Bldg_898_Q A_2.docx

DOCX document 16 KB Posted

Attached to
Paintbooth Federal contract opportunity
Solicitation number
FA4801-15-R-0029
Issued by
Department of the Air Force Air Combat Command

About this file

FINAL Q A

View the file

Other files for this federal contract opportunity

Other files attached to Paintbooth, newest first.
File Type Posted
Amendment.pdf PDF
Bldg_898_Q A_1.docx DOCX document
Bldg_898_Q A.docx DOCX document
Corrosion_Control_UFC_4_211_02.pdf PDF
FA4801-15-R-0029-0002.pdf PDF
FA4801-15-R-0029 _Bldg_898_Paintbooth_Retrofit.pdf PDF
FA4801-15-R-0029 _Bldg_898_Paint_Booth_Amendment.pdf PDF
ATCH_3-_NCIC_Base_Access.pdf PDF
ATCH_2-_CCFRG_Version_10_17DEC2012.pdf PDF
FA4801-15-R-0029 _Bldg_898_Paintbooth_Retrofit.doc DOC document
ATCH_1-_SOO _Bldg_898_Paintbooth_Retrofit.docx DOCX document
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA4801-15-R-0029 Q&A’s 898 Paintbooth Retrofit Question: We see that there are exhaust fans and recirculation fans, however we do not see a reference to an intake fan/motor. Are we to assume that we are to provide an intake fan? If so please advise on the size.

Answer: There is an intake fan and the contractor is NOT required to replace or provide. The Intake fan’s motor Is 40hp

Further discussion has revealed that the NESHAP filters are requred based on the configuration of the airflow system. These booths have recirculating air as a result for the saftery of the personnel in the booth NESHAP filters ARE required.