The document is a Salient Characteristics specification sheet for Cummins mobile generators produced by Global Data Specialists, featuring two models: a 70kW and a 200kW generator. Both generators are U.S. EPA Tier IV Final certified diesel gensets with dual-speed engines capable of operating at 50 or 60 Hz, designed for standby and prime power applications. Key features include advanced electronic engine controls, integrated aftertreatment systems, high-pressure common rail fuel systems, and Cummins Direct Flow air filtration for improved efficiency and reduced emissions.
The generators are specifically configured for mission-critical military applications, with the 70kW model supporting Command Post activities for JB Charleston and the 200kW model supporting CE UCC activities. Both models include comprehensive features such as PowerCommand 3.3 control systems, Stamford alternators, sound-attenuated lockable enclosures, 24-hour fuel tanks, and DOT-approved trailers. The generators offer flexible voltage options (208-480V), paralleling capabilities, and come with a 3-year/3000-hour industrial mobile base warranty. Each model is mounted on a trailer with multiple hitch options and is designed for rapid deployment and relocation in military operational contexts.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_Clarifications.pdf | ||
| Brand name Justification and Approval Mobile Generators_Redacted.pdf | ||
| Amended_ RFQ Fill-in sheet Mobile Generators.pdf | ||
| Combined Synopsis Solicitation Mobile Generators.pdf | ||
| Attachment 3. Clauses_FA441825Q0009.pdf | ||
| Attachment 2. RFQ Fill-in sheet.pdf | ||
| Attachment 1. Generator Salient Characteristics.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SALIENT CHARACTERISTICS
GLOBAL DATA SPECIALISTS
Mobile 70KW generator
I. GENERAL OVERVIEW.
This Cummins® rental package is a fully integrated mobile power generation system, providing optimum performance, reliability, and versatility for Standby and Prime Power applications.
II. SPECIFICATIONS.
C70D2RE, Diesel Genset, 50/60Hz, 70kW, Standby-Rental U.S. EPA, Nonroad (Portable) Application C70D2RE, Diesel Genset, 50/60 Hz, 70kW, Standby-Rental Duty Rating - Prime Power (PRP) Emissions - Compliance EPA Tier 4 Final Certified Voltage 208 - 480 Variable Alternator - 60Hz, 208/416 - 240/480 Volt, 125/80C Standby/Prime Electric Brake Trailer Ball Hitch - 2 5/16 inch UN31A Certified Fuel Tank Generator Set Control - PowerCommand 3.3, Paralleling with MLD Distribution Panel - Rental Bus Bar Connection Coolant Heater Packaging - Cummins Power Generation Genset Warranty - Industrial Mobile Base, Prime 3 Years/3000 hours Cam Lock Distribution Panel - U.S. Rental Quick Fit Kit Auxiliary DEF Connections
III. APPLICATIONS:
Mission critical load consists of Command Post activities for JB Charleston in the event the Command Post needs to relocate.
IV. PHYSICAL DESIGN:
Cummins diesel engines
• U.S. Tier IV Final and EU SIIIa certified Cummins QSB5-G11 engines which meet emissions limits without the use of a diesel particulate filter (DPF)
• Dual speed engine for operation at 50 or 60 Hz
• Advanced electronic engine controls with integrated aftertreatment system provide superior fuel efficiency while reducing emissions
• High-pressure common rail fuel system reduces engine noise and smoke
• Cummins Direct Flow™ air filtration offering improved air management, longer service life, and easier serviceability
• 2-stage fuel filtration with optimum particle and water separation Control features
• The most advanced, reliable and capable generator set control system on the market today
• Controls provide precise frequency and voltage regulation, alarm and status message display in one easy to operate customer interface Stamford alternators
• 12-lead reconnectable alternators fitted with voltage selection switch
• Permanent magnet excitation for improved performance in non-linear load applications Engine controls
• Oil pressure and coolant temperature gauge
• Fuel level gauge, Diesel Exhaust Fluid (DEF) level gauge and battery voltage gauge
• Digital Hour meter (5-digit read out)
• Engine control module includes remote start capability Rental package enclosure
• Camlock & busbar distribution panel
• Sound attenuated, white powder coated lockable enclosure
• 24-hour fuel tank (75% prime) with leak detection sensor
• Single wall fuel tank with 110% fluid containment basin
• Transport Canada Tank
• Roof mounted, single point lift
• Cooling system rated for 122 °F (50 °C) at 100% standby ambient
• Complete engine fluid containment reservoir
• 4 position voltage selector switch (60Hz: 277/480 or 139/240 or 120/208 VAC 3 phase or 120/240 VAC 1 phase). Also first position 50Hz: 230/400 VAC 3 phase)
• 2 position voltage selector (60Hz: 277/480 or 347/600 VAC 3 phase).
