Q-A_Bldg_50_answers.pdf
PDF 42 KB Posted
- Attached to
- Proposals Federal contract opportunity
- Solicitation number
- FA4625-17-Q-0003
About this file
Updated Q A added pull alarms
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Q-A_Bldg_50_answers_2.pdf | ||
| FirePrev_DG_WAFB_10_Mar_16.pdf | ||
| Bldg_layout.pdf | ||
| Q-A_Bldg_50_answers.pdf | ||
| Combo_-_FAP_12Oct16.pdf | ||
| Traffic_Code_Cell_Phone.pdf | ||
| Foreign_National_Access.pdf | ||
| Designated_Tobacco_Use.pdf | ||
| Comm_Room_2d_Floor.jpg | JPG image | |
| Fire_Panel_Parts_Breakdown_12Oct16.xlsx | XLSX spreadsheet | |
| First_Floor_Boxes.jpg | JPG image | |
| SOW_Tower_12_Oct_16.pdf | ||
| Drug-Free_Workplace_and_Alcohol.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fa4625-17-Q-0003
Questions and Answers
1. Are "to scale drawings " available? Yes
2. Are the ceilings suspended or hard lid? Both
3. What is the existing alarm system,i.e. name and model number.
AsBuilt IP Fire Series Intelligent Fire Controls.
Wheelock SAFEPATH4 Facility Communications System Monaco BT-XF with 36 zones
4. Is plenum cable acceptable?
All wiring shall be class “A” or “X” circuits per NFPA 72, and installed in conduit per NFPA 70 (NEC). Circuits shall be installed such that the outgoing and return conductors, exiting from and returning to the control unit, respectively, are routed separately.
The main fire alarm control panel shall have a dedicated circuit breaker. Fire alarm control panel circuit breakers shall be labeled and properly identified by the color “red”.
All conduit, junction/back boxes, covers and couplings, when provided, are permitted to be painted to match the room finishing in finished areas. The inside cover of the junction box must be identified as “Fire Alarm” and the conduit must have painted red bands 3/4-in. (20 mm) wide at 20 ft. (6 m) intervals and on both sides of all floor, wall, and ceiling penetrations.
All conduit, junction/back boxes, covers and couplings, when provided, must be factory painted red in unfinished areas (e.g., above ceilings, mechanical rooms, etc.).
All wiring shall be color-coded. Bell System circuit: Red for positive, black for negative, blue for shielded cable. Initiating devices shall be: Blue for positive, white for negative, and red for shielded cable. All wire types and sizes shall be that as required by the system manufacturer.
Fire alarm circuit identification shall be accomplished in accordance with NFPA 70. Signaling line and speaker circuits shall utilize twisted shielded cable.
Signaling line and speaker circuits shall utilize twisted shielded cable.
5. What is the Name/Make/Model # of the original boxes being replaced?
See Question 3
6. Do the Pull stations alarms have to be lowered?
No they will stay in same positon.
7. Period of Performance will be part of your proposal.