PERFORMANCE WORK STATEMENT
FOR FIRE SYSTEMS
AT THE AVIANO & GHEDI (BRESCIA) AIR BASES, ITALY
APPENDIX - C: SUPPRESION SYSTEM ELECTRCIAL
COMPONENTS
CONTENTS
SECTION TITLE
1 Water Based Fire Suppression Systems
2 Stand Pipe Systems
3 Aviano Pumps and Air Compressors
SECTION 1
Water Based Fire Suppression Systems
AREA “A-1”
1. Bldg # 106 Wet sprinkler system with 77 sprinkler heads, 1 line, 1 automatic alarm valve (VIKING J-1, 175 psi, 4”, year 1995), 1 retardant chamber, 2 pressure gauges, 2 drains, 1 twin Fire Dept. connection, 1 water bell, 2 test valves, 1 tamper switch and 1 water pressure switch connected to the fire alarm panel.
2. Bldg # 110 Wet sprinkler system with 71 sprinkler heads (1 upright, 8 pendant, 62 pendant concealed), 2 lines, 1 backflow preventing device, 2 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 water bell, 1 PIV, 2 valves with tamper switch, 2 valves without tamper switch, 1 check valve, 2 inspector test valves, 1 pressure relief valve, 1 flow switch in mechanical room, 2 floor valves with tamper switches, 2 floor flow switches, and 2 floor inspector test valves. All switches are connected to main fire alarm panel.
3. Bldg # 116 Wet sprinkler system with 225 pendant sprinkler heads, 168 upright sprinkler heads, 1 tampered
PIV, 2 tampered main gate valves (6”), 1 backflow preventing device AMES 2000 (6”) with 3 ball valves ¾”, 1 main drain (2”), 1 water pressure gauge with 1 three-way valve ¼”, 2 lines (ground and first floor), 2 tampered butterfly valves, 2 flow switches connected to fire alarm panel, 2 inspector test valves equipped with total 4 ball valves 1” and 2 site glasses water flow, 1 F.D. truck twin connection, 1 check valve VIKING mod. G-1 (4”, 2004).
4. Bldg # 170 Wet sprinkler system with 192 sprinkler heads, 1 line, 1 automatic alarm valve (CSC, 175 psi, 4”), 1 retardant chamber, 2 pressure gauges, 1 main drain, 1 twin Fire Dept. connection, 1 water bell, 3 test valves and 1 water flow switch connected to the fire alarm station.
5. Bldg # 172 Wet sprinkler system with 16 sprinkler heads, 1 line, 1 automatic valve (NIBCO fig. WD 3510-4, 250 psi, 4”, year 1996), no retardant chamber, 2 pressure gauges, 1 drain (test valve), 1 twin Fire Dept.
connection, 1 water bell, 1 water pressure switch connected to the main fire alarm station and 1 tamper switch not connected.
6. Bldg # 147 Wet sprinkler system with 1 PIV, 1 twin Fire Dept. truck connection, and 1 water bell located outside sprinkler room; inside sprinkler room: 1 check valve 4", 3 butterfly valves 6" with tamper switches, 1 backflow preventer 6", 1 butterfly valve 4" with tamper, 1 wet line, 1 automatic sprinkler valve "VICTAULIC"
4" mod. S/751 300 PSI (Apr '05), 1 test valve 2", 2 water pressure gauges, 1 check valve ½", 1 retardant chamber "VICTAULIC" mod. S/752 ('05), 2 ball valves ½", 1 automatic drain valve ½" on trim, 2 pressure switches ("SYSTEM SENSOR" mod. EPS10-1 e "POTTER" PS40-1A), 1 butterfly valve 2" with tamper, 1 water flow gauge; inside facility: 117 sprinkler heads SSU-1 155 o F-68 o C, 117 sprinkler heads SSP 155 o F-68 o C, 1 inspector test valve; all switches connected to main Fire Alarm Panel.
7. Bldg # 179 Wet sprinkler system with 261 pendant sprinkler heads, 100 upright sprinkler heads, 7 long probe dry pendant sprinkler heads, 1 tampered PIV, 2 tampered main gate valves (6”), 1 backflow preventing device, 1 automatic sprinkler valve (6”), trimmer circuit with assorted valves, water pressure gauges, check valves, calibrated orifices, 1 drain, 1 retardant chamber, 1 inspector test valve, 2 water flow switches connected to fire alarm panel, 1 F.D. truck twin connection, 1 check valve VIKING mod. G-1 (4”, 2004).
AREA “A-2”
8. Bldg # 219 Wet sprinkler system with 80 sprinkler heads, 3 lines, 3 automatic alarm valve (N/A), 3 retardant chambers, 6 pressure gauges, 3 main drains, 3 twin Fire Dept. connections, 3 water bells, 3 test valves, 3 water flow switches and 3 water pressure switches connected to the main fire alarm station.
9. Bldg # 240-A Wet sprinkler system with 37 sprinkler heads, 1 line, 1 automatic alarm valve (CSC Central, 3”), no retardant chamber, 2 pressure gauges, 1 main drain, no twin Fire Dept. connection, 1 water bell, 1 test valve and 1 water pressure switch connected to the main fire alarm station.
10. Bldg # 250 Wet sprinkler system with 65 pendent sprinkler heads, 1 backflow preventing device, 1 main gate valve, 1 automatic sprinkler valve (4”), trimmer circuit with assorted valves, gauges, check valves, calibrated orifices, 1 retardant chamber, 2 water pressure gauges with three-way valves ¼”, 1 main drain, 1 check valve, 1
F.D. truck twin connection, 1 water bell, 1 inspector test valve, 1 water pressure switches connected to fire alarm panel.
