Q-A_Bldg_50_answers.pdf

PDF 42 KB Posted

Attached to
Proposals Federal contract opportunity
Solicitation number
FA4625-17-Q-0003
Issued by
Department of the Air Force Global Strike Command

About this file

Updated Q A added pull alarms

View the file

Other files for this federal contract opportunity

Other files attached to Proposals, newest first.
File Type Posted
Q-A_Bldg_50_answers_2.pdf PDF
FirePrev_DG_WAFB_10_Mar_16.pdf PDF
Bldg_layout.pdf PDF
Q-A_Bldg_50_answers.pdf PDF
Combo_-_FAP_12Oct16.pdf PDF
Traffic_Code_Cell_Phone.pdf PDF
Foreign_National_Access.pdf PDF
Designated_Tobacco_Use.pdf PDF
Comm_Room_2d_Floor.jpg JPG image
Fire_Panel_Parts_Breakdown_12Oct16.xlsx XLSX spreadsheet
First_Floor_Boxes.jpg JPG image
SOW_Tower_12_Oct_16.pdf PDF
Drug-Free_Workplace_and_Alcohol.pdf PDF
Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fa4625-17-Q-0003

Questions and Answers

1. Are "to scale drawings " available? Yes

2. Are the ceilings suspended or hard lid? Both

3. What is the existing alarm system,i.e. name and model number.

AsBuilt IP Fire Series Intelligent Fire Controls.

Wheelock SAFEPATH4 Facility Communications System Monaco BT-XF with 36 zones

4. Is plenum cable acceptable?

All wiring shall be class “A” or “X” circuits per NFPA 72, and installed in conduit per NFPA 70 (NEC). Circuits shall be installed such that the outgoing and return conductors, exiting from and returning to the control unit, respectively, are routed separately.

The main fire alarm control panel shall have a dedicated circuit breaker. Fire alarm control panel circuit breakers shall be labeled and properly identified by the color “red”.

All conduit, junction/back boxes, covers and couplings, when provided, are permitted to be painted to match the room finishing in finished areas. The inside cover of the junction box must be identified as “Fire Alarm” and the conduit must have painted red bands 3/4-in. (20 mm) wide at 20 ft. (6 m) intervals and on both sides of all floor, wall, and ceiling penetrations.

All conduit, junction/back boxes, covers and couplings, when provided, must be factory painted red in unfinished areas (e.g., above ceilings, mechanical rooms, etc.).

All wiring shall be color-coded. Bell System circuit: Red for positive, black for negative, blue for shielded cable. Initiating devices shall be: Blue for positive, white for negative, and red for shielded cable. All wire types and sizes shall be that as required by the system manufacturer.

Fire alarm circuit identification shall be accomplished in accordance with NFPA 70. Signaling line and speaker circuits shall utilize twisted shielded cable.

Signaling line and speaker circuits shall utilize twisted shielded cable.

5. What is the Name/Make/Model # of the original boxes being replaced?

See Question 3

6. Do the Pull stations alarms have to be lowered?

No they will stay in same positon.

7. Period of Performance will be part of your proposal.