Atch_10_-_BoD_Rosemount_Level_Transmitters.pdf
PDF 6 MB Posted
- Attached to
- Repair CHPP Ash Handling System Controls Federal contract opportunity
- Solicitation number
- FA500419BA015
About this file
Amendment 0001 - Attachment 10 - BoA Rosemount Level Transmitters
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation_Amendment_-_FA500419BA0150002.pdf | ||
| Atch_1_-_Specification_with_Sequence_of_Operations,_I-O_List,_&_Data_Sheets.pdf | ||
| Solicitation_Amendment_FA500419BA0150002_SF_30.pdf | ||
| Atch_9_-_Partial_Design_Analysis.pdf | ||
| Atch_7_-_Wage_Determination_(Revised).pdf | ||
| Atch_12_-_01_50_00.pdf | ||
| Solicitation_Amendment_FA500419BA0150001_SF_30.pdf | ||
| Solicitation_Amendment_-_FA500419BA0150001.pdf | ||
| Atch_8_-_Q&A_Responses.pdf | ||
| Atch_13_-_01_73_29.pdf | ||
| Atch_14_-_02_41_00.pdf | ||
| Atch_16_-_Sequence_of_Operations,_I-O_List,_&_Data_Sheets.pdf | ||
| Atch_15_-_40_95_00.pdf | ||
| Atch_11_-_01_14_00.pdf | ||
| MFR_for_FBO.pdf | ||
| Solicitation_-_FA500419BA015.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Product Data Sheet November 2017
00813-0100-4408, Rev BA
Rosemount™ 5408 and 5408:SIS Level Transmitters Non-Contacting Radar
Unique energy-efficient two-wire FMCW radar technology for optimal performance
Engineered and user tested for best in class safety, reliability, and ease-of-use
Built on 40 years of inventing and redefining radar level measurement
Intuitive commissioning experience driven by wizards and adaptive graphics
Rosemount 5408:SIS, optimal for safety applications and IEC 61508 certified to SIL 2
Safe, easy, and remote proof testing without process interruptions
Rosemount 5408 Series November 2017
Emerson.com/Rosemount
Introduction
Measurement principle
The Rosemount 5408 and 5408:SIS are two-wire non-contacting radar transmitters for continuous level measurement of liquids, slurries, and solids. The measurement principle is fast-sweep Frequency Modulated Continuous Wave (FMCW).
Radar signals are continuously transmitted towards the product surface with a microwave frequency modulated over a span. The level is proportional to the frequency difference between currently received and transmitted signal.
Technology to redefine reliability
The Rosemount 5408 and 5408:SIS are optimized for reliable and accurate performance even in challenging process conditions. FMCW technology maximizes radar signal strength and produces a robust and reliable measurement (with 30 times more power on the surface than traditional two-wire non-contacting radars).
The transmitters can operate with only 12 Vdc lift-off voltage and they are self-powered for up to 2 seconds to maintain operation despite cable glitches or lightning.
Ease-of-use at every touch point
The Rosemount 5408 and 5408:SIS are designed to simplify operator tasks. They deliver ease-of-use at every touch point, from the pictorial user instructions and graphical, intuitive wizards to the PTFE seal that requires no O-ring material for simplifying model selection.
Dedicated to safety
The Smart Diagnostics Suite provides operators with early alerts in case of antenna build-up, weak power supply, or abnormal surface conditions. Also, a local memory enables full insight into the last seven days of measurements, alerts, and echo profiles.
The Rosemount 5408:SIS is the ideal choice for functional safety such as overfill prevention. It is safety certified (SIL 2/SIL 3), supports long proof-test intervals guaranteed to suit your schedule, and can be tested remotely without any process interruption.
Contents
Ordering Information
Specifications
Product Certifications
Dimensional Drawings
30x fin fin fout fout t f f d=Distance d
Frequency (GHz)
Transmitted signal Reflected signal
Time (s)
Rosemount 5408 SeriesNovember 2017
Emerson.com/Rosemount
Application examples
The Rosemount 5408 and 5408:SIS are ideal for level measurements over a broad range of liquid and solids applications. The transmitters are virtually unaffected by changing density, temperature, pressure, media dielectric, pH, and viscosity. Furthermore, non-contacting radar level is ideal when internal tank obstructions are a limiting factor.
Storage and buffer tanks
The Rosemount 5408 provides accurate and reliable level measurement for both metallic or non-metallic vessels containing almost any liquid (e.g. oil, gas condensate, water, chemicals).
Reactors Blenders and mixers
The Rosemount 5408 is ideal for the most challenging applications, including reactors where there can be agitation, foaming, condensation as well as high temperatures and pressures.
The Rosemount 5408 can help you withstand the rigors of blenders and mixing tanks.
Easy to install and commission, it is also unaffected by virtually any fluid property change.
Open atmospheric applications Still pipe and chamber installations
The Rosemount 5408 measures reliably in open applications, from short range sumps or ponds to long range dams.
The Rosemount 5408 is an excellent choice for level measurement in tanks with still pipes. It may also be used in chambers, but guided wave radar is generally the best fit for these applications.
Bulk solids Safety applications
The Rosemount 5408 is the ideal solution for small to medium sized silos with rapid level changes. The narrow beam avoids internal obstructions while still keeping good level measurement.
The Rosemount 5408:SIS is the ideal choice for safety functions such as overfill prevention, level deviation monitoring or dry-run prevention.
SIL 2
Emerson.com/Rosemount
Ordering Information
Rosemount 5408 Level Transmitter
The Rosemount 5408 is a two-wire non-contacting radar transmitter for level measurements over a broad range of liquids and slurries. It uses a unique energy efficient radar technology based on the FMCW principle to ensure reliable performance even in challenging conditions.
Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 23 for more information on material selection.
