This amendment item list revises the drawings and specifications for the repair of CRL Building 975 at Minot Air Force Base. The revisions include correcting window type notes on two drawings and replacing paragraphs in the direct digital control systems specification to require a new building controller that integrates with the base-wide EMCS and does not require a gateway device. The specification is also revised to not require providing a notebook computer. The related federal contract opportunity is for the repair of CRL Building 975 at Minot AFB, with the goal of completing a total renovation of the interior and exterior site work. The project work includes 15% general work, 35% architectural work, 25% mechanical work, and 25% electrical work. The solicitation was issued by the Department of the Air Force Global Strike Command.

View the file

Other files for this federal contract opportunity

Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT ITEM LIST #1

REPAIR CRL- B975

PROJECT NUMBER AFPID 1007592

08 JAN 20

REVISED 15 JAN 20

AMENDMENT LIST:

1. Sheet A-101: In Rooms 06 and 07, Window Type note is correct.

Sheet A-202: Window Elevation #2, change window type to ‘Type 06, Verify’.

REVISED:

2. Change specification 23 09 23.13 20, paragraphs 1.3.b, 2.1.a and 2.1.4 to the following:

1.3 BACNET DIRECT DIGITAL CONTROL SYSTEMS FOR HVAC DESCRIPTION

b. Provide a new DDC building controller and IP network connection to integrate the operation of the building's DDC controls with the operation of the base wide Energy Management and Control System (EMCS) by Johnson Controls Inc. Provide a shelf or counter near the building controller for the maintenance staff at the base to connect a laptop computer to the DDC system for access and have the ability to view the operation of the mechanical systems and make adjustments. The new DDC system shall be completely compatible and shall communicate with the EMCS system without the use of a gateway interface device.

2.1 DDC SYSTEM

a. Provide a networked DDC system for both stand-alone and base wide control in compliance with the latest revision of the ASHRAE 135 BACnet standard. Include all programming, objects, and services required to meet the sequence of control. Provide BACnet communications between the DDC system and native BACnet devices furnished with HVAC equipment and variable frequency drives. Devices provided shall be certified in the BACnet Testing Laboratories (BTL) Product Listing.

2.1.4 NOT USED, (NO Notebook Computer shall be provided.).