This document contains questions and answers regarding solicitation number FA524023R0022 for repair of electrical and fire suppression systems and upgrade of a fire alarm system at Building B26006 for the Department of the Air Force Pacific Air Forces. The questions and answers provide clarification on submission requirements, confirming that a technical approach and cost estimate are not mandatory and instead to refer only to Section L requirements. Additional responses direct offerors to solicitation amendments for electrical as-builts, fire alarm and suppression shop drawings, and mechanical as-builts, and provide details on scope of work items including kitchen hood and Ansul fire suppression systems and related gas components.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Question # Reference Question/Comment Government Response
1 FA524023R0022
Please clarify submission requirements. In accordance with SOW page 9, item 2.8.A of submittals, provide an overview of the technical approach, product catalog data cuts and construction schedule. It contradicts Section L instructions, which state that only completed SF1442, Performance Fact Sheets, and Bonding are necessary for submittal.
Section 2.8 A has been removed from the Statement of Work (SOW). Please refer to the updated SOW in SAM.
Section L requirements remain as is.
2 FA524023R0022
Kindy clarify whether the Technical Approach and
Detailed Cost Estimate are mandatory for our proposal submission.
Technical Approach and Detailed Cost Estimate are not required at time of proposal, please refer to the updated
Statement of Work in SAM. Section L requirements remain as is.
3 FA524023R0022 Request for electrical as-builts for B26006 Refer to Solicitation Amednment FA524023R00220002
4 FA524023R0022
There is 2 ea. Hood washing system in the kitchen of Top of the Rock. However, the scope of work is not included for the system. Do we need to include the system or not?
Refer to SOW 2.3.1.a, "Resuse Kitchen Hood"
5 FA524023R0022
I counted a total of 3x Ansul systems in the kitchen. 1x was tagged NOT IN USE. Please advise if this deactivated system is included with scope of work, or if we are to demo this completely.
Replace all Ansul system.
6 FA524023R0022
Gas is not mentioned in the overview. Will we be replacing gas valves integrated with the ansul systems? There are existing manual reset relays which indicate electric gas valves to be installed somewhere in the kitchen.
Replace as required to complete the system.
7 FA524023R0022 Request for fire alarm shop drawings. The site visit limited what I could see with the fire alarm. Refer to Solicitation Amednment FA524023R00220003
8 FA524023R0022 Please RFI existing fire suppression shop drawings. Refer to Solicitation Amednment FA524023R00220003
9 FA524023R0022 We would like to request the Mechanical As Built of B26006 Refer to Solicitation Amednment FA524023R00220003
10 FA524023R0022 Can you provide a list of kitchen equipment each kitchen hood is serving Refer to Solicitation Amednment FA524023R00220003