11. Bldg # 254 Mist sprinkler system, wet and dry, with 541 sprinkler heads, 2 lines, 2 automatic alarm valve
(VIKING, 4”), 2 retardant chamber, 6 pressure gauges, 1 main drain, 1 twin Fire Dept. connection, 2 water bells, 12 test valves and 2 water pressure switch connected to the fire alarm station.
12. Bldg # 258 Mist sprinkler system, wet and dry, with 520 sprinkler heads, 2 lines, 2 automatic alarm valve
(VIKING, 4”), 2 retardant chamber, 6 pressure gauges, 1 main drain, no twin Fire Dept. connection, 1 water bell, 10 test valves and 2 water pressure switches connected to the fire alarm station.
AREA “C”
13. Bldg # 430 Wet sprinkler system with 338 upright sprinkler heads, 68 pendant sprinkler heads, 2 lines, 2 automatic alarm valves (CSC 8”, year1997), 2 retardant chambers, 5 pressure gauges, 1 main drain in pump room, 1 twin Fire Dept. connection, 2 water bells, 6 test valves inside bays with flow indicator (side glass), 2 water flow switches, 1 tamper switch, 8 tamper switches on lines inside building (not connected to FACP), and 2 water pressure switches connected to the fire alarm station.
14. Bldg # 430 Bay # 1 – first floor Wet sprinkler system with 75 upright sprinkler heads.
AREA “F”
15. Bldg # 914 Sprinkler system consists of 9 pendant sprinkler heads, 1 side wall sprinkler head, 1 wet line, 1 automatic sprinkler valve GEM 2 ½" (1994) 175 psi, 1 retardant chamber Mod. F, 2 water pressure gauges, 1 main drain, 1 Fire Dept. twin connection, 1 water bell, 7 assorted valves and 1 pressure switch connected to main Fire Alarm Panel.
16. Bldg # 973 Wet sprinkler system with 6 sprinkler heads, 1 line, a 1 ½” manual valve.
17. Bldg # 1010 Wet sprinkler system with 1 main gate valve, three wet circuits, new West area protected with 92 upright sprinkler heads, existing Central area protected with 47 pendant and 196 upright sprinkler heads, new
East area protected with 90 pendant and 67 upright sprinkler heads, 3 automatic sprinkler valves (4”), 3 trimmer circuits with assorted valves, water pressure gauges, check valves, calibrated orifices, 3 drain, 3 retardant chambers, 3 water pressure switches connected to fire alarm panel, 1 water bell, 1 check valve, and 1 F.D. truck twin connection.
18. Bldg # 1029 Mist sprinkler system, wet and dry, with 618 sprinkler heads, 4 lines, 1 automatic alarm valve
(VIKING E-1, 6”), 3 automatic alarm valves (VIKING F-1, 6”), 3 retardant chamber (VIKING mod. BS year
1983), total of 9 pressure gauges, 1 main drain, 1 twin Fire Dept. connection plus for 4 extra connections, 1 water bell and 3 water pressure switch connected to the main fire alarm station.
19. Bldg # 1032 Wet sprinkler system with 15 sprinkler heads, 1 line, 1 automatic alarm valve (CSC 4”), 1 retardant chamber (CSC mod. F), 2 pressure gauges, 1 main drain, 1 twin Fire Dept. connection, 1 water bell, 1 test valve with glass flow indicator and 1 water pressure switch connected to the fire alarm station.
20. Bldg # 1078 Wet sprinkler system with 336 pendant, 55 upright and 14 side wall sprinkler heads, 1 PIV w/tamper, 1 pressure gauge on main supply line (6”), 2 gate valves (6”) w/tamper, 1 WATTS backflow preventing device (6”), 1 F.D. truck connection, 1 check valve (4”), 1 gate valve (6”) w/tamper, 4 gate valves (2
½”) w/cap and fire hose connectors. There are 3 wet distribution lines. Freight, loading docks and baggage areas with 1 butterfly valve (6”) w/tamper, 1 check valve (6”), 1 drain gate valve (2”), 1 water pressure gauge, 1 water flow switch, and 1 gate valve (1”) to be used for flow switch test. ATOC with 1 butterfly valve (2”) w/tamper, 1 check valve (2”), 1 drain gate valve (2”), 1 water pressure gauge, 1 water flow switch, and 1 gate valve (1”) to be used for flow switch test. Passengers’ area with 1 butterfly valve (4”) w/tamper, 1 check valve
(4”), 1 drain gate valve (2”), 1 water pressure gauge, 1 water flow switch, and 1 gate valve (1”) to be used for flow switch test. All switches are connected to main fire alarm panel.
21. Bldg # 1078 Dry sprinkler system covers 3 external areas (North and South loading docks and West baggage area) with 37 total upright sprinkler heads and 3 inspector test valve stations. Inside mechanical room # G-45 there is a 4” water supply line, 1 drain ball valve (1”), 1 gate valve (4”) w/tamper, 1 TYCO (4”) dry pipe sprinkler valve (4”) w/trim, and 1 air compressor with 50 lt tank. All switches are connected to main fire alarm
22. Bldg # 1099 Wet sprinkler system with 33 sprinkler heads, 1 line, 1 automatic alarm valve (CSC 3”), 1 retardant chamber, 4 pressure gauges, 1 main drain, 1 twin Fire Dept. connection, 1 water bell, 1 test valve, 6 tamper switches, 1 water flow switch and 1 water pressure switch connected to the main fire alarm station.
23. Bldg # 1173 Wet sprinkler system with 297 pendant sprinkler heads, 1 CALEFFI backflow preventing device
(4”), pump group by-pass with 2 butterfly valves (3”) and 1 check valve (3”), 1 butterfly valve (4”) w/tamper, 1
VICTAULIC mod S/751 automatic sprinkler valve (4”) w/trim, 1 drain gate valve (2”), 1 retardant chamber, 1 pressure switch, 1 water bell (gong), 2 gate valves (2 ½”), 2 check valves (2 ½”), 2 water pressure relief valves
(1”), 2 gate valves (2 “) w/F.D. truck connection, 1 drain ball valve (2”), and 1 attic drain ball valve(1 ¼”).
