Macrotec Consulting, LLC.
9724 Mild Weather Ct. · Las Vegas, NV 89148 Phone: (702) 338-8213 · Fax: (702) 629-5677
Demolition Investigation Report Asbestos and Lead Based Paint Survey
Project Information:
Creech Air Force Base Bldg. 81 Work Order #C11118 21244
Report Info:
Macrotec Project # 13581 July 3, 2013
Prepared For:
Vince Bowers 99th Civil Engineering Squadron – CES/CEV Nellis AFB, NV 89191
Prepared By:
Dustin McAllister - Macrotec Consulting, LLC.
Table of Contents:
Introduction Scope of Services Site Description Sample Collection Methodology Sample Analysis Methodology Sample Assessment Recommendations Inspection Limitations
Appendix A Asbestos Assessment Appendix B Lead Assessment Appendix C Picture Page Appendix D Sample Location Diagram Appendix E Asbestos Laboratory Report Appendix E.1 Lead XRF Results Appendix F Certifications
Asbestos / Lead Survey Macrotec Project # 13581 Creech Air Force Base – Bldg. 81 Page 2
INTRODUCTION
Macrotec Consulting performed an inspection for Asbestos-Containing Building Materials and Lead Based Paint on June 27th 2013. The inspection was conducted for the project defined as: Demolition of building 95 at Creech Air Force Base in Indian Springs, NV.
The intent of this inspection was to identify materials containing asbestos and lead based paint, within the subject site, that may be impacted during planned renovation activities. Macrotec’s inspection services were conducted at the request of Vince Bowers of the 99th Civil Engineering Squadron.
Dustin McAllister, a certified lead inspector, License No. NV-I-16781-1, and a Nevada Asbestos Abatement Consultant, License No.IM0961, and Jason McAllister, a Nevada Asbestos Abatement Consultant, License No. IMP0901, and a certified lead inspector, License No. NV-I-125427-1 conducted these services for Macrotec Consulting.
SCOPE OF SERVICES
Asbestos
Macrotec’s inspection services were conducted to identify the presence of any materials containing asbestos pursuant to the requirements of:
Nevada OSHA - NAC 618.960 OSHA’s “Criteria to rebut the designation of installed material as PACM
(Presumed Asbestos Containing Material)”, 1926.1101(k)(5).
EPA’s: 40 CFR Part 61 National Emission Standard for Hazardous Air
Pollutants (NESHAP).
These regulations outline inspection and abatement requirements for materials containing asbestos.
Lead
Macrotec collected X-Ray Fluorescence (XRF) readings to identify the presence and content level of lead above the action level (1.0 mg/cm2). The sampling for this project was collected in compliance with the U.S. Department of Housing and Urban Development (HUD) and the Environmental Protection Agencies (EPA) regulatory requirements.
SITE DESCRIPTION
The subject site is a wood framed one story office trailer.
Creech Air Force Base – Bldg. 81 Page 3
Macrotec’s inspection was limited to this location only.
COLLECTION METHODOLOGY
Asbestos
An initial walk through of the subject site was conducted to identify homogeneous suspect materials containing asbestos and lead based paint, and their respective locations. This information was then used to develop a sample collection strategy.
Samples were collected by pre-wetting sample areas with water, then cutting or scraping the sample from the substrate with an appropriate sampling tool.
Whenever possible, samples were collected from areas previously damaged or deteriorating. To avoid potential contamination due to unknown asbestos and no building systems, components, or structures were demolished to obtain samples of potentially hidden materials containing asbestos.
Each suspect bulk sample was sealed in its own zip lock plastic container and labeled with a unique identification number. Sampling tools were individually cleaned before and after each sample was collected to avoid sample cross contamination. Decontamination was accomplished using single use, pre-moistened cloths.
Asbestos samples were recorded on Macrotec’s chain-of-custody form. This form accompanied the samples to Triangle Enivronmental Service Center, Inc. (TESC), located in Moseley, Virginia. The National Voluntary Laboratory Accreditation Program (NVLAP) accredits TESC for analysis of bulk building material samples for asbestos.
Lead
Painted surfaces were then tested using an X-Ray Fluorescence (XRF) analyzer.
The XRF was a Niton XLp 300A paint analyzer serial #26948. The instrument was calibrated to the manufactures specifications before the inspection, every four hours, and after the inspection was finished, verified against the National Institute of Standards and Testing (NIST) Standard Reference Material (SRM) 2573 lead. The analyzer was in control at all times of the NIST SRM lead standard.
Interior and exterior XRF readings were taken on determined surfaces on each building component in each room equivalent. The HUD definition of lead based paint is lead equal to or greater than 1.0 mg/cm2. All results above this level are considered positive and all results found below this level are considered negative.
SAMPLE ANALYSIS METHODOLOGY
Creech Air Force Base – Bldg. 81 Page 4
Asbestos
Suspect asbestos samples were subjected to analysis by polarized light microscopy (PLM). Bulk sample analysis was conducted in accordance with the EPA’s “Test Method for the Determination of Asbestos in Bulk Building Materials, EPA/600/R-93/116, 1993.
Lead
To determine lead content, the painted surfaces were tested using an X-Ray Fluorescence (XRF) analyzer. The XRF was used in accordance with chapter seven of the Guidelines of the Evaluation and Control of Lead Based Paint Hazards in Housing published by HUD
SAMPLE ASSESSMENT
Asbestos
Macrotec’s inspection of the subject site found Eight (8) separate suspect asbestos building materials, of which a total of Ten (10) samples were collected and submitted for analysis.
