Questions and Answers.pdf

PDF 77 KB Posted

Attached to
Install of Electrical Equipment to Power Forklift Battery Charger
Solicitation number
FA466125Q0187
Issued by

About this file

This document is a Questions & Answers (Q&A) file for solicitation FA466125Q0187, providing clarifications for contractors regarding electrical installation requirements. The Q&A addresses seven key points about wall penetrations, electrical work, and installation specifications, including: wall penetration is allowed if utilities are not damaged (with required repairs and painting), no prior permits were pulled for electrical points, contractors can use existing conduit runs meeting NEC requirements, and conduit can be run on walls at a minimum height of 30 inches off the floor. The document notes the facility has a 27-foot floor-to-roof height and that no as-built electrical floor plans are currently available. A structural subject matter expert (SME) may be consulted to confirm compatibility of components with existing installations.

View the file

Other files

File Type Posted
Site Visit Questions and Answers.pdf PDF
Breaker Panel Pictures.pdf PDF
Battery Charger Pictures.pdf PDF
FA466125Q01870001 RFQ.pdf PDF
2. Statement of Work.pdf PDF
4. Wage Determination.pdf PDF
3. Battery Charger Technical Information.pdf PDF
FA466125Q0187 RFQ.pdf PDF
1. FAR Provisions and Clauses.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA466125Q0187-Questions & Answers

1. Is making a wall penetration allowed?

a. Yes, it is allowed as long as its not damaging any utilities in the walls.

Contractors must repair and paint the walls with the correct material.

2. In the past were there permits pulled or is it required to add electrical points of use?

a. No, permits were pulled or not required to add electrical points. Contractors can use existing conduit runs if needed and meets the NEC conduit fill requirement.

3. Are any closed permits on file or records kept on current install?

a. No, we do not have permits on file or records kept for the current install.

4. Can you confirm that we can use components to match what’s currently used?

a. Yes, we would need our structural SME to gather this information.

5. Is the conduit to be ran on the wall or attached to the rafters?

a. Contractors can run the conduit on the wall and does not have to be attached to the rafters. The height from the floor to the roof is 27 feet.

6. If on the wall, at what height?

a. A minimum of 30inches off the floor. Any height above that is okay.

7. Can a floor layout/ schematic be provided?

a. Yes, but we currently do not have any as-builts specifically for electrical floor plans.