Attachment 10 - UFGS 28 31 70.pdf
PDF 279 KB Posted
- Attached to
- Camp Warlord Fire Alarm
- Solicitation number
- FA446024Q0288
About this file
This document is a solicitation for a fire alarm upgrade project at Camp Warlord on Little Rock Air Force Base. The contractor shall furnish, remove, and replace the fire notification system in 13 facilities at Camp Warlord within 180 days of contract award. Key details include:
The solicitation number is FA446024Q0288, and the work must comply with NFPA guidelines and all federal, state, and local regulations. A site visit is scheduled for 24 September 2024, and all questions are due by 25 September 2024. Quotes in response to the solicitation must be submitted by 4:00 PM (CDT) on 26 September 2024. The Department of the Air Force, Air Mobility Command is the issuing agency.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USACE / NAVFAC / AFCEC UFGS- 28 31 70 ( August 2020)
Pr epar i ng Act i v i t y: USACE Super sedi ng UFGS- 28 31 00. 00 10 ( November 2008) UFGS- 28 31 49 ( Apr i l 2006) UFGS- 28 31 63. 00 20 ( Oct ober 2007) UFGS- 28 31 64. 00 10 ( August 2009) UFGS- 28 31 74. 00 20 ( Febr uar y 2010)
UNI FI ED FACI LI TI ES GUI DE SPECI FI CATI ONS
Ref er ences ar e i n agr eement wi t h UMRL dat ed Jul y 2024
SECTI ON TABLE OF CONTENTS
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
SECTI ON 28 31 70
I NTERI OR FI RE ALARM SYSTEM, ADDRESSABLE
08/ 20
PART 1 GENERAL
1. 1 REFERENCES
1. 2 RELATED SECTI ONS
1. 3 SUMMARY
1. 3. 1 Scope
1. 3. 2 Qual i f i ed Fi r e Pr ot ect i on Engi neer ( QFPE)
1. 4 DEFI NI TI ONS
1. 4. 1 I nt er f ace Devi ce
1. 4. 2 Fi r e Al ar m Cont r ol Uni t ( FACU)
1. 4. 3 Remot e Fi r e Al ar m Cont r ol Uni t
1. 4. 4 Ter mi nal Cabi net
1. 4. 5 Cont r ol Modul e and Rel ay Modul e
1. 4. 6 Desi gnat ed Fi r e Pr ot ect i on Engi neer ( DFPE)
1. 4. 7 Qual i f i ed Fi r e Pr ot ect i on Engi neer ( QFPE)
1. 5 SUBMI TTALS
1. 6 SYSTEM OPERATI ON
1. 6. 1 Al ar m I ni t i at i ng Devi ces and Not i f i cat i on Appl i ances ( Vi sual , Audi bl e)
1. 6. 2 Funct i ons and Oper at i ng Feat ur es
1. 6. 3 El evat or Recal l
1. 7 TECHNI CAL DATA AND SI TE- SPECI FI C SOFTWARE
1. 8 EXI STI NG EQUI PMENT
1. 9 QUALI TY ASSURANCE
1. 9. 1 Submi t t al Document s
1. 9. 1. 1 Pr econst r uct i on Submi t t al s
1. 9. 1. 2 Shop Dr awi ngs
SECTI ON 28 31 70 Page 1
1. 9. 1. 3 Namepl at es
1. 9. 1. 4 Wi r i ng Di agr ams
1. 9. 1. 5 Syst em Layout
1. 9. 1. 6 Not i f i cat i on Appl i ances
1. 9. 1. 7 I ni t i at i ng Devi ces
1. 9. 1. 8 Bat t er y Power
1. 9. 1. 9 Vol t age Dr op Cal cul at i ons
1. 9. 1. 10 Pr oduct Dat a
1. 9. 1. 11 Ai r Sampl i ng Smoke Det ect i on Syst em Cal cul at i ons
1. 9. 1. 12 Oper at i on and Mai nt enance ( O&M) I nst r uct i ons
1. 9. 1. 13 As- Bui l t Dr awi ngs
1. 9. 2 Qual i f i cat i ons
1. 9. 2. 1 Fi r e Al ar m Syst em Desi gner
1. 9. 2. 2 Super vi sor
1. 9. 2. 3 Techni c i an
1. 9. 2. 4 I nst al l er
1. 9. 2. 5 Test Techni c i an
1. 9. 2. 6 Manuf act ur er
1. 9. 3 Regul at or y Requi r ement s
1. 10 DELI VERY, STORAGE, AND HANDLI NG
1. 11 MAI NTENANCE
1. 11. 1 Spar e Par t s
1. 11. 2 Speci al Tool s
PART 2 PRODUCTS
2. 1 GENERAL PRODUCT REQUI REMENT
2. 2 MATERI ALS AND EQUI PMENT
2. 2. 1 St andar d Pr oduct s
2. 2. 2 Namepl at es
2. 2. 3 Keys
2. 2. 4 I nst r uct i ons
2. 3 FI RE ALARM CONTROL UNI T
2. 3. 1 Cabi net
2. 3. 2 Si l enci ng Swi t ches
2. 3. 2. 1 Al ar m Si l enci ng Swi t ch
2. 3. 2. 2 Super vi sor y/ Tr oubl e Si l enci ng Swi t ch
2. 3. 3 Non- I nt er f er i ng
2. 3. 4 Memor y
2. 3. 5 Fi el d Pr ogr ammabi l i t y
2. 3. 6 I nput / Out put Modi f i cat i ons
2. 3. 7 Reset t i ng
2. 3. 8 Wal k Test
2. 3. 9 Hi st or y Loggi ng
2. 3. 10 Manual Access
2. 3. 11 Heat Det ect or Sel f - Test Rout i nes
2. 4 VI DEO DI SPLAY UNI T ( VDU)
2. 5 REMOTE ANNUNCI ATOR
2. 5. 1 LCD Annunci at or
2. 5. 2 Gr aphi c Annunci at or
2. 5. 2. 1 Mat er i al s
2. 5. 2. 2 Pr ogr ammi ng
2. 5. 3 Pr i nt er
2. 6 MANUAL STATI ONS
2. 7 SMOKE DETECTORS
2. 7. 1 Spot Type Det ect or s
2. 7. 2 Pr oj ect ed Beam Smoke Det ect or
2. 7. 3 Duct Smoke Det ect or s
2. 8 AI R SAMPLI NG SMOKE DETECTI ON SYSTEM
SECTI ON 28 31 70 Page 2
2. 9 HEAT DETECTORS
2. 9. 1 Heat Det ect or s
2. 9. 1. 1 Combi nat i on Fi xed- Temper at ur e and Rat e- of - Ri se Det ect or s
2. 9. 1. 2 Rat e Compensat i ng Det ect or s
2. 9. 1. 3 Li ne- Type Fi xed Temper at ur e Det ect or s
2. 9. 1. 4 Fi xed Temper at ur e Det ect or s
2. 10 FLAME DETECTORS
2. 10. 1 I nf r ar ed ( I R) Si ngl e Fr equency Fl ame Det ect or
2. 10. 2 I nf r ar ed ( I R) Mul t i Fr equency Fl ame Det ect or
2. 10. 3 Ul t r avi ol et ( UV) Fl ame Det ect or s
2. 10. 4 Combi nat i on UV/ I R Fl ame Det ect or
2. 11 MULTI - CRI TERI A DETECTORS
2. 12 CARBON MONOXI DE DETECTOR
2. 13 ADDRESSABLE I NTERFACE DEVI CES
2. 14 ADDRESSABLE CONTROL MODULES
2. 15 I SOLATI ON MODULES
2. 16 NOTI FI CATI ON APPLI ANCES
2. 16. 1 Audi bl e Not i f i cat i on Appl i ances
2. 16. 1. 1 Hor ns
2. 16. 1. 2 Bel l s
2. 16. 1. 3 Chi mes
2. 16. 2 Vi sual Not i f i cat i on Appl i ances
2. 17 ELECTRI C POWER
2. 17. 1 Pr i mar y Power
2. 18 SECONDARY POWER SUPPLY
2. 18. 1 Bat t er i es
2. 18. 1. 1 Capaci t y
2. 18. 1. 2 Bat t er y Power Cal cul at i ons
2. 18. 2 Bat t er y Char ger s
2. 19 SURGE PROTECTI VE DEVI CES
2. 20 WI RI NG
2. 20. 1 Al ar m Wi r i ng
2. 21 AUTOMATI C FI RE ALARM TRANSMI TTERS
2. 21. 1 Radi o Tr ansmi t t er and I nt er f ace Panel s
2. 21. 1. 1 Oper at i on
2. 21. 1. 2 Bat t er y Power
2. 21. 1. 3 Tr ansmi t t er Housi ng
2. 21. 1. 4 Ant enna
2. 21. 2 Di gi t al Al ar m Communi cat or Tr ansmi t t er ( DACT)