The following table summarizes the materials that were found to be asbestos containing, the locations where the material is located, the material’s friability and its NESHAP classification.
Material Number
Material Description
Material Locations
Material Friability
NESHAP
5 Penetration Roof Mastic This material is on the roof penetrations of the building
Non- Friable
Category I
See Appendix A for a listing of the materials, material locations, samples, sample locations and results for this project.
Lead
Macrotec collected One Hundred Sixteen (16) XRF paint readings within the subject site.
Some painted surfaces were found to be leaded (painted materials and/or surfaces above the HUD action level of 1.0 mg/cm2). OSHA regulations require the implementation of worker protection if there is a potential that paint with any amount of lead in it will be disturbed during demolition or renovation activities.
Category I nonfriable asbestos-containing material means asbestos containing packings, gaskets, resilient floor covering, and asphalt roofing products containing more than 1% asbestos as determined by Polarized Light Microscopy (PLM)
Creech Air Force Base – Bldg. 81 Page 5
See Appendix B for a listing of materials that contain lead above the HUD action level and above the “Limit of Detection” (LOD). See Appendix D.1 for a listing of all the painted surfaces, XRF readings, and XRF reading locations and results for this project.
RECOMMENDATIONS
Asbestos
US EPA and Nevada Department of Industrial Relations regulations require the removal of all regulated asbestos-containing materials (RACM) prior to any renovation or demolition that could impact or disturb RACM. In accordance with these regulations Macrotec recommends:
Hiring a Certified Asbestos Consultant to develop a project specification based on this investigation and any other additional findings.
Hiring a Nevada licensed Asbestos Abatement Contractor to remove all asbestos materials, which are either regulated or may become regulated during the course of renovation and/or demolition activities.
Hiring a Certified Asbestos Consultant to monitor the removal activities and to provide final clearance inspection reports.
Macrotec recommends the removal of all ACM (in the manner described above) whenever feasible.
Lead
US EPA OSHA regulations require the implementation of worker protection if there is a potential that paint with lead in it will be disturbed during renovation activities. In accordance with these regulations Macrotec recommends:
Hiring an EPA Licensed Lead Consultant to develop a project specification based on this investigation and any other additional findings.
Hiring an EPA Licensed Lead Abatement Contractor to stabilize and/or remove all regulated lead painted materials.
Hiring an EPA Licensed Lead Consultant to monitor the removal activities and provide final clearance inspection reports.
Creech Air Force Base – Bldg. 81 Page 6
INSPECTION LIMITATIONS
The information contained in this report is limited to those areas and suspect materials found to be visually accessible through reasonable means.
Macrotec conducted a non-destructive survey. No demolition of building materials was conducted to determine the presence of asbestos in wall cavities, chases or other inaccessible areas. Macrotec cannot warrant that these areas do not contain asbestos in locations other than those noted in this report, however, a good faith effort was made to conduct a comprehensive survey.
• Macrotec accepts no liability for additional materials or under reporting of asbestos materials that exist below other floor coverings.
• This report is not represented as, nor is it intended to be, an asbestos abatement scope of work or project specification.
• If suspect materials are discovered during future demolition operations, cease all general work activities which could impact the discovered suspect materials, until confirmation sampling can be conducted.
Thank you for allowing Macrotec Consulting to assist you with your environmental consulting needs. Please contact me with any questions regarding this report at (702) 338-8213.
Appendix A
Appendix A - Asbestos Assessment
Macrotec Job #13581 - WO #C11118 - 21244
The following table lists each of the materials suspected to contain asbestos at the subject site. For each material the sample number, location and laboratory result are listed. If the material was found to contain asbestos, the friablity and NESHAP classification is identified.
1 Wall System (Drywall & Mud) This material is located on the walls throughout the building
No Asbestos Detected
AB1 Interior - Break Room - South Wall None Detected
AB2 Interior - Office 2 - SE Corner None Detected
AB3 Interior - Conference 2 - NW Corner None Detected
2 Spray Texture on Walls This material is located atop the walls throughout the building
No Asbestos Detected
AB4 Interior - Break Room - West Wall None Detected
AB5 Interior - Main Room - NW Corner None Detected
AB6 Interior - Office 3 - South Wall None Detected
AB7 Interior - Conference Room - North Wall None Detected
AB8 Interior - Office 1 - SE Corner None Detected
3 12X12 Beige Floor Tile This material is located on the floor in the Main Room, Break Room and Bathroom
No Asbestos Detected
AB9 Interior - Main Room - NW Corner None Detected
4 Yellow Mastic Beneath Tile This material is located on the floor in the Main Room, Break Room and Bathroom
No Asbestos Detected
AB10 Interior - Main Room - NW Corner None Detected
5 Floor Tile - Top Layer This material is located on the top layer of flooring in the Bathroom
No Asbestos Detected
AB11 Interior - Bathroom - NE Corner None Detected
6 Yellow Mastic Beneath Carpet This material is located on the top layer of flooring in the Bathroom
No Asbestos Detected
AB12 Interior - Bathroom - NE Corner None Detected
Asbestos Survey
Bldg. 21244
Macrotec Job #13581
Macrotec Job #13581 - WO #C11118 - 21244
7 Yellow Mastic Beneath Carpet This material is located beneath the carpet in the offices and conference rooms
No Asbestos Detected
AB13 Interior - Office 2 - SE Corner None Detected
8 Yellow Mastic Beneath Gray Base Cove This material is located behind the base cove throughout the building except the Bathroom
No Asbestos Detected
AB14 Interior - Conference Room - NE Corner None Detected
9 Brown Mastic Beneath Black Base Cove This material is located behind the base cove throughout the building except the Bathroom
