This document is Amendment 2 to the Solicitation FA462524Q1050 for a Wastewater Treatment Plant Belt Filter Press Control Panel. The solicitation is for the removal of the existing control panel and the fabrication and installation of a new control panel at Whiteman Air Force Base. The government clarifies that this is a commodity acquisition with incidental services, and not a construction project. The new control panel is required to replicate the existing functionality using modern components, with some functional upgrades as outlined in the Performance Work Statement. The government confirms the belt press is fully operational, but states that the dewatering operations will have to be halted during the installation of the new control panel, which must be completed within 30 days. The government considers details about the belt press, such as its capacity and manufacturer, to be irrelevant to the control panel requirement. The solicitation does not allow for innovative approaches like integrating a PLC and HMI screen, as the government requires replicating the existing functionality.

View the file

Other files for this federal contract opportunity

Other files attached to Wastewater Treatment Plant Belt Filter Press Control Panel, newest first.
File Type Posted
FA462524Q1050 Amendment 3.pdf PDF
FA462524Q1050_Amendment 1.pdf PDF
Atch 3_Existing Schematics.pdf PDF
WWTP Panel COMBO_FA462524Q1050.pdf PDF
Atch 1_PWS_24 April 2024.pdf PDF
Atch 2_Provisions and Clauses.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA462524Q1050 Page 1 of 6

Wastewater Treatment Plant Control Panel

FA462524Q1050

Amendment 2: Additional Questions and Answers

Please elaborate on the following questions:

1. What is the magnitude of the construction project?

a. This acquisition is being solicited as a commodity with incidental services

(removal of old equipment and installation of the new panel), the procedures of FAR 36.204 do not apply.

b. This acquisition is for a fabricated new control panel to the specifications in the PWS. Once fabricated and delivered to the base, the contractor shall remove the old panel and install the new panel and perform a function check to insure performs as needed. Please see PWS for more details.

2. The belt press's capacity (gallons per minute/tons per hour).

a. The Government considers this to be irrelevant to the requirement of a fabricated panel as specified in the PWS.

3. Is the belt press functional?

a. Yes, it is fully operational and performs all the functions that’s required of it.

4. The control panel seems to be analog-based, there are more efficient ways of implementing the control panel, such as integrating a PLC and utilization of HMI (Human Machine Interface) screen to control the many parameters, would you be open to such innovation and effective implementation approaches?

a. No, please see “FA462524Q1050_Amendment 1” Question 1.

5. Does the belt press process any heavy metals, PFAS, or other notable hazardous material contaminants?

a. No, just Bio Solids. However, the scope of this requirement is just the control panel replacement where there are no contaminates.

6. Would you require any wiring or cabling out of the control cabinet?

a. If the PWS states that then yes, otherwise no.

7. Would the contractor be required to conduct mechanical works to amend the belt press beyond replacing drives/motors/sensors related to the control panel?

a. A startup is required to ensure the new panel performs all the functions that are identified in the PWS.

8. Do you have a redundancy filter press to provide sludge dewatering during work, or would dewatering plans halt while the control panel is integrated with the machine?

a. We will have to halt dewatering operations during the install of the new panel.

The Contractor will have up to 30 days from the time they start removing the old panel and have the new panel up and operating.

9. What is the filter press model, and who is the belt press manufacturer?

a. The Government considers this to be irrelevant to the requirement of a fabricated panel as specified in the PWS.

10. Please provide relevant photos of your facility with the control panel, polymer dosing and mixing, and relevant drives at the belt press.

a. Please see the photos displayed below.

FA462524Q1050 Page 2 of 6

FA462524Q1050 Page 3 of 6

FA462524Q1050 Page 4 of 6

FA462524Q1050 Page 5 of 6

FA462524Q1050 Page 6 of 6