Attachment 1 - Salient Characteristics.pdf
PDF 39 KB Posted
- Attached to
- Electrical Load Update Federal contract opportunity
- Solicitation number
- FA485524Q0029
About this file
This document is an attachment titled "Salient Characteristics" that outlines the technical specifications for 400 Hz Frequency Converters required under a federal contract opportunity.
The key details are:
- Input: 50/60Hz, 480VAC, 3-Phase, 3 wire, grounded
- Output: 120/208VAC, 3-Phase, 50kW, 4 wire at 400Hz
- Ambient Operating Temperature: -20 to +110F
- Humidity: 0 to 60%
- Dimensions specified
The related federal contract opportunity is for the "Electrical Load Update" solicitation (FA485524Q0029) issued by the Department of the Air Force Special Operations Command. The solicitation is requesting the delivery and installation of two 400 Hz Frequency Converters meeting the specifications detailed in the "Salient Characteristics" attachment. Other relevant attachments include the Statement of Work, floor plans, provisions/clauses, and questions & answers.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Attachment 6 - Updated Questions and Answers BLDG 679.pdf | ||
| Attachment 3 - BLDG 593 Floor Plan.pdf | ||
| Attachment 4 - BLDG 679 Floor Plan.pdf | ||
| Attachment 5 - Provisions and Clauses.pdf | ||
| Attachment 2 - SOW 593 and 679.pdf | ||
| Attachment 6 - Questions and Answers BLDG 679.pdf | ||
| Combo - Electrical Load Update.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
400 Hz Frequency Converter Salient Specifications
Input Voltage: 50/60Hz, 480VAC, 3-Phase, 3 wire, grounded (4 wire)
Input Frequency: 50/60 Hz
Output power: 120/208VAC, 3-Phase, 50kW, 4 wire
Output Frequency: 400Hz
Ambient Operating Temperature:
Maximum: -20 to +110F
Humidity: 0 to 60% minimum
Dimensions: <85”L x <80”W x <80”H
Altitude: 0 – 4500 ft
Outdoor Housing Capability
Interface: Physical operator controls and display
Instrumentation:
- Elapsed Time
- Voltage Digital Meter
- Current Digital Meter
- Frequency Digital Meter
- Panel Illumination
- Incoming Power Monitor and indication
- Input breaker Closed indication
- Summary Fault indication
- Over temperature
- Transformer Over temperature
- Input/output fault Indication
External Controls:
- On/Off Pushbuttons
- Alarm Silence
- Alarm Reset
- Emergency off
- Input Circuit Breaker
- Output Contactor
- Output Voltage Adjust
- Output Power On/Off
- Bypass
- Emergency Stop
Protective Circuits:
- Overload Protection
- E&F Interlock
- Over / under voltage
- Short Circuit
- Audible Alarm
- Surge Protection