Table 1. Rosemount 5408 Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Model Product description
5408 Radar Level Transmitter ★
Profile
A Standard Monitoring & Control Applications ★
Measurement type
1 Liquid Level Measurement ★
3 Solids Level Measurement ★
4 Liquid & Solids Level Measurement ★
Performance class
S Standard ★
Signal output
H 4–20 mA with digital signal based on HART® Revision 6 protocol (HART Revision 7 available as option) ★
Housing material
A Aluminum ★
S Stainless Steel (SST) ★
Conduit/cable threads
1 ½-14 NPT ★
2 M20 x 1.5 ★
3(1) G½
Hazardous locations certifications
NA None ★
E1 ATEX Flameproof ★
Emerson.com/Rosemount
I1 ATEX Intrinsic Safety ★
N1 ATEX Type n ★
E5 FM Explosion-proof, Dust Ignition-proof ★
I5 FM Intrinsically Safe; Nonincendive ★
E6 Canadian Explosion-proof, Dust Ignition-proof ★
I6 Canadian Intrinsically Safe; Nonincendive ★
E7 IECEx Flameproof, Dust Ignition-proof ★
I7 IECEx Intrinsic Safety ★
N7 IECEx Type n ★
E2 INMETRO (Brazil) Flameproof ★
I2 INMETRO (Brazil) Intrinsic Safety ★
N2 INMETRO (Brazil) Type n ★
E3 NEPSI (China) Flameproof ★
I3 NEPSI (China) Intrinsic Safety ★
N3 NEPSI (China) Type n ★
IP KCCs (Korea) Intrinsic Safety ★
Materials of construction Available antenna types
1 316/316L/EN 1.4404 Cone, Parabolic ★
7 All PTFE Wetted Parts Process Seal ★
Process connection type Available antenna types
F(2) Flat Face Flange Cone, Parabolic ★
R(3) Raised Face Flange All ★
N NPT Thread Cone ★
G BSPP (G) Thread Cone, Parabolic ★
B Bracket Mounting Cone ★
C Tri Clamp Process Seal ★
W Welded Connection Parabolic ★
Process connection size Available process connections Available antenna types
A 1½-in. Thread Cone ★
2 2-in./DN50/50A Flange, Thread(4), Tri Clamp(5) Cone, Process Seal ★
3 3-in./DN80/80A Flange, Thread(4), Tri Clamp(5) Cone, Process Seal ★
B 3½-in. Thread, Welded Parabolic ★
4 4-in./DN100/100A Flange, Thread(4) Cone, Process Seal ★
Table 1. Rosemount 5408 Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Emerson.com/Rosemount
6 6-in./DN150/150A Flange Cone ★
8 8-in./DN200/200A Flange Cone, Parabolic ★
T 10-in./DN250/250A Flange Parabolic ★
Z None (use when ordering bracket mounting) Bracket Mounting Cone ★
Process connection rating (see Table 3, Table 4, and Table 5 for available flanges)
ZZ For use with non-flange process connection type ★
ASME flanges
AA ASME B16.5 Class 150 ★
AB ASME B16.5 Class 300 ★
AC ASME B16.5 Class 600 ★
EN flanges Note
DK EN1092-1 PN6 N/A ★
DA EN1092-1 PN16 PN10 and PN16 dimensions are identical for DN50 to DN150 ★
DB EN1092-1 PN40 PN25 and PN40 dimensions are identical for DN50 to DN150 ★
DC EN1092-1 PN63 N/A ★
DD EN1092-1 PN100 N/A ★
JIS flanges
JK JIS 5K ★
JA JIS 10K ★
JB JIS 20K ★
Antenna type Operating pressure Operating temperature
CAA Cone Antenna (PTFE seal) -15 to 363 psig (-1 to 25 bar) -76 to 392 °F (-60 to 200 °C) ★
CAB Cone Antenna (PTFE seal) -15 to 725 psig (-1 to 50 bar)(6) -40 to 302 °F (-40 to 150 °C) ★
CAC Cone Antenna (PTFE seal) -15 to 1450 psig (-1 to 100 bar) -40 to 212 °F (-40 to 100 °C) ★
CAD Cone Antenna (PTFE seal) -15 to 44 psig (-1 to 3 bar) -76 to 482 °F (-60 to 250 °C) ★
CBF Cone Antenna (PEEK seal, FVMQ) -15 to 754 psig (-1 to 52 bar) -76 to 338 °F (-60 to 170 °C) ★
CBK Cone Antenna (PEEK seal, Kalrez® 6375) -15 to 754 psig (-1 to 52 bar) 5 to 482 °F (-15 to 250 °C) ★
CBM Cone Antenna (PEEK seal, FKM) -15 to 754 psig (-1 to 52 bar) -13 to 428 °F (-25 to 220 °C) ★
CBV Cone Antenna (PEEK seal, Viton®) -15 to 754 psig (-1 to 52 bar) -22 to 392 °F (-30 to 200 °C) ★
SAA Process Seal Antenna -7 to 363 psig (-0.5 to 25 bar)(7) -76 to 392 °F (-60 to 200 °C)(7) ★
PAS Parabolic Antenna, Swivel Mount -7 to 43 psig (-0.5 to 3 bar) -67 to 392 °F (-55 to 200 °C) ★
Table 1. Rosemount 5408 Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
Emerson.com/Rosemount
Antenna size Available antenna types
2 2-in. (DN50) Cone, Process Seal ★
3 3-in. (DN80) Cone, Process Seal ★
4 4-in. (DN100) Cone, Process Seal ★
8 8-in. (DN200) Parabolic ★
Options (include with selected model number)
Antenna extensions (see page 38) Total length
S1 Extended Cone Antenna 24-in. (600 mm) ★
S2 Extended Cone Antenna, Segmented 48-in. (1200 mm) ★
Purging connection (see page 23)(8)
PC1 Purging Connector (Purge Ring) ★
Display
M5 LCD Display ★
Functional safety options
EF1 Ready for upgrade to Rosemount 5408:SIS ★
Diagnostic functionality
DA1 Smart Diagnostics Suite (see page 21) ★
HART revision configuration
HR7 4-20 mA with digital signal based on HART Revision 7 protocol ★
Open air applications configuration(9)
OA Open Air Applications Configuration; LPR (Level Probing Radar) ★
Factory configuration
C1 Factory Configuration per Configuration Data Sheet ★
Alarm limits
C4 NAMUR Alarm and Saturation Levels, High Alarm ★
C5 NAMUR Alarm and Saturation Levels, Low Alarm ★
C8(10) Standard Rosemount Alarm and Saturation Levels, Low Alarm ★
Welding standard for flanges(11)
AW According to ASME IX ★
EW According to EN-ISO ★
Table 1. Rosemount 5408 Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject http://www.emerson.com/documents/automation/193128.pdf
Emerson.com/Rosemount
Special quality assurance
Q4 Calibration Data Certificate ★
Hydrostatic testing(12)
Q5 Hydrostatic Testing, including certificate ★
Material traceability certification(13)
Q8 Material Traceability Certification per EN 10204 3.1 (2.1 for non-metallic) ★
Materials certification(14)
Q15 NACE® Material Recommendation per NACE MR0175/ISO 15156 ★
Q25 NACE Material Recommendation per ANSI/NACE MR0103/ISO 17495-1 ★
Q35 NACE Material Recommendation per NACE MR0175/ISO 15156 and ANSI/NACE MR0103/ISO 17495-1 ★
Welding procedure qualification record documentation(11)
Q66 Welding Procedure Qualification Record (WPQR) ★
Q67 Welder Performance Qualification (WPQ) ★
Q68 Welding Procedure Specification (WPS) ★
Q79 WPQR/WPQ/WPS ★
Dye penetration test certificate(11)
Q73 Certificate of Liquid Penetrant Inspection ★
Positive material identification certificate
Q76 Positive Material Identification Certificate of Conformance ★
Extended product warranty
WR3 3-year Limited Warranty ★
WR5 5-year Limited Warranty ★
Conduit electrical connector (shipped uninstalled)(15)
EC M 12, 4-pin, Male connector (eurofast®) ★
MC A size Mini, 4-pin, Male connector (minifast®) ★
Specials (see page 24)
PXXXX Custom Engineered Solutions beyond standard model codes. Consult factory for details.
