Attachment 7-Haz Mat Portable Storage Container-RFIs.pdf

PDF 37 KB Posted

Attached to
Hazardous Material Portable Storage Building
Solicitation number
FA441925Q0052
Issued by

About this file

This document is a Combined List of Pre-Bid Request for Information (RFI) for a Haz Mat Portable Storage Container dated 17 Sept 2025. The RFI seeks clarification on multiple aspects of a hazardous materials storage container, including specifications for a 170 sq. ft. minimum floor space unit. Key requirements include a self-contained dry chemical fire suppression system (preferably 2-hour fire rated), interior electrical rated for Class 1 Div 2 Hazardous Locations, and a center two-door configuration with a ramp for easy transfer of 55-gallon drums.

The project involves the 188th CE Squadron and 85th Fighter Group, with the squadron responsible for electrical connection and foundation. The proposed container should be approximately 22' x 8' and will require specific delivery logistics. The RFI highlights several open questions about precise container dimensions, fire rating, and exact specifications, indicating that potential bidders need to seek further clarification before submitting a proposal.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Haz Mat Portable Storage Container

Combined list of Pre-Bid RFI’s – 17 Sept 2025

1.Do you have additional information?

2.The SOW does not indicate a size, whether the building needs to be fire rated, 2HR or 4HR or just Insulated.

It does need to include a self-contained dry chemical fire suppression system. 2hr fire rated would be desired as it would cover a vast array of hazardous chemicals.

3.The SOW states 170 sq. Ft minium. Is that interior of exterior? Are there any size constraints as far as the size? For example, is a 22' X 8' unit acceptable?

That is requested amount of available floor space. A 22x8 unit would be acceptable.

4.Who will be required to run the electrical connection to the building and make the connection to the building?

188th CE Squadron

5.Who is responsible for providing the slab foundation?

188th CE Squadron/85th Fighter Group

6.Does the Interior Electrical need to be rated for Class 1 Div 2 Hazardous Locations?

Yes

7.What is the door configuration?

Center, Two door configuration with ramp leading up to make ease of transferring 55 gal drums in and out of facility.

8. Could you please confirm the size of the container being requested?

Unit that can provide a minimum of 170 sq ft of usable floor space.

9.For the delivery, do you prefer a tilt-bed or a flatbed truck?

Will specify once we know size, dimensions and weights of container.