• Shore power (15A/120V) – for coolant heater, battery charger, engine oil heater and battery warmer
• Conveniently located analog gauges and heated Human Machine Interface (HMI) display Rental package options
• Optional Auxiliary Fuel and DEF connections
• DOT approved electric brake trailer with heavy duty center mounted jack, ball or pintle hitch
• DOT approved hydraulic brake trailer with heavy duty center mounted jack, ball or pintle hitch power.cummins.com ©2019 Cummins Inc. PDA061E859 NAS-6311-EN (11/19)
Specification sheet
Rental Power 70 kW U.S EPA Tier IV Emissions
Description This Cummins Power Generation rental package is a fully integrated mobile power generation system, providing optimum performance, reliability, and versatility for standby and prime power applications.
Features Cummins diesel engines
• U.S. Tier IV Final and EU SIIIa certified Cummins
QSB5-G11 engines which meet emissions limits without the use of a diesel particulate filter (DPF)
• Dual speed engine for operation at 50 or 60 Hz
• Advanced electronic engine controls with integrated aftertreatment system provide superior fuel efficiency while reducing emissions
• High-pressure common rail fuel system reduces engine noise and smoke
• Cummins Direct Flow™ air filtration offering improved air management, longer service life, and easier serviceability
• 2-stage fuel filtration with optimum particle and water separation
Control features
• The most advanced, reliable and capable generator set control system on the market today
• Controls provide precise frequency and voltage regulation, alarm and status message display in one easy to operate customer interface
Stamford alternators
• 12-lead reconnectable alternators fitted with voltage selection switch
• Permanent magnet excitation for improved performance in non-linear load applications
Engine controls
• Oil pressure and coolant temperature gauge
• Fuel level gauge, Diesel Exhaust Fluid (DEF) level gauge and battery voltage gauge
• Digital Hour meter (5-digit read out)
• Engine control module includes remote start capability Rental package enclosure
• Camlock & busbar distribution panel
• Sound attenuated, white powder coated lockable enclosure
• 24-hour fuel tank (75% prime) with leak detection sensor
• Single wall fuel tank with 110% fluid containment basin
• Transport Canada Tank
• Roof mounted, single point lift
• Cooling system rated for 122 °F (50 °C) at 100% standby ambient
• Complete engine fluid containment reservoir
• 4 position voltage selector switch (60Hz: 277/480 or
139/240 or 120/208 VAC 3 phase or 120/240 VAC 1 phase). Also first position 50Hz: 230/400 VAC 3 phase)
• 2 position voltage selector (60Hz: 277/480 or 347/600 VAC 3 phase).
• Shore power (15A/120V) – for coolant heater, battery charger, engine oil heater and battery warmer
• Conveniently located analog gauges and heated Human Machine Interface (HMI) display
Rental package options
• Optional Auxiliary Fuel and DEF connections
• DOT approved electric brake trailer with heavy duty center mounted jack, ball or pintle hitch
• DOT approved hydraulic brake trailer with heavy duty center mounted jack, ball or pintle hitch
Standby Rating Prime Rating Model Voltages 60 Hz kW (kVA) 50 Hz kW (kVA) 60 Hz kW (kVA) 50 Hz kW (kVA) Sound Level
Full load at 7m Alternator
Model
C70D2RE
480-600
Switchable 70 (87) - 63 (78) - 67 dB(A) UCI274D
208/240/480 70 (87) 63 (78) 63 (78) 50 (63) 67 dB(A) UCI224G
Engine specifications Engine model QSB5-G11 Alternator data sheet UCI Tier rating Tier IV Design 4 cycle, In-Line, turbocharged and after-cooled Bore 107 mm (4.21 in.)