2. 21. 3 Si gnal s t o Be Tr ansmi t t ed t o t he Base Recei v i ng St at i on
2. 22 SYSTEM MONI TORI NG
2. 22. 1 Val ves
2. 22. 2 Hi gh/ Low [ Ai r ] [ Ni t r ogen] Super vi sor y Swi t ches
2. 22. 3 Room Low Temper at ur e Super vi sor y Swi t ch
2. 22. 4 El ect r omagnet i c Door Hol der s
2. 23 ENVI RONMENTAL ENCLOSURES OR GUARDS
2. 24 FI REFI GHTER TELEPHONE COMMUNI CATI ON SYSTEM
2. 24. 1 Gener al
2. 24. 2 Feat ur es
2. 24. 3 Handset s
PART 3 EXECUTI ON
3. 1 VERI FYI NG ACTUAL FI ELD CONDI TI ONS
3. 2 I NSTALLATI ON
3. 2. 1 Fi r e Al ar m Cont r ol Uni t ( FACU)
3. 2. 2 Bat t er y Cabi net s
3. 2. 3 Manual St at i ons
3. 2. 4 Not i f i cat i on Appl i ances
SECTI ON 28 31 70 Page 3
3. 2. 5 Smoke and Heat Det ect or s
3. 2. 6 Car bon Monoxi de Det ect or s
3. 2. 7 Ai r Sampl i ng Smoke Det ect or
3. 2. 8 Gr aphi c Annunci at or
3. 2. 9 LCD REMOTE Annunci at or
3. 2. 10 El ect r omagnet i c Door Hol der Rel ease
3. 2. 11 Fi r ef i ght er Tel ephones
3. 2. 12 Cei l i ng Br i dges
3. 3 SYSTEM FI ELD WI RI NG
3. 3. 1 Wi r i ng wi t hi n Cabi net s, Encl osur es, and Boxes
3. 3. 2 Ter mi nal Cabi net s
3. 3. 3 Al ar m Wi r i ng
3. 3. 4 Back Boxes and Condui t
3. 3. 5 Conduct or Ter mi nat i ons
3. 4 DI SCONNECTI ON AND REMOVAL OF EXI STI NG SYSTEM
3. 5 CONNECTI ON OF NEW SYSTEM
3. 6 FI RESTOPPI NG
3. 7 PAI NTI NG
3. 8 FI ELD QUALI TY CONTROL
3. 8. 1 Test Pr ocedur es
3. 8. 2 Pr e- Gover nment Test i ng
3. 8. 2. 1 Ver i f i cat i on of Compl i ant I nst al l at i on
3. 8. 2. 2 Request f or Gover nment Fi nal Test
3. 8. 3 Cor r ect i on of Def i c i enci es
3. 8. 4 Gover nment Fi nal Test s
3. 9 MI NI MUM SYSTEM TESTS
3. 9. 1 Syst em Test s
3. 9. 2 Audi bi l i t y Test s
3. 10 SYSTEM ACCEPTANCE
3. 11 I NSTRUCTI ON OF GOVERNMENT EMPLOYEES
3. 11. 1 I nst r uct or
3. 11. 2 Requi r ed I nst r uct i on Ti me
3. 11. 2. 1 Techni cal Tr ai ni ng
3. 11. 3 Techni cal Tr ai ni ng Manual
3. 12 EXTRA MATERI ALS
3. 12. 1 Repai r Ser vi ce/ Repl acement Par t s
3. 12. 2 Spar e Par t s
3. 12. 3 Document St or age Cabi net
- - End of Sect i on Tabl e of Cont ent s - -
SECTI ON 28 31 70 Page 4
USACE / NAVFAC / AFCEC UFGS- 28 31 70 ( August 2020)
Pr epar i ng Act i v i t y: USACE Super sedi ng UFGS- 28 31 00. 00 10 ( November 2008) UFGS- 28 31 49 ( Apr i l 2006) UFGS- 28 31 63. 00 20 ( Oct ober 2007) UFGS- 28 31 64. 00 10 ( August 2009) UFGS- 28 31 74. 00 20 ( Febr uar y 2010)
UNI FI ED FACI LI TI ES GUI DE SPECI FI CATI ONS
Ref er ences ar e i n agr eement wi t h UMRL dat ed Jul y 2024
SECTI ON 28 31 70
I NTERI OR FI RE ALARM SYSTEM, ADDRESSABLE
08/ 20
NOTE: Thi s speci f i cat i on cover s t he r equi r ement s f or an addr essabl e i nt egr at ed f i r e det ect i on, f i r e al ar m syst em.
Adher e t o UFC 1- 300- 02 Uni f i ed Faci l i t i es Gui de Speci f i cat i ons ( UFGS) For mat St andar d when edi t i ng t hi s gui de speci f i cat i on or pr epar i ng new pr oj ect speci f i cat i on sect i ons. Edi t t hi s gui de speci f i cat i on f or pr oj ect speci f i c r equi r ement s by addi ng, del et i ng, or r evi s i ng t ext . For br acket ed i t ems, choose appl i cabl e i t em( s) or i nser t appr opr i at e i nf or mat i on.
Remove i nf or mat i on and r equi r ement s not r equi r ed i n r espect i ve pr oj ect , whet her or not br acket s ar e pr esent .
Comment s, suggest i ons and r ecommended changes f or t hi s gui de speci f i cat i on ar e wel come and shoul d be submi t t ed as a Cr i t er i a Change Request ( CCR) .
NOTE: For OCONUS pr oj ect s, t hi s speci f i cat i on sect i on shoul d be edi t ed f or speci f i c Host Nat i on r equi r ement s. Coor di nat e compl i ance wi t h Host Nat i on r equi r ement s wi t h t he Desi gnat ed Fi r e Pr ot ect i on Engi neer ( DFPE) .
SECTI ON 28 31 70 Page 5
NOTE: For Fami l y Housi ng pr oj ect s at NAVFAC NE use r egi onal gui de speci f i cat i on sect i on 28 31 46. 00 22 ( N- 13854N) HOUSEHOLD FI RE WARNI NG EQUI PMENT t o speci f y r esi dent i al f i r e war ni ng syst ems i n l i eu of t hi s sect i on.
NOTE: Thi s speci f i cat i on sect i on i ncl udes r equi r ement s f r om UFC 3- 600- 01 ( change 43, 7 Febr uar y 2020)
NOTE: Thi s gui de speci f i cat i on cover s car bon monoxi de al ar m det ect or s f or pr ot ect i on i n i ndoor l ocat i ons wher e f uel - bur ni ng appl i ances/ equi pment ar e used.
PART 1 GENERAL
1. On t he dr awi ngs, show l ocat i on of cont r ol uni t , bat t er i es and char ger ( i f r emot el y mount ed) , super vi s i ng st at i on t r ansmi t t er , annunci at or , pr i mar y power suppl y, r emot e annunci at or , det ect or s, not i f i cat i on appl i ances ( unl ess per f or mance r equi r ement s ar e speci f i ed) , and each al ar m i ni t i at i ng devi ce i ncl udi ng f i r e ext i ngui shi ng syst em swi t ches.
2. Show si ngl e- l i ne f i r e al ar m syst ems r i ser di agr am. Each devi ce on t he r i ser shoul d be i dent i f i ed by t ype. I ndi cat e connect i on of equi pment .
3. A f i r e al ar m oper at i ng mat r i x must be pl aced on t he dr awi ngs. Show act i ons of i nput devi ces such as det ect or s, manual st at i ons, wat er f l ow swi t ches, i ni t i at i ng devi ces, et c. on one axi s and out put f unct i ons such as door r el eases, smoke cont r ol f ans, el evat or r el ays, i ndi cat i ng/ not i f i cat i on appl i ances et c. on t he ot her . Ent r i es whi ch r equi r e descr i pt i ons, expl anat i on of pr ocesses, sequences, i nt er f aces, et c. can be f l agged by symbol s keyed t o suppl ement ar y not es. Al t er nat el y pr ovi de a zone- by- zone sequence of oper at i on or a schedul e i dent i f y i ng al l i ni t i at or s, out put s, and i nt er f aces.