Typical model number: 5408 A 1 S H A 1 E5 1 R 3 AB CAB 3 M5 DA1
1. G½ thread form is not available with hazardous locations approvals.
2. Type A flat face for EN 1092-1 flanges.
3. Type B1 raised face for EN 1092-1 flanges.
4. Only available with cone antenna.
5. Only available with process seal antenna.
Table 1. Rosemount 5408 Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
Emerson.com/Rosemount
6. Pressure limit is derated for process temperatures above 100 °F (38 °C), see Figure 5 on page 22 for details.
7. Refer to Figure 7 on page 22 for pressure/temperature ratings of Tri Clamp connection.
8. Option code PC1 is for cone antennas only, and requires matching flange and antenna sizes. Note that all parabolic antennas come with an integrated air purge connection.
9. Only available with parabolic antenna and 4-in. (DN100) cone antenna.
10. The standard alarm setting is high.
11. Only applies to flanged process connections with welded construction; only applicable to cone antennas (see Table 3 on page 15).
12. Hydrostatic testing is only available for cone antennas and process seal antennas with flanged process connections.
13. Certificate includes all pressure retaining and wetted parts.
14. Not available with parabolic antenna.
15. Requires ½-14 NPT conduit/cable threads (code 1). Available with Intrinsically Safe approvals only.
Emerson.com/Rosemount
Rosemount 5408:SIS Level Transmitter
Safety certified to IEC 61508 for SIL2 applications with SIL3 capability, the Rosemount 5408:SIS reduces cost of risk, increases efficiency and protects your staff and the environment.
Specification and selection of product materials, options, or components must be made by the purchaser of the equipment. See page 23 for more information on material selection.
Table 2. Rosemount 5408:SIS Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject to additional delivery lead time.
Model Product description
5408 Radar Level Transmitter ★
Profile(1)
F Functional Safety / SIS Applications ★
Measurement type
1 Liquid Level Measurement ★
4(2) Liquid & Solids Level Measurement ★
Performance class
S Standard ★
Signal output
H 4–20 mA with digital signal based on HART Revision 6 protocol (HART Revision 7 available as option) ★
Housing material
A Aluminum ★
S Stainless Steel (SST) ★
Conduit/cable threads
1 ½-14 NPT ★
2 M20 x 1.5 ★
3(3) G½
Hazardous locations certifications
NA None ★
E1 ATEX Flameproof ★
I1 ATEX Intrinsic Safety ★
N1 ATEX Type n ★
E5 FM Explosion-proof, Dust Ignition-proof ★
Emerson.com/Rosemount
I5 FM Intrinsically Safe; Nonincendive ★
E6 Canadian Explosion-proof, Dust Ignition-proof ★
I6 Canadian Intrinsically Safe; Nonincendive ★
E7 IECEx Flameproof, Dust Ignition-proof ★
I7 IECEx Intrinsic Safety ★
N7 IECEx Type n ★
E2 INMETRO (Brazil) Flameproof ★
I2 INMETRO (Brazil) Intrinsic Safety ★
N2 INMETRO (Brazil) Type n ★
E3 NEPSI (China) Flameproof ★
I3 NEPSI (China) Intrinsic Safety ★
N3 NEPSI (China) Type n ★
IP KCCs (Korea) Intrinsic Safety ★
Materials of construction Available antenna types
1 316/316L/EN 1.4404 Cone, Parabolic ★
7 All PTFE Wetted Parts Process Seal ★
Process connection type Available antenna types
F(4) Flat Face Flange Cone, Parabolic ★
R(5) Raised Face Flange All ★
N NPT Thread Cone ★
G BSPP (G) Thread Cone, Parabolic ★
B Bracket Mounting Cone ★
C Tri Clamp Process Seal ★
W Welded Connection Parabolic ★
Process connection size Available process connections Available antenna types
A 1½-in. Thread Cone ★
2 2-in./DN50/50A Flange, Thread(6), Tri Clamp(7) Cone, Process Seal ★
3 3-in./DN80/80A Flange, Thread(6), Tri Clamp(7) Cone, Process Seal ★
B 3½-in. Thread, Welded Parabolic ★
4 4-in./DN100/100A Flange, Thread(6) Cone, Process Seal ★
6 6-in./DN150/150A Flange Cone ★
8 8-in./DN200/200A Flange Cone, Parabolic ★
T 10-in./DN250/250A Flange Parabolic ★
Z None (use when ordering bracket mounting) Bracket Mounting Cone ★
Table 2. Rosemount 5408:SIS Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
Emerson.com/Rosemount
Process connection rating (see Table 3, Table 4, and Table 5 for available flanges)
ZZ For use with non-flange process connection type ★
ASME flanges
AA ASME B16.5 Class 150 ★
AB ASME B16.5 Class 300 ★
AC ASME B16.5 Class 600 ★
EN flanges Note
DK EN1092-1 PN6 N/A ★
DA EN1092-1 PN16 PN10 and PN16 dimensions are identical for DN50 to DN150 ★
DB EN1092-1 PN40 PN25 and PN40 dimensions are identical for DN50 to DN150 ★
DC EN1092-1 PN63 N/A ★
DD EN1092-1 PN100 N/A ★
JIS flanges
JK JIS 5K ★
JA JIS 10K ★
JB JIS 20K ★
Antenna type Operating pressure Operating temperature
CAA Cone Antenna (PTFE seal) -15 to 363 psig (-1 to 25 bar) -76 to 392 °F (-60 to 200 °C) ★
CAB Cone Antenna (PTFE seal) -15 to 725 psig (-1 to 50 bar)(8) -40 to 302 °F (-40 to 150 °C) ★
CAC Cone Antenna (PTFE seal) -15 to 1450 psig (-1 to 100 bar) -40 to 212 °F (-40 to 100 °C) ★
CAD Cone Antenna (PTFE seal) -15 to 44 psig (-1 to 3 bar) -76 to 482 °F (-60 to 250 °C) ★
CBF Cone Antenna (PEEK seal, FVMQ) -15 to 754 psig (-1 to 52 bar) -76 to 338 °F (-60 to 170 °C) ★
CBK Cone Antenna (PEEK seal, Kalrez 6375) -15 to 754 psig (-1 to 52 bar) 5 to 482 °F (-15 to 250 °C) ★
CBM Cone Antenna (PEEK seal, FKM) -15 to 754 psig (-1 to 52 bar) -13 to 428 °F (-25 to 220 °C) ★
CBV Cone Antenna (PEEK seal, Viton) -15 to 754 psig (-1 to 52 bar) -22 to 392 °F (-30 to 200 °C) ★
SAA Process Seal Antenna -7 to 363 psig (-0.5 to 25 bar)(9) -76 to 392 °F (-60 to 200 °C)(9) ★
PAS Parabolic Antenna, Swivel Mount -7 to 43 psig (-0.5 to 3 bar) -67 to 392 °F (-55 to 200 °C) ★
Antenna size Available antenna types
2 2-in. (DN50) Cone, Process Seal ★
3 3-in. (DN80) Cone, Process Seal ★
4 4-in. (DN100) Cone, Process Seal ★
8 8-in. (DN200) Parabolic ★
Table 2. Rosemount 5408:SIS Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
Emerson.com/Rosemount
Options (include with selected model number)
Antenna extensions (see page 38) Total length
S1 Extended Cone Antenna 24-in. (600 mm) ★
S2 Extended Cone Antenna, Segmented 48-in. (1200 mm) ★
Purging connection (see page 23)(10)
PC1 Purging Connector (Purge Ring) ★