24. Bldg # 1174 Wet sprinkler system with 31 pendant and 170 upright sprinkler heads, 1 wet distribution line
(loop), 2 butterfly valves w/tamper and 1 backflow preventing device (inside underground pit), 4 butterfly valves (4”) w/tamper, 2 check valves (4”), 2 ball valves (1”), 1 check valve (1”), 2 gate valves (2 ½”) F.D. truck connections w/cap, 1 check valve (4”), 1 cap (4”), 1 pressure relief valve (1”), 1 butterfly valve (3”), 1 water flow measuring device, 1 butterfly valve (4”) w/tamper, 1 ASTRA mod. B automatic sprinkler valve (4”) w/trim, 1 drain ball valve (2”), 1 retardant chamber, 1 pressure switch, 1 flow switch, 1 water bell (gong), and 1 inspector test valve. All switches are connected to main fire alarm panel.
25. Bldg # 1204 Wet sprinkler system with 15 upright rapid, 5 pendant rapid, 75 upright, 166 pendant sprinkler heads, 3 wet distribution lines, 1 pressure gauge, 1 ball valve (1/2”), 2 gate valves (6”) w/tamper, 2 check valves
(6”), 1 gate valve (3”) w/tamper, 1 check valve (3”), 3 gauges, 3 flow switches, and 3 drain ball valves (1”), total of 4 inspector testing valves for the 3 lines to ESFR heads, wet & dry system pipes, and to reel stations.
26. Bldg # 1204 Dry sprinkler system with 36 upright and 1 inspector test valve. Inside facility there is a 6” water supply line, 1 gate valve (6”) w/tamper, 1 VIKING dry pipe sprinkler valve (6”) w/trim, 1 drain ball valve (2”), and 1 air compressor.
27. Bldg # 1204 Dry sprinkler system with 36 upright and 1 inspector test valve. Inside facility there is a 6” water supply line, 1 gate valve (6”) w/tamper, 1 VIKING dry pipe sprinkler valve (6”) w/trim, 1 drain ball valve (2”), and 1 air compressor.
28. Bldg # 1204-3 Substation provides water for Bldg 1204 sprinkler system. Wet sprinkler system protects pumping room with 1 PIV w/tamper, 8” water supply line, 4 gate valves (8”) w/tamper, 1 WATTS backflow preventing device (8”), 1 check valve (8”), 4 F.D. truck connection w/cap, and 1 check valve (6”). Main pumps and Jokey are provided with 4 gate valves (8”) w/tamper, 2 check valves (8”), 2 ball valves (1 ¼”), 1 check valve (1 ¼”). There is a pump testing circuit consisting of 1 butterfly valve (6”) w/tamper, 2 gate valves (6”) w/tamper, 1 water flow measuring device, and 4 gate valves (2 ½”) with fire hose connector and cap.
Connected prior to pumps’ main collector there is 1 gate valve (2”) w/tamper, 1 check valve (2”), 1 flow switch, 6 upright sprinkler heads and 1 inspector test valve.
29. Bldg # 1227 Wet sprinkler system with 69 pendant sprinkler heads, 54 upright sprinkler heads, 1 PIV, 1 main butterfly valves (8”), 1 backflow preventing device (8”) with 3 gauges and 3 ball valves (¾”), 1 butterfly valve
(6”), 1 (tampered but not connected) butterfly valve (6”), 1 automatic sprinkler valve (6”), trimmer circuit with 9 assorted valves, water pressure gauges, filter, and calibrated orifices, 1 drain, 1 retardant chamber, 1 water pressure switch connected to fire alarm panel, 1 water bell, 1 check valve (4”), and 1 F.D. truck twin connection.
30. Bldg # 1229 Wet sprinkler system with 51 pendant sprinkler heads, 1 wet distribution line, 1 PIV, water line
4”, 3 gate valves (4”) w/tamper, 1 BRANDONI backflow preventing device (4”), 1 F.D. truck connection, 1 check valve (4”), 1 VIKING J-1 automatic sprinkler valve (4”) w/trim, 1 drain ball valve (2”), 1 retardant chamber, 1 pressure switch, 1 water bell (gong), and 1 inspector test valve. Tamper switches and pressure switch are connected to main fire alarm panel.
31. Bldg # 1335 Wet sprinkler system with 80 sprinkler heads, 1 line, 1 automatic alarm valve (VIKING 6” Mod.
J-1 250 PSI, check valve Mod. D-2 175 PSI), 2 pressure gauges, 1 drain (test valve), 1 twin Fire Dept.
connection, 1 water bell, 2 tamper switches and 1 water pressure switch connected to the main fire alarm station.
32. Bldg # 1342 Wet sprinkler system with 72 sprinkler heads, 1 line, 1 automatic alarm valve (N/A), 2 pressure gauges, 2 main drains, 1 twin Fire Dept. connection, 1 water bell and 1 water pressure switch connected to the fire alarm station.
33. Bldg # 1379 Wet sprinkler system with 46 sprinkler heads, 1 line, 1 automatic alarm valve (N/A), 2 pressure gauges, 2 main drains, 1 twin Fire Dept. connection, 1 water bell and 1 water pressure switch connected to the fire alarm station.
34. Bldg # 1380 Wet sprinkler system with 78 upright sprinkler heads, 32 pendant sprinkler heads, 1 PIV, 2 gate valves (6”), 1 backflow preventing device with 2 ball valves ¾” and 1 regulator, 1 automatic sprinkler valve
GEM mod. F-200 (6”, 2003), trimmer circuit with assorted valves, water pressure gauges, check valves, calibrated orifices, 1 drain, 1 retardant chamber, 2 water pressure gauges with three-way valves ¼”, 1 water bell
(gong) and 1 strainer ¾”, 1 main drain 2”, 1 Fire Dept. twin connection, 1 inspector test valve, and 1 pressure switch connected to main Fire Alarm Panel.