4. Addr essabl e Fi r e Al ar m Syst ems gener al l y ut i l i ze Si gnal Li ne Ci r cui t s ( SLC) f or communi cat i on bet ween devi ces. Nor mal l y al l devi ces ar e addr essabl e or wi l l have an addr essabl e i nt er f ace devi ce i nst al l ed i nt egr al l y wi t h t he devi ce. I ni t i at i ng Devi ce Ci r cui t s ( I DC) shoul d be pr ovi ded f or i nt er f aci ng t o exi st i ng I DC l oops or connect i on bet ween non- addr essabl e devi ces and t he SLC.
SECTI ON 28 31 70 Page 6
1. 1 REFERENCES
NOTE: Thi s par agr aph i s used t o l i s t t he publ i cat i ons c i t ed i n t he t ext of t he gui de speci f i cat i on. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by basi c desi gnat i on onl y and l i s t ed i n t hi s par agr aph by or gani zat i on, desi gnat i on, dat e, and t i t l e.
Use t he Ref er ence Wi zar d' s Check Ref er ence f eat ur e when you add a Ref er ence I dent i f i er ( RI D) out si de of t he Sect i on' s Ref er ence Ar t i c l e t o aut omat i cal l y pl ace t he r ef er ence i n t he Ref er ence Ar t i c l e. Al so use t he Ref er ence Wi zar d' s Check Ref er ence f eat ur e t o updat e t he i ssue dat es.
Ref er ences not used i n t he t ext wi l l aut omat i cal l y be del et ed f r om t hi s sect i on of t he pr oj ect speci f i cat i on when you choose t o r econci l e r ef er ences i n t he publ i sh pr i nt pr ocess.
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
AMERI CAN SOCI ETY OF MECHANI CAL ENGI NEERS ( ASME)
ASME A17. 1/ CSA B44 ( 2019) Saf et y Code f or El evat or s and Escal at or s
ASTM I NTERNATI ONAL ( ASTM)
ASTM F402 ( 2018) St andar d Pr act i ce f or Saf e Handl i ng of Sol vent Cement s, Pr i mer s, and Cl eaner s Used f or Joi ni ng Ther mopl ast i c Pi pe and Fi t t i ngs
FM GLOBAL ( FM)
FM APP GUI DE ( updat ed on- l i ne) Appr oval Gui de ht t ps: / / www. appr oval gui de. com/
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE C62. 41. 1 ( 2002; R 2008) Gui de on t he Sur ges Envi r onment i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 4 ( 2018) St andar d f or I nt egr at ed Fi r e Pr ot ect i on and Li f e Saf et y Syst em Test i ng
SECTI ON 28 31 70 Page 7
NFPA 70 ( 2023) Nat i onal El ect r i cal Code
NFPA 72 ( 2022; ERTA 22- 1) Nat i onal Fi r e Al ar m and Si gnal i ng Code
NFPA 90A ( 2024) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems
NFPA 170 ( 2024; ERTA 1 2023) St andar d f or Fi r e Saf et y and Emer gency Symbol s
U. S. DEPARTMENT OF DEFENSE ( DOD)
UFC 3- 601- 02 ( 2021) Fi r e Pr ot ect i on Syst ems I nspect i on, Test i ng, and Mai nt enance
UFC 4- 010- 06 ( 2023) Cyber secur i t y of Faci l i t y- Rel at ed Cont r ol Syst ems
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
47 CFR 15 Radi o Fr equency Devi ces
47 CFR 90 Pr i vat e Land Mobi l e Radi o Ser vi ces
UNDERWRI TERS LABORATORI ES ( UL)
UL 228 ( 2006; Repr i nt Mar 2022) UL St andar d f or Saf et y Door Cl oser s- Hol der s, Wi t h or Wi t hout I nt egr al Smoke Det ect or s
UL 268 ( 2023) UL St andar d f or Saf et y Smoke Det ect or s f or Fi r e Al ar m Syst ems
UL 268A ( 2008; Repr i nt Aug 2023) Smoke Det ect or s f or Duct Appl i cat i on
UL 464 ( 2023) UL St andar d f or Saf et y Audi bl e Si gnal i ng Devi ces f or Fi r e Al ar m and Si gnal i ng Syst ems, I ncl udi ng Accessor i es
UL 497A ( 2001; Bul . 2019) UL St andar d f or Saf et y Secondar y Pr ot ect or s f or Communi cat i ons Ci r cui t s
UL 497B ( 2004; Repr i nt Feb 2022) UL St andar d f or Saf et y Pr ot ect or s f or Dat a Communi cat i ons and Fi r e Al ar m Ci r cui t s
UL 521 ( 1999; Repr i nt Feb 2023) UL St andar d f or Saf et y Heat Det ect or s f or Fi r e Pr ot ect i ve Si gnal i ng Syst ems
UL 864 ( 2023) UL St andar d f or Saf et y Cont r ol Uni t s and Accessor i es f or Fi r e Al ar m Syst ems
UL 1283 ( 2017; Repr i nt Feb 2024) UL St andar d f or
SECTI ON 28 31 70 Page 8
Saf et y El ect r omagnet i c I nt er f er ence Fi l t er s
UL 1449 ( 2021; Repr i nt Dec 2022) UL St andar d f or Saf et y Sur ge Pr ot ect i ve Devi ces
UL 1638 ( 2023) UL St andar d f or Saf et y Vi s i bl e Si gnal i ng Devi ces f or Fi r e Al ar m and Si gnal i ng Syst ems, I ncl udi ng Accessor i es
UL 1971 ( 2002; Repr i nt Feb 2024) UL St andar d f or Saf et y Si gnal i ng Devi ces f or t he Deaf and Har d of Hear i ng
UL 2034 ( 2024; Repr i nt Aug 2024) UL St andar d f or Saf et y Si ngl e and Mul t i pl e St at i on Car bon Monoxi de Al ar ms
UL 2075 ( 2013; Bul . 2019) UL St andar d f or Saf et y Gas and Vapor Det ect or s and Sensor s
UL Fi r e Pr ot Di r UL Pr oduct I Q ( updat ed onl i ne) at ht t ps: / / pr oduct i q. ul pr opsect or . com/ en
1. 2 RELATED SECTI ONS
Sect i on 25 05 11 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS, appl i es t o t hi s sect i on, wi t h t he addi t i ons and modi f i cat i ons speci f i ed her ei n. I n addi t i on, r ef er t o t he f ol l owi ng sect i ons f or r el at ed wor k and coor di nat i on:
[ Sect i on 21 13 13 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON] [ Sect i on 21 30 00 FI RE PUMPS] [ Sect i on 21 23 00 WET CHEMI CAL FI RE EXTI NGUI SHI NG SYSTEMS] [ Sect i on 21 13 16 DRY PI PE FI RE SPRI NKLER SYSTEMS] [ Sect i on 21 13 18 PREACTI ON FI RE SPRI NKLER SYSTEMS] [ Sect i on 21 13 19 DELUGE FI RE SPRI NKLER SYSTEMS] [ Sect i on 23 30 00 HVAC AI R DI STRI BUTI ON] [ Sect i on 21 13 24. 00 10 AQUEOUS FI LM- FORMI NG FOAM ( AFFF) FI RE
PROTECTI ON SYSTEM]
[ Sect i on 21 13 25 HI GH- EXPANSI ON FOAM SYSTEM, FI RE PROTECTI ON] [ Sect i on 21 21 01 CARBON- DI OXI DE FI RE- EXTI NGUI SHI NG SYSTEMS] [ Sect i on 21 23 00 WET CHEMI CAL FI RE EXTI NGUI SHI NG SYSTEMS] [ Sect i on 08 71 00 DOOR HARDWARE f or [ door r el ease] [ door unl ocki ng] and addi t i onal wor k r el at ed t o f i ni sh har dwar e. ] [ Sect i on[ s] [ 14 21 13 ELECTRI C TRACTI ON FREI GHT ELEVATORS] [ 14 21 23
ELECTRI C TRACTI ON PASSENGER ELEVATORS] [ and] [ 14 24 13 HYDRAULI C FREI GHT ELEVATORS] [ 14 24 23 HYDRAULI C PASSENGER ELEVATORS] f or addi t i onal wor k r el at ed t o el evat or s. ]
[ Sect i on 07 84 00 FI RESTOPPI NG f or addi t i onal wor k r el at ed t o f i r est oppi ng. ]
1. 3 SUMMARY
1. 3. 1 Scope
a. Thi s wor k i ncl udes desi gni ng and [ pr ovi di ng a new, compl et e, ] [ modi f y i ng t he exi st i ng] f i r e al ar m syst em as descr i bed her ei n and on t he cont r act dr awi ngs[ f or t he _____________] . I ncl ude syst em wi r i ng, r aceways, pul l boxes, t er mi nal cabi net s, out l et and
SECTI ON 28 31 70 Page 9 mount i ng boxes, cont r ol equi pment , i ni t i at i ng devi ces, not i f i cat i on appl i ances, super vi s i ng st at i on f i r e al ar m t r ansmi t t er s, and ot her accessor i es and mi scel l aneous i t ems r equi r ed f or a compl et e oper at i onal syst em even t hough each i t em i s not speci f i cal l y ment i oned or descr i bed. Pr ovi de syst em[ s] compl et e and r eady f or oper at i on. [ Exi st i ng i nt er i or f i r e al ar m syst em was manuf act ur ed by [ _____] . ] Desi gn and i nst al l at i on must compl y wi t h UFGS 25 05 11 and UFC 4- 010- 06
b. Pr ovi de equi pment , mat er i al s, i nst al l at i on, wor kmanshi p, i nspect i on, and t est i ng i n st r i ct accor dance wi t h NFPA 72, except as modi f i ed her ei n. [ The syst em l ayout on t he dr awi ngs show t he i nt ent of cover age and suggest ed l ocat i ons. Fi nal quant i t y, syst em l ayout , and coor di nat i on ar e t he r esponsi bi l i t y of t he Cont r act or . ]
[ c. Each r emot e f i r e al ar m cont r ol uni t must be power ed f r om a wi r i ng r i ser speci f i cal l y f or t hat use or f r om a l ocal emer gency power panel l ocat ed on t he same f l oor as t he r emot e f i r e al ar m cont r ol uni t .