Stroke 124.0 mm (4.88 in.)
Displacement 4.5 liters (274.6 in3) Cylinder block Cast iron, In-Line 4 cylinder Battery capacity 2 x 760 cca Battery charging alternator 70 amps Starting voltage 24 volt, negative ground Fuel system Direct injection HPCR system Fuel filter Dual Spin on fuel filter with water separator Air cleaner type 2-stage, dry replaceable element with dust ejector Lube oil filter type(s) Single spin-on, full flow Standard cooling system 120 °F (49 °C) ambient radiator
Alternator specifications Design Brushless, 4 pole, drip proof revolving field Stator Double layer concentric, 2/3 winding pitch Rotor Singe bearing, flexible disc Insulation system Class H per NEMA MG1-1.65 Standard temperature rise 125/40 ºC prime Exciter type PMG (permanent magnet generator) Phase rotation A (U), B (V), C (W) Alternator cooling Direct drive centrifugal blower fan AC waveform total harmonic distortion < 1.5% no load, < 5% non-distorting balance linear load Telephone influence factor (TIF) < 50 per NEMA MG1-22.43 Telephone harmonic factor (THF) < 2%
Power capability specifications (Assume power factor = 0.80 for 3 phase amps)
Standby rating 240 V, 1 Phase
Amps 60Hz 208 V, 3 Phase
Amps 60Hz 480 V, 3 Phase
Amps 60Hz 240 V, 3 Phase
Amps 60Hz 400 V, 3 Phase
Amps 50Hz 600 V, 3 Phase
Amps 60Hz
C70D2RE 195 243 105 210 114 84
Electrical power panel specifications
Model voltage 120 V duplex receptacles 240 V twist
Load lug connection (stud diameter)
Load lug circuit breakers
120/480 Volt 2 - 20 Amp GFCI 3 - 50 Amp 1/2 inch 400 Amp 480-600 Volt 1/2 inch 150 Amp
PowerCommand 3.3 Control System
An integrated microprocessor based generator set control system providing voltage regulation, engine protection, alternator protection, operator interface and isochronous governing. Refer to document S-1570 for more detailed information on the control.
Simplified display for rental operators - simplified display tailored for rental equipment operations for ease of use.
Power management – Control function provides battery monitoring and testing features and smart starting control system.
Advanced control methodology – Three phase sensing, full wave rectified voltage regulation, with a PWM output for stable operation with all load types.
Regulation compliant – Prototype tested: UL, CSA and CE compliant.
Service - InPower™ PC-based service tool available for detailed diagnostics, setup, data logging and fault simulation.
Easily upgradeable – PowerCommand controls are designed with common control interfaces.
Reliable design – The control system is designed for reliable operation in harsh environment.
Operator panel features Operator/display functions
• 320 x 240 pixels graphic LED backlight LCD
• Auto, manual, start, stop, fault reset and lamp test/panel lamp switches
• Alpha-numeric display with pushbuttons
• LED lamps indicating genset running, remote start, not in auto, common shutdown, common warning, manual run mode, auto mode and stop
Alternator data
• Line-to-neutral and line-to-line AC volts
• 3-phase AC current
• Frequency
• kW, kVar, power factor kVA (three phase and total)
Engine data
• DC voltage
• Lube oil pressure
• Coolant temperature
• Comprehensive FAE data (where applicable) Other data
• Fault history
• Data logging and fault simulation (requires InPower)
Standard control functions Digital governing
• Integrated digital electronic isochronous governor
• Temperature dynamic governing Digital voltage regulation
• Integrated digital electronic voltage regulator
• 3-phase, 4-wire line-to-line sensing
• Configurable torque matching AmpSentry AC protection
• AmpSentry protective relay
• Over current and short circuit shutdown
• Over current warning
• Single and three phase fault regulation
• Over and under voltage shutdown
• Over and under frequency shutdown
• Overload warning with alarm contact
• Reverse power and reverse var shutdown
• Field overload shutdown Engine protection
• Battery voltage monitoring, protection and testing
• Overspeed shutdown
• Low oil pressure warning and shutdown
• High coolant temperature warning and shutdown
• Low coolant level warning or shutdown
• Low coolant temperature warning
• Fail to start (overcrank) shutdown
• Fail to crank shutdown
• Cranking lockout
• Sensor failure indication
• Full authority electronic engine protection Control functions
• Time delay start and cool down
• Real time clock for fault and event time stamping
• Cycle cranking
• Load shed
• Remote emergency stop
For more information contact your local Cummins distributor or visit power.cummins.com
©2019 Cummins Power Generation Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
PDA061E859 NAS-6311-EN (11/19)
Ratings definitions Standby:
Applicable for supplying emergency power for the duration of normal power interruption. No sustained overload capability is available for this rating. (Equivalent to Fuel Stop Power in accordance with ISO3046, AS2789, DIN6271 and BS5514).
