A2-Maint
37 KB Posted
- Attached to
- CO-GENERATION PLANT MAINTENANCE
- Solicitation number
- FA5209-11-T-0127
About this file
A2-Maint appendix
Text of this file
A2.1.Equipment List
| A2.1. List of Equipment and Systems | ||
| Gas Engine | ||
| No. of Equipment | 2 ea | |
| Type | Water cooled, 4 cycle, Plug ignition type | |
| Model | 12NHLG-ST | |
| Rating of the out-put power | 647 kw | |
| Rating of the revolutions per minute | 1500 min⁻ˡ | |
| No. of cylinders, locations | 12 cylinders, "V" locate | |
| Cylinder dia x stroke | 165 x 185 mm | |
| Stroke capacity | 47.47 liter | |
| Averaged effectively pressure | 1.09 Mpa | |
| Averaged piston speed | 9.25 m/s | |
| Direction of the revolution | Left revolution, view from the generator | |
| Lubricant oil | GM40 | |
| Stored capacity of lubricant oil | Max.487 liter, Min.291 liter | |
| Stored capacity of cooling water | 90 liter | |
| Engine Start | Automatically or remote controlled cell-motor | |
| Engine Stop | Automatically or remote manually controlled fuel stop | |
| Lubricant oil circulation system | Powered circulation by the gear pump | |
| Engine cooling system | Powered circulation by the cooling pump | |
| Supercharger | Exhaust gas turbine | |
| Vibration Protection | Air spring type protector | |
| Gas consumption | 128.7 +5% m³N/Hr | |
| Lubricant oil consumption | 1.08 g/kW·Hr | |
| An overload proof stress | 110% within 30 minutes | |
| An overspeed proof stress | 110% within 1 minute | |
| Manufacture Date | ||
| Maker | YANMAR | |
| Alternating Current Generator | ||
| No. of Equipment | 2 ea | |
| Model | GFC1355E-4 | |
| Capacity | 625 kVA | |
| Voltage | 6,600 V | |
| Rotary Speed | 1,500 min¯¹ | |
| Phase ·Frequency | 3Ø, 50Hz | |
| Power Factor | 0.8 | |
| Excitation Type | Brush-less | |
| Weight | 1,870 kg | |
| Maker | JM&G | |
| Exhaust Gas Boiler (Hot Water) | ||
| No. of Equipment | 2 ea | |
| Model | ECW-G29-8-11 | |
| Operating Pressure | 98 kPa | |
| Max Capacity | 294 kW | |
| Max Temperature | 120ºC | |
| Heating Surface | 7.89 M² | |
| Manufacture Date | Oct 2003 | |
| Maker | MIURA Boiler | |
| A2.1. List of Equipment and Systems (cont.) | ||
| Panel Type Heat Exchanger (HE-2) | ||
| No. of Equipment | 2 ea | |
| Model | LX-125A-TNHJ-15 | |
| Max Usable Pressure | 1.00 MPaG (Both A&B sides) | |
| Max Usable Temperature | 99.00ºC (Both A&B sides) | |
| Holding Capacity | 7.8 liters | |
| Heating Surface | 2.6 M² | |
| Weight | 320 kg | |
| Manufacture Date | Oct 2003 | |
| Maker | HISAKA Seisakusho | |
| Panel Type Heat Exchanger (HE-3) | ||
| No. of Equipment | 2 ea | |
| Model | LX-115A-TNHJ-29 | |
| Max Usable Pressure | 1.00 MPaG (Both A&B sides) | |
| Max Usable Temperature | 99.00ºC (Both A&B sides) | |
| Holding Capacity | 15.6 liters | |
| Heating Surface | 5.4 M² | |
| Weight | 340 kg | |
| Manufacture Date | Oct 2003 | |
| Maker | HISAKA Seisakusho | |
| Cooling Water Circulation Pump (PCD-1-1) | ||
| No. of Equipment | 2 ea | |
| Model | 65LPD 55.5A | |
| Capacity | 583 liter/min | |
| Head | 26 M | |
| Motor | 200V, 20.8A, 5.5 kw, 50Hz | |