Wher e r emot e f i r e cont r ol uni t s ar e pr ovi ded, equi pment f or not i f i cat i on appl i ances may be l ocat ed i n t he r emot e f i r e al ar m cont r ol uni t s. ]
[ d. Wher e a f i r e pump i s pr ovi ded, t he f i r e al ar m syst em must moni t or and t r ansmi t t he f i r e pump cont r ol l er s i gnal s i n accor dance wi t h t he pr ovi s i ons of NFPA 72. ]
[ e. Wher e an emer gency gener at or pr ovi des st andby power suppl y f or l i f e saf et y syst em ci r cui t s, t he gener at or must be moni t or ed by t he Fi r e Al ar m Cont r ol Uni t ( FACU) and t r ansmi t emer gency gener at or s i gnal s i n accor dance wi t h NFPA 72. ] f . The f i r e al ar m syst em must be i ndependent of t he bui l di ng secur i t y, bui l di ng management , and ener gy/ ut i l i t y moni t or i ng syst ems ot her t han f or cont r ol f unct i ons.
1. 3. 2 Qual i f i ed Fi r e Pr ot ect i on Engi neer ( QFPE)
NOTE: UFC 3- 600- 01 r equi r es t hat shop dr awi ngs must bear t he Revi ew St amp and pr of essi onal engi neer i ng st amp of t he QFPE pr i or t o submi ssi on t o t he Gover nment f or appr oval .
NOTE: The t er m Qual i f i ed Fi r e Pr ot ect i on Engi neer ( QFPE) shoul d be consi der ed i nt er changeabl e wi t h t he t er ms " Fi r e Pr ot ect i on Desi gner of Recor d ( FPDOR) " and/ or " Fi r e Pr ot ect i on QC Speci al i st " wher e r ef er r ed t o i n ot her appl i cabl e cont r act document s.
The i nt ent of def i ni ng t he QFPE r ol es and r esponsi bi l i t i es her e i s NOT t o r equi r e per sonnel i n addi t i on t o t he QFPE, FPDOR, and/ or FPQC speci al i st r ef er enced el sewher e i n t he appl i cabl e cont r act document s.
Ser vi ces of t he QFPE must i ncl ude:
SECTI ON 28 31 70 Page 10
a. Revi ewi ng SD- 02, SD- 03, and SD- 05 submi t t al packages f or compl et eness and compl i ance wi t h t he pr ovi s i ons of t hi s speci f i cat i on.
Const r uct i on ( shop) dr awi ngs and cal cul at i ons must be pr epar ed by, or pr epar ed under t he i mmedi at e super vi s i on of , t he QFPE. The QFPE must af f i x t hei r pr of essi onal engi neer i ng st amp wi t h s i gnat ur e t o t he shop dr awi ngs, cal cul at i ons, and mat er i al dat a sheet s, i ndi cat i ng appr oval pr i or t o submi t t i ng t he shop dr awi ngs t o t he DFPE.
b. Pr ovi di ng a l et t er document i ng t hat t he SD- 02, SD- 03, and SD- 05 submi t t al package has been r evi ewed and not i ng any out st andi ng comment s.
c. Per f or mi ng i n- pr ogr ess const r uct i on sur vei l l ance pr i or t o i nst al l at i on of cei l i ngs ( r ough- i n i nspect i on) .
d. Wi t nessi ng pr e- Gover nment [ and f i nal Gover nment ] f unct i onal per f or mance t est i ng and per f or mi ng a f i nal i nst al l at i on r evi ew.
e. Si gni ng appl i cabl e cer t i f i cat es under SD- 07.
1. 4 DEFI NI TI ONS
Wher ever ment i oned i n t hi s speci f i cat i on or on t he dr awi ngs, t he equi pment , devi ces, and f unct i ons must be def i ned as f ol l ows:
1. 4. 1 I nt er f ace Devi ce
An addr essabl e devi ce t hat i nt er connect s har d wi r ed syst ems or devi ces t o an anal og/ addr essabl e syst em.
1. 4. 2 Fi r e Al ar m Cont r ol Uni t ( FACU)
A mast er cont r ol uni t havi ng t he f eat ur es of a f i r e al ar m cont r ol uni t
( FACU) .
1. 4. 3 Remot e Fi r e Al ar m Cont r ol Uni t
A cont r ol uni t , physi cal l y r emot e f r om t he f i r e al ar m cont r ol uni t , t hat r ecei ves i nput s f r om aut omat i c and manual f i r e al ar m devi ces; may suppl y power t o det ect i on devi ces and i nt er f ace devi ces; may pr ovi de t r ansf er of power t o t he not i f i cat i on appl i ances; may pr ovi de t r ansf er of condi t i on t o r el ays or devi ces connect ed t o t he cont r ol uni t ; and r epor t s t o and r ecei ves s i gnal s f r om t he f i r e al ar m and mass not i f i cat i on cont r ol uni t .
1. 4. 4 Ter mi nal Cabi net
A st eel cabi net wi t h l ocki ng, hi nge- mount ed door wher e t er mi nal st r i ps ar e secur el y mount ed i nsi de t he cabi net .
1. 4. 5 Cont r ol Modul e and Rel ay Modul e
Ter ms ut i l i zed t o descr i be emer gency cont r ol f unct i on i nt er f ace devi ces as def i ned by NFPA 72.
1. 4. 6 Desi gnat ed Fi r e Pr ot ect i on Engi neer ( DFPE)
The DoD f i r e pr ot ect i on engi neer t hat over sees t hat Ar ea of Responsi bi l i t y f or t hat pr oj ect . Thi s i s somet i mes r ef er r ed t o as t he " cogni zant " f i r e pr ot ect i on engi neer . I nt er pr et r ef er ence t o " aut hor i t y havi ng
SECTI ON 28 31 70 Page 11 j ur i sdi ct i on" and/ or AHJ i n r ef er enced st andar ds t o mean t he Desi gnat ed Fi r e Pr ot ect i on Engi neer ( DFPE) . The DFPE may be r esponsi bl e f or r evi ew of t he cont r act or submi t t al s havi ng a " G" desi gnat i on, and f or wi t nessi ng f i nal i nspect i on and t est i ng.
