STATEMENT OF WORK Water Fountain (Updated 13 Feb).docx
DOCX document 16 KB Posted
- Solicitation number
- FA460025Q0019
About this file
This Statement of Work outlines requirements for installing three combination icemaker and hot/cold water dispensers at facility B301D for the 97th Intelligence Squadron at Offutt Air Force Base, NE. The units must utilize 115-120V outlets, fit within 20" W x 60" H x 23" D space, include a 3-stage filtration system (Dual Reverse Osmosis, Pre-Carbon, Mineral Carbon and Sediment), dispense hot water from a .6-gallon reservoir and cold water from a 2-gallon reservoir at 1 gallon per minute, produce 30-40 lbs of ice daily, and feature touchless operation.
The contractor is responsible for installing required electrical outlets, drainage, water supply, and the units themselves, including all necessary tools, equipment, parts, and cleanup. Installation must occur during business hours (Mon-Fri 0800-1600). The 55 CES will handle removal of existing water coolers and oversee the project through their R&O section, with Anna Mosier (402-232-5725) serving as the POC. Per the solicitation, a site visit is scheduled for February 11, 2025, technical questions are due February 13, 2025, and quotes are due February 28, 2025, with offers valid through September 30, 2025.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
97 IS B301D/Install Combination Ice Maker and Hot/Cold Water Dispenser
1. This requirement is to install 3 combination Icemaker and Hot/Cold water dispensers in 3 different locations throughout B301D facility for the 97th Intelligence Squadron on Offutt Air Force Base (AFB), NE.
2. The provided installed items shall meet the following requirements:
-A Combination Ice Maker and Hot/ Cold Water Dispenser Shall utilize 115-120V outlets. The unit shall internally adjust supplied water in order to provide the hot & cold-water dispensing.
-The condensate pump, if required to meet drainage needs based on the locations, shall utilize the current 115V-120V outlets. Power consumption of the water/ice dispenser shall be limited to 1.2 Amp (120 W) for cold water & icemaking, and 6 Amp (720 W) max for the hot water.
-The unit must be sized to fit in a space no larger than 20” wide by 60” High By 23” Deep.
3. The unit must have a filtration process that includes a 3-stage system at a minimum. This includes a Dual Reverse Osmosis, Pre-Carbon, Mineral Carbon and Sediment. This filtration system must be enclosed inside the unit. The unit must dispense Hot water from a minimum .6-gallon reservoir and cold water from a 2-gallon reservoir with a 1-gallon flow rate per minute. The unit must produce 30lbs to 40lbs of ice per day. The unit must have touchless operation system.
4. Contractor shall be responsible for the installation of 115V/120V outlets, drain, and water supply to support the installation of Combination Ice Maker and Hot/ Cold Water Dispenser and condensate pump.
5. Contractor shall be responsible for the installation of Combination Ice Maker and Hot/ Cold Water Dispenser and condensate pump. Contractor shall be responsible for providing all the tools, equipment, and parts necessary to install the machines. Contractor shall be responsible for all cleanup and the disposal of any waste generated during the installation.
6. The 97IS will be the main POC for all coordination with the contractor. Installation of the Combination Ice Maker and Hot/ Cold Water Dispenser machines shall be accomplished during a time standard business hours Mon-Fri 0800-1600.
7. The 55 CES shall be responsible for the removal and disposal of previously existing water coolers mentioned in this SOW. This will be accomplished by the WFSM aka Plumbing shop (CEOIU) as the shop schedule allows. 55 CES shall have no other requirement other than overseeing this CBR through its completion by the R&O section of the operations flight (CEOER). The 55 CES representative for this CBR is Anna Mosier 402-232-5725. All contact for the CBR shall go through the 55 CES listed representative unless agreed upon otherwise outside of this SOW. 55 CES shall incur no other cost or expense and no other shop shall be tasked to do any work on this CBR.