35. Bldg # 1391 Wet sprinkler system with 66 pendant (57 o C) and 2 pendant (79 o C for walk-through refrigerator) sprinkler heads, 1 wet line, 1 back flow preventing device AMES 4000 SS (6”), 2 KENNEDY valves (6”), 2 tamper switches, 1 automatic sprinkler valve VIKING J-1 (6”, year 2002), 1 retardant chamber VIKING C-1, 2 pressure gauges, 1 main drain, 1 pressure switch, 1 fire inspector test valve, 1 water bell, 1 check valve VIKING
G-1 (4”, PN 10), 1 Fire Dept. truck twin connection, and 1 PIV. All switches are connected to main Fire Alarm
Panel. Box contains total of 6 spare sprinkler heads (5 pendant and 1 pendant for refrigerator).
36. Bldg # 1403 Wet sprinkler system with 315 sprinkler heads, 2 lines, 1 automatic alarm valve (VIKING J-1, 6”, year 1998), 1 retardant chamber, 3 pressure gauges, 1 main drain with flow indicator, 1 twin Fire Dept.
connection, 1 water bell, 1 test valve in building, 3 tamper switches, 2 water flow switches and 1 water pressure switches connected to the fire alarm station.
37. Bldg # 1404 Wet sprinkler system with 260 sprinkler heads, 6 sprinkler heads inside walkthrough freezer, 2 wet lines, 1 backflow preventing device, 1 automatic sprinkler valve, 1 retardant chamber, 2 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 water bell, 1 PIV, 4 valves, 1 check valve, 1 inspector test valve, 2 floor valves, 2 floor flow switches, 4 tamper switches, 2 floor tamper switches, 1 pressure switch. All switches are connected to main Fire Alarm Panel.
38. Bldg # 1405 Wet sprinkler system with 287 sprinkler heads (4 up-right, 181 pendant, 102 up-right with spray), 1 wet line, 1 backflow preventing device, 1 automatic sprinkler valve, 1 retardant chamber, 2 gauges, 1 main drain, 1 valve test, 1 Fire Dept. twin connection, 1 water bell, 1 PIV, 2 valves, 1 check valve, 22 drain valves for gym court, 2 flow switches, and 4 tamper switches. All switches are connected to main Fire Alarm Panel.
39. Bldg # 1411 Wet sprinkler system with 1156 sprinkler heads, 4 lines, 4 automatic alarm valves (VIKING J-1, 250 psi, year 1999), 4 retardant chambers (VIKING C-1, year 1999), 8 pressure gauges, 1 main drain, 4 Fire
Dept. twin connections, 4 water bells, 6 test valves, 10 tamper switches, 9 water flow switches and 4 water pressure switches connected to the fire alarm station.
40. Bldg # 1412 Wet sprinkler system with 54 pendant and 55 upright sprinkler heads, PIV w/tamper, 2 gate valves (6”) w/tamper, 1 AMES backflow preventing device (6”), 1 F.D. truck connection, 1 automatic dripping valve, 1 check valve (4”), 1 VIKING J-1 sprinkler valve (6”) w/trim, 1 drain ball valve (2”), 1 retardant chamber, 1 pressure switch, and 1 water bell (gong). Internal distribution lines for ground floor and attic, 2 butterfly valves (6”) w/tamper, 2 flow switches, 2 gauges, 2 3-way valves (1/8”), 4 gate valves (1”), and 2 flow switch test valves w/side glass.
41. Bldg # 1413 Wet sprinkler system with 135 pendant and 107 upright sprinkler heads, 4 distribution lines, 1
PIV, 2 gate valves (6”) w/tamper, 1 AMES-2000 backflow preventing device (6”), 1 F.D. truck connection, 1 check valve (6”), 1 gate valve (4”) w/tamper, 1 drain ball valve (1/2”), 2 gate valves (2 ½”), 1 automatic sprinkler valve (6”) w/trim, 1 drain ball valve (2”), 1 retardant chamber, 1 pressure switch, 1 water bell (gong), 3 gate valves (6”) w/tamper, 1 gate valve (2”) w/tamper, 3 check valves (6”), 4 flow switches, 3 gauges, and 3 flow switch test valves w/side glass.
42. Bldg # 1422 Wet sprinkler system with 3 different circuits, 447 pendant sprinkler heads, 7 upright sprinkler heads, total of 4 pressure gauges, 3 test valve, 6 main drain, 1 twin Fire Dept connection, 6 tamper switches and
3 water flow switches connected to main fire alarm panel.