No Asbestos Detected
AB15 Interior - Conference Room - NE Corner None Detected
10 Ceiling Tile Panel This material is located on the ceiling throughout the building.
No Asbestos Detected
AB16 Interior - Main Room - Adj. Office 3 None Detected
11 Sheet Rock Beneath Tile This material is located beneath the ceiling tile on the ceiling throughout the building.
No Asbestos Detected
AB17 Interior - Main Room - Adj. Office 3 None Detected
12 Wall Panel This material is located on the east wall of the Main Room
No Asbestos Detected
AB18 Interior - Main Room - East Wall None Detected
13 Paper - Behind Stucco This material is located behind the stucco wall on the exterior
No Asbestos Detected
AB19 Exterior - West Side - Center None Detected
14 Paper Behind Metal Base This material is located behind the lower metal walls on the exterior
No Asbestos Detected
AB20 Exterior - West Side - Center None Detected
Asbestos Survey
Bldg. 21244
Macrotec Job #13581 - WO #C11118 - 21244
15 Stucco This material is located on the exterior walls of the building
No Asbestos Detected
AB21 Exterior - West Side - Center None Detected
AB22 Exterior - South Side - East End None Detected
AB23 Exterior - East Side - North End None Detected
16 Asphalt Roof Shingle This material is located on the roof of the building
No Asbestos Detected
AB24 Exterior - Roof - South End None Detected
17 Black Tar Paper This material is located below the roof of the roof of the building
No Asbestos Detected
AB25 Exterior - Roof - South End None Detected
18 Mastic on Penetration This material is located on the penetrations of the roof
Non-Friable, Category I
AB26 Exterior - Roof - Center 5% Chrysotile
19 Caulk on Vent This material is located on the roof vent
No Asbestos Detected
AB27 Exterior - Roof - Center None Detected
20 Silver Paint on Pipes This material is located on the pipe penetrations on the roof
No Asbestos Detected
AB28 Exterior - Roof - Center None Detected
21 Concrete Pad This material is located on the pipe penetrations on the roof
No Asbestos Detected
AB29 Exterior - North End None Detected
Asbestos Survey
Bldg. 21244
Macrotec Job #13581
Dustin Highlight
Appendix B
Appendix B - Lead Assessment
Macrotec Job #13581 - WO #C11118 - 21244
The following table lists each of the painted surfaces found to contain lead at the subject site, Materials with a result greater than 1.0 mg/cm2 are considered leaded by the EPA and HUD. Note: OSHA requires PPE for materials containing any amount of lead. For each painted surface, the description, material location and result are listed.
Painted Surface Description
Painted Surface Location
XRF Result (mg/cm2)
This material is located on the exterior walls of the building
1.4 -1.7Brown Stucco Wall
This material is located on the exterior windows of the building
1.7Brown Stucco Window Frame
This material is located on the baseboard of the
Bathroom
2.9Black Vinyl Baseboard
This material is located on the east wall of the
Break Room
1.9Beige Drywall Wall
Lead Paint Survey
Bldg. 21244
Appendix C
NESHAP Asbestos Survey Macrotec Project # 13581 Creech Air Force Base—Bldg. 81 Appendix C
Picture 1— Black Vinyl Base Cove in the Bathroom that Contains Lead
Note— The Exterior Stucco Walls and Window Frames and the East Interior Drywall Wall in the Break Room Con-tain lead based paint
Appendix D
Asbestos & Lead Survey
NAFB Bldg. 81
Macrotec Project # 13581
Appendix A
* Diagram Not Drawn To Scale
Sample Location Diagram
AB1
The Red Outlined Areas Above Was Tested for Lead Based Paint with a XRF Analyzer. See Results Page for Materials & Locations.
AB2
AB3
Office 1
Break
Office 2
Office 3 Conf. Rm
Main Rm.
Bathroom
AB4
AB5
AB6
AB7
AB8
AB9
AB10
AB11
AB12
AB13
AB18
AB17
AB15
AB16
AB14
AB19
AB20Roof
AB21
AB22
AB23
AB24
AB25
AB26
AB27
AB28
AB29
Appendix E
Macrotec Consulting
TRIANGLE ENVIRONMENTAL SERVICE CENTER, INC.