1. 4. 7 Qual i f i ed Fi r e Pr ot ect i on Engi neer ( QFPE)
A QFPE i s an i ndi v i dual who i s a l i censed pr of essi onal engi neer ( P. E. ) , who has passed t he f i r e pr ot ect i on engi neer i ng wr i t t en exami nat i on admi ni st er ed by t he Nat i onal Counci l of Exami ner s f or Engi neer i ng and Sur veyi ng ( NCEES) and has r el evant f i r e pr ot ect i on engi neer i ng exper i ence.
1. 5 SUBMI TTALS
NOTE: Revi ew submi t t al descr i pt i on ( SD) def i ni t i ons i n Sect i on 01 33 00 SUBMI TTAL PROCEDURES ( or t he par t i cul ar speci f i cat i on sect i on f or submi t t al pr ocedur es i n t hi s pr oj ect ) and edi t t he f ol l owi ng l i s t , and cor r espondi ng submi t t al i t ems i n t he t ext , t o r ef l ect onl y t he submi t t al s r equi r ed f or t he pr oj ect . The Gui de Speci f i cat i on t echni cal edi t or s have cl assi f i ed t hose i t ems t hat r equi r e Gover nment appr oval , due t o t hei r compl exi t y or cr i t i cal i t y, wi t h a " G" . Gener al l y, ot her submi t t al i t ems can be r evi ewed by t he Cont r act or ' s Qual i t y Cont r ol Syst em. Onl y add a " G" t o an i t em, i f t he submi t t al i s suf f i c i ent l y i mpor t ant or compl ex i n cont ext of t he pr oj ect .
For Ar my pr oj ect s, f i l l i n t he empt y br acket s f ol l owi ng t he " G" c l assi f i cat i on, wi t h a code of up t o t hr ee char act er s t o i ndi cat e t he appr ovi ng aut hor i t y. Codes f or Ar my pr oj ect s usi ng t he Resi dent Management Syst em ( RMS) ar e: " AE" f or Ar chi t ect - Engi neer ; " DO" f or Di st r i ct Of f i ce ( Engi neer i ng Di v i s i on or ot her or gani zat i on i n t he Di st r i ct Of f i ce) ; " AO" f or Ar ea Of f i ce; " RO" f or Resi dent Of f i ce; and " PO" f or Pr oj ect Of f i ce. Codes f ol l owi ng t he " G" t ypi cal l y ar e not used f or Navy and Ai r For ce pr oj ect s.
The " S" c l assi f i cat i on i ndi cat es submi t t al s r equi r ed as pr oof of compl i ance f or sust ai nabi l i t y Gui di ng Pr i nci pl es Val i dat i on or Thi r d Par t y Cer t i f i cat i on and as descr i bed i n Sect i on 01 33 00 SUBMI TTAL
PROCEDURES.
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" or " S" c l assi f i cat i on. Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e f or i nf or mat i on onl y. When used, a code f ol l owi ng t he " G" c l assi f i cat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment .
Shop dr awi ngs ( SD- 02) , pr oduct dat a ( SD- 03) and cal cul at i ons ( SD- 05) must be pr epar ed by t he f i r e al ar m desi gner and combi ned and submi t t ed as one compl et e package. The QFPE must r evi ew t he SD- 02/ SD- 03/ SD- 05 submi t t al
SECTI ON 28 31 70 Page 12 package f or compl et eness and compl i ance wi t h t he Cont r act pr ovi s i ons pr i or t o submi ssi on t o t he Gover nment . The QFPE must pr ovi de a Let t er of Conf i r mat i on t hat t hey have r evi ewed t he submi t t al package f or compl i ance wi t h t he cont r act pr ovi s i ons. Thi s l et t er must i ncl ude t hei r r egi st er ed pr of essi onal engi neer st amp and si gnat ur e. Par t i al submi t t al s and submi t t al s not r evi ewed by t he QFPE wi l l be r et ur ned by t he Gover nment di sappr oved wi t hout r evi ew.
Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL
PROCEDURES:
SD- 01 Pr econst r uct i on Submi t t al s
Qual i f i ed Fi r e Pr ot ect i on Engi neer ( QFPE) ; G, [ _____]
Fi r e al ar m syst em desi gner ; G, [ _____]
Super vi sor ; G, [ _____]
Techni c i an; G, [ _____]
I nst al l er ; G, [ _____]
Test Techni c i an; G, [ _____]
Fi r e Al ar m Syst em Si t e- Speci f i c Sof t war e Acknowl edgement ; G, SD- 02 Shop Dr awi ngs
Namepl at es; G, [ _____]
I nst r uct i ons; G, [ _____]
Wi r i ng Di agr ams; G, [ _____]
Syst em Layout ; G, [ _____]
Not i f i cat i on Appl i ances; G, [ _____]
I ni t i at i ng devi ces; G, [ _____]
Bat t er y Power ; G, [ _____]
Vol t age Dr op Cal cul at i ons; G, [ _____]
SD- 03 Pr oduct Dat a
Fi r e Al ar m Cont r ol Uni t ( FACU) ; G, [ _____]
[ Vi deo Di spl ay Uni t ( VDU) ; G, [ _____] ]
LCD Annunci at or ; G, [ _____]
Manual St at i ons; G, [ _____]
Smoke Det ect or s; G, [ _____]
Duct Smoke Det ect or s; G, [ _____]
SECTI ON 28 31 70 Page 13
[ Pr oj ect ed Beam Smoke Det ect or ; G, [ _____] ]
[ Ai r sampl i ng smoke det ect or s; G, [ _____] ]
Heat Det ect or s; G, [ _____]
[ Fl ame Det ect or s; G, [ _____] [ Mul t i - Cr i t er i a Det ect or s; G, [ _____] ]
Car bon monoxi de det ect or ; G, [ _____]
Addr essabl e I nt er f ace Devi ces; G, [ _____]
Addr essabl e Cont r ol Modul es; G, [ _____]
I sol at i on Modul es; G, [ _____]
Not i f i cat i on Appl i ances; G, [ _____]
Bat t er i es; G, [ _____]
Bat t er y Char ger s; G, [ _____]
[ Suppl ement al Not i f i cat i on Appl i ance Ci r cui t Panel s; G, [ _____] ]
[ Auxi l i ar y Power Suppl y Panel s; G, [ _____] ]
Sur ge Pr ot ect i ve Devi ces; G, [ _____]
Al ar m Wi r i ng; G, [ _____]
[ Back Boxes and Condui t ; G, [ _____] ]
[ Cei l i ng Br i dges f or Cei l i ng- Mount ed Appl i ances; G, [ _____] ]
Ter mi nal Cabi net s; G, [ _____]
Di gi t al Al ar m Communi cat or Tr ansmi t t er ( DACT) ; G, [ _____]
[ Aut omat i c Fi r e Al ar m Tr ansmi t t er s ( i ncl udi ng housi ng) ; G, [ _____] ]
[ Radi o Tr ansmi t t er and I nt er f ace Panel s; G, [ _____] ]
El ect r omagnet i c Door Hol der s; G, [ _____]
Envi r onment al Encl osur es or Guar ds; G, [ _____]
[ Fi r ef i ght er Tel ephone; G, [ _____] ]
[ Pr i nt er ; G, [ _____] ]
Document St or age Cabi net ; G, [ _____]
SD- 05 Desi gn Dat a
[ Ai r Sampl i ng Smoke Det ect i on Syst em Cal cul at i ons; G, [ _____]
SECTI ON 28 31 70 Page 14
SD- 06 Test Repor t s
Test Pr ocedur es; G, [ _____]
SD- 07 Cer t i f i cat es
Ver i f i cat i on of Compl i ant I nst al l at i on; G, [ _____]
Request f or Gover nment Fi nal Test ; G, [ _____]
SD- 10 Oper at i on and Mai nt enance Dat a
Oper at i on and Mai nt enance ( O&M) I nst r uct i ons; G, [ _____]
I nst r uct i on of Gover nment Empl oyees; G, [ _____]
SD- 11 Cl oseout Submi t t al s
As- Bui l t Dr awi ngs
Spar e Par t s
1. 6 SYSTEM OPERATI ON
NOTE: Ci r cui t wi r i ng must be Cl ass " B" unl ess Cl ass " A" or " X" i s r equi r ed by t he l ocal i nst al l at i on and as per mi t t ed by NFPA 72 ( SLC: " A" , " B" , or " X" ; I DC and NAC: " A" or " B" ) .