Display
M5 LCD Display ★
Functional safety options
EF2 Extended SIS Package ★
Diagnostic functionality
DA1 Smart Diagnostics Suite (see page 21) ★
HART revision configuration
HR7 4-20 mA with digital signal based on HART Revision 7 protocol ★
Factory configuration
C1 Factory Configuration per Configuration Data Sheet ★
Alarm limits
C4 NAMUR Alarm and Saturation Levels, High Alarm ★
C5 NAMUR Alarm and Saturation Levels, Low Alarm ★
C8(11) Standard Rosemount Alarm and Saturation Levels, Low Alarm ★
Welding standard for flanges(12)
AW According to ASME IX ★
EW According to EN-ISO ★
Special quality assurance
Q4 Calibration Data Certificate ★
Hydrostatic testing(13)
Q5 Hydrostatic Testing, including certificate ★
Material traceability certification(14)
Q8 Material Traceability Certification per EN 10204 3.1 (2.1 for non-metallic) ★
Table 2. Rosemount 5408:SIS Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject http://www.emerson.com/documents/automation/193128.pdf
Emerson.com/Rosemount
Quality certification for safety
QS Certificate of FMEDA Data ★
QT Safety-certified to IEC 61508 with certificate of FMEDA data ★
Materials certification(15)
Q15 NACE Material Recommendation per NACE MR0175/ISO 15156 ★
Q25 NACE Material Recommendation per ANSI/NACE MR0103/ISO 17495-1 ★
Q35 NACE Material Recommendation per NACE MR0175/ISO 15156 and ANSI/NACE MR0103/ISO 17495-1 ★
Welding procedure qualification record documentation(12)
Q66 Welding Procedure Qualification Record (WPQR) ★
Q67 Welder Performance Qualification (WPQ) ★
Q68 Welding Procedure Specification (WPS) ★
Q79 WPQR/WPQ/WPS ★
Dye penetration test certificate(12)
Q73 Certificate of Liquid Penetrant Inspection ★
Positive material identification certificate
Q76 Positive Material Identification Certificate of Conformance ★
Extended product warranty
WR3 3-year Limited Warranty ★
WR5 5-year Limited Warranty ★
Paint option for aluminum housing
PY1 Housing and Covers in Yellow per RAL 1003 ★
PY2 Covers in Yellow per RAL 1003 ★
PR1 Housing and Covers in Red per RAL 3002 ★
PR2 Covers in Red per RAL 3002 ★
PO1 Housing and Covers in Orange per Munsell 2.5 YR 6/14 ★
PO2 Covers in Orange per Munsell 2.5 YR 6/14 ★
Conduit electrical connector (shipped uninstalled)(16)
EC M 12, 4-pin, Male connector (eurofast) ★
MC A size Mini, 4-pin, Male connector (minifast) ★
Specials (see page 24)
PXXXX Custom Engineered Solutions beyond standard model codes. Consult factory for details.
Typical model number: 5408 F 1 S H A 1 E5 1 R 3 AB CAB 3 M5 DA1 EF2 QT
Table 2. Rosemount 5408:SIS Level Transmitter Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
Emerson.com/Rosemount
1. The Rosemount 5408:SIS has two operational modes: Safety (SIS) and Control/Monitoring. Safety (SIS) mode must be set when used in Safety Instrumented Systems. Control/Monitoring mode is intended for use in a Basic Process Control System (BPCS).
2. Solids level measurement is only available when operating in Control/Monitoring mode.
3. G½ thread form is not available with hazardous locations approvals.
4. Type A flat face for EN 1092-1 flanges.
5. Type B1 raised face for EN 1092-1 flanges.
6. Only available with cone antenna.
7. Only available with process seal antenna.
8. Pressure limit is derated for process temperatures above 100 °F (38 °C), see Figure 5 on page 22 for details.
9. Refer to Figure 7 on page 22 for pressure/temperature ratings of Tri Clamp connection.
10. Option code PC1 is for cone antennas only, and requires matching flange and antenna sizes. Note that all parabolic antennas come with an integrated air purge connection.
11. The standard alarm setting is high.
12. Only applies to flanged process connections with welded construction; only applicable to cone antennas (see Table 3 on page 15).
13. Hydrostatic testing is only available for cone antennas and process seal antennas with flanged process connections.
14. Certificate includes all pressure retaining and wetted parts.
15. Not available with parabolic antenna.
16. Requires ½-14 NPT conduit/cable threads (code 1). Available with Intrinsically Safe approvals only.
Table 3. Cone Antenna - Availability of Flanged Process Connections (Type(1) vs. Size and Rating)
1. F = Flat Face (process connection type code F)
R = Raised Face (process connection type code R)
Process connection size Process connection rating
ASME B16.5 flanges EN1092-1 flanges JIS B2220 flanges
Class 150(2)
2. Forged one-piece flange (see page 42)
Class 300(2) Class 600(3)
3. Welded construction (see page 42)
PN16(4)
4. Welded construction for type A flat face; forged one-piece flange for type B1 raised face.
PN40(4) PN63(3) PN100(3) 10K(2) 20K(3)
2-in./DN50/50A R R R F F, R F, R F R R
3-in./DN80/80A R R R F, R F, R F, R F, R R R
4-in./DN100/100A R R N/A F, R F, R F F R R
6-in./DN150/150A R R N/A F, R F, R N/A N/A R R
8-in./DN200/200A R R N/A F, R F, R N/A N/A R R
Table 4. Process Seal Antenna - Availability of Flanged Process Connections (Type(1) vs. Size and Rating)
1. R = Raised Face (process connection type code R)
Process connection size Process connection rating
ASME B16.5 flanges(2)
2. Forged one-piece flange
EN1092-1 flanges(2) JIS B2220 flanges(2)
Class 150 Class 300 PN6 PN16 PN40 10K
2-in./DN50/50A R R R R R R
3-in./DN80/80A R R R R R R
4-in./DN100/100A R R R R R R
Emerson.com/Rosemount
Table 5. Parabolic Antenna - Availability of Flanged Process Connections (Type(1) vs. Size and Rating)
1. F = Flat Face face (process connection type code F)
R = Raised Face face (process connection type code R)
Process connection size Process connection rating
ASME B16.5 Class 150 flange EN1092-1 PN6 flange JIS B2220 5K flange
8-in./DN200/200A R F R
10-in./DN250/250A R F R
Table 6. Accessories
HART modem and cable
03300-7004-0002 MACTek® VIATOR® HART modem and cables (USB connection)
Emerson.com/Rosemount
Specifications
Performance specifications
General
Conformance to specification (±3 [Sigma])
Technology leadership, advanced manufacturing techniques, and statistical process control ensure specification conformance to at least ±3.