Nominally rated.
Prime (unlimited running time):
Applicable for supplying power in lieu of commercially purchased power. Prime power is the maximum power available at a variable load for an unlimited number of hours. A 10% overload capability is available for limited time. (Equivalent to Prime Power in accordance with ISO8528 and Overload Power in accordance with ISO3046, AS2789, DIN6271, and BS5514).
Dimensions
Model Dim “A” mm (in.)
Dim “B” mm (in.)
Dim “C” mm (in.)
Weight w/o fuel kg (lbs.) **
Weight with fuel kg (lbs.) **
Fuel capacity liters (gal)*
C70D2RE 3063 (121) 1262 (50) 1953 (77) 2522 (5560) 2976 (6560) 495 (131)
With trailer 4798 (189) 2106 (83) 2444 (96) 3221 (7100) 3674 (8100) 495 (131)
* Onboard DEF capacity is sized for 24 hours of operation at 10 gallons ** Weights are CAD determined & within +/- 2%
Fuel consumption Standby Prime
60 Hz Ratings, kW (kVA) 70 (87) 63 (78) Hours of operation
Load ¼ ½ ¾ Full ¼ ½ ¾ Full 75% PRP US Gal/hr. 2.3 4.0 5.9 8.0 2.1 3.8 5.3 7.2 27 L/hr. 8.7 15.1 22.3 30.3 7.9 14.4 20.1 27.3 27
Note: DEF consumption less than 4% of fuel consumption
** Fuel consumption number are conservative pending final test.
Trailer information
Model Tire size Tire type Load range Number of tires per trailer
Lug pattern
C70D2RE 225/75-R15 Radial 2535 lbs. - each 4 8 hole
Certifications These generator sets are certified to following standards:
CAN/CSA STD C22.2 NO. 100
CAN/CSA STD C22.2 NO. 14
C
B
A
SALIENT CHARACTERISTICS
GLOBAL DATA SPECIALISTS
Mobile 200KW generator
I. GENERAL OVERVIEW.
mobile power generation system, providing optimum performance, reliability, and versatility for Standby and Prime Power applications.
II. SPECIFICATIONS.
C200D2RE, Diesel Genset, 50/60Hz, 200kW, Standby-Rental U.S. EPA, Nonroad (Portable) Application Duty Rating - Prime Power (PRP) Emissions - Compliance EPA Tier 4 Final Certified C200D2RE, Diesel Genset, 50/60 Hz, 200kW, Standby-Rental Voltage 208 - 480 Variable Alternator - 60Hz, 208/416 - 240/480 Volt, 125/80C Standby/Prime Electric Brake Trailer Ball Hitch - 2 5/16 inch UN31A Certified Fuel Tank Generator Set Control - PowerCommand 3.3, Paralleling with MLD Distribution Panel - Rental Bus Bar Connection Packaging - Cummins Power Generation Genset Warranty - Industrial Mobile Base, Prime 3 Years/3000 hours Battery Charger - Rental Cam Lock Distribution Panel - U.S. Rental Quick Fit Kit Auxiliary DEF Connections Paralleling Harness
III. APPLICATIONS:
Mission critical load consists of CE UCCactivities in the event the CE UCC needs to reloc
IV. PHYSICAL DESIGN:
Cummins diesel engines . U.S. Tier IV Final and EU SIIIa certified Cummins QSB7-G9 engines which meet emissions limits without the use of a Diesel Particulate Filter
(DPF)
. Dual speed engine for operation at 50 or 60 Hz . Advanced electronic engine controls with integrated after-treatment system provide superior fuel efficiency while reducing emissions . High-pressure common rail fuel system reduces engine noise and smoke . Cummins Direct Flow™ air filtration offering improved air management, longer service life, and easier serviceability . 2-stage fuel filtration with optimum particle and water separation Control features . The most advanced, reliable and capable generator set control system on the market today . PowerCommand® 3.3 with Masterless Load Demand (MLD) technology enables smartly adapting power to match varying load demand.