13509 East Boundary Road, Suite B, Midlothian, VA 23112
1*.(0-2(+0/+ ^ LI[3 1*.(0-2(+0/-
BULK ASBESTOS SAMPLE ANALYSIS SUMMARY
9724 Mild Weather Ct.
Las Vegas, NV 89148
13581
Bldg 81
130701N
7/1/2013 7/2/2013 7/2/2013
F. JiangJOB SITE:
TESC LOGIN #:
DATE OF RECEIPT:
DATE OF ANALYSIS:
DATE OF REPORT:
ANALYST:
TESC
SAMPLE #
CLIENT SAMPLE ID
& GROSS DESCRIPTION
ESTIMATED
% ASBESTOS
NON ASBESTOS
% FIBERS
NON FIBROUS
% MATERIALS
CLIENT:
CLIENT JOB/ #:
10% Cellulose 90%AB1-Drywall / White powder, brown fibers NAD1A
100%AB1-Mud / White powder NAD1B
10% Cellulose 90%AB2-Drywall / White powder, brown fibers NAD2A
100%AB2-Mud / White powder NAD2B
10% Cellulose 90%AB3-Drywall / White powder, brown fibers NAD3A
100%AB3-Mud / White powder NAD3B
100%AB4 / White powder NAD4
100%AB5 / White powder NAD5
100%AB6 / White powder NAD6
100%AB7 / White powder NAD7
Tuesday, July 02, 2013 Page 1 of 4
JQ\_[Ub QaU Q]Q[hiUT Y] QSS^aTQ]SU fYcX jB]cUaY\ EUcX^T V^a cXU =UcUa\Y]QcY^] ^V 9bRUbc^b Y] ;d[Z B]bd[QcY^] JQ\_[Ubk( >H9 2,,+E0)4.),.,( =US* -54.
and "Method for the Determination of Asbestos in Bulk Building Materials", EPA 600/R-93/116, July 1993. None Detected: not detected at/or below the detected limit of method (Reporting limit: 1% Asbestos). Glass fiber is analyzed for quality control blank. TESC recommends by point count or Transmission Electron Microscopy (TEM), for materials regulated by the EPA NESHAP (National Emission Standards for Hazardous Air Pollutants) and found to contain less than ten percent (<10%) asbestos by Polarized Light Microscopy (PLM). Both services are available for an additional fee. This report shall not be reproduced, except in full written approval of Triangle Environmental Service Center, Inc. This report must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. This test report relates only to the item(s) tested.
NVLAP Lab Code: 200794-0 LEGEND NAD=No Asbestos Detected, Lino.=Linoleum, JC=Joint Compound][
Reviewed By Authorized Signatory:
Feng Jiang, MS Senior Geologist, Laboratory Director Yuedong Fang, Senior Geologist
13509 East Boundary Road, Suite B, Midlothian, VA 23112
1*.(0-2(+0/+ ^ LI[3 1*.(0-2(+0/-
BULK ASBESTOS SAMPLE ANALYSIS SUMMARY
9724 Mild Weather Ct.
Las Vegas, NV 89148
13581
Bldg 81
130701N
7/1/2013 7/2/2013 7/2/2013
F. JiangJOB SITE:
TESC LOGIN #:
DATE OF RECEIPT:
DATE OF ANALYSIS:
DATE OF REPORT:
ANALYST:
TESC
SAMPLE #
CLIENT SAMPLE ID
& GROSS DESCRIPTION
ESTIMATED
% ASBESTOS
NON ASBESTOS
% FIBERS
NON FIBROUS
% MATERIALS
CLIENT:
CLIENT JOB/ #:
100%AB8 / White powder NAD8
100%AB9 / Beige vinyl NAD9
100%AB10 / Yellow adhesive NAD10
100%AB11 / Off-white vinyl NAD11
100%AB12 / Yellow adhesive NAD12
100%AB13 / Yellow adhesive NAD13
100%AB14 / Yellow adhesive NAD14
100%AB15 / Brown adhesive NAD15
98% Cellulose 2%AB16 / Brown fibers NAD16
20% Cellulose 80%AB17 / White powder, brown fibers NAD17
Tuesday, July 02, 2013 Page 2 of 4
JQ\_[Ub QaU Q]Q[hiUT Y] QSS^aTQ]SU fYcX jB]cUaY\ EUcX^T V^a cXU =UcUa\Y]QcY^] ^V 9bRUbc^b Y] ;d[Z B]bd[QcY^] JQ\_[Ubk( >H9 2,,+E0)4.),.,( =US* -54.
and "Method for the Determination of Asbestos in Bulk Building Materials", EPA 600/R-93/116, July 1993. None Detected: not detected at/or below the detected limit of method (Reporting limit: 1% Asbestos). Glass fiber is analyzed for quality control blank. TESC recommends by point count or Transmission Electron Microscopy (TEM), for materials regulated by the EPA NESHAP (National Emission Standards for Hazardous Air Pollutants) and found to contain less than ten percent (<10%) asbestos by Polarized Light Microscopy (PLM). Both services are available for an additional fee. This report shall not be reproduced, except in full written approval of Triangle Environmental Service Center, Inc. This report must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. This test report relates only to the item(s) tested.
