FP Sheets_ JBC B570 Revised RTA Drawings.pdf
PDF 2 MB Posted
- Attached to
- Repair Maintenance Facility – B570 Federal contract opportunity
- Solicitation number
- FA441821R0014
About this file
This solicitation is for repair and maintenance services at a facility located at Joint Base Charleston - Air Base in Charleston, South Carolina. The services include all labor, equipment, materials, and supervision to complete project number DKFX 1054125 for repairs at the Repair Maintenance Facility Hangar B570. The solicitation is issued as a 100% HUBZone set-aside using trade-off procedures. No award will be made until funds are available, and the government reserves the right to cancel the solicitation before or after the closing date without obligation to reimburse any offeror costs. The Department of the Air Force Air Mobility Command is the issuing agency.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 21R0014 - B570 - Pre-Bid Questions and Answers_Revised.pdf | ||
| Solicitation Amendment 02 FA441821R00140002.pdf | ||
| B570 Site Visit Sign-in.pdf | ||
| B570 Addendum 01 (Final).pdf | ||
| 21R0014 - B570 - Pre-Bid Questions and Answers_R2.pdf | ||
| Solicitation Amendment 01 FA441821R00140001.pdf | ||
| Asbestos and Lead Survey Report B570.pdf | ||
| 06_20200916 Green Procurement B570.pdf | ||
| 21-05-14 JBC B570 RTA Drawings.pdf | ||
| 21-05-14 JBC B570 RTA Specs.pdf | ||
| Wage Determination.pdf | ||
| FA441821R0014 B570 20210603.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INSPECTION
COVER
PRESSURE/
VACUUM VENT
CAPPED SURROGATE
TEST CONNECTION
TEST VALVE
(NORMALLY
CLOSED)
5 PIPE DIAMETERS OF
STRAIGHT PIPE
DOWNSTREAM OF INDUCTOR
FOAM INDUCTOR
SUPERVISED FOAM
CONCENTRATE
VALVE (NORMALLY
OPEN)
TO FOAM
GENERATORS
TO TEST
HEADER
TEST VALVE
(NORMALLY
CLOSED)
SUPERVISED FOAM
SOLUTION VALVE
(NORMALLY OPEN)
5 PIPE DIAMETERS OF
STRAIGHT PIPE UPSTREAM
OF INDUCTOR
VALVE GAUGE COCKS
3 FT BEFORE AND 3 FT
AFTER FOAM
INDUCTOR
CHECK VALVE
ATMOSPHERIC FOAM
CONCENTRATE
STORAGE TANK
FLOW CONTROL VALVE
OS&Y VALVE WITH
TAMPER SWITCH
(NORMALLY OPEN)
TO EXISTING UNDERGROUND
WATER SUPPLY
FC
50 GALLON FLOOR MOUNTED
SURGE ARRESTOR WITH
SUPERVISED ISOLATION
VALVE AND DRAIN
HEF RISER MANIFOLD
BATTERIES
CHARGER
SIGNALING LINE CIRCUITS (TYP)
(#14AWG, 3/4"C)
HEF NOTIFICATION APPLIANCE CIRCUITS (TYP)
(#14AWG, 3/4"C)
NEW DET-TRONICS
EAGLE QUANTUM
PREMIER
DETECTION/RELEASING
CONTROL PANEL
TO BUILDING
FIRE ALARM
CONTROL
PANEL
(SEE 5/F-001)
FO
120VAC
20A FUSED
DISC SW.
120 VAC
POWER
SOURCE
FSCP
TVSS
IR3
FO
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
G
E W
B
A IR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
E D
B
Y
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L E
S T
O N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P
A R
T M
E N
T O
F D
E F
E N
S E
C H
A R
L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
B S
H A
W
E M
C D
O N
A L D
J T
O R
N E
R
M L A
Z O
/1
/2
S U
P R
E S
S
IO
N D
IA
G
R A
M S
DKFX 1054125
05/14/2021
F-003
/1
/2
/1
/2
/1
/2
SCALE: NOT TO SCALE3
FOAM SUPRESSION SIGN STATIONS
SCALE: NOT TO SCALE2
FOAM SYSTEM ONE LINE DIAGRAM -
TYPICAL FOR EACH HEF RISER
SCALE: NOT TO SCALE1
FIRE SUPPRESSION CONTROL RISER DIAGRAM
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
M A R K A. L A Z O
S
O U
TH
CAROL IN
A
R E G I S T E R E D
PR
OF E
SS I ON
A L E N G I N E E R
No. 20943
5/14/2021
/1
/2
/1
/2
/1
/2
/1
/2 mlazo Line mlazo Line
F
F F
F
F
TS TS TS
FS FS
FS TS
S
FOFO
FACPFSCP DACT
B
ELEC/FIRE ALARM
DF1 DF1DF1
DF1
DF1
DF1
DF2
DF1
DF1 DF2DF5
DF6 DF7
DF1 DF1
DF2
DF2 DF8 DF8
DF10
DF12
DF11DF10
DF13DF14
IR
DF3
SEE SHEET F-101
MATCHLINE SEE SHEET FD102
MATCHLINE
SEE SHEET FD101
MATCHLINE
DF16
DF4
GRAPHIC SCALE
16'4' 8'24"
SCALE: 1/8"=1'-0"
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
GENERAL NOTES
SHEET KEYNOTES
G
E W
B
A IR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L E
S T
O N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P
A R
T M
E N
T O
F D
E F
E N
S E
C H
A R
L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
PLAN NORTH
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
B S
H A
W
E M
C D
O N
A L D
J T
O R
N E
R
M L A
Z O
/1
/2
F
IR
S T
F L
O O
R D
E M
O L
IT
IO
N
P L
A N
A
R E
A C
DKFX 1054125
05/14/2021
FD103
/1
/2
/1
/2
/1
/2
SCALE: 1/8" = 1'-0"1
FIRST FLOOR DEMOLITION PLAN - AREA C
R R
KEY PLAN
1. FIRE ALARM SYSTEM COMPONENTS
OUTSIDE OF THE THE RENOVATION
AREA MUST REMAIN OPERATIONAL.