MLD capable generators allow sharing of information among paralleled generator sets.
. Controls provide precise frequency and voltage regulation, alarm and status message display in one easy to operate customer interface Engine controls . Oil pressure and coolant temp gauge . Fuel level gauge, Diesel Exhaust Fluid (DEF) level gauge and battery voltage gauge . Hour meter . Engine control module includes remote start capability Stamford alternators . 12-lead reconnectable alternators fitted with voltage selection switch . Permanent magnet excitation for improved performance in non-linear load applications Rental package enclosure . Camlock distribution panel . Sound attenuated, white powder coated lockable enclosure . 24-hour fuel tank (75% prime) with leak detection sensor . Single wall fuel tank with 110% fluid containment basin . Transport Canada Tank . Roof mounted, single point lift . Cooling system rated for 122 °F (50 °C) at 100% Standby ambient . Complete engine fluid containment reservoir . 4 position voltage selector switch (277/480 or 139/240 or 120/208 VAC 3 phase or 120/240 VAC 1 phase) . Shore power (15 A/120 V) – for coolant heater and battery charger . Conveniently located analog gauges and heated Human Machine Interface (HMI) display
Rental package options . Optional auxiliary fuel and DEF connections . DOT approved electric brake trailer with heavy duty center mounted jack, ball or pintle hitch . DOT approved hydraulic brake trailer with heavy duty center mounted jack, ball or pintle hitch
©2020 Cummins Inc. PDA057K702 NAS-5887-EN (5/20)
Specification sheet
Rental Power 200 kW U.S. EPA Tier IV emissions
Description mobile power generation system, providing optimum performance, reliability, and versatility for Standby and Prime Power applications.
Engine controls
Oil pressure and coolant temp gauge
Fuel level gauge, Diesel Exhaust Fluid (DEF) level gauge and battery voltage gauge
Hour meter
Engine control module includes remote start capability Stamford alternators
12-lead reconnectable alternators fitted with voltage selection switch
Permanent magnet excitation for improved performance in non-linear load applications
Rental package enclosure
Camlock distribution panel
Sound attenuated, white powder coated lockable enclosure
24-hour fuel tank (75% prime) with leak detection sensor
Single wall fuel tank with 110% fluid containment basin
Transport Canada Tank
Roof mounted, single point lift
Cooling system rated for 122 °F (50 °C) at 100% Standby ambient
Complete engine fluid containment reservoir
4 position voltage selector switch (277/480 or 139/240 or 120/208 VAC 3 phase or 120/240 VAC 1 phase)
Shore power (15 A/120 V) – for coolant heater and battery charger
Conveniently located analog gauges and heated Human Machine Interface (HMI) display
Rental package options
Optional auxiliary fuel and DEF connections
DOT approved electric brake trailer with heavy duty center mounted jack, ball or pintle hitch
DOT approved hydraulic brake trailer with heavy duty center mounted jack, ball or pintle hitch
Features
Cummins diesel engines
U.S. Tier IV Final and EU SIIIa certified Cummins QSB7-G9 engines which meet emissions limits without the use of a Diesel Particulate Filter
(DPF)
Dual speed engine for operation at 50 or 60 Hz
Advanced electronic engine controls with integrated after-treatment system provide superior fuel efficiency while reducing emissions
High-pressure common rail fuel system reduces engine noise and smoke
Cummins Direct Flow™ air filtration offering improved air management, longer service life, and easier serviceability
2-stage fuel filtration with optimum particle and water separation
Control features
The most advanced, reliable and capable generator set control system on the market today
PowerCommand® 3.3 with Masterless Load Demand (MLD) technology enables smartly adapting power to match varying load demand.