Reference conditions
Measurement target: Metal plate, no disturbing objects
Temperature: 68 to 86 °F (20 to 30 °C)
Ambient pressure: 14 to 15 psi (960 to1060 mbar)
Relative humidity: 25-75%
Damping: Default value, 2 s
Reference accuracy(1)
±0.08 in. (±2 mm)
Repeatability
±0.04 in. (±1 mm)
Ambient temperature effect(2)
±0.04 in. (±1 mm)/10 K
Sensor update rate
Minimum 1 update per second
Maximum level rate
40 mm/s as default, adjustable up to 200 mm/s
Measuring range
Maximum measuring range(3)(4)
Rosemount 5408: 130 ft. (40 m)
Rosemount 5408:SIS: 130 ft. (40 m) in Control/Monitoring mode 82 ft. (25 m) in Safety (SIS) mode
Accuracy over measuring range
The measuring range is limited by the blind zone at the very top of the tank. In the blind zone, the accuracy exceeds ±0.20 in. (±5
mm) and measurements may not be possible. Measurements close to the blind zone will have reduced accuracy (see Figure 1).
For the extended cone antennas, the reduced accuracy zone ends 11.8 in. (30 cm) below the antenna end.
Figure 1. Accuracy Over Measuring Range
A. Device Reference Point
1. Refer to the IEC 60770-1 standard for a definition of radar specific performance parameters and if applicable corresponding test procedure.
2. Ambient temperature effect specification valid over temperature range -40 °F to 176 °F (-40 °C to 80 °C).
3. Note that a combination of adverse process conditions, such as heavy turbulence, foam, and condensation, together with products with poor reflection may affect the measuring range.
4. The Rosemount 5408:SIS has two operational modes: Safety (SIS) and Control/Monitoring. Safety (SIS) mode must be set when used in Safety Instrumented Systems. Control/Monitoring mode is intended for use in a Basic Process Control System (BPCS).
±0.08 in.
(2 mm)
7.9 in.
(20 cm)
19.7 in.
(50 cm)
±0.20 in.
(5 mm)
A
D istance
Accuracy
Emerson.com/Rosemount
Beam angle and beam width
Figure 2. Beam Angle and Beam Width
Table 8. Beam angle ()
Table 9. Beam Width, ft. (m)
Environment
Vibration resistance
2 g at 10-180 Hz according to IEC 61298-3, level “field with general application”
IACS UR E10 test 7
For compliance with these standards, the transmitter housing must be fully tightened into the sensor module. This is achieved by rotating the transmitter housing clockwise to thread limit.
For further details, see the Rosemount 5408 and 5408:SIS Reference Manual.
Table 7. Recommended Measuring Range for Solids, ft. (m)(1)
Antenna Light powder(2) Heavy powder(3) Grain size products(4) Larger particles(5)
2-in. (DN50) cone/process seal N/A(6) 33 (10) 33 (10) 39 (12)
3-in. (DN80) cone/process seal 4-in. (DN100) process seal
10 (3) 49 (15) 49 (15) 59 (18)
4-in. (DN100) cone 23 (7) 66 (20) 130 (40) 130 (40)
8-in. (DN200) parabolic 46 (14) 115 (35) 130 (40) 130 (40)
1. The figures given in the table should be considered as guidelines; the total measuring range may differ depending on other contributing application conditions such as product filling, how the product piles up, silo diameter vs. angle of repose, internal obstacles within the silo, etc.
2. Plastic powder/granules/pellets (Dielectric constant: 1.2-2.0)
3. Lime powder, cement, sand, etc. (Dielectric constant: 1.5-2.5)
4. Grain, kernels, brans, etc. (Dielectric constant: 1.5-4.0)
5. Wood chips, pellets, etc. (Dielectric constant: 1.7- 4.5)
6. Consider using the Rosemount 5303.
Antenna size Beam angle
2-in. (DN50) cone/process seal 18°
3-in. (DN80) cone/process seal 14°
4-in. (DN100) cone/process seal 10°
8-in. (DN200) parabolic 4.5°
D
W
Distance (D)
Beam width (W)
2-in. cone/ process seal
3-in. cone/ process seal
4-in. cone/ process seal
Parabolic
16 (5) 5.2 (1.6) 4.0 (1.2) 2.9 (0.9) 1.3 (0.4)
33 (10) 10.4 (3.2) 8.1 (2.5) 5.7 (1.8) 2.6 (0.8)
49 (15) 15.6 (4.8) 12.1 (3.7) 8.6 (2.6) 3.9 (1.2)
66 (20) 20.8 (6.3) 16.1 (4.9) 11.5 (3.5) 5.2 (1.6)
82 (25) 26.0 (7.9) 20.1 (6.1) 14.3 (4.4) 6.4 (2.0)
98 (30) 31.2 (9.5) 24.2 (7.4) 17.2 (5.3) 7.7 (2.4)
131 (40) 41.6 (12.7) 32.2 (9.8) 23.0 (7.0) 10.3 (3.1) http://www.emerson.com/documents/automation/202470.pdf
Emerson.com/Rosemount
Electromagnetic compatibility (EMC)
EMC Directive (2014/30/EU): EN 61326-1
EN 61326-2-3
NAMUR recommendations NE21(1)
For Rosemount 5408:SIS and Rosemount 5408 with option code EF1, the blue plug on the terminal block must be connected.
Pressure Equipment Directive (PED)
Complies with 2014/68/EU article 4.3
Built-in lightning protection
EN 61326, IEC 61000-4-5, level 6kV
Radio approvals
Radio Equipment Directive (RED) 2014/53/EU:
ETSI EN 302 372, ETSI EN 302 729 and EN 62479
Part 15 of the FCC Rules
Industry Canada RSS 211
Functional specifications
General
Field of applications
Continuous level measurements for tank monitoring, process control, and overfill prevention on a broad range of liquids, slurries, and solids.
Ideal for applications with varying and harsh process conditions, such as heavy turbulence, foaming, product build-up, condensing vapors, sticky, viscous, corrosive, and crystallizing products.
Measurement principle
Frequency Modulated Continuous Wave (FMCW)
Frequency range
24.05 to 27.0 (26.5(2)) GHz
Maximum output power
-5 dBm (0.32 mW)
Internal power consumption
< 1 W in normal operation
Humidity
0 - 100% relative humidity, non-condensing
Turn-on time(3)
< 40 s
Functional safety
The Rosemount 5408:SIS Level Transmitter is IEC 61508 certified accordingly:
Low and high demand: Type B element
SIL 2 for random integrity @ HFT=0
SIL 3 for random integrity @ HFT=1
SIL 3 for systematic capability
Safety deviation
±2.0% of analog output span
Transmitter response time(4)(5)
< 6 s at damping value 2 s (default)
< 2 s at damping value 0 s (minimum)
Table 10. Failure Rates According to IEC 61508 in FIT(6)
Table 11. Suggested Proof-tests
The FMEDA report includes failure rate data, assessment details, and assumptions regarding failure rate analysis.