NVLAP Lab Code: 200794-0 LEGEND NAD=No Asbestos Detected, Lino.=Linoleum, JC=Joint Compound][
Reviewed By Authorized Signatory:
13509 East Boundary Road, Suite B, Midlothian, VA 23112
1*.(0-2(+0/+ ^ LI[3 1*.(0-2(+0/-
BULK ASBESTOS SAMPLE ANALYSIS SUMMARY
9724 Mild Weather Ct.
Las Vegas, NV 89148
13581
Bldg 81
130701N
7/1/2013 7/2/2013 7/2/2013
F. JiangJOB SITE:
TESC LOGIN #:
DATE OF RECEIPT:
DATE OF ANALYSIS:
DATE OF REPORT:
ANALYST:
TESC
SAMPLE #
CLIENT SAMPLE ID
& GROSS DESCRIPTION
ESTIMATED
% ASBESTOS
NON ASBESTOS
% FIBERS
NON FIBROUS
% MATERIALS
CLIENT:
CLIENT JOB/ #:
98% Cellulose 2%AB18 / Brown fibers NAD18
98% Cellulose 2%AB19 / Brown fibers NAD19
98% Cellulose 2%AB20 / White fibers NAD20
100%AB21 / Gray granular NAD21
100%AB22 / Gray granular NAD22
100%AB23 / Gray granular NAD23
20% Fiberglass 80%AB24 / Black tar-like NAD24
98% Cellulose 2%AB25 / Black fibers NAD25
95%AB26 / Black adhesive 5% Chrysotile26
100%AB27 / Gray adhesive NAD27
Tuesday, July 02, 2013 Page 3 of 4
JQ\_[Ub QaU Q]Q[hiUT Y] QSS^aTQ]SU fYcX jB]cUaY\ EUcX^T V^a cXU =UcUa\Y]QcY^] ^V 9bRUbc^b Y] ;d[Z B]bd[QcY^] JQ\_[Ubk( >H9 2,,+E0)4.),.,( =US* -54.
and "Method for the Determination of Asbestos in Bulk Building Materials", EPA 600/R-93/116, July 1993. None Detected: not detected at/or below the detected limit of method (Reporting limit: 1% Asbestos). Glass fiber is analyzed for quality control blank. TESC recommends by point count or Transmission Electron Microscopy (TEM), for materials regulated by the EPA NESHAP (National Emission Standards for Hazardous Air Pollutants) and found to contain less than ten percent (<10%) asbestos by Polarized Light Microscopy (PLM). Both services are available for an additional fee. This report shall not be reproduced, except in full written approval of Triangle Environmental Service Center, Inc. This report must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. This test report relates only to the item(s) tested.
NVLAP Lab Code: 200794-0 LEGEND NAD=No Asbestos Detected, Lino.=Linoleum, JC=Joint Compound][
Reviewed By Authorized Signatory:
13509 East Boundary Road, Suite B, Midlothian, VA 23112
1*.(0-2(+0/+ ^ LI[3 1*.(0-2(+0/-
BULK ASBESTOS SAMPLE ANALYSIS SUMMARY
9724 Mild Weather Ct.
Las Vegas, NV 89148
13581
Bldg 81
130701N
7/1/2013 7/2/2013 7/2/2013
F. JiangJOB SITE:
TESC LOGIN #:
DATE OF RECEIPT:
DATE OF ANALYSIS:
DATE OF REPORT:
ANALYST:
TESC
SAMPLE #
CLIENT SAMPLE ID
& GROSS DESCRIPTION
ESTIMATED
% ASBESTOS
NON ASBESTOS
% FIBERS
NON FIBROUS
% MATERIALS
CLIENT:
CLIENT JOB/ #:
100%AB28 / Silver paint chips NAD28
100%AB29 / Gray granular NAD29
Total Samples/Layers Analyzed: 32
Tuesday, July 02, 2013 Page 4 of 4
JQ\_[Ub QaU Q]Q[hiUT Y] QSS^aTQ]SU fYcX jB]cUaY\ EUcX^T V^a cXU =UcUa\Y]QcY^] ^V 9bRUbc^b Y] ;d[Z B]bd[QcY^] JQ\_[Ubk( >H9 2,,+E0)4.),.,( =US* -54.
and "Method for the Determination of Asbestos in Bulk Building Materials", EPA 600/R-93/116, July 1993. None Detected: not detected at/or below the detected limit of method (Reporting limit: 1% Asbestos). Glass fiber is analyzed for quality control blank. TESC recommends by point count or Transmission Electron Microscopy (TEM), for materials regulated by the EPA NESHAP (National Emission Standards for Hazardous Air Pollutants) and found to contain less than ten percent (<10%) asbestos by Polarized Light Microscopy (PLM). Both services are available for an additional fee. This report shall not be reproduced, except in full written approval of Triangle Environmental Service Center, Inc. This report must not be used by the customer to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the Federal Government. This test report relates only to the item(s) tested.