MLD capable generators allow sharing of information among paralleled generator sets.
Controls provide precise frequency and voltage regulation, alarm and status message display in one easy to operate customer interface
Standby rating Prime rating
Sound level full load @ 7m
Model Voltages (V)
60 Hz kW (kVA)
50 Hz kW (kVA)
60 Hz kW (kVA)
50 Hz kW (kVA) Alternator model
C200D2RE 208/240/480 200 (250) 172 (215) 180 (225) 156 (195) 73 dBA UCDI274J
Engine specifications
Engine model QSB7-G9
Alternator data sheet UCDI274J (208/240/480)
Tier rating Tier IV
Design 4 cycle, in-line, turbocharged and after-cooled
Bore 107.0 mm (4.21 in.)
Stroke 124.0 mm (4.88 in.)
Displacement 6.69 L (408 in3)
Cylinder block Cast iron, In-line 6 cylinder
Battery capacity 2 x 760 cca
Battery charging alternator 70 Amps
Starting voltage 24 Volt, negative ground
Fuel system Direct injection HPCR system
Fuel filter Dual Spin on fuel filter with water separator
Air cleaner type 2-stage, dry replaceable element with dust ejector
Lube oil filter type(s) Single spin-on, full flow
Standard cooling system 122 °F (50 °C) ambient radiator
Alternator specifications
Design Brushless, 4 pole, drip-proof revolving field
Stator Double layer concentric, 2/3 winding pitch
Rotor Singe bearing, flexible disc
Insulation system Class H per NEMA MG1-1.65 (208/240/480 VAC)
Standard temperature rise 125/40 ºC prime (208/480 VAC)
Exciter type PMG (Permanent Magnet Generator)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion < 1.5% no load, < 5% non-distorting balance linear load
Telephone Influence Factor (TIF) < 50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) < 2%
Power capability specifications (Assume power factor = 0.80 for 3 phase Amps) Standby rating
240 V, 1 phase
Amps 60 Hz 208 V, 3 phase
Amps 60 Hz 480 V, 3 phase
Amps 60 Hz 240 V, 3 phase
Amps 60 Hz 400 V, 3 phase
Amps 50 Hz
C200D2RE 558 694 301 601A 310
Electrical power panel specifications
Model voltage 120 V duplex receptacles 240 V twist
Load lug connection (stud diameter)
Load lug circuit breakers
120/480 2 - 20 Amps GFCI 3 - 50 Amps 1/2 inch 800 Amps
PowerCommand 3.3 Control System
An integrated microprocessor based generator set control system providing voltage regulation, engine protection, alternator protection, operator interface and isochronous governing. Refer to document S-1570 for more detailed information on the control.
Simplified display for rental operators – simplified display tailored for rental equipment operations for ease of use.
Masterless Load Demand (MLD) – The controller is capable of smartly managing power from paralleled generators to match varying load patterns.
Power management – Control function provides battery monitoring and testing features and smart starting control system.
Advanced control methodology – Three phase sensing, full wave rectified voltage regulation, with a PWM output for stable operation with all load types.
Regulation compliant – Prototype tested: UL, CSA and CE compliant.
Service – InPower™ PC-based service tool available for detailed diagnostics, setup, data logging and fault simulation.
Easily upgradeable – PowerCommand controls are designed with common control interfaces.
Reliable design – The control system is designed for reliable operation in harsh environment.