| Manufacture Date | Dec 2003 | |
| Maker | EBARA | |
| Jacket Hot Water Circulation Pump (PH-1-1) | ||
| No. of Equipment | 2 ea | |
| Model | 80LPD 57.5A | |
| Capacity | 750 liter/min | |
| Head | 31 M | |
| Motor | 200V, 29.6A, 12 kw, 50Hz | |
| Manufacture Date | Dec 2003 | |
| Maker | EBARA | |
| WAX Type Temperature Control Valve | ||
| No. of Equipment | 2 ea | |
| Model & Type | L1 | |
| Size | 80A | |
| Temperature | 25 / 35 ºC | |
| Manufacture Date | Sep 2003 | |
| Maker | TEIPI Thermal Engineering | |
| 3 - Way Modutrol Valve | ||
| No. of Equipment | 4 ea | |
| Type | M904F1076 | |
| Volts | DC 24V | |
| Hz | 50 - 60 | |
| Watts | 17 | |
| DEG. | 160 | |
| SEC | 60 | |
| Maker | YAMATAKE | |
| A2.1. List of Equipment and Systems (cont.) | ||
| Plate Type Heat Exchanger (Heat Recovery) | ||
| Installed Location | Co-Gene Plant, Bldg. 123-15 (MR-1) | |
| No. of Equipment | 1 ea | |
| Model | LX-125A-NJ-11 | |
| Heating Capacity | 199 kw | |
| Hot Water Flow Rate | 800 L/min | |
| Max Usable Pressure | 0.5 MPaG | |
| Max Usable Temp | 99 ºC | |
| Storage Capacity | 5.6 Liter | |
| Heating Surface | 1.8 m² | |
| Manufacture Date | Mar 2005 | |
| Maker | HISAKA Seisakusho | |
| Plate Type Heat Exchanger (Heat Recovery) | ||
| Installed Location | Bldg. 112-07 (MR-2) | |
| No. of Equipment | 1 ea | |
| Model | LX-125A-NHP-15 | |
| Heating Capacity | 258 kw | |
| Max Usable Pressure | 1.0 MPaG | |
| Max Usable Temp | 99 ºC | |
| Storage Capacity | 7.8 Liter | |
| Heating Surface | 7.8 m² | |
| Manufacture Date | Jun 2003 | |
| Maker | HISAKA Seisakusho | |
| Plate Type Heat Exchanger for DHW (Heat Recovery) | ||
| Installed Location | Boiler Plant, Bldg. 134 | |
| No. of Equipment | 1 ea | |
| Model | LX-195A-NP-43 | |
| Heating Capacity | ||
| Max Usable Pressure | 0.5 MPaG | |
| Max Usable Temp | 99 ºC | |
| Storage Capacity | 23.5 Liter | |
| Heating Surface | 8.2 m² | |
| Manufacture Date | Dec 2004 | |
| Maker | HISAKA Seisakusho | |
| Plate Type Heat Exchanger for HHW (Heat Recovery) | ||
| Installed Location | Boiler Plant, Bldg. 134 | |
| No. of Equipment | 1 ea | |
| Model | RX-185A-NP-67 | |
| Heating Capacity | ||
| Max Usable Pressure | 0.5 MPaG | |
| Max Usable Temp | 99 ºC | |
| Storage Capacity | 23.7 Liter | |
| Heating Surface | 16.58 m² | |
| Manufacture Date | Dec 2004 | |
| Maker | HISAKA Seisakusho |
&CAttachment 1 to RFQ FA5209-11-T-0127
&CA2-&P
Sheet2
Sheet3
Other files
| File | Type | Posted |
|---|---|---|
| Questions and Answers 11-T-0127.doc | DOC document | |
| Pre-proposal Conference Minutes | — | |
| Co-Generation Solicitation.rtf | RTF text file | |
| ATTENDANCE SHEET-cogeneration plant.doc | DOC document | |
| A456(Minimum Requirement).xls | XLS spreadsheet | |
| A1-Maint | — | |
| PWS FINAL SOLICITATION RFQ 1 Aug 11.doc | DOC document | |
| A3-(Maintenance Schedule) RFQ.xls | XLS spreadsheet | |
| B1 Maintenance Report | — | |
| Notice to Offeror.doc | DOC document | |
| A-6 Market Research questionnaire | — |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
File details come from the government source that posted it. Updated .