NVLAP Lab Code: 200794-0 LEGEND NAD=No Asbestos Detected, Lino.=Linoleum, JC=Joint Compound][
Reviewed By Authorized Signatory:
Appendix E.1
Time Duration Component Substrate Side Color Site Building Room Results Depth PbC PbC Error PbL PbL Error PbK PbK Error
6/27/13 11:25 2.22 Wall Stucco A Beige Creech 81 Exterior Null 7.54 < LOD 2.25 < LOD 0.14 < LOD 2.25
6/27/13 11:25 7.97 Wall Stucco A Beige Creech 81 Exterior POS 2.36 1.5 0.4 < LOD 0.03 1.5 0.4
6/27/13 11:26 4.16 Wall Stucco A Brown Creech 81 Exterior POS 1 1.7 0.7 < LOD 0.03 1.7 0.7
6/27/13 11:27 6.71 Wall Stucco C Brown Creech 81 Exterior POS 1.5 1.5 0.5 < LOD 0.03 1.5 0.5
6/27/13 11:28 7.95 Wall Stucco D Brown Creech 81 Exterior POS 2.17 1.4 0.4 < LOD 0.03 1.4 0.4
6/27/13 11:28 1.28 HVAC Metal D Beige Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.01
6/27/13 11:28 1.27 HVAC Metal D Beige Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.29
6/27/13 11:29 1.28 Base Metal D Gray Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.25
6/27/13 11:29 1.28 Electric Box Metal D Beige Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.6
6/27/13 11:29 1.28 Base Metal C Gray Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.43
6/27/13 11:30 1.27 Stair Metal C Gray Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.1
6/27/13 11:30 1.28 Stair Metal C Gray Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.1
6/27/13 11:30 1.28 Stair Landing Metal C Gray Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.1
6/27/13 11:31 1.28 Stair Rail Metal C Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.95
6/27/13 11:31 1.27 Stair Rail Metal C Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.95
6/27/13 11:31 1.28 Door Metal C Brown Creech 81 Exterior NEG 1.24 < LOD 0.03 < LOD 0.03 < LOD 3.14
6/27/13 11:31 0.96 Doorframe Metal C Brown Creech 81 Exterior Null 1 < LOD 0.03 < LOD 0.03 < LOD 6
6/27/13 11:31 1.27 Doorframe Metal C Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.45
6/27/13 11:32 4.45 Window Frame Stucco C Brown Creech 81 Exterior POS 2.74 1.7 0.7 < LOD 0.03 1.7 0.7
6/27/13 11:33 18.45 Stair Metal A Gray Creech 81 Exterior NEG 1.33 < LOD 0.4 < LOD 0.03 < LOD 0.4
6/27/13 11:34 1.27 Stair Rail Metal A Brown Creech 81 Exterior NEG 1.35 < LOD 0.04 < LOD 0.04 < LOD 3.3
6/27/13 11:34 1.28 Stair Landing Wood A Gray Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.1
6/27/13 11:34 1.27 Stair Landing Wood A Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.8
6/27/13 11:34 1.28 Stair Landing Wood A Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.65
6/27/13 11:34 1.28 Stair Landing Wood A Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.95
6/27/13 11:35 1.28 Stair Landing Wood A Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.95
6/27/13 11:35 1.27 Door Metal A Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.55
6/27/13 11:35 1.28 Doorframe Metal A Brown Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.23
6/27/13 11:35 1.28 Gutter Metal A Brown Creech 81 Exterior NEG 3 < LOD 1.79 < LOD 0.11 < LOD 1.79
6/27/13 11:36 1.28 Base Metal B Gray Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.95
6/27/13 11:36 1.28 Pipe Metal B Beige Creech 81 Exterior NEG 3.51 < LOD 0.16 < LOD 0.16 < LOD 3.75
6/27/13 11:37 1.27 Gutter Metal B Beige Creech 81 Exterior NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.4
6/27/13 11:37 1.92 Electric Box Metal B Beige Creech 81 Exterior NEG 3.61 < LOD 0.09 < LOD 0.09 < LOD 3
6/27/13 11:38 0.96 Cal Orange POS 1.24 1.9 0.9 1.9 0.9 < LOD 4.65
6/27/13 11:38 1.28 Cal Orange POS 1.02 1.5 0.4 1.5 0.4 < LOD 3.15
6/27/13 11:39 1.27 Cal Orange POS 1.11 1.7 0.5 1.7 0.5 < LOD 3.15
6/27/13 12:32 1.27 Wall FRP A White Creech 81 Bathroom NEG 1.11 < LOD 0.04 < LOD 0.04 < LOD 2.12
6/27/13 12:33 1.28 Wall FRP B White Creech 81 Bathroom NEG 1.07 < LOD 0.03 < LOD 0.03 < LOD 2.49
6/27/13 12:33 1.28 Wall FRP C White Creech 81 Bathroom NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.39
6/27/13 12:33 1.27 Wall FRP D White Creech 81 Bathroom NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.28
6/27/13 12:33 1.27 Ceiling CT White Creech 81 Bathroom NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.1
6/27/13 12:34 1.26 Door Wood C White Creech 81 Bathroom NEG 3.41 < LOD 0.31 < LOD 0.31 < LOD 2.34
6/27/13 12:34 1.27 Doorframe Wood C Brown Creech 81 Bathroom NEG 1.71 < LOD 0.22 < LOD 0.22 < LOD 2.33
6/27/13 12:34 3.19 Floor VCT C Beige Creech 81 Bathroom NEG 4.29 < LOD 0.18 < LOD 0.18 < LOD 1.65
6/27/13 12:35 1.28 Cabinet Wood B Brown Creech 81 Bathroom NEG 1.04 < LOD 0.18 < LOD 0.18 < LOD 2.98
6/27/13 12:35 1.27 Counter Wood B Beige Creech 81 Bathroom NEG 1 < LOD 0.09 < LOD 0.09 < LOD 3.15