Operator panel features
Operator/display functions
Displays paralleling breaker status
Provides direct control of the paralleling breaker
320 x 240 pixels graphic LED backlight LCD
Auto, manual, start, stop, fault reset and lamp test/panel lamp switches
Alpha-numeric display with pushbuttons
Heated HMI
LED lamps indicating genset running, remote start, not in auto, common shutdown, common warning, manual run mode, auto mode and stop
Paralleling control functions
First Start Sensor System selects first genset to close to bus
Phase Lock Loop Synchronizer with voltage matching
Sync check relay
Isochronous kW and kVar load sharing
Enhanced safety features for paralleling generators
Alternator data
Line-to-Neutral and Line-to-Line AC volts
3-phase AC current
Frequency kW, kVar, power factor kVA (three phase and total)
Engine data
DC voltage
Lube oil pressure
Coolant temperature
Other data
Fault history
Data logging and fault simulation (requires InPower)
Standard control functions
Digital governing
Integrated digital electronic isochronous governor
Temperature dynamic governing
Digital voltage regulation
Integrated digital electronic voltage regulator
3-phase, 4-wire Line-to-Line sensing
Configurable torque matching
AmpSentry AC protection
AmpSentry protective relay
Over current and short circuit shutdown
Over current warning
Single and three phase fault regulation
Over and under voltage shutdown
Over and under frequency shutdown
Overload warning with alarm contact
Reverse power and reverse Var shutdown
Field overload shutdown
Engine protection
Battery voltage monitoring, protection and testing
Overspeed shutdown
Low oil pressure warning and shutdown
High coolant temperature warning and shutdown
Low coolant level warning or shutdown
Low coolant temperature warning
Fail to start (overcrank) shutdown
Fail to crank shutdown
Cranking lockout
Sensor failure indication
Full authority electronic engine protection
Control functions
Time delay start and cool down
Real time clock for fault and event time stamping
Cycle cranking
Load shed
Remote emergency stop
For more information contact your local Cummins distributor or visit power.cummins.com
©2020 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
NAS-5887-EN (5/20)
Ratings definitions Standby:
Applicable for supplying emergency power for the duration of normal power interruption. No sustained overload capability is available for this rating.
(Equivalent to Fuel Stop Power in accordance with ISO3046, AS2789, DIN6271 and BS5514). Nominally rated.
Prime (unlimited running time):
Applicable for supplying power in lieu of commercially purchased power. Prime Power is the maximum power available at a variable load for an unlimited number of hours. A 10% overload capability is available for limited time. (Equivalent to Prime Power in accordance with ISO8528 and Overload Power in accordance with ISO3046, AS2789, DIN6271, and
BS5514).
Dimensions
Model Dim ‘A mm (Inches) Dim ‘B’ mm (inches) Dim ‘C’
Mm (inches)
Set weight dry* kg (lbs)
Set weight wet*
Kg (lbs)
Fuel capacity litres (gal)
C200D2RE 3700 (146) 1450 (57) 1700 (67) 3220 (7100) 4000 (8820) 965 (255)
With trailer 5740 (226) 2140 (84) 2309 (91) 3950 (8710) 4730 (10430) 965 (255)
* Onboard DEF capacity is sized for 24 hours of operation at 15 gallons
Fuel consumption
Standby Prime
60 Hz Ratings, kW (kVA) 200 (250) 180 (225) Hours of operation
Load ¼ ½ ¾ Full ¼ ½ ¾ Full 75% Load
US Gal/hr 5.0 8.1 11.3 14.9 4.8 7.7 10.6 13.7 24
L/hr 18.9 30.7 42.8 56.4 8.2 29.1 40.1 51.9 24
Note: DEF consumption less than 4% of fuel consumption.
Trailer information
Model Tire size Tire type Load range Number of tires per trailer Lug pattern
C200D2RE ST235/85R16 Radial 2755 lbs – each 4 8 hole
Certifications These generator sets are certified to following standards:
CAN/CSA STD C22.2 NO. 100
CAN/CSA STD C22.2 NO. 14
| Mobile 30KW generator - SALIENT CHARACTERISTICS |
| 30RMP-1060A_NAS-6585 |
| Mobile 70KW generator - SALIENT CHARACTERISTICS |
| C70D2RE_NAS-6311-EN |
| Mobile 100KW generator - SALIENT CHARACTERISTICS |
| C100D2RE_NAS-6299-EN_2 |
| Mobile 200KW generator - SALIENT CHARACTERISTICS |
| C200D2RE_NAS-5887-EN_0 |