1. In challenging applications where the dynamic of the Rosemount 5408 and 5408:SIS sensitivity is utilized by multiple factors such as small aperture antenna, very low product dielectric constant and/or turbulent surface, the margin for additional influence due to extreme EMC may be limited.
2. For LPR (Level Probing Radar), option code OA.
3. Time from when power is applied to the transmitter until performance is within specifications.
4. Step response time as per IEC 61298-2.
5. The transmitter response time will be a function of the configured Damp-ing value. Rosemount Radar Master Plus has a built-in function to calculate the transmitter’s measurement response time (requires option code EF2).
λSD λSU λDD λDU SFF
0 260 737 79 92.7%
6. FIT = Failure In Time per billion hours
Proof-test Proof-test coverage
Remaining dangerous, undetected failures
1-point level and analog output verification
73% 21 FIT
2-point level and analog output verification
84% 13 FIT
Analog output verification
33% 53 FIT
Level deviation monitoring
61% 31 FIT
http://www.emerson.com/catalog/en-us/rosemount-5408-non-contacting-radar-transmitter
Emerson.com/Rosemount
Display and configuration
LCD display (option code M5)
Toggles between selected output variables
Shows diagnostic information (alerts)
Figure 3. LCD Display
Remote display
Data can be read remotely by using the Rosemount 751 Field Signal Indicator, see the corresponding Product Data Sheet for more information.
Configuration tools
Rosemount Radar Master Plus for Rosemount 5408 Series (accessible through any Field Device Integration (FDI) based tool, e.g Instrument Inspector™ Application(1))
Device Descriptor (DD) based systems, e.g. AMS Device Manager, 475 Field Communicator, AMS Trex™ Device Communicator, and DeltaV™, or any other EDDL or enhanced-EDDL host
Field Device Integration (FDI) based systems
Damping(2)
User selectable (default is 2 s, minimum is 0 s)
Output units
Level and distance: ft., in., m, cm, mm
Level rate: ft/s, in./min, in./s, m/h, m/s
Volume: ft3, in.3, yd3, US gal, imperial gal, barrel (bbl), m3, l
Temperature: °F, °C
Signal strength: mV
Table 12. Output Variables
4-20 mA HART
Output
Two-wire, 4-20 mA. Digital process variable is superimposed on 4-20 mA signal, and available to any host that conforms to the HART protocol. The digital HART signal can be used in multidrop mode.
HART Revision
Revision 6 (default)
Revision 7 (option code HR7)
The HART revision can be switched in field.
Power supply
Transmitter operates on 12-42.4 Vdc transmitter terminal voltage (12-30 Vdc in Intrinsically Safe installations).
Power consumption
Max. 1 W, current max. 23 mA
Load limitations
For HART communication, a minimum loop resistance of 250 is required.
Maximum loop resistance is determined by the voltage level of the external power supply, as described by Figure 4.
1. Included in delivery of the transmitter. For additional information, visit Emerson.com/RosemountRadarMasterPlus.
2. The Damping parameter defines how fast the device responds to level changes (step response). A high value makes the level steady but the device reacts slowly to level changes in the tank.
Variable 4-20 mA Digital output
LCD display
Level
Distance (Ullage)
Volume
Scaled Variable(1)
1. Only for transmitters ordered with Smart Diagnostics Suite (option code
DA1).
Electronics Temperature
N/A
Signal Quality(1) N/A
Level Rate N/A
Signal strength N/A
Percent of Range N/A
Percent of Range Auxiliary
N/A
User Defined(1) http://www.emerson.com/documents/automation/73690.pdf www.Emerson.com/RosemountRadarMasterPlus
Emerson.com/Rosemount
Figure 4. Load Limitations
Maximum Loop Resistance = 43.5 * (External Power Supply Voltage - 12)
Signal wiring
Use 24-14 AWG. Twisted pairs and shielded wiring are recommended for environments with high EMI (electromagnetic interference).
Analog signal on alarm
The transmitter automatically and continuously performs self-diagnostic routines. If a failure or a measurement error is detected, the analog signal will be driven offscale to alert the user. High or low failure mode is user-configurable.
Table 13. Signal on Alarm
Analog saturation levels
The transmitter will drive the output to high or low saturation values if measurement goes outside the 4-20 mA range values.
Table 14. Saturation Levels
Diagnostics
Alerts
The Rosemount 5408 and 5408:SIS are compliant with NAMUR NE 107 Field Diagnostics for standardized device diagnostic information.
Tools and logging in Rosemount Radar Master Plus
Echo curve
Measurement and alert log
Rosemount Radar Master Plus, embedded in Instrument Inspector, enables easy and powerful troubleshooting with the echo curve tool as well as the measurement and alert log.
The measurement and alert log holds records of the last seven days of level readings and echo curve profiles, as well as the 50 last alert events. The logs can be transferred from the transmitter’s internal memory to a local computer and be presented in a graphical time line, enabling analysis of historical behaviors.
Smart Diagnostics Suite (option code DA1)
Signal Quality Metrics - Diagnostics package that monitors the relations between surface, noise, and threshold. The function can be used to detect abnormal conditions in the process such as antenna contamination or sudden loss of signal strength.
Signal Quality is available as output variable and it comes with user configurable alerts.
Power Advisory - The transmitter automatically measures and monitors the input voltage. If the voltage is too low, operators will be provided with an early alert.
Scaled Variable - The scaled variable configuration allows the user to convert a transmitter variable into an alternative measurement, such as open channel flow, mass, or calibrated level (e.g. 5 point verification).
User Defined Variable - Allows designating more than 200 variables in the device as output variable.
Process temperature and pressure rating
The following figures give the maximum process temperature (measured at the lower part of the flange, Tri Clamp, or threaded connection) and pressure rating for different antenna types.
Final rating may be lower depending on flange selection.
Standard High Low
Rosemount standard ≥ 21.75 mA
(default) ≤ 3.75 mA
(option code C8)
NAMUR NE43
≥ 22.50 mA
(option code C4) ≤ 3.6 mA
(option code C5)
Standard High Low
Rosemount standard (default and option code C8)
20.8 mA 3.9 mA
NAMUR NE43
(option code C4 and C5)
20.5 mA 3.8 mA
42.42417.8
20 30 40 50
External Power Supply Voltage (Vdc)
Lo op
R es is ta nc e
(O hm s)
Emerson.com/Rosemount
Figure 5. Cone Antenna (PTFE Seal)(1)
Figure 6. Cone Antenna (PEEK Seal)
Figure 7. Process Seal Antenna
Figure 8. Parabolic Antenna
Temperature limits
Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications, see “Product Certifications” on page 28.
Table 15. Ambient Temperature Limits
The ambient temperature limits may be further restricted by the process temperature as described by Figure 9.