43. Bldg # 1423 Wet sprinkler system with 3 different circuits, 447 pendant sprinkler heads, 7 upright sprinkler heads, total of 4 pressure gauges, 3 test valve, 6 main drain, 1 twin Fire Dept connection, 6 tamper switches and
44. Bldg # 1424 Wet sprinkler system with 3 different circuits, 447 pendant sprinkler heads, 7 upright sprinkler heads, total of 4 pressure gauges, 3 test valve, 6 main drain, 1 twin Fire Dept connection, 6 tamper switches and
45. Bldg # 1425 Wet sprinkler system with 3 different circuits, 447 pendant sprinkler heads, 7 upright sprinkler heads, total of 4 pressure gauges, 3 test valve, 6 main drain, 1 twin Fire Dept connection, 6 tamper switches and
46. Bldg # 1426 Wet sprinkler system with 3 different circuits, 447 pendant sprinkler heads, 7 upright sprinkler heads, total of 4 pressure gauges, 3 test valve, 6 main drain, 1 twin Fire Dept connection, 6 tamper switches and
47. Bldg # 1427 Wet sprinkler system with 3 different circuits, 447 pendant sprinkler heads, 7 upright sprinkler heads, total of 4 pressure gauges, 3 test valve, 6 main drain, 1 twin Fire Dept connection, 6 tamper switches and
48. Bldg # 1430 Wet sprinkler system with 300 pendant and 27 upright sprinkler heads, 1 distribution line (loop), 1 PIV w/tamper, 2 gate valves (10”) w/tamper, 1 strainer (10”), 1 AMES-2000 backflow preventing device
(10”), 1 F.D. truck connection, 1 check valve (6”), 2 butterfly valve (8”) w/tamper, 1 water flow meter (8”), 6 gate valves (2 ½”) valves w/fire hose connection and cap, 1 pressure release valve to drain (8”), 1 gate valve
(10”) w/tamper, 1 gauge, 2 butterfly valves (10”) w/ tamper, 1 check valve (10”), 2 gate valves (1 ¼”) w/tamper, 1 check valve (1 ¼”), 1 gate valve (8”) w/tamper, 1 VIKING J-1 automatic sprinkler valve (8”) w/trim, 1 drain ball valve (2”), 1 retardant chamber, 1 pressure switch, and 1 water bell (gong). In bay there are 2 drain gate valves (4”), and 2 inspector test valves (1”) w/site glass.
49. Bldg # 1434 Wet sprinkler system with 246 pendant sprinkler heads, 143 upright sprinkler heads, 1 PIV, 2 tampered gate valves, 1 backflow preventing device, 1 automatic sprinkler valve, trimmer circuit with assorted valves, water pressure gauges, check valves, calibrated orifices, 1 drain, 1 retardant chamber, 1 water pressure switch, 1 water flow switch, 1 water bell, 1 check valves, 1 Fire Dept. twin connection, 1 inspector test valve, all switches connected to fire alarm panel. Switches are not connected to fire alarm panel.
50. Bldg # 1435 Main water supply line consists of one VIKING PIV, two 10” KENNEDY gate valves, two
POTTER OSYSU-1 tamper switches, one 10” AMES 2000SS backflow preventing device, two F.D. truck connections, and one 4” VIKING butterfly valve with position micro-switch. Wet sprinkler system consists of
290 upright and 146 pendent sprinkler heads, one 6” AG H series alarm check valve, one 6” VIKING butterfly valve with position micro-switch, one SYSTEM SENSOR EPS10-1 pressure switch, and one water bell (gong).
51. Bldg # 1442 Sprinkler system consists of 565 sprinkler heads, 5 wet line, 1 automatic sprinkler valve, 1 retardant chamber, 2 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 water bell, 2 valves, 1 check valve, 5 floor flow switches, 7 tamper switches, and 1 pressure switch. All switches are connected to Fire Alarm Panel.
52. Bldg # 1445 Wet sprinkler system with 193 upright sprinkler heads, 145 pendant sprinkler heads, 17 sidewall sprinkler heads, 1 PIV, 3 tampered gate valves, 1 backflow preventing device, 4 water pressure gauges with three-way valves ¼”, 2 tampered butterfly valves, 2 main drains, 3 check valves, 1 Fire Dept. twin connection, 2 inspector test valves, 2 site glasses water flow, and 2 water flow switches connected to fire alarm panel.
53. Bldg # 1446 Wet sprinkler system with 449 upright and 174 pendant sprinkler heads, 3 distribution lines, a 10” water supply line from Bldg 1447 Substation, 1 gate valve w/tamper and 1 check valve (6”) for ESFR, 1 gate valve w/tamper and 1 check valve (3”) for standpipe hoses, 1 gate valve w/tamper and 1 check valve (8”) for overhead sprinkler system, 3 gauges, 3 flow switches, and 3 drain and flow switch test valves (1”), 2 inspector test valves (1”), and 2 drain valves (2”).
54. Bldg # 1448 Substation provides water for Bldg 1446 sprinkler system. Basic water line consists of 1 PIV w/tamper, 8” water supply line, 2 gate valves (8”) w/tamper, 1 WATTS backflow preventing device (8”), F.D.
truck connection consists of 4 gate valves (2 ½”) w/cap and 1 check valve (6”). Connected on main collector there is 2 water pressure gauge, 1 gate valve (2”) w/tamper, 1 check valve (2”), 1 drain ball valve (1”), 1 flow switch, and 2 upright sprinkler heads. Connected to line for Bldg 1446 there is 1 gate valve (8”) prior system testing circuit consisting of 1 check valve (6”), 1 drain ball valve (1”), 4 gate valves (2 ½”) with fire hose connectors.
55. Bldg # 1462 Wet sprinkler system with 40 pendent and 292 upright sprinkler heads, one spare sprinkler heads kit (wrench is missing), one PIV, one 6” backflow preventing device, two 6” gate valves with tamper switches, one 6” AG alarm valve with trim circuit, one 6” butterfly valve with tamper switch, one F.D. truck connection with check valve, one test/drain valve in the most demanded area, one pressure switch, and one water bell
(gong). All switches are connected to facility FACP.
56. Bldg # 1464 Wet sprinkler system with 222 pendant sprinkler heads, 1 PIV, 2 tampered gate valves, 1 backflow preventing device, 1 automatic sprinkler valve (4”), trimmer circuit with assorted valves, water pressure gauges, check valves, calibrated orifices, 1 drain, 1 retardant chamber, 1 water pressure switch, 1 water bell, 1 check valves, 1 Fire Dept. twin connection, 1 inspector test valve, all switches connected to fire alarm
57. Bldg # 1467 Wet sprinkler system with 580 sprinkler heads, 2 lines, 2 automatic alarm valves (VIKING J-1, 12 bar, 4”, year 1998), 2 retardant chambers (VIKING C-1, year 1998), 6 pressure gauges, 1 main drain, 2 Fire
Dept. twin connections, 2 water bells, 7 tamper switches and 2 water pressure switches connected to the fire alarm station. Inside the dorm there are 3 water flow indicators, 3 test valves, 3 water flow switches, and 3 water pressure switches connected to the fire alarm station.