6/27/13 12:36 3.82 Sink Porcelain B White Creech 81 Bathroom NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.51
6/27/13 12:36 1.28 Toilet Porcelain A White Creech 81 Bathroom NEG 3.57 < LOD 0.31 < LOD 0.31 < LOD 4.51
6/27/13 12:36 3.19 Baseboard Vinyl A Black Creech 81 Bathroom POS 2.25 2.9 1.4 1 0.2 2.9 1.4
6/27/13 12:37 1.27 Closet Shelf Wood A White Creech 81 Bathroom NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.66
6/27/13 12:38 1.59 Wall Drywall A Beige Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.32
6/27/13 12:38 2.22 Wall Drywall B Beige Creech 81 Break NEG 2.87 < LOD 0.07 < LOD 0.07 < LOD 2.15
6/27/13 12:38 1.89 Wall Drywall C Beige Creech 81 Break NEG 5.77 < LOD 0.29 < LOD 0.29 < LOD 2.36
6/27/13 12:38 3.2 Wall Drywall D Beige Creech 81 Break POS 7.88 1.9 0.7 1.9 0.7 1.7 1
6/27/13 12:39 1.26 Ceiling CT White Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.14
6/27/13 12:39 1.26 Doorframe Wood B White Creech 81 Break NEG 3.21 < LOD 0.35 < LOD 0.35 < LOD 2.37
6/27/13 12:39 1.27 Doorframe Wood B Red Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.96
6/27/13 12:40 1.27 Cabinet Wood A White Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.87
6/27/13 12:41 1.27 Counter Wood A Beige Creech 81 Break NEG 1.34 < LOD 0.14 < LOD 0.14 < LOD 3.25
6/27/13 12:43 1.27 Window Frame Wood A White Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.55
6/27/13 12:46 1.28 Window Sill Wood A White Creech 81 Break NEG 1.19 < LOD 0.04 < LOD 0.04 < LOD 2.47
6/27/13 12:46 1.28 Window Frame Wood A White Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.55
6/27/13 12:47 1.27 Window Sill Wood C White Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.18
6/27/13 12:47 3.19 Floor VCT C Beige Creech 81 Break NEG 2.39 < LOD 0.07 < LOD 0.07 < LOD 1.57
6/27/13 12:48 1.91 Baseboard Vinyl B Beige Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.85
6/27/13 12:48 2.56 Wall Drywall A Beige Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.88
6/27/13 12:49 1.59 Wall Drywall B Beige Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.53
6/27/13 12:49 1.27 Wall Drywall C Beige Creech 81 Main NEG 3 < LOD 0.18 < LOD 0.18 < LOD 2.69
6/27/13 12:49 1.27 Wall Drywall D Beige Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.52
6/27/13 12:49 1.27 Ceiling CT White Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.22
6/27/13 12:49 1.27 Trim Wood A White Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.1
6/27/13 12:50 1.27 Door Metal A White Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.86
6/27/13 12:50 1.27 Doorframe Metal A White Creech 81 Main NEG 1.15 < LOD 0.03 < LOD 0.03 < LOD 4.13
6/27/13 12:50 1.27 Doorframe Metal C White Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 4.28
6/27/13 12:50 1.27 Door Metal C White Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 4.08
6/27/13 12:51 1.27 Window Frame Metal C White Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.48
6/27/13 12:51 1.28 Window Sill Metal C White Creech 81 Main NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.31
6/27/13 12:52 1.61 Wall Drywall A Beige Creech 81 Office 2 NEG 1.11 < LOD 0.03 < LOD 0.03 < LOD 2.51
6/27/13 12:52 3.18 Wall Drywall B Beige Creech 81 Office 2 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 1.2
6/27/13 12:52 1.27 Wall Drywall C Beige Creech 81 Office 2 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.81
6/27/13 12:52 1.27 Wall Drywall D Beige Creech 81 Office 2 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.71
6/27/13 12:53 1.27 Ceiling CT White Creech 81 Office 2 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.09
6/27/13 12:53 1.27 Vent Metal A White Creech 81 Office 2 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.83
6/27/13 12:53 1.27 Door Wood B White Creech 81 Office 2 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.57
6/27/13 12:54 1.27 Doorframe Wood B White Creech 81 Office 2 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.55
6/27/13 12:55 2.56 Wall Drywall A Beige Creech 81 Office 1 NEG 7.34 < LOD 0.37 < LOD 0.37 < LOD 2
6/27/13 12:55 2.55 Wall Drywall B Beige Creech 81 Office 1 NEG 4.64 < LOD 0.17 < LOD 0.17 < LOD 2.08
6/27/13 12:55 1.59 Wall Drywall C Beige Creech 81 Office 1 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.42
6/27/13 12:55 1.28 Wall Drywall D Beige Creech 81 Office 1 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.57
6/27/13 12:55 1.26 Ceiling Drywall White Creech 81 Office 1 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.11
6/27/13 12:56 1.28 Door Wood C Brown Creech 81 Office 1 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.87