2. FIRE SPRINKLER SYSTEM
COMPONENTS OUTSIDE OF THE
RENOVATION AREA MUST REMAIN
OPERATIONAL.
3. VERIFY TYPE AND QUANTITY OF FIRE
ALARM, FIRE SPRINKLER, AND FOAM
SUPPRESSION COMPONENTS IN
RENOVATION AREAS.
4. EXISTING FOAM SUPPRESSION
PIPING IN HANGAR BAY MUST REMAIN
UNLESS OTHERWISE NOTED.
DF1 EXISTING FIRE ALARM INITIATING DEVICE
TO REMAIN.
DF2 EXISTING FIRE ALARM NOTIFICATION
APPLIANCE TO REMAIN.
DF3 DEMOLISH EXISTING UV/IR FLAME
DETECTORS AND ASSOCIATED CONTROLS
AND EQIPMENT.
DF4 DEMOLISH EXISTING BLADDER TYPE HIGH
EXPANSION FOAM (HEF) CONCENTRATE
STORAGE TANK, PROPORTIONING VALVE
AND ASSOCIATED PIPING AS SHOWN IN
FIGURE 2 ON SHEET FD104.
DF5 DEMOLISH EXISTING FOAM SUPRESSION
MANUAL RELEASING STATIONS, ABORT
STATIONS, ASSOCIATED CONTROLS AND
EQUIPMENT
DF6 DEMOLISH EXISTING POTTER PFC FOAM
SUPRESSION RELEASING CONTROL
PANEL.
DF7 DEMOLISH EXISTING MONACO FIRE
ALARM CONTROL PANEL.
DF8 DEMOLISH EXISTING FIRE SUPPRESSION
NOTIFICATION APPLIANCE.
DF10 EXISTING WET-PIPE SPRINKLER RISER TO
REMAIN.
DF11 DEMOLISH EXISTING FOAM SUPPRESSION
RISER
DF12 EXISTING FIRE DEPARTMENT
CONNECTION TO REMAIN.
DF13 EXISTING FOAM PIPING TO REMAIN.
DF14 DEMOLISH EXISTING FOAM PIPING.
DF16 CUT AND CAP EXISTING 10"
UNDERGROUND FIRE SUPPLY PIPING.
DEMOLISH EXISTING TEE AT ENTRANCE
TO FOAM ROOM. REFER TO DETAIL 4,
SHEET F-003 FOR COORDINATION AND
ADDITIONAL INFORMATION.
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
M A R K A. L A Z O
S
O U
TH
CAROL IN
A
R E G I S T E R E D
PR
OF E
SS I ON
A L E N G I N E E R
No. 20943
5/14/2021
/1
/2
/1
/2
/1
/2
/1
/2 mlazo Line mlazo Cloud+ mlazo Cloud+ Remove demo hatching and Keynote #14.
mlazo Line mlazo Line
R R
F
F
F
F
DF1
DF2
DF2 DF2
DF2
DF1
DF1DF2DF2
DF2
DF2
DF2
DF2
DF1
DF2
DF2
DF10
DF12DF10
DF10
MATCHLINE
SEE SHEET FD101
DF15
DF15
DF15
DF15
D .I. P
IP
E
EXISTING 10" D.I. PIPE
EXISTING MINIMUM (2) 3/4" ROD
W/ BITUMINOUS COATING TO
REMAIN
EXISTING MINIMUM (2) 3/4"
ROD W/ BITUMINOUS
COATING TO REMAIN
EXISTING CONCRETE
THRUST BLOCK TO
REMAIN
CUT EXISTING 10" DUCTILE
IRON PIPE FLUSH TO FLOOR.
FILL PIPE WITH FLOWABLE
FILL IN ACCORDANCE WITH
SCDOT SUPPLEMENTAL
TECHNICAL SPECIFICATIONS
SC-M-210.
CUT AND CAP EXISTING 10" DUCTILE IRON
PIPE AND CAP. FILL PIPE WITH FLOWABLE
FILL IN ACCORDANCE WITH SCDOT
SUPPLEMENTAL TECHNICAL SPECIFICATIONS
SC-M-210.