58. Bldg # 1467 D Sprinkler system wet type, with 580 sprinkler heads, 2 lines, 2 automatic alarm valves
(VIKING J-1, 12 bar, 4”, year 1998), 2 retardant chambers (VIKING C-1, year 1998), 6 pressure gauges, 1 main drain, 2 Fire Dept. twin connections, 2 water bells, 7 tamper switches and 2 water pressure switches connected to the fire alarm station. Inside the dorm there are 3 water flow indicators, 3 test valves, 3 water flow switches, and 3 water pressure switches connected to the fire alarm station.
59. Bldg # 1467 K Wet sprinkler system with 95 sprinkler heads.
60. Bldg # 1476 Wet sprinkler system with 112 upright and 133 pendant sprinkler heads, 2 distribution lines, 1
PIV, 1 water bell (gong), 1 F.D. truck twin connection with check valve (4”), water supply line with 2 gate valves (6”) w/tamper, 1 AMESS-3000 backflow preventing device with testing circuit (6”), 1 automatic sprinkler valve (6”) w/trim, retardant chamber, water pressure switch connected to the fire alarm station, 1 drain gate valve (2”), 1 inspector test valve, and there are 14 flush/drain ball valves (1”) with plug in the attic area.
61. Bldg # 1478 Wet sprinkler system with 146 pendant sprinkler heads, 4 upright sprinkler heads, 1 PIV, 2 tampered gate valves, 1 backflow preventing device, 1 automatic sprinkler valve (4”), trimmer circuit with assorted valves, water pressure gauges, check valves, calibrated orifices, 1 drain, 1 retardant chamber, 1 water pressure switch, 1 water bell, 1 inspector test valve, 1 check valve, 1 Fire Dept. twin connection.
62. Bldg # 14781 Wet sprinkler system with 38 pendant sprinkler heads, 95 upright sprinkler heads, 1 PIV, 2 tampered gate valves, 1 backflow preventing device, 1 automatic sprinkler valve (4”), trimmer circuit with assorted valves, water pressure gauges, check valves, calibrated orifices, 1 drain, 1 retardant chamber, 1 water pressure switch, 1 water bell, 1 inspector test valve, 1 check valve, 1 Fire Dept. twin connection.
63. Bldg # 1480 Wet sprinkler system with 370 sprinkler heads, 3 wet line, 1 backflow preventing device, 4 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 PIV, 2 valves, 1 check valve, 3 inspector test valve, 2 drains, 3 floor valves, 3 floor flow switches, and 6 tamper switches. All switches are connected to Fire Alarm
Panel.
64. Bldg # 1481 Wet sprinkler system with 370 sprinkler heads, 3 wet line, 1 backflow preventing device, 4 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 PIV, 2 valves, 1 check valve, 3 inspector test valve, 2 drains, 3 floor valves, 3 floor flow switches, and 6 tamper switches. All switches are connected to Fire Alarm
65. Bldg # 1482 Wet sprinkler system 370 sprinkler heads, 3 wet line, 1 backflow preventing device, 4 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 PIV, 2 valves, 1 check valve, 3 inspector test valve, 2 drains, 3 floor valves, 3 floor flow switches, and 6 tamper switches. All switches are connected to Fire Alarm Panel.
66. Bldg # 1483 Wet sprinkler system with 370 sprinkler heads, 3 wet line, 1 backflow preventing device, 4 gauges, 1 main drain, 1 Fire Dept. twin connection, 1 PIV, 2 valves, 1 check valve, 3 inspector test valve, 2 drains, 3 floor valves, 3 floor flow switches, and 6 tamper switches. All switches are connected to Fire Alarm
67. Bldg # 1484 Wet sprinkler system 525 sprinkler heads (22 up-right, 179 pendant, 324 pendant concealed), 6 wet lines, 1 automatic sprinkler valve, 1 Fire Dept. twin connection, 1 PIV, 1 water bell, 3 flow switches, and 6 tamper switches. All switches are connected to main Fire Alarm Panel.
AREA “G”
68. Bldg # 1568 Wet sprinkler system with 95 pendant sprinkler heads, 1 back-flow preventing device (AMES
4000, 4”), 1 automatic sprinkler valve (Viking J-1, 4”), 1 retardant chamber (Viking C-1), 2 pressure gauges, 1 main drain, 1 test valve on automatic valve, 1 twin Fire Truck connection, 1 water bell, 1 PIV, 1 shut-off valve, 1 check valve (Viking G-1, 4”), 1 pressure switch connected to fire alarm panel.
SECTION 2
Standpipe Systems
1. Bldg # 116 Facility has on sprinkler water distribution lines also a total of 5 standpipe hoses with nozzle, 4 at ground floor and 1 at first floor.
2. Bldg # 147 This facility is provided with a total of 6 standpipe hoses with nozzle.
3. Bldg # 254 See Appendix C Section 1 description.
4. Bldg # 430 Facility has a total of 6 standpipe hoses with nozzles connected to the sprinkler distribution lines.
5. Bldg # 1029 See Appendix C Section 1 description.
6. Bldg # 1174 Facility has a total of 2 standpipe hose with nozzle installed.
7. Bldg # 1204 Facility has a total of 4 standpipe hose with nozzle installed.
8. Bldg # 1235 Facility has a total of 4 standpipe hose with nozzle installed.
9. Bldg # 1302 Facility has on sprinkler water distribution line also a total of 18 standpipe hoses with nozzle.
10. Bldg # 1360 HQ Facility has 1 standpipe hose with nozzle.
11. Bldg # 1404 Facility has 1 standpipe hose with nozzle.
12. Bldg # 1407 This facility has a total of 4 standpipe hoses with nozzle. Standpipe hoses line is provided with 1
PIV, 2 main gate valves, 2 tamper switches, 1 backflow preventing device, 1 check valve, 1 F.D. truck twin connection, and 1 flow switch connected to fire alarm panel.
