FA524023R0019 Amendment 003 Q A.pdf
PDF 79 KB Posted
- Attached to
- 36 CES HVAC Direct Digital Controls (DDC) Upgrade for 644 CBCS Federal contract opportunity
- Solicitation number
- FA524023R0019
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| FA524023R0019 Amendment 003 Combined Synopsis Solicitation.pdf | ||
| FA524023R0019 Amendment 002 Q A.pdf | ||
| Amendment 001 - Site Visit Details and Instructions.pdf | ||
| FA524023R0019 Attachment 1 - Performance Work Statement (PWS).pdf | ||
| FA524023R0019 Attachment 3 - Wage Determination 2015-5693.pdf | ||
| FA524023R0019 Attachment 5 - Evaluation Criteria.pdf | ||
| FA524023R0019 Attachment 7 - Past Performance Fact Sheet.pdf | ||
| FA524023R0019 Attachment 2 - Mandatory Pricing Sheet.xlsx | XLSX spreadsheet | |
| FA524023R0019 Attachment 6 - Clauses and Provisions.pdf | ||
| FA524023R0019 Attachment 8 - Past Performance Questionnaire.pdf | ||
| FA524023R0019 Combined Synopsis Solicitation.pdf | ||
| FA524023R0019 Attachment 4 - Additional Instructions to Offerors.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA524023R0019 - HVAC DDC SYSTEMS UPGRADE for 644 CBCS 16 June 2023 Amendment 003 – RFI from Site Visit Q&A
Q1: Is the contract intent to include DDC graphics for each building for the HVAC? If so, please provide equipment lists per building.
A1: Yes. Please see equipment list below:
B30 1 DX Unit 5 Vavs
B9115 2 AHUs 3 Condensers 5 VAVs
B18001 1 Chiller 8 AHUs 112 VAVs
B18006 1 Chiller 12 AHUs 3 FCUs 79 VAVs
B22002 1 Ducted Split Unit 1 Package Unit
B24016 2 Chillers 9 AHUs 40 VAVs
B61202 1 Chiller 2 AHUs 20 VAVs 10 Exhaust Fans
B61250 2 AHUs 2 Condensers 14 VAVs
B61310 1 Ducted Split Unit 4 VAVs
B61312 3 Dehumidifiers 1 AHU 1 Condenser 5 VAVs
B61316 3 Dehumidifiers 1 AHU 1 Condenser 5 VAVs
Q2: Is the contract intent to have either a or b?
A. Full read/write capabilities from the server down to the field controller level (CH, AHU, VAV, EF, etc. controller). If so, then any changes to the sequence of operations will not be able to be implemented in the future for these field controllers with one controls vendor, or
B. Full programming tool interoperability/compatibility from the server down to the field controller level (CH, AHU, VAV, EF, etc. controller If so, then a unified controls manufacturer from the server, workstation, and field controllers (CH, AHU, VAV, EF, etc. controller) level will need to be installed.
A2: B