Ci r cui t s and pat hways must have sur vi vabi l i t y l evel s as def i ned by NFPA 72.
Fi r e al ar m syst em component s r equi r i ng power , except f or t he FACU( s) power suppl y, must oper at e on 24 vol t s DC unl ess not ed ot her wi se i n t hi s sect i on.
The i nt er i or f i r e al ar m syst em must be a compl et e, super vi sed, noncoded, anal og/ addr essabl e f i r e al ar m syst em conf or mi ng t o NFPA 72, and UL 864.
Syst ems meet i ng UL 2017 onl y ar e not accept abl e. The syst em must be act i vat ed i nt o t he al ar m mode by act uat i on of an al ar m i ni t i at i ng devi ce.
The syst em must r emai n i n t he al ar m mode unt i l t he i ni t i at i ng devi ce i s r eset and t he cont r ol uni t i s r eset and r est or ed t o nor mal .
1. 6. 1 Al ar m I ni t i at i ng Devi ces and Not i f i cat i on Appl i ances ( Vi sual , Audi bl e)
a. Connect al ar m i ni t i at i ng devi ces t o i ni t i at i ng devi ce c i r cui t s ( I DC) [ Cl ass " A" ] [ Cl ass " B" ] , or t o s i gnal i ng l i ne c i r cui t s ( SLC) Cl ass [ " A" ] [ " B" ] [ " X" ] and i nst al l ed i n accor dance wi t h NFPA 72.
b. Connect not i f i cat i on appl i ances t o not i f i cat i on appl i ance ci r cui t s ( NAC) [ Cl ass " A] [ Cl ass " B" ] .
1. 6. 2 Funct i ons and Oper at i ng Feat ur es
The syst em must pr ovi de t he f ol l owi ng f unct i ons and oper at i ng f eat ur es:
SECTI ON 28 31 70 Page 15
a. Power , annunci at i on, super vi s i on, and cont r ol f or t he syst em.
Addr essabl e syst ems must be mi cr ocomput er ( mi cr opr ocessor or mi cr ocont r ol l er ) based wi t h a mi ni mum wor d si ze of ei ght bi t s wi t h suf f i c i ent memor y t o per f or m as speci f i ed.
b. Vi sual al ar m not i f i cat i on appl i ances must be synchr oni zed as r equi r ed by NFPA 72.
c. El ect r i cal super vi s i on of t he pr i mar y power ( AC) suppl y, pr esence of t he bat t er y, bat t er y vol t age, and pl acement of syst em modul es wi t hi n t he cont r ol uni t .
d. An audi bl e and vi sual t r oubl e s i gnal t o act i vat e upon a s i ngl e br eak or open condi t i on, or gr ound f aul t [ ( or shor t c i r cui t f or Cl ass " X" ) ] . The t r oubl e s i gnal must al so oper at e upon l oss of pr i mar y power ( AC) suppl y, absence of a bat t er y suppl y, l ow bat t er y vol t age, or r emoval of al ar m or super vi sor y cont r ol uni t modul es. Af t er t he syst em r et ur ns t o nor mal oper at i ng condi t i ons, t he t r oubl e s i gnal must agai n sound unt i l t he t r oubl e i s acknowl edged. A smoke det ect or i n t he pr ocess of bei ng ver i f i ed f or t he act ual pr esence of smoke must not i ni t i at e a t r oubl e condi t i on.
e. A t r oubl e s i gnal s i l ence f eat ur e t hat must s i l ence t he audi bl e t r oubl e s i gnal , wi t hout af f ect i ng t he v i sual i ndi cat or .
f . Pr ogr am capabi l i t y v i a swi t ches i n a l ocked por t i on of t he FACU t o bypass t he aut omat i c not i f i cat i on appl i ance ci r cui t s, [ f i r e r epor t i ng syst em] [ ai r handl er shut down] [ smoke cont r ol oper at i on] [ el evat or r ecal l ] [ door r el ease] [ door unl ocki ng] f eat ur es. Oper at i on of t hi s pr ogr ammed act i on must i ndi cat e on t he FACU di spl ay[ and pr i nt er out put ] as a super vi sor y or t r oubl e condi t i on. [ Not i f i cat i on appl i ance bypass must be sel ect abl e by f l oor . ]
g. Al ar m f unct i ons must over r i de t r oubl e or super vi sor y f unct i ons.
Super vi sor y f unct i ons must over r i de t r oubl e f unct i ons.
h. The syst em must be capabl e of bei ng pr ogr ammed f r om t he cont r ol uni t keyboar d. Pr ogr ammed i nf or mat i on must be st or ed i n non- vol at i l e memor y.
i . The syst em must be capabl e of oper at i ng, super vi s i ng, and/ or moni t or i ng non- addr essabl e al ar m and super vi sor y devi ces.
j . Ther e must be no l i mi t , ot her t han maxi mum syst em capaci t y, as t o t he number of addr essabl e devi ces t hat may be i n al ar m si mul t aneousl y.
k. Wher e t he f i r e al ar m syst em i s r esponsi bl e f or i ni t i at i ng an act i on i n anot her emer gency cont r ol devi ce or syst em, such as [ HVAC, ] [ at r i um exhaust , ] [ smoke cont r ol , ] [ el evat or r ecal l , ] [ r el easi ng ser vi ce, ] t he addr essabl e f i r e al ar m r el ay must be l ocat ed i n t he v i c i ni t y of t he emer gency cont r ol devi ce.
l . An al ar m si gnal must aut omat i cal l y i ni t i at e t he f ol l owi ng f unct i ons:
( 1) Tr ansmi ssi on of an al ar m si gnal t o [ t he f i r e depar t ment ] [ a r emot e super vi s i ng st at i on] .
( 2) Vi sual i ndi cat i on of t he devi ce oper at ed on t he FACU, [ Vi deo
SECTI ON 28 31 70 Page 16
Di spl ay uni t ( VDU) , ] [ and on t he [ gr aphi c ] [ r emot e ] annunci at or ] . [ I ndi cat i on on t he gr aphi c annunci at or must be by f l oor , zone or c i r cui t , and t ype of devi ce. ]
[ ( 3) Recor d t he event on t he syst em pr i nt er . ]
( 4) Act uat i on of al ar m not i f i cat i on appl i ances.
( 5) Recor di ng of t he event el ect r oni cal l y i n t he hi st or y l og of t he
FACU.
[ ( 6) Rel ease of door s hel d open by el ect r omagnet i c devi ces. ]
[ ( 7) Oper at i on of t he [ smoke cont r ol syst em] [ at r i um exhaust syst em] . ]
[ ( 8) Rel ease of power t o el ect r i c l ocks ( del ayed egr ess l ocks) on door s t hat ar e par t of t he means of egr ess. ]
[ ( 9) El evat or r ecal l as descr i bed i n t hi s sect i on. ]
NOTE: Use t hi s par agr aph onl y wher e a det ect or or det ect i on syst em i s t o r el ease a speci al f i r e ext i ngui shi ng syst em.
[ ( 10) Oper at i on of [ _____] must r el ease t he [ _____] f i r e ext i ngui shi ng syst em af t er a [ _____] second t i me del ay. ]
[ ( 11) Oper at i on of a spr i nkl er wat er f l ow swi t ch ser vi ng an el evat or machi ner y r oom or el evat or shaf t must oper at e shunt t r i p c i r cui t br eaker ( s) t o shut down power t o t he el evat or s i n accor dance wi t h
ASME A17. 1/ CSA B44. ]
[ ( 12) Oper at i on of an i nt er f ace t hat oper at es v i br at i ng pager s wor n by hear i ng- i mpai r ed occupant s. ]
m. A super vi sor y s i gnal must aut omat i cal l y i ni t i at e t he f ol l owi ng f unct i ons:
( 1) Vi sual i ndi cat i on of t he devi ce oper at ed on t he FACU, [ Vi deo Di spl ay uni t ( VDU) , ] [ and on t he [ gr aphi c ] [ r emot e ] annunci at or ] . [ I ndi cat i on on t he gr aphi c annunci at or must be by f l oor , zone or c i r cui t , and t ype of devi ce. ]
[ ( 2) Recor d t he event on t he syst em pr i nt er . ]
( 3) Tr ansmi ssi on of a super vi sor y s i gnal t o [ t he f i r e depar t ment ] [ a r emot e super vi s i ng st at i on] .