13. Bldg # 1409 This facility is provided with a total of 4 standpipe hoses with nozzles, 2 at ground floor and 2 at first floor. Standpipe hoses line is provided with 1 PIV, 2 main gate valves, 2 tamper switches, 1 backflow preventing device, 1 check valve, 1 F.D. truck twin connection, and 1 flow switch connected to fire alarm panel.
14. Bldg # 1411 See Appendix C Section 1 description.
15. Bldg # 1412 See Appendix C Section 1 description.
16. Bldg # 1413 Facility has 6 standpipe hose with nozzle installed.
17. Bldg # 1422 This facility has a total of 9 standpipe hoses with nozzles.
18. Bldg # 1423 Facility has a total of 9 standpipe hose with nozzles, 3 for each floor.
19. Bldg # 1424 Facility has a total of 9 standpipe hose with nozzles, 3 for each floor.
20. Bldg # 1425 Facility has a total of 9 standpipe hose with nozzles, 3 for each floor.
21. Bldg # 1426 Facility has a total of 9 standpipe hose with nozzles, 3 for each floor.
22. Bldg # 1427 Facility has a total of 9 standpipe hose with nozzles, 3 for each floor.
23. Bldg # 1430 Facility has 6 standpipe hose with nozzle installed.
24. Bldg # 1431 Facility has 1 PIV, 1 (2”) water supply line, 1 F.D. truck twin connection, 2 standpipe hoses with nozzles inside cabinets located in corridors # 39 and # 40.
25. Bldg # 1435 Dry sprinkler system consists of 39 upright sprinkler heads, one 6” GLOBE EUROPE D dry pipe valve, one 6” VIKING butterfly valve with position micro-switch, one SYSTEM SENSOR EPS10-1 pressure switch, one POTTER PS40-1 pressure switch, one FIAC 3HP air compressor 50 liters, one GLOBE
EUROPE AMD H-1 air maintenance device, and one water bell (gong).
26. Bldg # 1445 Facility has a total of 10 standpipe hoses.
27. Bldg # 1446 Facility has a total of 2 standpipe hoses with nozzles installed.
28. Bldg # 1464 Facility has a total of 2 standpipe hoses UNI 45, 20 meter length (year 2004), with two position nozzle (open-close).
29. Bldg # 1467 D The system consists of 3 dry lines with 1 Fire Dept. twin connection each. A total of 10 standpipe hoses are dislocated around the building.
30. Bldg # 1476 Facility has a total of 4 standpipe hose.
31. Bldg # 1478 Facility has a total of 4 standpipe hose with nozzles.
32. Bldg # 14781 Facility has 1 standpipe hose with nozzle.
33. Bldg # 1480 Facility has a total of 6 standpipe hose with nozzles.
34. Bldg # 1481 Facility has a total of 6 standpipe hose with nozzles.
35. Bldg # 1482 Facility has a total of 6 standpipe hose with nozzles.
36. Bldg # 1483 Facility has a total of 6 standpipe hose with nozzles.
37. Bldg # 1484 Facility has a total of 18 standpipe hose with nozzles, 3 for each floor and wing.
SECTION 3
Fire Pumps and Air Compressors
1. Bldg # 110 Sprinkler system of this facility consists of:
- 1 diesel pump LOMBARDINI type 8 LD 665-2 with battery
- 1 pump control panel
- 1 working pressure switch
- 1 safety pressure switch
2. Bldg # 219 Sprinkler system of this facility has a dedicated mechanical room with pumps. System consists of:
- 1 (Jockey) pump SALMSON 40-8 T type {220/380 Volts, 50 Hz, 11/6,3 Amps, 3 kW, 4 Hp, 2850 rpm, Q= 3-10 m /h, H= 66-42,5 m} year 1997
- 1 (Electric) pump SALMSON NO-6S-200-H1 type {Q= 120 m /h, H= 43m, 2920 rpm} year 04/1997
- 1 (Diesel) pump VM Motors Detroit Diesel Company with battery
- 3 pump control panels
- 4 water pressure gauges
- 3 water pressure controls
- 3 expansion tanks 24 lt
- 2 test valves
3. Bldg # 254 Mist type sprinkler system, wet and dry. Wet part consists of:
- 1 (Jockey) MTH serial T 51 L
- 1 (Electric) pump PEERLESS 4 AE 10 G
- 2 pump control panel
- 2 water pressure gauges
- 2 water pressure controls
4. Bldg # 254 Underground Dorm Garages dry sprinkler system consists of:
- 1 air compressor is installed on dry part of sprinklers system in the open garage
- 1 water pressure switch
- 1 air pressure control
- 1 air pressure gauge
- 1 tank drain valve
5. Bldg # 258 Underground Dorm Garages dry sprinkler system consists of:
- 1 air compressor is installed on dry part of sprinklers system in the open garage.
