #6 hours labor.

Bldg# 904 – August 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#18 Notifier Plexiglass sign for Manual call points MCP-PLEX #3 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

2. The FACP does not comply UNI EN 54-2 The FACP is not installed in accordance with point 5.5.2.3 of UNI 9795 - Ed. 1999, 2005, 2010, 2013 and 2021: "5.5.2.3 The control unit must be installed in such a way that all the equipment of which it is composed is easily accessible for maintenance operations, including replacements.

These operations must be able to be carried out on site ".

The FACP internal buzzer does not work Informative comment, for the resolution of the aforementioned problems it is recommended to replace the FACP with one certified according to the regulations in force and reinstall it at a lower and accessible altitude (Right now, the FACP is located above a door).:

#1 Fireclass Expandable zone conventional fire alarm control panel J424-8 #1 Fireclass Expander modules J400-EXP8 #1 Plastic surface mounting enclosure 400X300 X80 SCA639.4080 #2 CSB 12V 8Ah Long Life backup battery GPL1272F2 #12 meters Teaflex Zinc plated pipe 32 mm TEASTD324 #3 Teaflex Zinc plated elbow 32 mm TEAC04 #6 Teaflex MALE CONNECTOR 32 mm M32X1,5 TEAARM32M #4 Teaflex Pipe to pipe connector 32 mm TEAARG32 #1 Legrand Metal Box. 410X315X150 ALU VERNIC LEG387746 #110 Berica Cavi Fire Cable 2x1 mm² BECB56C02100FRSB #32 normal duty hours labor

Assorted material for fixing and wall mounting.

Total: €

3. Control lines not supervised – (To be carried out only after the realization of point "2") Laying of a 4 conductors control line for monitoring the controlled line:

#200 Mt Berica Cavi Fire Cable 4x1,5 mm² BECB56C04150FRSB #40 Duty hour

4. The repeater of the detector in room 5 does not work – To be replaced

#Notifier optical repeater INDICATOR #1 hour labor.

Total: €

5. The flashing light outside room 62 does not work – To be replaced

#1 NOTIFIER VISUAL/ACOUSTIC SIGNALLING DEVICE WITH WHITE LED EN 54-3, CWSS-

RW-S5

#1 hour labor.

Bldg# 904-1 – August 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#5 Notifier Plexiglass sign for Manual call points MCP-PLEX #1 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

2. The alarm bell on east side does not work – To be replace

#1 Notifier ACOUSTIC SIGNALLING DEVICE IP 65 EN 54-3 CWSO-RR-W1

Bldg# 904.2 – February 2022 INSPECTION ADDENDUM

Here below the list of problems found during the ITMS and our proposals to solve them:

DETECTION SYSTEM

1. It was not possible to obtain drawings or certifications of the building. – Informational comment

2. Verification not feasible due to the absence of any kind of references like drawings, floor plans, labels, etc. – Informational comment

Bldg# 907 – August 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021. – Providing and installation of special signs in accordance with ISO 7010 and UNI 9795.

#8 Notifier Plexiglass sign for Manual call points MCP-PLEX #2 Duty hour

Total : €

Alternatively, it is possible to install metal signs (more subject to wear and rust) at a lower cost of 57% (labor excluded).

2. The FACP does not comply UNI EN 54-2 – Panel without certification to be use in fire protection systems

For the aforementioned anomalies it is recommended to replace the panel with one certified according to the regulations in force.

#1 Fireclass Expandable zone conventional fire alarm control panel J424-8 #1 Fireclass Expander modules J400-EXP8 #1 Plastic surface mounting enclosure 400X300 X80 SCA639.4080 #2 CSB 12V 8Ah Long Life backup battery GPL1272F2 # Various materials for electrical wiring and short piping.

#9 Normal Duty Hours Labor

Total: €

3. Smoke detectors do not comply with the requirements of par. 6.4.3.7 of the UNI 9795 Ed. 1999 and/or of par. 5.4.3.8 of the UNI 9795 Ed. 2005 and/or of par. 5.4.3.7 of the UNI 9795 Ed. 2010 and Ed. 2013. The distance between detectors and ceiling exceeds the allowed values. – removal of the old detectors installed in the lower part of the trusses and installation of six new smoke detectors in the upper part of the roof

#6 Notifier Conventional smoke detectors SD-851E A #6 Notifier Standard base for 800 Series detectors B401 #20 MT of metal flexible conduit Teaflex L25G #12 joints Teaflex TEAEXCMMFG025 #6 metal boxes Legrand LEG387741 #60 MT Berica Cavi Fire Cable 2x1 mm² BECB56C02100FRSB Various materials for electrical wiring and short piping.

#20 hours labor).

4. Control lines not supervised – To supervise the control lines is necessary:

#30 Teaflex Zinc plated pipe 25 mm TEASTD254 #8 Mt Teaflex Metal flexible conduit. 25mm TEAL25G #8 Teaflex MALE CONNECTOR 25 mm M25X1,5 TEAARM25M #8 Teaflex Pipe to pipe connector 25 mm TEAARG25 #12 Teaflex PIPE-HOSE CONNECTOR AR- FR 25.A 25/25 #14 Teaflex Fixed Male thread. Brass fittings with metallic continuity 25mm

TEAEXCMMFG025

#5 metal box Legrand LEG387741 #60 MT Berica Cavi Fire Cable 2x1 mm² BECB56C02100FRSB Various materials for electrical wiring and short piping.

#40 hours labor

Total : €

5. The FACP internal buzzer does not work – Replace the buzzer

#1 MURATA ELECTRONICS 23mm 12V piezo buzzer PKB24SPCH-3601 (ELCO) #1 hour labor

Total : €

6. The flashing light ot main entrance does not work – To be replace

# NOTIFIER VISUAL/ACOUSTIC SIGNALLING DEVICE WITH WHITE LED EN 54-3, CWSS-

RW-S5

#1 hour labor.

Total: €

Standpipe and Hose Systems

7. There isn't the automatic drain valve as per point 8.17.2.6 of NFPA 13 Ed 2013 and per point

16.12.7 of NFPA 13 Ed 2019. – “The piping between the check valve and the outside hose coupling shall be equipped with an approved automatic drain valve in areas subject to freezing”.

Installation of a automatic drip valve:

#1 Viking Automatic Ball Drip Valve, ½” 04292B Various fittings for horizontal installation #4 hour labor

Total : €

8. There isn't a Fire Dept Connection sign as per point 8.17.2.4.7.1 of NFPA 13 Ed 2013 and Ed 2016, and as per Table A.16.17 (Sprinkler System Signage Summary) of NFPA 13 Ed 2019. – Providing and installing of a proper FDC Sign:

Total of:

Bldg# 909 – August 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The FACP internal buzzer does not work – Replace the buzzer

#1 MURATA ELECTRONICS 23mm 12V piezo buzzer PKB24SPCH-3601 (ELCO)

Bldg# 914 – August 2022 INSPECTION ADDENDUM

Here below the list of non-compliance or other problems found during the ITMS of which it is possible to calculate a quote to solve them. The costs indicated are calculated on the basis of the price lists updated for the current month, and are therefore subject to changes over time.

DETECTION SYSTEM

1. The manual call points are not indicated with a specific sign as per point 6.1.6 of UNI 9795 Ed 1999, 2005, 2010, 2013, 2021.