EXISTING CONCRETE
FOOTING
FINISHED GRADE
BUILDING 570 EXTERIOR WALL
DEMOLISH EXISTING
TEE
EXISTING WATER SUPPLY TO REMAIN.
ISOLATE WATER SUPPLY AND CUT DURING
MODIFICATION AND PLACEMENT OF NEW
ELBOW/FIRE SUPPLY AS SHOWN IN DETAIL
2 SHEET F-104
DEMOLISH EXISTING EXPANSION
TANK AND VALVE
EXISTING 2 1/2" MAIN
DRAIN HEADER TO
REMAIN
EXISTING MAIN
DRAIN PIPING TO
REMAIN
DEMOLISH EXISTING 8"
CHECK VALVE
EXISTING 6" ALARM VALVE
WITH VARIABLE PRESSURE
TRIM TO REMAIN
EXISTING WATER FLOW
DETECTOR TO REMAIN
DEMOLISH EXISTING
EXPANSION TANK SURGE
PROTECTOR (TYPICAL)
EXISTING 8" RISER
MANIFOLD TO
REMAIN
TO EXISTING WET PIPE
SPRINKLER SYSTEM TO
REMAIN
TO EXISTING HIGH
EXPANSION FOAM
SYSTEM TO EXISTING
SPRINKLER SYSTEM
IN EQUIPMENT
ROOM TO REMAIN
EXISTING 6" SPRINKLER
RISER TO REMAIN
DEMOLISH EXISTING 6"
FLOW CONTROL VALVE
DEMOLISH EXISTING 6"
OS&Y CONTROL VALVE
WITH TAMPER SWITCH
DEMOLISH EXISTING
BALL VALVE WITH
TAMPER SWITCH
DEMOLISH EXISTING 2"
CHECK VALVE
DEMOLISH EXISTING 2"
HYDRAULIC BALL VALVE
DEMOLISH EXISTING 2"
MANUAL BALL VALVE
DEMOLISH EXISTING 450
GALLON HORIZONTAL
BLADDER TANK
EXISTING PIPE
SUPPORT TO
REMAIN
DEMOLISH
EXISTING MAIN
DRAIN PIPING
FROM FOAM RISER
EXISTING 6" OS&Y CONTROL
VALVE WITH TAMPER
SWITCH
GRAPHIC SCALE
16'4' 8'24"
SCALE: 1/8"=1'-0"
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
GENERAL NOTES
SHEET KEYNOTES
G
E W
B
A IR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L E
S T
O N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P
A R
T M
E N
T O
F D
E F
E N
S E
C H
A R
L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
PLAN NORTH
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
B S
H A
W
E M
C D
O N
A L D
J T
O R
N E
R
M L A
Z O
/1
/2
F
IR
S T
F L
O O
R D
E M
O L
IT
IO
N
P L
A N
A
R E
A D
DKFX 1054125
05/14/2021
FD104
/1
/2
/1
/2
/1
/2
SCALE: 1/8" = 1'-0"1
FIRST FLOOR DEMOLITION PLAN - AREA D
R R
KEY PLAN
1. FIRE ALARM SYSTEM COMPONENTS
OUTSIDE OF THE THE RENOVATION
AREA MUST REMAIN OPERATIONAL.
2. FIRE SPRINKLER SYSTEM
COMPONENTS OUTSIDE OF THE
RENOVATION AREA MUST REMAIN
OPERATIONAL.
3. THE CONTRACTOR MUST VERIFY TYPE
AND QUANTITY OF FIRE ALARM,
FIRE SPRINKLER, AND FOAM
SUPPRESSION COMPONENTS IN
RENOVATION AREAS.
4. EXISTING FOAM SUPPRESSION
PIPING IN HANGAR BAY MUST REMAIN
UNLESS OTHERWISE NOTED.
DF1 EXISTING FIRE ALARM INITIATING DEVICE
TO REMAIN.
DF2 EXISTING FIRE ALARM NOTIFICATION
APPLIANCE TO REMAIN.
DF10 EXISTING WET-PIPE SPRINKLER RISER TO
REMAIN.
DF12 EXISTING FIRE DEPARTMENT
CONNECTION TO REMAIN.
DF15 DEMOLISH EXISTING ABOVE CEILING
WET-PIPE SPRINKLER PIPING AND
SPRINKLER HEADS. CAP SPRINKLER
PIPING WHERE IT ENTERS ROOM FOR
FUTURE SPRINKLER SYSTEM
CONNECTION.
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D
SCALE: NOT TO SCALE2
FIRE SUPPLY PIPING DEMOLITION DETAIL
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
M A R K A. L A Z O
S
O U
TH
CAROL IN
A
R E G I S T E R E D
PR
OF E
SS I ON
A L E N G I N E E R
No. 20943
5/14/2021
/1
/2
/1
/2
/1
/2
/1
/2 mlazo Cloud+ mlazo Cloud+ Remove all demolition work associated with the HEF system. The existing system already meets the AFCEC minimum reliability standards. Water to bladder tank is already connected downstream of the flow control valve.
File details come from the government source that posted it. Updated .