- 1 water pressure switch
- 1 air pressure control
- 1 air pressure gauge
6. Bldg # 263 Fire Suppression Systems’ Pumping Station.
7. Bldg # 411 Fire Suppression Systems’ Pumping Station.
8. Bldg # 91601 Fire Suppression Systems’ Pumping Station.
9. Bldg # 1029 Wet sprinkler system consists of:
- 1 (Jockey) pump ANTRIEBSTECUNIK RF0,75/2-7 {220/380 Volts, 3 phases, 4,5/2,5 Amps, 1,10 kW, IP54}
- 1 (Electric motor) ROTOR NI type XF 250M04 {380 V, 3 phase, 10,3 A, 55 kW, 75 Hp, IP 55}
- 1 impeller pump NIJHUIS type HGT 1.150400 {Q= 227 m /h, H= 40 m, 1480 rpm}
- 1 pump control panel
- 1 water pressure switch MELETRON
- 1 water pressure multistage switch DANFOSS
10. Bldg # 1029 Dry sprinkler system consists of:
- 1 air compressor 50 lt tank, 10 bar, electric consumption 1,5 kW
- 1 water pressure switch
- 1 air pressure control
- 1 air pressure switches
11. Bldg # 1078 See Appendix C Section 1 description.
12. Bldg # 1099 System consists of:
- 1 (Jockey) pump SALMSON type 75-B T, numMatr. 060298, 7,5 Hp, 5,5 kW, 50 Hz {380/660 Volts, 12/7
Amps, 2850 g/min, Q= 4/16 m /h, H= 90/50 m} year 1997
- 1 (Electric motor) SALMSON type K21R 200-LX2, numMatr. 05082530, 380 Volts, 64 Amps, 37 kW, 50
Hz, 2850 g/min, year 1997
- impeller pump (characteristics not readable)
- 1 (Diesel engine) VM Motor Detroit tipo SUN 4105E, numMatr. 10B03325, 2300 g/min, with battery
- impeller pump SALMSON type MP 80 670, Q= 114 m /h, H= 76 m, 2300 g/min
- 3 water pressure controls
13. Bldg # 1173 System consists of WILO water pumping unit mod. GPOA 2-80-250 T 18.5+P 5.5 UNI with 2 main electric pumps and 1 Jokey pump providing Q= 82-25m /h water flow and H= 55-75 m, connected to a 4” line, a 3” by-pass, and 3 expansion tanks 24 lt capacity each. Pumping unit has an electric panel for each pump, assorted valves, gauges, and pressure controlling switches.
14. Bldg 1174 System consists of LOWARA water pumping unit mod. SV6002/2F75T with 2 main electric pumps providing each Q=30-85 m /h water flow and H=42.6-16.4 m, and 1 Jokey pump, connected to a 4” line, and 3 expansion tanks 24 lt capacity each. Pumping unit has an electric panel for each pump, assorted valves, gauges, and pressure controlling switches.
15. Bldg # 1204 East Overhang. See Appendix C Section 1 description.
16. Bldg # 1204 West Overhang. See Appendix C Section 1 description.
17. Bldg 1204-3 System consists of 2 ARMSTRONG electric pumps mod. 6x5x9,5F and 1 Jokey pump, connected to an 8” line. Pumping unit has an electric panel for each pump, assorted valves, gauges, and pressure controlling switches. On main line to Bldg 1204 there is 1 ball valve (2”) and 1 expansion tank 200 lt.
18. Bldg # 1302 System is provided with a fire pump group DAB mod. 1NKP-G 50-200/210/18,5 JET UNI consisting of:
- 1 electric pump DAB
- 23 water pressure gauges
- 3 operating pressure switches
- 1 electric Jockey pump DAB
- 1 operating pressure switch
- 1 water pressure gauge
- 1 expansion tank 20 lt
19. Bldg 1430 System consists of GRUPPO ELETTROIMPIANTI diesel pump providing Q=343 m /h and H=34 m water flow and 1 Jokey pump. Pumping unit has an electric panel for each pump, assorted valves, gauges, and pressure controlling switches.
20. Bldg # 1435 System consists of:
- Water supply line
- Two 10” VIKING butterfly valves
- Two 8” VIKING G-1 check valves
- One electric fire pump SPP KP12X [Q= 5667 liters/minute, Speed= 2950 rpm, p= 6,3 bar, P= 88 kW]
- Two 8”VIKING butterfly valves with position switch
- One 8” VIKING G-1 check valve
- One diesel fire pump SPP TD15I [Q= 1500 USgpm, Speed= 2600 rpm, p= 86,8 psi]
- Two 8”VIKING butterfly valves with position switch
- One 8” VIKING check valve
- One 6” OCV 108FC fire pump relief valve
- One Jokey fire pump LOWARA SV21F15T/A [Q= 1,2-4,2 m /h, H= 103-41 meters, P= 1,5 kW]
- Jokey pump control panel
- 1 differential pressure switch
- 2 ball valves
- 1 check valve, 3 POTTER PS40 pressure switches
- By-pass circuit
- Two 6” GLOBE GLR300W butterfly valves with position switch
- One 6” VIKING G-1 check valve
- Dry sprinkler system is provided with one FIAC 3HP air compressor with 50 liters tank
21. Bldg # 1467 Sprinkler system is supplied with:
- 1 (Jockey) pump GRUNDFOSS CR-2, cat. n. 84.703200, 50 Hz, 380/415 Volts, 3,2/3,1 Amps, 2850 rpm
- 1 (Electric) US Motors mod. N/A, frame 324TS, type D, ENCL DP, SF 1,15, ID # Co8-98107415-001R-
01, code E, DES B, 380 Volts, insul class F, 2940 rpm, 50 Hp, 3 ph, 50 Hz
- 1 impeller pump CENTRIFUGAL FIRE PUMP, SPLIT CASE, LISTED 453 A, MFR point N-AURORA-
IL, type 4”, 1623 CF, gpm 500, AT 50 psi, 2950 rpm, psi at 150% 81,02, B.H.P. 42,23, stage ONE
- 2 pump control panels
- 2 water pressure gauges
- 2 water pressure controls
- 1 expansion tanks 80 lt
22. Bldg # 14611 Fire Suppression Systems’ Pumping Station.
AREA “G”
23. Bldg # 15706 Fire Suppression Systems’ Pumping Station.