( 4) Oper at i on of a duct smoke det ect or must shut down t he appr opr i at e ai r handl er i n accor dance wi t h NFPA 90A i n addi t i on t o ot her r equi r ement s of t hi s par agr aph and as al l owed by NFPA 72.
( 5) Recor di ng of t he event el ect r oni cal l y i n t he hi st or y l og of t he
FACU.
n. A t r oubl e condi t i on must aut omat i cal l y i ni t i at e t he f ol l owi ng f unct i ons:
SECTI ON 28 31 70 Page 17
( 1) Vi sual i ndi cat i on of t he devi ce oper at ed on t he FACU, [ Vi deo Di spl ay uni t ( VDU) , ] [ and on t he [ gr aphi c ] [ r emot e ] annunci at or ] . [ I ndi cat i on on t he gr aphi c annunci at or must be by f l oor , zone or c i r cui t , and t ype of devi ce. ]
[ ( 2) Recor d t he event on t he syst em pr i nt er . ]
( 3) Tr ansmi ssi on of a t r oubl e s i gnal t o [ t he f i r e depar t ment ] [ a r emot e super vi s i ng st at i on] .
( 4) Recor di ng of t he event el ect r oni cal l y i n t he hi st or y l og of t he
FACU.
[ o. Act i vat i on of a car bon monoxi de al ar m i ni t i at i ng devi ce must aut omat i cal l y i ni t i at e t he f ol l owi ng f unct i ons:
( 1) Vi sual i ndi cat i on of t he devi ce oper at ed on t he , [ LCD, LED Di spl ay uni t ( VDU) , ] [ and on t he [ gr aphi c ] [ r emot e ] annunci at or ] . [ I ndi cat i on on t he gr aphi c annunci at or must be by f l oor and r oom number , devi ce addr ess, and devi ce t ype. ]
( 2) Tr ansmi ssi on of a car bon monoxi de al ar m si gnal t o [ t he f i r e depar t ment ] [ a r emot e super vi s i ng st at i on] .
( 3) Act i vat i on of al l s t r obes and t he car bon monoxi de al ar m si gnal t hr oughout t he bui l di ng.
( 4) Recor di ng of t he event el ect r oni cal l y i n t he hi st or y l og of t he
FACU. ]
p. Syst em cont r ol equi pment must be pr ogr ammed t o pr ovi de a 60- mi nut e t o 180- mi nut e del ay i n t r ansmi ssi on of t r oubl e s i gnal s r esul t i ng f r om pr i mar y power f ai l ur e.
[ 1. 6. 3 El evat or Recal l
NOTE: Del et e t hi s par agr aph i f no el evat or wor k i s i ncl uded i n t he pr oj ect .
Pr ovi de el evat or r ecal l i n accor dance wi t h ASME A17. 1/ CSA B44, Sect i on [
14 21 13 ELECTRI C TRACTI ON FREI GHT ELEVATORS] [ 14 21 23 ELECTRI C TRACTI ON
PASSENGER ELEVATORS] [ 14 24 13 HYDRAULI C FREI GHT ELEVATORS] [ 14 24 23
HYDRAULI C PASSENGER ELEVATORS] , and as speci f i ed her ei n. Act i vat i on of any smoke det ect or i n an el evat or shaf t , machi ne r oom, or l obby ( except at desi gnat ed r ecal l l evel ) must cause al l el evat or s associ at ed wi t h t hat shaf t , machi ne r oom, or l obby t o r et ur n nonst op t o t he desi gnat ed l evel .
Act i vat i on of a smoke det ect or i n t he l obby or machi ne r oom at t he desi gnat ed l evel must cause al l el evat or s associ at ed wi t h t hat l obby t o r et ur n nonst op t o t he assi gned al t er nat e l evel . Act i vat i on of a det ect or i n an el evat or shaf t , machi ne r oom, or l obby must al so cause i l l umi nat i on of el evat or cab war ni ng si gnal ( f i r e hat ) and compl et e oper at i on of f i r e al ar m syst em as speci f i ed i n par agr aph t i t l ed " Funct i ons and Oper at i ng Feat ur es" .
SECTI ON 28 31 70 Page 18
] 1. 7 TECHNI CAL DATA AND SI TE- SPECI FI C SOFTWARE
Techni cal dat a and si t e- speci f i c sof t war e ( meani ng t echni cal dat a t hat r el at es t o comput er sof t war e) t hat ar e speci f i cal l y i dent i f i ed i n t hi s pr oj ect , and may be r equi r ed i n ot her speci f i cat i ons, must be del i ver ed, st r i ct l y i n accor dance wi t h t he CONTRACT CLAUSES. The f i r e al ar m syst em manuf act ur er must submi t wr i t t en conf i r mat i on of t hi s cont r act pr ovi s i on as " Fi r e Al ar m Syst em Si t e- Speci f i c Sof t war e Acknowl edgement " . I dent i f y dat a del i ver ed by r ef er ence t o t he speci f i cat i on par agr aph agai nst whi ch i t i s f ur ni shed. Dat a t o be submi t t ed must i ncl ude compl et e syst em, equi pment , and sof t war e descr i pt i ons. Descr i pt i ons must show how t he equi pment wi l l oper at e as a syst em t o meet t he per f or mance r equi r ement s of t hi s cont r act . The si t e- speci f i c sof t war e dat a package must al so i ncl ude t he f ol l owi ng:
a. I t ems i dent i f i ed i n NFPA 72, t i t l ed " Si t e- Speci f i c Sof t war e" .
b. I dent i f i cat i on of pr ogr ammabl e por t i ons of t he syst em equi pment and capabi l i t i es.
c. Descr i pt i on of syst em r evi s i on and expansi on capabi l i t i es and met hods of i mpl ement at i on det ai l i ng bot h equi pment and sof t war e r equi r ement s.
d. Pr ovi s i on of oper at i onal sof t war e dat a on al l modes of pr ogr ammabl e por t i ons f or f i r e al ar m .
e. Descr i pt i on of Fi r e Al ar m Cont r ol Uni t equi pment oper at i on.
f . Descr i pt i on of auxi l i ar y and r emot e equi pment oper at i ons.
g. Li br ar y of appl i cat i on sof t war e.
h. Oper at i on and mai nt enance manual s.
[ 1. 8 EXI STI NG EQUI PMENT
NOTE: I f an addi t i on t o an exi st i ng f i r e al ar m syst em i s r equi r ed, t he cont r act dr awi ngs or t hi s sect i on must i ncl ude t he make, model number , and ot her per t i nent i nf or mat i on of exi st i ng component s t hat ar e t o oper at e wi t h t he new equi pment . Si nce new i nt er f aces wi l l have t o be compat i bl e wi t h t he exi st i ng syst em or t o t he cent r al f i r e al ar m r epor t i ng syst em, i t may be necessar y t o edi t maj or i t ems out of t hi s speci f i cat i on. I f a new FACU i s r equi r ed, i t has t o be compat i bl e wi t h t he exi st i ng cent r al f i r e al ar m r epor t i ng syst em. When an exi st i ng syst em i s t o be expanded, show t he f ol l owi ng i nf or mat i on on t he cont r act dr awi ngs:
1. Manuf act ur er and model of exi st i ng cont r ol uni t .
2. Number of exi st i ng i ni t i at i ng c i r cui t s ( zones) , not i f i cat i on appl i ance ci r cui t s, and cont r ol c i r cui t s ser ved by t he cont r ol uni t .
3. Number of exi st i ng al ar m not i f i cat i on appl i ances on t he syst em.
SECTI ON 28 31 70 Page 19
4. Tot al cal cul at ed cur r ent dr aw of al l devi ces ser ved by each exi st i ng st andby bat t er y under bot h super vi sor y ( st andby) and al ar m condi t i ons, i ncl udi ng NAC/ ext ender cont r ol uni t s and subcont r ol uni t s.