Figure 9. Ambient Temperature vs. Process Temperature
Flange rating
ASME
316 SST according to ASME B16.5 Table 2-2.2
EN
1.4404 according to EN 1092-1 material group 13E0
1. For antenna type code CAB, at 100 °F (38 °C), the rating decreases with increasing temperature per ASME B16.5 Table 2-2.2, Class 300.
(100)
(250)
(200)
(150)
(100)
-40 (-40)
(38)
-76 (-60)
-15 (-1)
44 (3)
(50)
(38.5)
(25)
Code CAC
Code CAB
Code CAA
Code CAD
Pressure psig (bar)
Temp.
°F (°C)
(250)
(220)
(200)
(170)
-76 (-60)
(-15)
-13 (-25)
-22 (-30)-15
(-1)
(52)
Pressure psig (bar)
Code CBF (FVMQ)
Code CBV (Viton)
Code CBM (FKM)
Code CBK (Kalrez 6375)
Temp.
°F (°C)
Pressure psig (bar)
(200)
-76 (-60)
-13 (-25)
-7 (-0.5)
363 (25)
232 (16)
Temperature °F (°C)
Tri Clamp
Description Operating limit Storage limit(1)
1. The minimum storage temperature is -22 °F (-30 °C) for the cone antenna with Kalrez 6375 O-ring (antenna type code CBK).
Without LCD display -40 °F to 176 °F (-40 °C to 80 °C)
-58 °F to 176 °F (-50 °C to 80 °C)
With LCD display(2)
2. LCD display may not be readable and LCD display updates will be slower at temperatures below -4 °F (-20 °C).
-40 °F to 176 °F (-40 °C to 80 °C)
(200)
-67 (-55)
-7 (-0.5)
43 (3)
Pressure psig (bar)
Temperature °F (°C)
176 (80)
104 (40)
(250)
-76 (-60)
(120)
-40 (-40)
Ambient temperature °F (°C)
Process temp.
°F (°C)
Emerson.com/Rosemount
JIS
316 SST according to JIS B2220 material group No. 2.2
Conditions used for flange strength calculations
Air purging
An air purge connection can prevent clogging of the antenna in extreme applications with dirt or heavy coating. The easiest way to determine if air purging is needed, is to inspect the tank internal conditions at the location intended for the transmitter.
If there is normally a thick layer of product build-up there, air purging is most likely needed. Typical purging media to use is air.
All parabolic antennas come with an integrated air purge connection (see Figure 10).
An air purge connection is also available for cone antennas with flanged connection by selecting option code PC1. This option consists of an antenna with purge holes and a separate air purge ring (see Figure 10).
Figure 10. Air Purging
Incoming air supply specification
Maximum pressure: 190 psi (13 bar)
Recommended pressure: 100 to 115 psi (7 to 8 bar)
Inlet/outlet connection: BSPP (G) 3/8-in.
Air consumption: 252 gal/min at 65 psi (955 l/min at 4.5 bar)
System integration
Rosemount 333 HART Tri-Loop™
By sending the digital HART signal to the optional HART Tri-Loop, it is possible to have up to three additional 4–20 mA analog signals.
See the Rosemount 333 HART Tri-Loop Product Data Sheet for additional information.
Emerson™ Wireless 775 THUM™ Adapter
The optional Emerson Wireless 775 THUM Adapter can be mounted directly on the transmitter or by using a remote mounting kit.
IEC 62591 (WirelessHART®) enables access to multivariable data and diagnostics, and adds wireless to almost any measurement point.
See the Emerson Wireless 775 THUM Adapter Product Data Sheet and Technical Note for additional information.
Physical specifications
Material selection
Emerson provides a variety of Rosemount products with various product options and configurations including materials of
Table 16. Forged One-piece Flange
ASME EN, JIS
Bolting material
SA193 B8M CL.2, SA193
B7, or SA320 L7
EN 1515-1/2, ISO 3506
A4-70 or
Bumax® 88
Gasket(1)
1. Not applicable to process seal antenna (features an integrated gasket).
Soft (1a) with min.
thickness 1.6 mm or Spiral wound gasket with nonmetallic filler (1b)
Soft (EN 1514-1) with min. thickness 1.6 mm or Spiral wound gasket with nonmetallic filler
(EN 1514-2)
Flange material
Stainless steel A182 Gr. F316 and
EN 10222-5-1.4404
Table 17. Welded Construction(1)
1. Only applicable to cone antenna flanges per Table 3.
ASME EN, JIS
Bolting material
SA193 B8M Cl.2 EN 1515-1/2, ISO 3506 A4-70
Gasket
Soft (1a) with min.
thickness 1.6 mm or Spiral wound gasket with nonmetallic filler (1b)
Soft (EN 1514-1) with min. thickness 1.6 mm or Spiral wound gasket with nonmetallic filler
(EN 1514-2)
Flange material
Stainless steel A182 Gr. F316 and
EN 10222-5-1.4404
Hub material
Stainless steel SA479 316 and
EN 10272-1.4404
http://www.emerson.com/documents/automation/73694.pdf http://www.emerson.com/documents/automation/73694.pdf http://www.emerson.com/documents/automation/87170.pdf http://www.emerson.com/documents/automation/87170.pdf http://www.emerson.com/documents/automation/87440.pdf
Emerson.com/Rosemount construction that can be expected to perform well in a wide range of applications. The Rosemount product information presented is intended as a guide for the purchaser to make an appropriate selection for the application. It is the purchaser’s sole responsibility to make a careful analysis of all process parameters (such as all chemical components, temperature, pressure, flow rate, abrasives, contaminants, etc.), when specifying product, materials, options, and components for the particular application. Emerson is not in a position to evaluate or guarantee the compatibility of the process fluid or other process parameters with the product, options, configuration, or materials of construction selected.
Engineered solutions
When standard model codes are not sufficient to fulfill requirements, please consult the factory to explore possible Engineered Solutions. This is typically, but not exclusively, related to the choice of wetted materials or the design of a process connection. These Engineered Solutions are part of the expanded offerings and may be subject to additional delivery lead time. For ordering, factory will supply a special P-labeled numeric option code that should be added at the end of the standard model string.
Housing and enclosure
Electrical connections
Two cable/conduit entries (½-14 NPT, M20 x 1.5, or G½)
Optional adapters: M12 4-pin male eurofast connector or A size Mini 4-pin male minifast connector
Materials
Electronics housing: Polyurethane-covered Aluminum or Stainless Steel Grade CF-8M (ASTM A743)
Sensor module: 316L SST
Weight(1)
Aluminum housing: 6.2 lb (2.8 kg)
Stainless steel housing: 10.0 lb (4.5 kg)
Ingress protection
IP 66/67/68(2) and NEMA® 4X
Tank connection
The tank connection consists of a tank seal, a flange, NPT or BSPP (G) threads, Tri Clamp, or a specific welded connection with swivel feature for parabolic antenna.
Flange dimensions
Follows ASME B16.5, JIS B2220, and EN 1092-1 standards. For more information, see “Standard flanges” on page 42.
Antenna versions
Cone antenna
Best choice for most applications, including closed vessels, still pipe/chamber installations, and open air applications
Extended cone antennas are available for tall nozzles (option code S1 and S2). Depending on measurement conditions, a reduction of sensitivity close to antenna end might be present.
Process seal antenna
All PTFE wetted parts ideal for use in corrosive and hygienic applications
Suitable for applications with heavy condensation/build-up
Parabolic antenna
Alternative for long measuring ranges in combination with conditions such as low reflective media
Suitable for a broad range of solid materials (may need air purging in dusty environments)
Material exposed to tank atmosphere
Cone antenna, PTFE seal
316/316L SST (EN 1.4404)
PTFE fluoropolymer
Cone antenna, PEEK seal
316/316L SST (EN 1.4404)
PEEK polyetheretherketone with PTFE fluoropolymer filler
FVMQ fluorosilicone, Kalrez 6375 perfluoroelastomer, FKM fluoroelastomer, or Viton fluoroelastomer (O-ring)
Process seal antenna
PTFE fluoropolymer
Parabolic antenna
316/316L SST (EN 1.4404)
PTFE fluoropolymer
FVMQ fluorosilicone (O-ring)
1. Fully functional transmitter with sensor module, housing, terminal block, LCD display, and covers.
2. The transmitter meets IP 68 at 9.8 ft. (3 m) for 30 minutes.
Emerson.com/Rosemount
Installation and mounting considerations
Tank installations
For optimal performance, the transmitter should be installed in locations with a clear and unobstructed view of the product surface.
The transmitter should be mounted with as few internal structures as possible within the signal beam, see “Beam angle and beam width” on page 18.
Do not install the transmitter in the center of the tank.
Do not mount close to or above the inlet stream.
Multiple Rosemount 5408 and 5408:SIS Level Transmitters can be used in the same tank without interfering with each other.
Table 18. Distance to Tank Wall (L)
Figure 11. Recommended Mounting Position
Non-metallic tanks
The walls in non-metallic tanks can be invisible to the radar signal, so nearby objects outside the tank may cause disturbing radar echoes. Wherever possible, the transmitter should be positioned so that objects close to the tank are kept outside the signal beam.
Antenna size
Choose as large antenna diameter as possible. A larger antenna diameter concentrates the radar beam, will be less susceptible to obstruction interference, and assures maximum antenna gain.
Antenna inclination
Ensure the antenna is aligned perpendicular to the product surface (see Figure 12). The parabolic antenna comes with a swivel connection that adjusts for angled tank roofs.
Note that if the surface echo is weak in solids applications, then a small inclination of the parabolic antenna toward the surface slope may improve the performance.
Figure 12. Inclination
Nozzle requirements for cone antenna
For best measurement performance, the cone antenna should extend at least 0.4 in. (10 mm) below the nozzle. If required, use the extended cone antenna versions (option code S1 or S2).
Application Minimum Recommended
Liquids 8 in. (200 mm) 1/2 of tank radius
Solids 8 in. (200 mm) 2/3 of tank radius
L
90°
Max. 3° Max. 1.5°
90°
Cone antenna/ process seal antenna
Parabolic antenna
Emerson.com/Rosemount
Figure 13. Mounting of the Cone Antenna
Table 19. Nozzle Requirements for Cone Antenna
Nozzle requirements for process seal antenna
The antenna can be used on nozzles up to 4 ft. (1.2 m).
Disturbing objects inside the nozzle may impact the measurement, and should therefore be avoided.
Figure 14. Mounting of the Process Seal Antenna
Table 20. Nozzle Requirements for Process Seal Antenna
Nozzle requirements for parabolic antenna
See Table 21 for nozzle height recommendations at different inclination angle.
Figure 15. Mounting of the Parabolic AntennaAntenna size
Minimum nozzle diameter (D)(1)
1. The antennas are sized to fit within schedule 80 or lower schedules.
Recommended maximum nozzle height (H)(2)(3)
2. The values are valid for cone antennas without antenna extension.
3. For liquid applications, the cone antenna can be recessed in smooth nozzles up to 4 ft. (1.2 m), but note that the accuracy may be reduced in the region close to the nozzle.
Antenna Antenna with air purge ring
2-in.
(DN50)
1.94 in.
(49.3 mm)
5.71 in.
(145 mm)
4.69 in.
(119 mm)
3-in.
(DN80)
2.80 in.
(71.0 mm)
5.63 in.
(143 mm)
4.61 in.
(117 mm)
4-in.
(DN100)
3.78 in.
(96.0 mm)
6.54 in.
(166 mm)
5.51 in.
(140 mm)
D
H
> 0.4 in. (10 mm)
D
H
Antenna size Minimum nozzle diameter (D)(1)
1. The antennas are sized to fit within schedule 120 or lower schedules.
Recommended maximum nozzle height (H)
2-in. (DN50) 1.77 in. (45 mm) 4 ft. (1.2 m)
3-in. (DN80) 2.76 in. (70 mm) 4 ft. (1.2 m)
4-in. (DN100) 2.76 in. (70 mm) 4 ft. (1.2 m)
D
H
Nozzle mounting α
Ø 8 in. (200 mm)
Flange mounting in manhole cover αH
Emerson.com/Rosemount
Table 21. Nozzle Requirements for Parabolic Antenna
Still pipe/chamber installations
Installation in still pipe/chamber is recommended for tanks where there are excessive foaming or turbulence. Still pipe/chamber may also be used to avoid disturbing objects in the tank. Consider the following still pipe requirements:
Pipe:
Pipes should be an all-metal material.
Pipe should have a constant inside diameter.
The inner surface must be smooth and clear of any rough edges. (Smooth pipe joints are acceptable, but may reduce accuracy.)
The end of the pipe must extend beyond the zero level.
Holes:
Maximum hole diameter is 1 in. (25 mm).
Minimum distance between holes is 6 in. (150 mm).
Holes should be drilled on one side only and deburred.
Drill one hole above maximum product surface.
Antenna:
All cone/process seal antenna sizes can be used for still pipe/chamber installations.
The gap between the cone antenna and the still pipe should be maximum 0.2 in. (5 mm). If required, order a larger antenna and cut on location. See Figure 17 on page 38 for antenna dimensions.
For more information, refer to the Guidelines for Choosing and Installing Radar in Stilling Wells and Bypass Chambers Technical Note.
Figure 16. Still Pipe Requirements
Ball-valve installations
The transmitter can be isolated from the process by using a valve:
Use a full-port ball valve.
Ensure there is no edge between the ball valve and the nozzle or still pipe, the inside should be smooth.
Valves can be combined with still pipes.
Nozzle size (D) Inclination angle (α)
Maximum nozzle height (H)(1)
1. Note that the inside of the nozzle must be smooth (i.e. avoid bad welding, rust, or deposit).
Pipe schedule std, Ø 8 in. (200 mm)
0° 5.9 in. (150 mm)
3° 5.5 in. (140 mm)
6° 1.6 in. (40 mm)
9° 1.2 in. (30 mm)
12° 1.0 in. (25 mm)
15° 0.6 in. (15 mm)
Pipe schedule std, Ø 10 in.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.