6/27/13 12:56 1.28 Doorframe Metal C Black Creech 81 Office 1 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.9
6/27/13 12:57 1.28 Window Frame Wood B White Creech 81 Office 1 NEG 1.02 < LOD 0.03 < LOD 0.03 < LOD 3.24
6/27/13 12:57 1.27 Window Sill Wood B White Creech 81 Office 1 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.43
6/27/13 12:58 1.6 Wall Drywall A Beige Creech 81 Office 3 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.73
6/27/13 12:58 1.92 Wall Drywall B Beige Creech 81 Office 3 NEG 3.39 < LOD 0.16 < LOD 0.16 < LOD 2.2
6/27/13 12:58 1.59 Wall Drywall C Beige Creech 81 Office 3 NEG 2.37 < LOD 0.1 < LOD 0.1 < LOD 2.62
6/27/13 12:59 1.92 Wall Drywall D Beige Creech 81 Office 3 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.23
6/27/13 12:59 1.27 Ceiling CT White Creech 81 Office 3 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.18
6/27/13 13:00 1.28 Door Wood B White Creech 81 Office 3 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.91
6/27/13 13:00 1.28 Doorframe Wood B White Creech 81 Office 3 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.29
6/27/13 13:00 0.32 Baseboard Vinyl D Gray Creech 81 Office 3 Null 10 < LOD 0.9 < LOD 0.9 < LOD 10.4
6/27/13 13:00 1.27 Baseboard Vinyl D Gray Creech 81 Office 3 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 3.13
6/27/13 13:01 0.32 Window Frame Wood C White Creech 81 Office 3 Null 1 < LOD 0.03 < LOD 0.03 < LOD 7.29
6/27/13 13:01 1.28 Window Frame Wood C White Creech 81 Office 3 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.62
6/27/13 13:01 1.28 Window Sill Wood C White Creech 81 Office 3 NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.25
6/27/13 13:02 1.27 Wall Drywall A Beige Creech 81 Conference NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.76
6/27/13 13:02 1.59 Wall Drywall B Beige Creech 81 Conference NEG 1.99 < LOD 0.11 < LOD 0.11 < LOD 2.44
6/27/13 13:02 0.64 Wall Drywall C Beige Creech 81 Conference Null 7.35 < LOD 1.05 < LOD 1.05 < LOD 5.26
6/27/13 13:02 1.27 Wall Drywall D Beige Creech 81 Conference NEG 2.79 < LOD 0.18 < LOD 0.18 < LOD 3.17
6/27/13 13:03 1.27 Ceiling Drywall White Creech 81 Conference NEG 1.15 < LOD 0.04 < LOD 0.04 < LOD 2.19
6/27/13 13:03 1.28 Trim Drywall A White Creech 81 Conference NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.49
6/27/13 13:03 1.27 Trim Wood D Beige Creech 81 Conference NEG 2.53 < LOD 0.08 < LOD 0.08 < LOD 2.47
6/27/13 13:03 1.28 Door Wood D Beige Creech 81 Conference NEG 1.09 < LOD 0.03 < LOD 0.03 < LOD 2.55
6/27/13 13:04 1.28 Doorframe Wood D Beige Creech 81 Conference NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.79
6/27/13 13:04 1.27 Window Frame Wood B Beige Creech 81 Conference NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.93
6/27/13 13:04 1.28 Window Sill Wood B Beige Creech 81 Conference NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.24
6/27/13 13:05 1.27 Shelf Wood C Beige Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.77
6/27/13 13:05 1.28 Shelf Wood C Beige Creech 81 Break NEG 1 < LOD 0.03 < LOD 0.03 < LOD 2.44
Appendix F
A s d z <-q-q9;1 99# q F:
=t) Fl :ri2dF"* iE*<:YE.E d r..,e a ) <:.2 = a<\
;ageE€ $:
E ; = |9 r.! sft;3rEE[ $Si=% E $-
< = --!lE3g 349<
EF
F z
Aa F i\
0.l/i 9A =0r
II
,.,1 p E9?
.=:i
!;co E S>P>z !i: d :E-t' Fd ?
R
-alil{
TQ
Fi F L.l ci {\\E *a ^|.'E,{>E g
:.o =\loo dsIG Eqls .=
Ol!* 2!al\ Azt\ h rr,,<o Ss?
!ao +aa ^^ :r nFs ais!a r! !4!-cs,)xFs:ic5r,i zIk>t tr4 h a9 &1z z (\ Eg= d=<z & =uJr
H
3si;9+EET E Eg22 Agc0z- x<E-L v 6O L^yt a::; I EEi g $=-6 EH f < l o
E z az U t-
-i F zIt f+ 6'c f= -o5o. acn
=s eF|.
=oooqt] -outa
SE-F;
cL3 0ro --cL= ooOrh =or-o cl o=5(D qt-
=o=oo
GI
oo
-FF
=o9' r+, o o_tr oo -o
CL II
rr+ q, so l+.
oI a o =111 oI oN s+ No o(Jr s6._{
H# g$ 6
$3$ [ ,i $$r $ Fr tSA € F'
*r$F * € g$ifi;s=3r lii ?i$ F3 g i$FEti ,* F g*sfi 3$ ti E s€$DgI d F liflF*€" F o
FilE
$E*#, $ g qsiqF H3X ; P 9oo t gs s
Es n ilo o
a. q) oU)
NJ
I sI
0a
N)
5I
IJJ
I u)
TI
o o
=RT3*I|.- EII
$ Tq$ g* ;Fil tF-.
f,a $rc Ei o) a o d- Q
| 1 13581 - Creech 81.pdf |
| 13581 - Creech Bldg. 81.pdf |
| 1 13581 - Creech 81.pdf |
| Appendix A.pdf |
| 2 13581 - asb asses.pdf |
| Appendix B.pdf |
| 3 13581 - pb asses.pdf |
| Appendix C.pdf |
| Picture Page.pdf |
| Appendix D.pdf |
| 4 13581 - Diagram.pdf |
| Appendix E.pdf |
| 5 13581 - asb lab.pdf |
| Appendix E.1.pdf |
| 6 13581 - XRF.pdf |
| Appendix F.pdf |
| Dustin NV '13-'14.PDF |
| Dustin Pb Insp 11-14.pdf |
| Macrotec Pb Cert '11.pdf |
| TESC PLM '13-'14 (03-31).pdf |
File details come from the government source that posted it. Updated .