5. Amper e- hour r at i ng and t ype of each exi st i ng bat t er y.
a. Equi pment and devi ces must be compat i bl e and oper abl e wi t h t he exi st i ng f i r e al ar mmass not i f i cat i on syst em and must not i mpai r r el i abi l i t y or oper at i onal f unct i ons of exi st i ng super vi s i ng st at i on f i r e al ar m syst em. [ The pr opr i et ar y t ype super vi s i ng st at i on ( PSS) i s l ocat ed [ i n Bui l di ng [ _____] . ] [ _____] . ] [ The super vi s i ng equi pment i s exi st i ng and consi st s of t he f ol l owi ng br ands and model s: [ super vi s i ng st at i on cont r ol uni t [ _____] . ] [ _____] [ s i gnal r epor t i ng component s [ _____] ] , [ annunci at or [ _____] ] [ _____] ] .
[ b. Equi pment and devi ces must be compat i bl e and oper abl e wi t h t he exi st i ng bui l di ng f i r e al ar m syst em. Equi pment must not i mpai r r el i abi l i t y or oper at i onal f unct i ons of t he exi st i ng syst em. The exi st i ng bui l di ng syst em cont r ol uni t i s [ _____] . ]
] 1. 9 QUALI TY ASSURANCE
1. 9. 1 Submi t t al Document s
1. 9. 1. 1 Pr econst r uct i on Submi t t al s
Wi t hi n 36 days of cont r act awar d but not l ess t han [ 14 days] [ _____] pr i or t o commenci ng any wor k on si t e, t he Cont r act or must submi t t he f ol l owi ng f or r evi ew and appr oval . SD- 02, SD- 03 and SD- 05 submi t t al s r ecei ved pr i or t o t he r evi ew and appr oval of t he qual i f i cat i ons of t he f i r e al ar m subcont r act or and QFPE must be r et ur ned di sappr oved wi t hout r evi ew. Al l r esul t ant del ays must be t he sol e r esponsi bi l i t y of t he Cont r act or .
1. 9. 1. 2 Shop Dr awi ngs
Shop dr awi ngs must not be smal l er t han [ I SO A1] [ ANSI D] [ t he Cont r act Dr awi ngs] . Dr awi ngs must compl y wi t h t he r equi r ement s of NFPA 72 and NFPA 170. Mi ni mum scal e f or f l oor pl ans must be 1/ 8" =1' .
1. 9. 1. 3 Namepl at es
Namepl at e i l l ust r at i ons and dat a t o obt ai n appr oval by t he Cont r act i ng Of f i cer bef or e i nst al l at i on.
1. 9. 1. 4 Wi r i ng Di agr ams
[ _____] copi es of poi nt - t o- poi nt wi r i ng di agr ams showi ng t he poi nt s of connect i on and t er mi nal s used f or el ect r i cal f i el d connect i ons i n t he syst em, i ncl udi ng i nt er connect i ons bet ween t he equi pment or syst ems t hat ar e super vi sed or cont r ol l ed by t he syst em. Di agr ams must show connect i ons f r om f i el d devi ces t o t he FACU and r emot e FACU, i ni t i at i ng c i r cui t s, swi t ches, r el ays and t er mi nal s, i ncl udi ng pat hway di agr ams bet ween t he cont r ol uni t and shar ed communi cat i ons equi pment wi t hi n t he pr ot ect ed pr emi ses. Poi nt - t o- poi nt wi r i ng di agr ams must be j ob speci f i c
SECTI ON 28 31 70 Page 20 and must not i ndi cat e connect i ons or c i r cui t s not bei ng ut i l i zed. Pr ovi de compl et e r i ser di agr ams i ndi cat i ng t he wi r i ng sequence of al l devi ces and t hei r connect i ons t o t he cont r ol equi pment . I ncl ude a col or - code schedul e f or t he wi r i ng.
1. 9. 1. 5 Syst em Layout
[ _____] copi es of pl an v i ew dr awi ng showi ng devi ce l ocat i ons, t er mi nal cabi net l ocat i ons, j unct i on boxes, ot her r el at ed equi pment , condui t r out i ng, condui t s i zes, wi r e count s, condui t f i l l cal cul at i ons, wi r e col or - codi ng, c i r cui t i dent i f i cat i on i n each condui t , and ci r cui t l ayout s f or al l f l oor s. I ndi cat e candel a r at i ng of each vi sual not i f i cat i on appl i ance. Cl ear l y i dent i f y t he l ocat i ons of i sol at i on modul es. I ndi cat e t he addr esses of al l devi ces, modul es, r el ays, and si mi l ar . I ndi cat e i f t he envi r onment f or t he FACU i s wi t hi n i t s envi r onment al l i s t i ng ( e. g.
t emper at ur e/ humi di t y) .
Pr ovi de a compl et e descr i pt i on of t he syst em oper at i on i n mat r i x f or mat s i mi l ar t o t he " Typi cal I nput / Out put Mat r i x" i ncl uded i n t he Annex of
NFPA 72.
[ For ai r sampl i ng smoke det ect i on syst ems, pr ovi de f l oor pl an l ayout s i ndi cat i ng l ocat i on of f i r e al ar m cont r ol uni t , ai r sampl i ng pi pi ng ( l engt hs of pi pe) and sampl i ng por t s ( s i zes and l ocat i ons) . Fl oor pl an must al so i ndi cat e geogr aphi c moni t or zone boundar i es, l ocat i on of di spl ay cont r ol uni t , bar l evel annunci at i on panel s i f separ at e, and al l ot her associ at ed equi pment t hat i s r equi r ed t o pr ovi de a compl et e oper at i onal syst em. ]
1. 9. 1. 6 Not i f i cat i on Appl i ances
Cal cul at i ons and suppor t i ng dat a on each ci r cui t t o i ndi cat e t hat t her e i s at l east 25 per cent spar e capaci t y f or not i f i cat i on appl i ances. Annot at e dat a f or each ci r cui t on t he dr awi ngs.
1. 9. 1. 7 I ni t i at i ng Devi ces
Cal cul at i ons and suppor t i ng dat a on each ci r cui t t o i ndi cat e t hat t her e i s at l east [ 25] [ _____] per cent spar e capaci t y f or i ni t i at i ng devi ces.
Annot at e dat a f or each ci r cui t on t he dr awi ngs.
1. 9. 1. 8 Bat t er y Power
Cal cul at i ons and suppor t i ng dat a as r equi r ed i n par agr aph Bat t er y Power Cal cul at i ons f or al ar m, al er t , and super vi sor y power r equi r ement s.
Cal cul at i ons i ncl udi ng amper e- hour r equi r ement s f or each syst em component and each cont r ol uni t component , and t he bat t er y r echar gi ng per i od, must be i ncl uded on t he dr awi ngs.
1. 9. 1. 9 Vol t age Dr op Cal cul at i ons
Vol t age dr op cal cul at i ons f or each not i f i cat i on c i r cui t i ndi cat i ng t hat suf f i c i ent vol t age i s avai l abl e f or pr oper oper at i on of t he syst em and al l component s, at a mi ni mum r at ed vol t age of t he syst em oper at i ng on bat t er i es. I ncl ude t he cal cul at i ons on t he syst em l ayout dr awi ngs.
1. 9. 1. 10 Pr oduct Dat a
[ _____] copi es of annot at ed descr i pt i ve dat a t o show t he speci f i c model , SECTI ON 28 31 70 Page 21 t ype, and si ze of each i t em. Cat al og cut s must al so i ndi cat e t he NRTL l i s t i ng. The dat a must be hi ghl i ght ed t o show model , s i ze, and opt i ons t hat ar e i nt ended f or consi der at i on. Dat a must be adequat e t o demonst r at e compl i ance wi t h al l cont r act r equi r ement s. Pr oduct dat a f or al l equi pment must be combi ned i nt o a s i ngl e submi t t al .
Pr ovi de an equi pment l i s t i dent i f y i ng t he t ype, quant i t y, make, and model number of each pi ece of equi pment t o be pr ovi ded under t hi s submi t t al .
The equi pment l i s t must i ncl ude t he t ype, quant i t y, make and model of spar e equi pment . Types and quant i t i es of equi pment submi t t ed must coi nci de wi t h t he t ypes and quant i t i es of equi pment used i n t he bat t er y cal cul at i ons and t hose shown on t he shop dr awi ngs.
[ 1. 9. 1. 11 Ai r Sampl i ng Smoke Det ect i on Syst em Cal cul at i ons
Submi t ai r…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .