21-05-14 JBC B570 RTA Drawings.pdf
PDF 25 MB Posted
- Attached to
- Repair Maintenance Facility – B570 Federal contract opportunity
- Solicitation number
- FA441821R0014
About this file
This document provides details on a federal contract solicitation for repair and maintenance services at Joint Base Charleston - Air Base in Charleston, South Carolina. The solicitation number is FA441821R0014 and seeks offers to complete project number DKFX 1054125 for repair and maintenance of Hangar B570. The work includes providing all labor, equipment, materials and supervision necessary. This is a 100% HUBZone set-aside utilizing trade-off procedures. No award will be made until funds are available and the government reserves the right to cancel the solicitation before or after the closing date with no obligation to reimburse offerors for any costs. The soliciting agency is the Department of the Air Force Air Mobility Command.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 21R0014 - B570 - Pre-Bid Questions and Answers_Revised.pdf | ||
| Solicitation Amendment 02 FA441821R00140002.pdf | ||
| B570 Site Visit Sign-in.pdf | ||
| 21R0014 - B570 - Pre-Bid Questions and Answers_R2.pdf | ||
| B570 Addendum 01 (Final).pdf | ||
| FP Sheets_ JBC B570 Revised RTA Drawings.pdf | ||
| Solicitation Amendment 01 FA441821R00140001.pdf | ||
| 06_20200916 Green Procurement B570.pdf | ||
| 21-05-14 JBC B570 RTA Specs.pdf | ||
| Asbestos and Lead Survey Report B570.pdf | ||
| Wage Determination.pdf | ||
| FA441821R0014 B570 20210603.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VICINITY MAP
SCALE: N.T.S.
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
G
E W
B
AIR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
E D
B
Y
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L E
S T
O N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P A
R T M
E N
T O
F D
E F E
N S
E C
H A
R L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
B S
H A
W
C C
O O
P E
R
M L A
Z O
L S
W
/8
/2
C O
V E
R S
H E
E T
DKFX 1054125
05/14/2021
G-001
/8
/2
/8
/2
/8
/2
REPAIR MAINTENANCE FACILITY, BLDG 570
JOINT BASE CHARLESTON
CHARLESTON, SOUTH CAROLINA
CONTRACT NO.: FA4418-17-D-0007
PROJECT NO.: DKFX 1054125
ISSUED: 14 MAY 2021
PROJECT LOCATION
TRUE NORTH
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
M A R K A. L A Z O
S
O U
TH
CAROL IN
A
R E G I S T E R E D
PR
OF E
SS I ON
A L E N G I N E E R
No. 20943
5/14/2021
/1
/2
/1
/2
/1
/2
/1
/2
HAUL ROUTE
ALTERNATE HAUL ROUTE
LAYDOWN AREA -
VERIFY EXISTING
CONDITIONS FOR
LIMITATIONS OF
CONTRACTOR
STORAGE
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
G
E W
B
AIR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L E
S T
O N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P A
R T M
E N
T O
F D
E F E
N S
E C
H A
R L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
B S
H A
W
C C
O O
P E
R
M L A
Z O
L S
W
/8
/2
S H
E E
T I
N D
E X
DKFX 1054125
05/14/2021
G-002
/8
/2
/8
/2
/8
/2
SHEET INDEX
SHEET
NUMBER SHEET NAME
MECHANICAL
M-001 LEGEND, ABBREVIATIONS, AND GENERAL NOTES
MD101 FIRST FLOOR DEMOLITION PLAN - AREA A
MD102 FIRST FLOOR DEMOLITION PLAN - AREA B
MD103 FIRST FLOOR DEMOLITION PLAN - AREA C
MD104 FIRST FLOOR DEMOLITION PLANS - AREA D
M-101 FIRST FLOOR PLAN - AREA A
M-102 FIRST FLOOR PLAN - AREA B
M-103 FIRST FLOOR PLAN - AREA C
M-104 FLOOR PLANS - AREA D
M-301 SECTIONS
M-501 DETAILS
M-502 DETAILS
M-601 SCHEDULES
M-701 CONTROLS
M-702 CONTROLS
M-703 CONTROLS
M-704 CONTROLS
ELECTRICAL
E-001 GENERAL NOTES, LEGENDS AND MOUNTING
HEIGHTS
ED101 ELECTRICAL DEMOLITION PLAN - AREA A
ED102 ELECTRICAL DEMOLITION PLAN - AREA B
ED103 ELECTRICAL DEMOLITION PLAN - AREA C
ED104 ELECTRICAL DEMOLITION PLANS
E-101 ELECTRICAL PLAN - AREA A
E-102 ELECTRICAL PLAN - AREA B
E-103 ELECTRICAL PLAN - AREA C
E-104 ELECTRICAL PLANS
E-501 DETAILS
E-502 LIGHTING FIXTURE SCHEDULE AND DETAILS
E-601 EXISTING RISER DIAGRAM
E-602 PANEL SCHEDULES
E-603 PANEL SCHEDULES
TOTAL: 83
SHEET INDEX
SHEET
NUMBER SHEET NAME
INTERIORS
IG101 SIGNAGE PLAN
IG601 SIGNAGE SCHEDULE & DETAILS
I-101 FIRST FLOOR FINISH PLAN
I-102 ENLARGED FIRST FLOOR FINISH PLAN - AREA A
I-103 ENLARGED FIRST FLOOR FINISH PLAN - AREA B
I-104 ENLARGED FIRST FLOOR FINISH PLAN - AREA C
I-105 ENLARGED FIRST FLOOR FINISH PLAN - AREA D
I-601 ROOM FINISH SCHEDULE & GENERAL NOTES
FIRE PROTECTION
F-001 ALARM GENERAL NOTES, LEGENDS, AND
DIAGRAMS
F-002 SUPPRESSION GENERAL NOTES AND LEGENDS
F-003 SUPRESSION DIAGRAMS
FD101 FIRST FLOOR DEMOLITION PLAN - AREA A
FD102 FIRST FLOOR DEMOLITION PLAN - AREA B
FD103 FIRST FLOOR DEMOLITION PLAN - AREA C
FD104 FIRST FLOOR DEMOLITION PLAN - AREA D
F-101 FIRE PROTECTION PLAN - AREA A
F-102 FIRE PROTECTION PLAN - AREA B
F-103 FIRE PROTECTION PLAN - AREA C
F-104 FIRE PROTECTION PLAN - AREA D
F-105 DET-TRONICS TRIPLE IR LAYOUT
PLUMBING
P-001 LEGEND, ABBREVIATIONS, AND GENERAL NOTES
P-101 FIRST FLOOR PLANS - AREA D
SHEET INDEX
SHEET
NUMBER SHEET NAME
GENERAL
G-001 COVER SHEET
G-002 SHEET INDEX
G-003 ENVIRONMENTAL REQUIREMENTS
G-101 BUILDING CODE SUMMARY
G-102 LIFE SAFETY PLAN
STRUCTURAL
S-001 GENERAL NOTES AND DESIGN LOADS
S-401 ENLARGED MEZZANINE ROOF FRAMING PLANS -
AREA D
S-501 MEZZANINE DETAILS
ARCHITECTURAL
A-001 GENERAL NOTES AND ABBREVIATIONS
A-002 SYMBOLS, MATERIALS, AND PARTITIONS
AD001 GENERAL DEMOLITION NOTES AND DETAILS
AD101 ARCHITECTURAL DEMOLITION PLAN
AD102 ARCHITECTURAL DEMOLITION PLAN - AREA A
AD103 ARCHITECTURAL DEMOLITION PLAN - AREA B
AD104 ARCHITECTURAL DEMOLITION PLAN - AREA C
AD105 ARCHITECTURAL DEMOLITION PLAN - AREA D
A-101 RENOVATION FLOOR PLAN
A-102 RENOVATION FLOOR PLAN - AREA A
A-103 RENOVATION FLOOR PLAN - AREA B
A-104 RENOVATION FLOOR PLAN - AREA C
A-105 RENOVATION FLOOR PLAN - AREA D
A-131 REFLECTED CEILING PLAN
A-151 ROOF PLAN
A-201 EXTERIOR ELEVATIONS
A-301 BUILDING SECTIONS
A-421 ENLARGED RESTROOM PLANS
A-501 ARCHITECTURAL DETAILS
A-502 INTERIOR ELEVATIONS
A-571 MOUNTING HEIGHTS & DETAILS
A-601 DOOR SCHEDULE
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D
PLAN NORTH
GRAVES AVE.
ARTHUR DR.
AVIATION AVE.
BACK GATE
S T E
W A
R T A
V E
DAVIS DR.
S
LO
A N
S T
PROJECT LOCATION
SCALE: NOT TO SCALE1
LAY DOWN PLAN & HAUL ROUTES
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
M A R K A. L A Z O
S
O U
TH
CAROL IN
A
R E G I S T E R E D
PR
OF E
SS I ON
A L E N G I N E E R
No. 20943
5/14/2021
/1
/2
/1
/2
/1
/2
/1
/2
THE PROPOSED PROJECT AREA IS ADJACENT TO JOINT BASE CHARLESTON AIR (JBCHS AIR)
ENVIRONMENTAL RESTORATION PROGRAM (ERP) CLEANUP SITES. THE ERP SITE IS INCLUDED IN THE JBCHS AIR RESOURCE CONSERVATION AND RECOVERY ACT (RCRA) HAZARDOUS WASTE PERMIT ISSUED TO JBCHS AIR BY THE SOUTH CAROLINA DEPARTMENT OF HEALTH AND ENVIRONMENTAL SCIENCE
(SCDHEC).
GROUNDWATER AND GROUNDWATER MONITORING WELLS
1. GROUNDWATER IN THE PROJECT AREA (EXPECTED WATER TABLE APPROXIMATELY 7 FEET BELOW
GROUND SURFACE) IS POTENTIALLY CONTAMINATED WITH TRICHLOROETHENE (TCE) AND VARIOUS OTHER VOLATILE ORGANIC COMPOUNDS (VOCs). GROUNDWATER MONITORING OF THE WELL
NETWORK IS REQUIRED BY SCDHEC IN ACCORDANCE WITH THE RCRA PERMIT ISSUED TO JBCHS
AIR.
2. A NUMBER OF DISCHARGES FROM THE BUILDING 570 AQUEOUS FILM FORMING FOAM (AFFF) SYSTEM ARE KNOWN TO HAVE OCCURRED. THE QUANTITIES OF AFFF RELEASED ARE UNKNOWN; HOWEVER, SEVERAL DISCHARGES FLOWED OUTSIDE THE HANGAR ONTO THE APRON, THE ADJACENT GRASSY
AREA, AND LIKELY INTO THE SINGLE STORM DRAIN INLET SOUTH OF THE BUILDING. PLEASE NOTE- ALL SAMPLES WERE COLLECTED SOUTH OF BUILDING 570 (SEE FIGURES FOR SAMPLE LOCATIONS).
3. BASED ON THE PFAS SI:
PFAS IN SOILS:
COMBINED PFAS COMPOUNDS WERE DETECTED IN THE SURFACE SOIL, SUBSURFACE SOIL, AND
SEDIMENT SAMPLES; HOWEVER, ALL CONCENTRATIONS WERE LESS THAN THE REGIONAL
SCREENING LEVELS (RSLS) OF 126 ΜG/KG. SOILS COLLECTED IN THE SI WERE SIGNIFICANTLY LOWER THAN THE REGIONAL SCREENING LEVELS, SO IT APPEARS PFAS IN SOILS ARE NOT A MAJOR
CONCERN NEAR THE BUILDING.
PFAS IN GROUNDWATER/SURFACE WATER:
COMBINED PFAS COMPOUNDS WERE GREATER THAN THE ENVIRONMENTAL PROTECTION AGENCY
(EPA) LIFETIME HEALTH ADVISORY (LHA) LEVEL OF 0.07 ΜG/L IN GROUNDWATER (7‐10 FEET BELOW
GROUND SURFACE) AND SURFACE WATER SAMPLES.
4. IF GROUNDWATER IS ENCOUNTERED AND SINCE IT WAS GREATER THAN THE LHA, THEN SAMPLING
AND DISPOSAL MUST BE IN ACCORDANCE WITH AFFF RELATED WASTE MANAGEMENT
IMPLEMENTATION GUIDANCE OR THE MOST CURRENT VERSION. CONTRACTOR SHALL INCLUDE
COST FOR TESTING OF GROUNDWATER IN ACCORDANCE WITH STANDARDS IDENTIFIED ABOVE.
5. SEVERAL MONITORING WELLS ARE LOCATED NEAR OR WITHIN THE PROPOSED PROJECT AREA.
EVERY EFFORT SHOULD BE MADE TO PROTECT THE INTEGRITY OF THESE MONITORING WELLS, AS
THEY ARE CURRENTLY BEING USED FOR GROUNDWATER MONITORING. DRIVING OVER THESE
FLUSH-MOUNTED WELLS AND THEIR PADS WILL DAMAGE THE INTEGRITY OF THE WELL PAD AND
SEAL. CONTACT JBCHS FOR WELL LOCATIONS. ANY WELLS DAMAGED OR DESTROYED DURING THE PROJECT MUST BE REPAIRED OR REPLACED. COORDINATION FOR PROPER ABANDONMENT AND RE- INSTALLATION SHOULD BE WITH THE REMEDIAL PROJECT MANAGER (RPM), CHRISTOPHER WARGO AT 843-963-2701 (CHRISTOPHER.WARGO.2@US.AF.MIL) AND SCDHEC BUREAU OF LAND AND WASTE MANAGEMENT, DIVISION OF WASTE MANAGEMENT, FEDERAL FACILITIES SECTION. NOTE THAT SUCH
COORDINATION IS NOT WITH THE SCDHEC BUREAU OF WATER.
6. WELL REPAIR, ABANDONMENT, AND REPLACEMENT ARE THE RESPONSIBILITY OF THE CONTRACTOR.
IF A WELL IS ABANDONED AND RE-INSTALLED, A REGISTERED LAND SURVEYOR MUST SURVEY THE
GROUND SURFACE, TOP OF CASING, AND TOP OF CONCRETE WELL PAD, AND PROVIDE THIS
INFORMATION TO THE JBCHS AIR RPM. VERTICAL ELEVATIONS NEED TO BE REFERENCED TO THE NORTH AMERICAN VERTICAL DATUM 1988 (NAVD 88), US SURVEY FEET AND HORIZONTAL LOCATIONS
(NORTHINGS AND EASTINGS) SHOULD BE REFERENCED TO A UNIVERSAL TRANSVERSE MERCATOR
COORDINATES ZONE 17 NORTH. ADDITIONALLY, A SC-CERTIFIED WELL DRILLER MUST BE USED FOR
ALL WELLS THAT ARE ABANDONED OR RE-INSTALLED, AND A SCDHEC FORM 1903 (WATER WELL
RECORD FORM) MUST BE PREPARED BY THE WELL DRILLER AND SUBMITTED TO THE PROPER
SCDHEC SECTION ABOVE (I.E. NOT THE BUREAU OF WATER) AND A COPY TO THE JBCHS AIR RPM. IF NECESSARY, ANY RE-INSTALLED MONITORING WELLS MUST BE PROPERLY DEVELOPED BY PUMPING
UNTIL GROUNDWATER IS CLEAR OF VISIBLE SEDIMENTS AND FIELD PARAMETER MEASUREMENTS
ARE STABILIZED (PH VARIES TO 0.1 STANDARD UNITS, SPECIFIC CONDUCTIVITY VARIES TO WITHIN
10%, AND TEMPERATURE IS CONSTANT FOR AT LEAST THREE CONSECUTIVE MEASUREMENTS).
7. ALL FIELD DOCUMENTATION, INCLUDING THE DEVELOPMENT LOGS AND WATER WELL RECORD
FORMS, MUST BE PROVIDED TO THE JBCHS AIR RPM.
INVESTIGATIVE-DERIVED WASTE
1. INVESTIGATIVE-DERIVED WASTE (SOIL CUTTINGS, DRILLING MUD, DEVELOPMENT WATER, AND/OR
GROUNDWATER) GENERATED BY RE-INSTALLATION OF A MONITORING WELL, OR EXCAVATED SOIL NOT PLANNED FOR REUSE FROM THE AREA FROM WHICH IT WAS EXCAVATED, MUST BE PROPERLY CONTAINED IN 55-GALLON DRUMS, LABELED (HOLD PENDING ANALYSIS UNTIL CHARACTERIZED, THEN HAZARDOUS OR NON-HAZARDOUS FOR TRANSPORTATION/DISPOSAL), STORED (HOLD
PENDING ANALYSIS AND NON-HAZARDOUS DRUMS CAN BE STORED ON SITE, BUT HAZARDOUS
DRUMS MUST BE STORED WITHIN THE FENCED AREA AT THE HAZ WASTE YARD), AND DISPOSED
WITH COORDINATION THROUGH MR. TOMMY HARDIN AT 843-963-3656 (JOHN.HARDIN@US.AF.MIL).
2. AFTER THE DATA IS EVALUATED, THE WASTE HAS BEEN CHARACTERIZED, AND A WASTE STREAM
CHARACTERIZATION PROCESS DOCUMENT (WSCPD) FOR CONTRACTORS HAS BEEN PREPARED, THE
WSCPD FORM MUST BE SIGNED BY MR. TOMMY HARDIN WELL IN ADVANCE OF SHIPMENT AND PRIOR
TO DISPOSAL. MR. HARDIN OR MR. WARGO WILL PROVIDE THE CONTRACTOR A WSCPD FORM.
DEWATERING/CONTAMINATED GROUNDWATER
1. IF DEWATERING OF GROUNDWATER IS REQUIRED, THE EXACT AMOUNT OF GROUNDWATER TO BE
DEWATERED FROM THE SITE WILL BE BASED ON THE DURATION OF PUMPING. DEWATERING
ACTIVITIES SHOULD BE MINIMIZED IN AN EFFORT TO REDUCE MIGRATION OF SITE CONTAMINANTS.
2. IF DEWATERING IS NECESSARY, ALL GROUNDWATER EXTRACTED FROM THE SUBSURFACE WITHIN SPECIFIED WORK AREA MUST BE CONTAINED IN FRAC TANKS (MOBILE STEEL STORAGE TANKS USED TO HOLD LIQUIDS) OR A SIMILAR TYPE OF STORAGE TANK. STORAGE TANKS MUST BE PROPERLY LABELED WITH A HOLD PENDING ANALYSIS LABEL UNTIL SAMPLES HAVE BEEN COLLECTED AND THE DATA HAVE BEEN RECEIVED/EVALUATED BY THE CONTRACTOR. AFTER THE DATA IS EVALUATED, THE WASTE HAS BEEN CHARACTERIZED, AND A WSCPD FOR CONTRACTORS HAS BEEN PREPARED, THE WSCPD FORM MUST BE SIGNED BY MR. TOMMY HARDIN WELL IN ADVANCE OF SHIPMENT AND
PRIOR TO DISPOSAL. MR. HARDIN OR MR. WARGO WILL PROVIDE THE CONTRACTOR A WSCPD
FORM. MR. HARDIN MUST SIGN ALL WASTE DISPOSAL MANIFESTS FOR OFF-BASE DISPOSAL.
PLEASE PLAN AHEAD.
ENVIRONMENTAL REQUIREMENTS:
3. IF THE REPORTED GROUNDWATER CONCENTRATIONS FROM DEWATERING ACTIVITIES ARE BELOW
THE NORTH CHARLESTON SEWER DISTRICT (NCSD) PRE-TREATMENT LIMITS, AND JBCHS (MR.
KURTIS EVANS AT 843-963-1483 OR KURTIS.EVANS@US.AF.MIL) AND NCSD HAVE BOTH REVIEWED
AND APPROVED THE RESULTS, THE GROUNDWATER CAN BE DISCHARGED TO A DESIGNATED
SANITARY SEWER MANHOLE. IF FRAC TANKS ARE UTILIZED FOR GROUNDWATER STORAGE AND
APPROVAL HAS BEEN GRANTED FOR DISPOSAL TO THE SANITARY SEWER, VACUUM TRUCKS WILL
LIKELY BE USED FOR TRANSPORTING THE GROUNDWATER WASTE FROM THE FRAC TANK TO THE
SANITARY SEWER. MR. EVANS WILL PROVIDE THE NCSD PRETREATMENT LIMITS TO THE
CONTRACTOR. THE LIQUID SAMPLES COLLECTED FOR CHARACTERIZATION FOR SANITARY SEWER
DISPOSAL MUST BE ANALYZED FOR VOCs VIA ENVIRONMENTAL PROTECTION AGENCY (USEPA)
METHOD 8260B. ADDITIONALLY, PH AND TEMPERATURE READINGS MUST BE MEASURED IN THE
FIELD AND NOT BY SUBMITTAL TO AN OFF-SITE LABORATORY. THE ANALYTICAL LABORATORY
UTILIZED MUST BE IN THE SCDHEC ENVIRONMENTAL LABORATORY CERTIFICATION PROGRAM
(REGULATION 61-81, ENTITLED "STATE ENVIRONMENTAL LABORATORY CERTIFICATION
REGULATION").
CONTAMINATED SOIL
1. SOIL IN THE PROJECT AREA APPROXIMATELY 7 FEET BELOW GROUND SURFACE IS POSSIBLY
CONTABMINATED WITH TCE OR OTHER VOCs. IF POSSIBLE, THE EXCAVATED SOIL SHOULD BE
PLACED BACK IN THE SAME AREA FROM WHICH EXCAVATED.
2. ANY SOIL TO BE REMOVED FROM THE SITE SHOULD BE EXCAVATED, CONTAINED IN 55-GALLON DRUMS OR PLASTIC-LINED ROLL-OFF BINS, COVERED, LABELED WITH HOLD PENDING ANALYSIS STICKERS, AND STORED ON BASE UNTIL THE SOIL HAS BEEN SAMPLED AND CHARACTERIZED. A COMPOSITE SOIL SAMPLE SHOULD BE COLLECTED FROM EVERY ROLL-OFF BIN (OR ONE COMPOSITE SAMPLE FROM EVERY FIVE 55-GALLON DRUMS) AND ANALYZED FOR VOCs. ONCE CHARACTERIZED, THE APPROPRIATE LABELS SHOULD BE PLACED ON THE STORAGE CONTAINERS.
3. ANY SOIL EXCAVATED AT THE SITE THAT CANNOT BE PLACED BACK IN THE EXCAVATION CLOSE TO
WHERE IT WAS EXCAVATED SHOULD BE PROPERLY DISPOSED OFF-BASE AND MUST BE
COORDINATED THROUGH MR. TOMMY HARDIN. AFTER THE DATA IS EVALUATED, THE WASTE HAS
BEEN CHARACTERIZED, AND A WSCPD FOR CONTRACTORS HAS BEEN PREPARED, ALL THE
INFORMATION MUST BE PROVIDED TO MR. TOMMY HARDIN WELL IN ADVANCE OF SHIPMENT AND
PRIOR TO DISPOSAL. MR. HARDIN WILL PROVIDE THE CONTRACTOR A WSCPD FORM. MR. HARDIN
MUST SIGN THE WASTE MANIFEST PRIOR TO OFF-BASE TRANSPORTATION AND DISPOSAL.
4. THE SAME DISPOSAL PROCEDURES AND COORDINATION MUST BE ADHERED TO FOR
CONTAMINATED SOIL AS FOR CONTAMINATED GROUNDWATER.
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
G
E W
B
A IR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L
E S
T O
N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P
A R
T M
E N
T O
F D
E F
E N
S E
C H
A R
L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
P .M
U R
R E
N
P .M
U R
R E
N
B
M
IN
O R
B
M
IN
O R
/8
/2
E N
V
IR
O N
M E
N T
A L
R E
Q U
IR
E
M E
N T
S
DKFX 1054125
5/14/2021
G-003
/8
/2
/8
/2
/8
/2
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
/1
/2
/1
/2
/1
/2
/1
/2
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
G
E W
B
AIR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L E
S T
O N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P A
R T M
E N
T O
F D
E F E
N S
E C
H A
R L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
B S
H A
W
C C
O O
P E
R
M L A
Z O
L S
W
/8
/2
B U
IL
D
IN
G
C O
D E
S U
M M
A R
Y
DKFX 1054125
05/14/2021
G-101
/8
/2
/8
/2
/8
/2
FIRE RESISTANCE RATING OF BLDG ELEMENTS
STRUCTURAL FRAME
(PER IBC TABLE 601)
BEARING WALLS
RATING AS
REQUIRED
(IN HOURS)
BUILDING ELEMENT RATING AS
DESIGNED
(IN HOURS)
NOTES
(PER IBC TABLE 601)
EXTERIOR
INTERIOR
NONBEARING WALLS
AND PARTITIONS
(PER IBC TABLE
601 AND 602)
- EXTERIOR
- INTERIOR
FLOOR CONSTRUCTION
INCLUDING SUPPORTING
BEAMS AND JOISTS
(PER IBC TABLE 601)
ROOF CONSTRUCTION
INCLUDING SUPPORTING
BEAMS AND JOISTS
(PER IBC TABLE 601)
FIRE PARTITIONS
(PER NFPA 101 40.3.6)
INCIDENTAL ACCESSORY
OCCUPANCIES
(PER IBC TABLE 509)
OCCUPANCY
SEPARATION WALLS
(PER IBC TABLE 508.4)
0 NA
0 NA
0 NA
EXISITNG
EXISTING
0 NA
EXISTING
0 NA EXISTING
0 NA EXISTING
NA NA EXISTING
0 NA EXISTING
0 NA EXISTING
BUILDING HEIGHT
AS DESIGNED
(PER IBC TABLE 504.3
AND 504.4)
AS ALLOWED BY IBC
TOTAL HEIGHT
IN FEET IN STORIES IN FEET IN STORIES
66 FT +/- 1 75 FT 3
66 FT +/- 1 75 FT 3
STRUCTURE IS AN EXISTING 1 STORY WITH MEZZANINE
NO YES
NO YES
NO YES
NO YES
NO YES
BASIC BUILDING CODE INFORMATION
CONSTRUCTION CLASSIFICATION:
TYPE:
(IBC 602)
DOES BUILDING HAVE ACCESSORY
OCCUPANCY (IES)?: (IBC 508.2)
WHAT PERCENT OF STORY IS
ACCESSORY OCCUPANCY?:
DOES BUILDING REQUIRE INCIDENTAL USE
AREA SEPARATION?:
(NFPA 101
6.1.14.1)
MIXED OCCUPANCIES?: (IBC 508.1)
OCCUPANCY GROUP:
NON SEPARATED?: (IBC 508.3)
SEPARATED?: (IBC 508.4)
NFPA IBC
EXISTING: (ASSUMED) II-B (0,0,0)
- EXISTING: INDUSTRIAL -Special Purpose
- Storage (Incidental)
- Business Use (Incidental)
- Assembly Non concentrated & Collaboration (Incidental)
NA SF
EXISTING HANGAR (GROUP I) NFPA 409 - Level II Renovation (IEBC)
- EXISTING: STORAGE S1
- Assembly A3 (Accessory)
- Business (Accessory)
FIRE PROTECTION / LIFE SAFETY /
ACCESSIBILITY CODE REVIEW
REPAIR MAINTENANCE FACILITY, BLDG 570
FIRE WALLS
(PER IBC TABLE 706.4):
FIRE BARRIERS
(PER UFC 4-211-01):
OTHER REQUIREMENTS: RATING AS
REQUIRED
(IN HOURS)
RATING AS
DESIGNED
(IN HOURS) NOTES
OPENING PROTECTIVES
(PER IBC SECTION 716
AND TABLE 716.5):
THRU-PENETRATIONS
(PER IBC SECTION 716
AND TABLE 716.5):
NA NA EXISTING
NA NA EXISTING HORIZONTAL &
VERTICAL BARRIERS ARE
RATED PER UFC 4-211-01,
SECTION 3-3.1.3
NA NA EXISTING
NA NA EXISTING
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
GENERAL FIRE PROTECTION REQUIREMENTS
SEPARATIONS:
(PER IBC SECTION 718)FIREBLOCKING REQUIRED?:
(PER IBC SECTION 718)DRAFTSTOPPING REQUIRED?:
(PER IBC SECTION 909)SMOKE CONTROL SYSTEM
REQUIRED?:
(PER IBC SECTION 709)SMOKE BARRIERS REQUIRED?:
(PER IBC SECTION 710)SMOKE PARTITION REQUIRED?:
(PER IBC SECTION 708)FIRE PARTITION REQUIRED?:
(PER IBC TABLE 508.4)FIRE BARRIER REQUIRED?:
ALARM AND DETECTION:
(PER UFC 3-600-01 9-18.6.1
AND NFPA 101 40.3.4.1)
FIRE ALARM SYSTEM REQUIRED?:
(PER UFC 3-600-01)
EMERGENCY ALARM SYSTEM
REQUIRED?:
FIRE ALARM SYSTEM PROVIDED?:
VERTICAL ENCLOSURES:
STAIRS:
SHAFT WALLS:
(PER NFPA 101, 7.1.3.2.1)
(PER IBC TABLE 713)
FIRE RATING:
FIRE RATING:
SHAFT ENCLOSURES: (PER IBC TABLE 713)
FIRE RATING:
FIRE RATING:
FIRE RATING:
FIRE RATING:
FIRE RATING:
(PER UFC 3-600-01)
EMERGENCY ALARM SYSTEM
PROVIDED?:
1 HR
1 HR
1 HR
1 HR
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
NO YES
SUPPRESSION:
(PER UFC 3-600-01
9-10.2.1 AND 9-10.2.2)
STANDPIPES REQUIRED?:
(PER UFC 3-600-01 9-7.2.1.1)SPRINKLERS REQUIRED?:
SPRINKLERS PROVIDED?:
(PER UFC 3-600-01 9-17.1)
PORTABLE EXTINGUISHERS
REQUIRED?:
(PER UFC 3-600-01)
OTHER SUPPRESSION
SYSTEMS REQUIRED?:
(PER UFC 3-600-01)
SMOKE AND HEAT VENTS
REQUIRED?:
MASS NOTIFICATION:
(UFC 04-010-01 AND
UFC 04-021-01)
MASS NOTIFICATION REQUIRED?:
MASS NOTIFICATION PROVIDED?:
LIGHT HAZARD AREAS: ORDINARY HAZARD AREAS:
*REFER TO FIRE PROTECTION SHEETS FOR WATER
SUPPLY INFORMATION AND DESIGN CRITERIA
ENCLOSURE PROTECTION:
ROOMS REQUIRING A
FIRE RATED SEPARATION:
(IBC 509)
(NFPA 409: 5.2.1, T6.1.14.4)
- ENTIRE BUILDING
ILLUMINATION OF
MEANS OF EGRESS
(NFPA 101: 7.8)
EMERGENCY LIGHTING
(NFPA 101: 7.9, AND
CHAPTERS 12-42)
MARKING OF MEANS
OF EGRESS
(NFPA 101: 7.10)
REQUIREDCODE ITEM PROVIDED NOTES
INTERIOR FINISHES
(NFPA 101: CHAPTER
10 AND TABLE A.10.2.2)
FIRE DAMPERS
(NFPA 90A)
SMOKE DAMPERS
(NFPA 90A)
DUCT SMOKE DETECTORS
(NFPA 90A)
ADDITIONAL LIFE SAFETY FEATURES
FT-CANDLE
YES Not required in unoccupied service equip areas per 7.14.4.2 when not req'd by occupancy Chapter
YES YES
Existing exit marking will be utilized where not modified, new lighting will be provided where directions to exits are required or modifications are required per finish replacemetnt.
New finishes to be provided in compliance with 40.3.3 and 10.2
YES YES
YES YES
YES YES
YES YES
YES YES
ROOF ACCESS
(UFC 3-600-01: 10-4
IBC 1011.12)
FIRE DEPARTMENT
VEHICLE ACCESS
(UFC 3-600-01: 9-1
NFPA 1: 3.5)
FIRE HYDRANT
INSTALLATION
(UFC 3-600-01: 9-3.5)
KITCHEN COOKING
EXHAUST EQUIPMENT
(NFPA 101: 9.2.3
NFPA 96)
ACCESSIBILITY
REQUIREMENTS
(ABA CHAPTERS 1-10)
EXISTING NOT IN SCOPEYES NA
YES NA
EXISTING NOT IN SCOPE
YES NA
YES NA
EXISTING NOT IN SCOPE
NO NA
EXISTING NOT IN SCOPE
APPLICABLE ON WHERE
MODIFICATIONS ARE MADE.
(IBC 311.2)
(IBC 303.4)
(IBC 304.1)
AREA CALCS BY OCCUPANCY - IBC
STORAGE S1 = 38,856 SF
ASSEMBLY A3 = 1,721 SF
BUSINESS B = 1,085 SF
TOTAL OCCUPIED AREA = 41,662 SF TOTAL GROSS AREA = 42,845 GSF
IBC T509 - INCIDENTAL BATTERY STOR. GREATER THAN T1206.2 - 1HR
IBC T707.3.10 - SEPARATING FIRE AREAS GROUP S1 - 3 HR
NFPA 409: 5.2.1 - HANGAR / SERVICE AREA - FIRE BARRIER - 2 HR
5.2.3 - HANGAR & SERVICE / ALL OTHER AREAS , SHOPS,
OFFICES, PARTS AND STORAGE - 1HR W/ 45MIN OPG.
MEANS OF EGRESS
EGRESS WIDTH
(PER NFPA 101, TABLE
7.3.3.1)
CORRIDOR WIDTH
(PER NFPA 101, 40.2.3.2)
CORRIDOR FIRE-
RESISTANCE RATING
(PER NFPA 40.3.6)
REQUIREDCODE ITEM PROVIDED NOTES
STAIR WIDTH (PER
NFPA 101, TABLE 7.3.3.1)
COMMON PATH OF
EGRESS TRAVEL (PER
NFPA 101, TABLE A.7.6)
EXIT ACCESS TRAVEL
DISTANCE (PER NFPA 101,
TABLE A.7.6)
DEAD ENDS (PER NFPA
101, 40.6.4)
MINIMUM NUMBER OF
EXITS FOR OCCUPANT
LOAD (PER NFPA 101,
7.4.1.2 AND 40.2.3)
VERTICAL EXIT
ENCLOSURES
(PER NFPA 101, 7.1.3.2.1)
HORIZONTAL EXIT
(PER NFPA 101, 7.2.4)
EXIT ACCESS
CORRIDOR WALLS
(PER NFPA 101, 7.1.3.1 (1))
.2IN / OCC NA EXISTING
28 in min.
existing
NA 44IN MIN NEW
EXISTING TO REMAIN - NOT
IN SCOPE
<400FT PER T42.2.6; 150FT
MAX SPACING OF
MANDOORS AT EXTERIOR
WALLS PER 40.6.3
EXISTING COORIDORS TO
REMAIN - NOT IN SCOPE
NEW MANDOORS REQUIRED
TO COMPLY WITH 150FT MAX
SPACING AT HANGAR
EXISTING STAIRS TO REMAIN
- NOT IN SCOPE
0 0
.3IN / OCC NA
100 ft
400 ft YES
<50 ft NA
2 7
YES NA
Note: Min of (2) Exits from Aircraft servicing areas to be provided at 150 ft max interval on exterior walls per 40.6.2.1, 2. Existing conditions not compliant.
.2IN / OCC
NO NA EXISTING TO REMAIN - NOT
IN SCOPE
NO NA OCCUPANCY IS NOT
CHANGING - NOT A PART OF
SCOPE
APPLICABLE CODES AND STANDARDS
A. UFC 1-200-01: GENERAL BUILDING REQUIREMENTS,8, OCTOBER 2019.
B. UFC 3-600-01: DESIGN: FIRE PROTECTION ENGINEERING FOR FACILITIES, AUG
2016 W/CHANGE 4, 7 FEBRUARY 2020.
C. UFC 4-021-01: DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, APR 2008
W/CHANGE 1, JAN 2010
D. IBC 2018: INTERNATIONAL BUILDING CODE FOR FIRE RESISTANCE
REQUIREMENTS, ALLOWABLE FLOOR AREA, BUILDING HEIGHT LIMITS, AND
BUILDING SEPARATION DISTANCE, EXCEPT AS MODIFIED BY UFC 3-600-01
E. NFPA 1, 2018: FIRE CODE, FOR DETERMINING VEHICLE ACCESS REQUIREMENTS
F. NFPA 101, 2018: LIFE SAFETY CODE, FOR BUILDING EGRESS AND LIFE SAFETY
EXCEPT AS MODIFIED IN UFC 3-600-01
G. NFPA 10, 2018: STANDARD FOR PORTABLE FIRE EXTINGUISHERS
H. NFPA 13, 2019: STANDARD FOR INSTALLATION OF SPRINKLER SYSTEMS,
MINIMUM REQUIREMENTS FOR DESIGN AND INSTALLATION OF AUTOMATIC FIRE
SPRINKLER SYSTEMS AND EXPOSURE PROTECTION
I. NFPA 30, 2018: FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, FOR
CONSTRUCTION REQUIREMENTS AND FIRE RESISTANCE RATINGS FOR LIQUID
STORAGE AREAS
J. NFPA 30A, 2018: CODE FOR MOTOR FUEL DISPENSING FACILITIES AND REPAIR
GARAGES, FOR OCCUPANCY CLASSIFICATION, CONSTRUCTION REQUIREMENTS
AND MEANS OF EGRESS FOR REPAIR GARAGES AND ORGANIZATIONAL
MAINTENANCE SHOPS
K. NFPA 70, 2017: NATIONAL ELECTRICAL CODE (NEC) - ARTICLE 500 HAZARDOUS
LOCATIONS AND ARTICLE 511 COMMERCIAL GARAGES, REPAIR AND STORAGE
L. NFPA 80, 2016: STANDARD FOR FIRE DOORS AND OTHER OPENING PROTECTIVES
M. NFPA 72, 2019: NATIONAL FIRE ALARM AND SIGNALING CODE
N. NFPA 90A, 2018: STANDARD INSTALLATION OF AIR CONDITIONING AND
VENTILATION SYSTEMS, FOR PROTECTION OF OPENINGS, SHAFTS, FIRE
DAMPERS, SMOKE DAMPERS, PENETRATIONS AND FAN CONTROL
O. NFPA 291, 2016: RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND
MARKING OF HYDRANTS
Q. NFPA 409, 2016: STANDARDS FOR AIRCRAFT HANGARS.
R. ABA (ARCHITECTURAL BARRIERS ACT) ACCESSIBILITY STANDARDS FOR DOD
FACILITIES, CHAPTERS 1-10, ADOPTED BY DOD BY MEMORANDUM DATED
OCTOBER 2008
S. UFC 4-211-01: AIRCRAFT MAINTENANCE HANGARS, 18 MAY 2020 W/ CHANGE 2
T. IMC 2018: INTERNATIONAL MECHANICAL CODE AS REFERENCED & MODIFIED BY
UFC 1-200-01
U. IPC 2018: INTERNATIONAL PLUMBING CODE AS REFERENCED & MODIFIED BY UFC
1-200-01
V. JOINT BASE CHARLESTON ARCHITECTURAL COMPATIBILITY PLAN.
W. UFC 3-301-01: STRUCTURAL ENGINEERING, 1 OCTOBER 2019
BUILDING AREA
PER IBC 507.4 - THE EXISTING 1 STORY HANGAR - BUILDING OCCUPANCY S1 WITH
PERIMETER FRONTAGE > 60 FT IN ALL DIRECTIONS IS ALLOWED TO BE UNLIMITED.
507.4 SPRINKLERED, ONE STORY BUILDINGS. THE AREA OF A GROUP A-4 BUILDING
NOT MORE THAN ONE STORY ABOVE GRADE PLAN OF OTHER THAN TYPE V
CONSTRUCTION, OR THE AREA OF A GROUP B, F, M, OR S BUILDING NO MORE
THAN ONE STORY ABOVE GRADE PLAN OF ANY CONSTRUCTION TYPE, SHALL NOT
BE LIMITED WHERE THE BUILDING IS PROVIDED WITH AN AUTOMATIC SPRINKLER
SYSTEM THROUGHOUT IN ACCORDANCE WITH SECTION 903.3.1.1 AND IS
SURROUNDED AND ADJOINED BY PUBLIC WAYS OR YARDS NOT LESS THAN 60
FEET (18.288MM) IN WIDTH.
UNPROTECTED/FULLY SPRINKLERED
@ ASSEMBLY
@ ASSEMBLY
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
M A R K A. L A Z O
S
O U
TH
CAROL IN
A
R E G I S T E R E D
PR
OF E
SS I ON
A L E N G I N E E R
No. 20943
5/14/2021
/1
/2
/1
/2
/1
/2
/1
/2
UPR
R
DN
GENERAL LIFE SAFETY SHEET NOTES:
1. DEVICES HAVE BEEN SHOWN; BUT THE CONTRACTOR SHALL ENSURE THE INSTALLATION
OF ALL LIFE SAFETY DEVICES INDICATED ON THE ENGINEERING DRAWINGS.
2. CONTRACTOR SHALL FIELD VERIFY THE LOCATION OF ANY EXISTING FIRE RATED
WALLS. ANY WORK DONE AROUND EXISTING FIRE RATED WALLS SHALL BE DONE WITH
REPAIRED IMMEDIATELY.
3. CONTRACTORS SHALL FOLLOW EM-385-1-1 AND NFPA 241, ALONG WITH THE
INSTALLATION’S FIRE REGULATIONS.
4. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE
PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS OR
PENETRATIONS SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS
OR STENCILING. SUCH IDENTIFICATION SHALL:
a. BE LOCATED WITHIN 15 FEET OF THE END OF EACH WALL AND AT INTERVALS NOT
EXCEEDING 30 FEET MEASURED HORIZONTALLY ALONG WITH WALL OR PARTITION.
b. INCLUDE LETTERING NOT LESS THAN 3 INCHES IN HEIGHT WITH A MINIMUM 3/8-INCH
STROKE IN A CONTRASTING COLOR INCORPORATING THE SUGGESTED WORDING,
“FIRE AND/OR SMOKE BARRIER – PROTECT ALL OPENINGS,” OR OTHER WORDING.
A
2 3 4
5 6 7 8 9 10 11 12 13 14
B
C
D
E
F
G
H
J
K
L
15 16
17 18 19 20
BREAK ROOM
CLEANING RM
ENTRY
HANGAR
DISPATCH
EXERCISE
MECHANICAL
FOAM EQUIP.
SYSTEM
ELEC/FIRE ALARM
CORRIDOR
LOCKERS
263 SF
50 5.26
634 SF
150 4.23
35024 SF
500 70.05
821 SF
300 2.74
142 SF
300 0.47
1510 SF
300 5.03
1666 SF
15 114.7
81 SF
500 0.16
1057 SF
50 20.35
165/12
165/12
165/12
165/12
165/12
165/12
165/69
165/80
DIAGONAL DISTANCE = 292 FT
REQUIRED SEPARATION = 146 FT
41 FT
F
T
TD= 145FT
PLUMBING INFORMATION
WATER CLOSETS
LAVATORIES
URINALS *
FEMALE - PROVIDEDFEMALE - REQUIREDMALE - PROVIDEDMALE - REQUIRED
MINIMUM PLUMBING FIXTURES REQUIRED/PROVIDED PER IBC SECTION TABLE 2902.1
OTHER FIXTURES
DRINKING FOUNTAINS
REQUIRED PROVIDED
UNISEX TOILET
OTHERS (LIST)
* URINALS - SEE IPC 419.2, URINALS MAY SUBSTITUTE FOR W.C.
WHERE MIXED OCCUPANCIES OCCUR WITHIN BUILDINGS, EXPAND THIS TABLE TO INDICATE OCCUPANT LOADS FOR EACH. THE MINIMUM REQUIRED TOILET FIXTURES ARE CALCULATED FOR THE TOTAL DESIGN OCCUPANT LOAD INDICATED IN TABLE 5-6
SERVICE SINK
Existing - not in scope 2 Existing - not in scope 1
Existing - not in scope 1 Existing - not in scope 1
Existing - not in scope 2 N/A N/A
Existing - not in scope Existing - not in scope
Existing - not in scope 0
Existing - not in scope 1
90' - 6 3/4" 90' - 6 3/4" 90' - 6 3/4"
ASSUMED FIRE AREA SEPARATION WALL
1HR FIRE BARRIER W/ 45MIN OPNG TYP
ASSUMED
SEPARATION WALL
1HR FIRE BARRIER
W/ 45MIN OPNG -
TYP
ASSUMED FIRE AREA SEPARATION WALL
1HR FIRE BARRIER W/ 45MIN OPNG TYP
ASSUMED FIRE AREA SEPARATION WALL
1HR FIRE BARRIER W/ 45MIN OPNG TYP
ASSUMED FIRE AREA SEPARATION WALL
1HR FIRE BARRIER W/ 45MIN OPNG TYP
ENTRY
MEN
WOMEN
JAN
D
IA
G O
N A
L D
IS
T
A N
C E
F
T
R E
Q U
IR
E
D S
E P
A R
A T
IO
N
F
T
47'-2" COMMON PATH
OCCUPANCY LOAD
OCCUPANCY AREA SF AREA/OCC NO. OCCUPANTS
STORAGE (S1) & HANGAR 35104 500 71
BUSINESS 1085 150 8
LOCKERS 1280 50 26
ASSEMBLY (A3) 1721 15 115
MECH / STOR / EQUIP. 2472 300 9
229 TOTAL OCCUPANTS
* OCCUPANT LOAD FOR EGRESS CALCULATED PER NFPA 101 TABLE 7.3.1.2 AND
UFC 3-600-01 TABLE10.1
62'-3"
TRAVEL
DISTANCE
400'-0"
ALLOWED
72 FT
F
T
F
T
55 FT
F
T
57 FT
F
T
F
T
FE
FE
FE
/4
/4
165/12
NEW 1HR HORIZONTAL FIRE
BARRIER W/ 45MIN OPNG TYP AT
ROOF STRUCTURE TO HANGAR
ASSUMED 1HR HORIZONTAL FIRE
BARRIER W/ 45MIN OPNG TYP AT
ROOF STRUCTURE TO HANGAR -
TYP.
FE
NEW
FE
NEW
FE
NEW
FE
NEW
SPACE USE LEGEND
AIRCRAFT HANGAR 1/500 SF
CIRCULATION / RESTROOMS ETC.
ASSEMBLY (less concentrated) & COLLABORATION 1/15 SF (net)
BUSINESS USE 1/150 SF
STORAGE / MECH ,ELEC, OTHER BLDG EQUIP
1/300 SF
LOCKERS / EXERCISE ROOMS
1/50 SF
(NFPA 101 TABLE 7.3.1.2, AND UFC 3-600-01 TABLE 10.1)
5 6
F
G
OFFICE
451 SF
150 3
165/5
ASSUMED FIRE AREA SEPARATION WALL
1HR FIRE BARRIER W/ 45MIN OPNG TYP
TO HANGAR
ASSUMED 1HR HORIZONTAL
FIRE BARRIER W/ 45MIN
OPNG TYP AT MEZZANINE
ROOF STRUCTURE TO
HANGAR - TYP.
150 SF
100 100
1-HR. RATED WALLS
LIFE SAFETY PLAN LEGEND
45'-0"
TRAVEL DISTANCE
FEC
FIRE EXTINGUISHER CABINET W/ 10LB. A: BC
DRY-CHEMICAL FIRE EXTINGUISHER
NOTE: FIRE EXTINGUISHERS SHALL BE
INSTALLED W/ TOP AT 4'-0" ABOVE FINISHED
FLOOR. PROVIDE STICK - ON LETTERING AND
DIRECTIONAL ARROWS TO IDENTIFY THE
CABINET OR EXTINGUISHERS LOCATION.
EXIT SIGN WITH DIRECTION ARROWS-
SEE ELECT. DWGS.
FE
BRACKET - MOUNTED FIRE
EXTINGUISHER: 10LB. A:BC
DRY - CHEMICAL TYPE
EGRESS CLEAR WIDTH
CAPACITY/NO. OF OCCUPANTS
FIRE ALARM VISUAL / AUDIO STROBE; SEE
ELECTRICAL
FULL HEIGHT WALLS (NO RATING)
ROOM AREA
OCCUPANT LOAD
AREA PER OCCUPANT
STARTING POINT FOR TRAVEL DISTANCE
36" 100/100
COMMON PATH END
CP
GRAPHIC SCALE
8' 16' 32'48"
SCALE: 1/16"=1'-0"
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
G
E W
B
AIR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L
E S
T O
N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P A
R T M
E N
T O
F D
E F E
N S
E C
H A
R L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
PLAN NORTH
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
B S
H A
W
C C
O O
P E
R
M L A
Z O
L S
W
/8
/2
L
IF
E S
A F
E T
Y P
L A
N
DKFX 1054125
05/14/2021
G-102
/8
/2
/8
/2
/8
/2
SCALE: 1/16" = 1'-0"1
LIFE SAFETY PLAN - OVERALL
SCALE: 1/16" = 1'-0"
LIFE SAFETY PLAN (MEZZANINE)
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
M A R K A. L A Z O
S
O U
TH
CAROL IN
A
R E G I S T E R E D
PR
OF E
SS I ON
A L E N G I N E E R
No. 20943
5/14/2021
/1
/2
/1
/2
/1
/2
/1
/2
DESIGN REFERENCES:
CODES AND STANDARDS:
IBC 2018 INTERNATIONAL BUILDING CODE, 2018 EDITION
IEBC 2018 INTERNATIONAL EXISTING BUILDING CODE, 2018 EDITION
ASCE/SEI 7-16 MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR
BUILDINGS AND OTHER STRUCTURES
RP 8 STANDARDS OF SEISMIC SAFETY FOR EXISTING FEDERALLY OWNED
AND LEASED BUILDINGS
UFC 1-200-01 DoD BUILDING CODE
UFC 3-301-01 STRUCTURAL ENGINEERING (DATED 1-OCT-2019)
UFC 4-010-01 DoD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS
UFC 4-211-01 AIRCRAFT MAINTENANCE HANGARS, WITH CHANGE 2
(DATED 18-MAY-2020)
ACI 318-14 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
AISC 325-17 STEEL CONSTRUCTION MANUAL, 15TH EDITION
AISC 360-16 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS
TMS 402/602-16 BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES
GENERAL NOTES:
1. THE STRUCTURE IS DESIGNED AS A STABLE UNIT AFTER ALL COMPONENT PARTS ARE
IN PLACE. THEREFORE, THE CONTRACTOR/ERECTOR SHALL PROVIDE ALL
NECESSARY SHORING AND BRACING AS REQUIRED TO ENSURE STABILITY DURING
ERECTION.
2. WHEN A DETAIL IS SHOWN ON THE STRUCTURAL DRAWINGS FOR ONE CONDITION, IT
SHALL APPLY TO ALL SIMILAR OR LIKE CONDITIONS, UNLESS NOTED OR SHOWN
OTHERWISE ON THE DRAWINGS.
3. CONTRACTOR SHALL FULLY COORDINATE ALL ARCHITECTURAL AND STRUCTURAL
DRAWINGS (INCLUDING DIMENSIONS AND ELEVATIONS) AND SHALL FULLY RESOLVE
ANY CONFLICTS PRIOR TO COMMENCING WORK.
4. FABRICATION DRAWINGS SHALL NOT BE REPRODUCTION OF STRUCTURAL CONTRACT
DRAWINGS.
5. MISCELLANEOUS STRUCTURAL ITEMS, CONDITIONS OR PIECES OF STEEL MAY BE
SHOWN ON ARCHITECTURAL DRAWINGS.
6. CONTRACTOR SHALL CONSULT GOVERNMENT FOR DIRECTION SHOULD UNCHARTED
OR INCORRECTLY CHARTED PIPING OR OTHER UTILITIES BE ENCOUNTERED DURING
SITE CLEARING, GRADING AND EXCAVATION.
7. DESIGN CRITERIA:
A: AREA D MEZZANINE ROOF LOADS
a. DEAD LOADS 13 PSF (TOTAL)
METAL DECK + GYPSUM FIBER BOARD FLOORING 5.5 PSF
ROOF FRAMING DEAD LOAD 3.5 PSF
CMEP 4 PSF
b. LIVE LOAD 20 PSF
B: GROUND SNOW LOAD, Pg: 5 PSF
a. SNOW EXPOSURE FACTOR, Ce: 0.9
b. SNOW IMPORTANCE FACTOR, Is: 1.1
c. THERMAL FACTOR, Ct: 1.0
C: WIND LOADS
a. ULTIMATE WIND SPEED, Vult: 155 MPH
b. RISK CATEGORY: III
c. WIND EXPOSURE: C
d. PRESSURE COEFFICIENT ZONE WIDTH, a:
HIGH ROOF: 11 FT
LOW ROOF: 8.5 FT
BREAKROOM ROOF: 4 FT
D: SEISMIC LOADS
a. RISK CATEGORY: III
b. SEISMIC IMPORTANCE FACTOR, Ie: 1.25
c. MAPPED SPECTRAL RESPONSE: SS = 1.854 g
S1 = 0.541 g
d. SITE CLASS: D
e. DESIGN SPECTRAL RESPONSE: SDS = 1.483 g
f. SEISMIC DESIGN CATEGORY: D
1. CONCRETE COMPRESSIVE STRENGTH SHALL BE 4,500 PSI AT 28 DAYS
PER CHAPTER 19 OF ACI 318-14.
2. REINFORCING STEEL SHALL BE ASTM A615, GRADE 60.
3. WELDED WIRE REINFORCEMENT SHALL BE ASTM A1064 AND PLACED AT
MID DEPTH OF SLAB, UNLESS OTHERWISE NOTED.
4. PROPORTION AND DESIGN CONCRETE MIXES TO RESULT IN CONCRETE
SLUMP AT POINT OF PLACEMENT NOT LESS THAN 3" AND NOT MORE
THAN 5".
5. ADDITION OF WATER TO READY-MIX IN THE FIELD SHALL NOT BE
ALLOWED.
6. DEPOSIT CONCRETE IN A CONTINUOUS OPERATION UNTIL THE PLACING
OF CONCRETE IS COMPLETE. IF POUR IS TO BE DISCONTINUOUS,
CONTRACTOR SHALL USE CONSTRUCTION JOINTS.
7. CONCRETE MUST BE CURED FOR A MINIMUM 21 DAYS PRIOR TO ANY
ADHESIVE ANCHOR INSTALLATION.
8. SEE SECTION 20.6 OF ACI 318 FOR MINIMUM REINFORCEMENT
PROTECTION REQUIREMENTS.
9. WHEN TRANSMITTING CONCRETE MIX DESIGN FOR REVIEW, INCLUDE
ALL RELEVANT INFORMATION - INCLUDING MIX DESIGN
PROPORTIONING, PRODUCT DATA SHEETS, TEST RECORD DATA, ETC. -
IN ONE SUBMITTAL. DO NOT TRANSMIT SEPARATELY.
10. SEE SPECIFICATION SECTION 03 30 53 FOR ADDITIONAL INFORMATION.
11. THESE NOTES SHALL APPLY TO EQUIPMENT PAD WORK SHOWN ON
MECHANICAL DRAWINGS.
12. TYPICAL CLASS B, NON-TOP BAR, REINFORCEMENT SPLICES SHALL BE
AS FOLLOWS UNLESS OTHERWISE NOTED:
MINIMUM CONCRETE PROTECTION FOR
REINFORCEMENT (ACI 318-14, SECT. 20.6):
1. CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3"
2. CONCRETE EXPOSED TO EARTH OR WEATHER:
#6 THROUGH #11: 2"
#3 THROUGH #5: 1 1/2"
3. CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH EARTH:
SLAB, WALLS, JOISTS: 3/4"
BEAMS, COLUMNS: 1 1/2"
CONCRETE NOTES:
4,500
#4
LAP DISTANCE BY BAR SIZE
f'c (PSI) 18"
#5
23"
#6
27"
#7
40"
#8
45"
STRUCTURAL STEEL:
1. 1/2"-DIAMETER BOLTS SHALL BE USED IN ALL STRUCTURAL STEEL BOLTED
CONNECTIONS UNLESS NOTED OTHERWISE. TIGHTEN BOLTS TO TENSION
REQUIRED BY AISC.
2. ANCHOR RODS SHALL BE ASTM F1554 GR. 36, THREADED ON EACH END,
WITH HEAVY HEX NUT AND WASHER AT EACH END UNLESS OTHERWISE
NOTED.
3. ALL WELDED CONSTRUCTION SHALL BE IN ACCORDANCE WITH AWS D1.1
AND AISC.
4. WELDING SHALL BE PERFORMED ONLY BY OPERATORS QUALIFIED BY THE
AWS STANDARD QUALIFICATION PROCEDURE TO PERFORM THE
PARTICULAR TYPE OF WORK REQUIRED.
5. MEMBERS EXPOSED TO WEATHER IN FINISHED STRUCTURE SHALL BE
GALVANIZED AFTER FABRICATION. DO NOT WELD TO GALVANIZED
PORTION OF STEEL.
6. STEEL BELOW GRADE SHALL BE PROTECTED BY A MINIMUM OF 3" OF
CONCRETE OR 4" OF MASONRY.
7. GROUT UNDER BEARING PLATES SHALL BE OF NON-SHRINK, NON-
METALLIC COMPOSITION.
8. NO SPLICES IN STRUCTURAL FRAMING MEMBERS ARE PERMITTED EXCEPT
AS INDICATED OR APPROVED.
9. STRUCTURAL STEEL SHALL BE AS FOLLOWS:
9.1. W-SHAPES ASTM A992
9.2. PLATES, ANGLES, CHANNELS ASTM A36
9.3. HSS ASTM A1085, GRADE A
9.4. BOLTS, TENSION-CONTROL ASTM F3125, ASTM 1852-X
9.5. WELDING ELECTRODE E70XX
10. ALL EXPOSED STRUCTURAL STEEL SHALL BE PRIMED AND PAINTED.
11. SEE SPECIFICATION 05 12 00 FOR ADDITIONAL INFORMATION.
1. THE EXISTING MEZZANINE PANEL ROOF SHALL BE DEMOLISHED
AND REPLACED WITH A METAL DECK + GYPSUM FIBER BOARD
PANEL ASSEMBLY. REFER TO DEMO AND FRAMING PLANS.
2. THE BASIS OF DESIGN FOR THE METAL DECK SHALL BE A MINIMUM
2-SPAN CONDITION WITH THE FOLLOWING MINIMUM PROPERTIES.
1-1/2" DEPTH, 20 GA
In = 0.217 in4/ft. Ip = 0.197 in4/ft.
Sn = 0.229 in3/ft. Sp = 0.224 in3/ft. Fy = 50 ksi
FASTENERS AS SHOWN IN DETAIL BELOW.
3. THE BASIS OF DESIGN FOR THE GYPSUM FIBER BOARD PANEL
SURFACE OVER METAL DECK SHALL INCLUDE THE FOLLOWING:
LOAD RATING CAPACITY: 20 PSF MIN.
FLUTE SPANABILITY (ASTM E661): 10" MIN.
PANEL ATTACHMENTS: THROUGH PANEL AND METAL
DECK. SCREW TYPE AND
SPACING PER PANEL
MANUFACTURER
MAXIMUM PANEL WEIGHT: 3.5 PSF
PANEL THICKNESS: 5/8"
PANEL FIRE CHARACTERISTICS: TYPE X (ASTM C1278)
4. SUBMIT GYPSUM FIBER BOARD PRODUCT DATA AND INSTALLATION
SHOP DRAWINGS FOR REVIEW AND APPROVAL.
MEZZANINE ROOFING NOTES:
a a a a
3 3
2 1 2
2 2
3 32 a a
3e
3e
3r
3r
2e
2n
2n
2r
LOW ROOF
HIGH ROOF
B R E A
KR
O O M
TYP.
a TYP. a
TYP.
EFFECTIVE AREA (SF)
10 20 100
-103 -103 -135 -184 -64 -79
ROOF
1'
WALL
WIND
ZONES
PRESSURE
(PSF) (SEE
ADJACENT
DIAGRAMS)
-101 -101 -124 -164 -62 -74
-97 -97 -97 -117 -55 -62
EFFECTIVE AREA (SF)
10 20 100
-112 -112 -147 -200 -70 -86
ROOF
1'
WALL
WIND
ZONES
PRESSURE
(PSF) (SEE
ADJACENT
DIAGRAMS)
-110 -110 -134 -178 -68 -80
-106 -106 -106 -127 -60 -67
HIGH ROOF
LOW ROOF
EFFECTIVE AREA (SF)
10 20 100
-103 -150 -103 -150 -178 -150 -61 -75
ROOF
2n 2e 2r 3r 3e
WALL
WIND
ZONES
PRESSURE
(PSF) (SEE
ADJACENT
DIAGRAMS)
-103 -130 -103 -130 -153 -130 -58 -70
-32 -83 -32 -82 -94 -83 -52 -58
BREAKROOM ROOF
36/4 PATTERN W/
#12 SCREWS INTO
SUPPORT MEMBERS
SECTION VIEW
EDGE
SUPPORT
MEMBER
SUPPORT
MEMBER
BELOW
STEEL
DECK
SIDELAP
CONNECTION
W/ #10 SCREWS
@ 18" O.C.
SUPPORT
MEMBER
PLAN VIEW
NOTES:
1. DECK SHALL BE GALVANIZED AND CONTINUOUS
OVER 2 OR MORE SPANS.
2. DESIGN LOADS AS SPECIFIED ON THE STRUCTURAL
GENERAL NOTES SHEET S-001.
3. FIELD VERIFY ALL DIMENSIONS PRIOR TO
FABRICATION.
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
G
E W
B
A IR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L
E S
T O
N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P
A R
T M
E N
T O
F D
E F
E N
S E
C H
A R
L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
P .M
U R
R E
N
P .M
U R
R E
N
B
M
IN
O R
B
M
IN
O R
/8
/2
G E
N E
R A
L N
O T
E S
A N
D D
E S
IG
N
L O
A D
S
DKFX 1054125
5/14/2021
S-001
/8
/2
/8
/2
/8
/2
J
JT JOINT
K
KSI KIPS/SQUARE INCH
L
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG. LONGITUDINAL
M
MATL. MATERIAL
MAX. MAXIMUM
MECH. MECHANICAL
MTL METAL
MPH MILE PER HOUR
MIN. MINIMUM
MISC. MISCELLANEOUS
N
N.S. NEAR SIDE
N.I.C. NOT IN CONTRACT
NTS NOT TO SCALE
NO. (#) NUMBER
O
O.C. ON CENTER
O.D. OUTSIDE DIAMETER
P
PL PLATE
LBS. POUNDS
PCF POUNDS/CUBIC FOOT
PSF POUNDS/SQUARE FOOT
PSI POUNDS/SQUARE INCH
PEMB PRE-ENGINEERED METAL
BUILDING
PT PRESSURE TREATED
PROJ. PROJECTION
R
RC REINFORCED CONCRETE
REINF. REINFORCEMENT
REQ'D REQUIRED
REV. REVISIONS / REVISED
S
SECT. SECTION
SIM. SIMILAR
S.O.G. SLAB ON GRADE
SL. SLOPE
SPEC. SPECIFICATION
SQ. SQUARE
S.S. STAINLESS STEEL
STD. STANDARD
STL. STEEL
STRUC. STRUCTURAL
T
T&B TOP & BOTTOM
T.O. TOP OF
TRANS. TRANSVERSE
TYP. TYPICAL
U
U.N.O. UNLESS NOTED OTHERWISE
V
V.I.F. VERIFY IN FIELD
VERT. VERTICAL
W
WWR WELDED WIRE
REINFORCEMENT
W/ WITH
W/O WITHOUT
WP WORKING POINT
A
A.F.F. ABOVE FINISHED FLOOR
A.B. ANCHOR BOLT
& AND
APPROX. APPROXIMATE
ARCH. ARCHITECTURAL
@ AT
B
BLKG. BLOCKING
BTM. BOTTOM
B.O. BOTTOM OF
BRDG. BRIDGING
BLDG. BUILDING
C
CLG. CEILING
CL. CENTERLINE
CLR. CLEAR
COL. COLUMN
CONC. CONCRETE
CMU CONCRETE MASONRY UNIT
CONN. CONNECTION
CONT. CONTINUOUS
C.J. CONTROL JOINT
COORD. COORDINATE
D
DEMO. DEMOLITION OR DEMOLISH
DET. DETAIL
Ø DIAMETER
DIM. DIMENSION
E
EA. EACH
E.W. EACH WAY
ELEC. ELECTRICAL OR ELECTRIC
EL. ELEVATION
EQ. EQUAL
EQUIP. EQUIPMENT
EX. EXISTING
E.J. (EXP. JT.) EXPANSION JOINT
EXP. EXPANSION/EXPOSED
EXT. EXTERIOR
F
F.S. FAR SIDE
FT. FEET
FRP FIBER REINFORCED POLYMER
FIN. FINISH
F.F. FINISHED FLOOR
FLR. FLOOR
FTG. FOOTING
G
GA. GAGE OR GAUGE
GALV. GALVANIZED
Gr. GRADE
H
HORIZ. HORIZONTAL
I
IN. INCH
I.D. INSIDE DIAMETER
INT. INTERIOR
SCALE: NOT TO SCALE2
WIND ZONE PLAN
SCALE: NOT TO SCALE3
WALL WIND ZONES
SCALE: NOT TO SCALE4
WIND PRESSURE TABLES
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D
SCALE: 3/4" = 1'-0"1
DECK FASTENING
STRUCTURAL ABBREVIATIONS:
No. 29581
S
O
UT
H CAROL IN
A
B
R A D L E Y W. M I N
O
R
L I C E N S E D
P
RO
FESS I ONA L
E N G I N E E R
14-M
AY-2021
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
/1
/2
/1
/2
/1
/2
/1
/2
25'-0"
NOTE: NEIGHBORING BREAKROOM REGION
IN AREA D NOT SHOWN FOR CLARITY.
5 6
D
E
F
G
2'-8" 6'-2"
S18
S16S16
S-501
S-501
S19
S19
OUTLINE OF MECHANICAL
UNIT ABOVE CRIBBING
S20
S20
S20
EXISTING STEEL COLUMN, TYP.
EXISTING STEEL FRAMING, TYP.
EXISTING CONCRETE SLAB
AT OFFICE FLOOR
S19
S19
S19
S19
S-501
S-501
S-501
S-501
S-501
S21
S22
EXISTING CMU WALL
BELOW, TYP.
EXISTING FRAMING
EXISTING CONCRETE SLAB
NEW METAL DECK AND FLOORING
NEW FRAMING
ITEM TO BE DEMOLISHED
EXISTING CMU WALL
1. ALL EXISTING CONDITIONS AND
STRUCTURAL MEMBERS ARE SHOWN
PER ORIGINAL DESIGN DOCUMENTS
AND NON-DESTRUCTIVE SITE
INVESTIGATIONS. GENERAL
CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND CONDITIONS PRIOR
TO DEMOLITION & CONSTRUCTION.
2. CONTRACTOR SHALL COORDINATE ALL
REQUIRED DUCT OPENINGS IN THE
NEW METAL DECK. REFER TO OPENING
SUPPORT DETAIL ON S-501.
5 6
D
E
F
G
25'-0"
NOTE: NEIGHBORING BREAKROOM REGION
IN AREA D NOT SHOWN FOR CLARITY.
S-501
TYP.
DS1
EXISTING CONCRETE SLAB TO
REMAIN (TYP. OF OFFICE FLOOR)
EXISTING CMU WALL TO REMAIN
ALL EXISTING STEEL
FRAMING TO REMAIN U.N.O
EXISTING STEEL COLUMN
TO REMAIN, TYP.
EXISTING STEEL
STAIR TO REMAIN
EXISTING STEEL
STAIR TO REMAIN
EXISTING HANDRAIL TO
REMAIN, TYP.
EXISTING CMU
WALL BELOW TO
REMAIN, TYP.
EXISTING CMU WALL
BELOW TO REMAIN, TYP.
GRAPHIC SCALE
0 2' 4' 8'12"
SCALE: 1/4"=1'-0"
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
LEGEND
KEYNOTES
GENERAL NOTES
G
E W
B
A IR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L
E S
T O
N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P
A R
T M
E N
T O
F D
E F
E N
S E
C H
A R
L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
P .M
U R
R E
N
P .M
U R
R E
N
B
M
IN
O R
B
M
IN
O R
/8
/2
E N
L A
R G
E D
M E
Z Z
A N
IN
E
R O
O F
F R
A M
IN
G
P L
A N
S
A R
E A
D
DKFX 1054125
5/14/2021
S-401
/8
/2
/8
/2
/8
/2
R R
KEY PLAN
SCALE: 1/4" = 1'-0"2
ENLARGED MEZZANINE LEVEL FRAMING PLAN - AREA D
DS1 DEMOLISH EXISTING ROOF PANELS.
S16 W6x12 CRIBBING BEAMS, TYP.
S18 NEW 1-1/2" DEEP 20 GA METAL DECK AND
GYPSUM FIBER BOARD PANEL SURFACE.
S19 DUCT OPENING THROUGH METAL DECK
AND FLOORING PER MECH.
S20 ANGLE FRAMING TO TRIM OUT DECK
PENETRATION. REFER TO DETAIL 4/S-501.
S21 NEW ANGLE CLIP ANCHORED INTO
EXISTING CMU WALL. SEE DETAIL
8/S-501.
S22 NEW METAL STUD ATTACHED TO
EXISTING COLUMN FLANGES. SEE DETAIL
9/S-501.
SCALE: 1/4" = 1'-0"1
ENLARGED MEZZANINE LEVEL DEMOLITION PLAN - AREA D
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D
No. 29581
S
O
UT
H CAROL IN
A
B
R A D L E Y W. M I N
O
R
L I C E N S E D
P
RO
FESS I ONA L
E N G I N E E R
14-M
AY-2021
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
/1
/2
/1
/2
/1
/2
/1
/2
MECHANICAL EQUIP.,
SEE MECH. DWGS.
EQUIP. ATTACHMENT
TO CRIBBING BY
MANUFACTURER
EXISTING STEEL BEAM, TYP.
EXISTING PERIMETER CMU WALL WHERE OCCURS.
NEW METAL DECK AND GYPSUM FIBER BOARD PANEL.
FIRE CAULK AT ALL PANEL-STEEL INTERFACES, TYP.
NEW WIDE-FLANGE STEEL
CRIBBING BEAMS TO SUPPORT
MECHANICAL EQUIP., TYP.
3/16
TYP.
CRIBBING
TO
EXISTING
L3x3x1/4 x 4"-LONG CONNECTION TAB
WITH (2) 1/2"Ø BOLTS PER LEG, TYP.
4" TYP.
L2x2x1/4 DECK SUPPORT ANGLE
WELDED TO CRIBBING BEAM FLANGE
3/16 3@12
TYP
EXISTING CMU WALL IN
LINE WITH EXISTING
STEEL TO REMAIN
EXISTING STEEL
BEAM TO REMAIN, TYP.
DEMOLISH EXISTING
ROOF PANELS
EXISTING HANDRAIL
CONNECTED TO STEEL BEAMS.
HANDRAIL TO REMAIN, TYP.
EXISTING CMU WALL IN
LINE WITH EXISTING STEEL
EXISTING STEEL BEAM, TYP.
NEW METAL DECK
AND GYPSUM FIBER BOARD
PANEL FLOORING ASSEMBLY
EXISTING HANDRAIL
CONNECTED TO STEEL BEAMS.
HANDRAIL TO REMAIN, TYP.
FASTENER PATTERN PER
FLOORING ASSEMBLY
MANUFACTURER. SEE S-001.
FASTENER PATTERN PER S-001
L2x2x1/4 END CLOSURE, TYP.
TYP.
2" MIN.
FIRE CAULK
3/16 3@24
TYP.
L3x3x1/4 TAB
WELDED TO WEB OF
EXISTING BEAM, TYP.
L3x3x1/4
L3x3x1/4
L x3 x
/4
L x3 x
/4
OPENING
WELD L3x3x1/4 TO L3x3 TAB.
COPE ENDS AS NEEDED.
NOTES:
1. ALL STEEL TO STEEL CONNECTIONS SHALL BE WELDED.
2. PROVIDE ANGLE FRAMING FOR PENETRATIONS LARGER
THAN 10" IN DIAMETER OR ALONG LONGEST DIMENSION
OR AS NOTED ON FRAMING PLANS.
METAL DECK SPAN DIRECTION
3/16
3/16 2"
WELD AT 2
SIDES
EXISTING STEEL BEAM, TYP.
SECTION A-A
A A
3/16
TYP
NEW METAL DECK
AND GYPSUM FIBER BOARD
PANEL FLOORING ASSEMBLY
EXISTING STEEL BEAM, TYP. 1-1/2x1-1/2 20 GA ANGLE CLIP WITH #10
SCREWS @ 18" O.C., TYP. WHERE GYPSUM
FIBER BOARD MEETS STEEL CRIBBING BEAMS
NEW WIDE-FLANGE
STEEL CRIBBING
BEAM, TYP.
FIRE CAULK, TYP.
MECHANICAL EQUIP.,
SEE MECH. DWGS.
EQUIP. ATTACHMENT
TO CRIBBING BY
MANUFACTURER
EXISTING CMU WALL IN
LINE WITH EXISTING STEEL
EXISTING STEEL BEAM, TYP.
NEW METAL DECK
AND GYPSUM FIBER BOARD
PANEL FLOORING ASSEMBLY
EXISTING HANDRAIL
CONNECTED TO STEEL BEAMS.
HANDRAIL TO REMAIN, TYP.
FASTENER PATTERN PER
FLOORING ASSEMBLY
MANUFACTURER. SEE S-001.
FASTENER PATTERN PER S-001
L2x2x1/4 END CLOSURE WITH 1x1 20 GA
ANGLE CLIP WITH #10 SCREWS @ 18" O.C.
FIRE CAULK
3/16 3@24
TYP.
EXISTING CMU WALL, TYP.
EXISTING CONCRETE SLAB, TYP.
EXISTING STEEL BEAM, TYP.
NEW METAL DECK
AND GYPSUM FIBER BOARD
PANEL FLOORING ASSEMBLY
FASTENER PATTERN PER
FLOORING ASSEMBLY
MANUFACTURER. SEE S-001.
1-1/2x1-1/2 20 GA ANGLE DECK
CLIP WITH #10 SCREWS @ 18"
O.C. THROUGH METAL DECK
1x1 20 GA WITH 3/16"Ø x 1-1/4" CONCRETE
SCREWS @ 18" O.C. THROUGH DECK CLIP
AND INTO EXISTING CONCRETE SLAB
FIRE CAULK AT PANEL EDGE, TYP.
M
IN
EXISTING STEEL BEAM, TYP.
EXISTING EXTERIOR
WALL ASSEMBLY, TYP.
FIRE CAULK, TYP.
EXISTING CMU WALL
L2x2x1/4 END
CLOSURE, TYP.
NEW METAL DECK
AND GYPSUM FIBER BOARD
PANEL FLOORING ASSEMBLY
CONTINUOUS 2x2 20 GA. ANGLE CLIP WITH 3/16"Ø x 1 1/4"
CONCRETE SCREWS @ 18" O.C.
2'-2" VERIFY IN FIELD
FASTENER PATTERN PER S-001, TYP.
EXISTING STEEL BEAM, TYP.
EXISTING EXTERIOR
WALL ASSEMBLY, TYP.
FIRE CAULK, TYP.
L2x2x1/4 END
CLOSURE, TYP.
NEW METAL DECK AND
GYPSUM FIBER BOARD
PANEL FLOORING ASSEMBLY
800S162-97 STUD ATTACHED TO INSIDE
FACE OF COLUMN FLANGES. PROVIDE
(4) #10 SCREWS AT EACH END.
EXISTING STEEL
COLUMN, TYP.
2'-2" VERIFY IN FIELD
GRAPHIC SCALE
SCALE: 1 1/2"=1'-0"
1'12" 6"
SCALE: 3/4"=1'-0"
1'12" 2'
CEMS Project No.:
Project Manager:
Phone No.:Summerville, SC Wilmington, NC
15-154U D. Yensan
843.875.3637
G
E W
B
A IR AS
I N 62 8T H
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
D S
G N
B Y
D R
W N
B Y
C H
K B
Y
A P
P R
O V
D A
T E
D A
T E
D A
T E
D A
T E
F O
R J
O
IN
T B
A S
E C
H A
R L
E S
T O
N
J O
IN
T
B A
S E
C H
A R
L E
S T
O N
A
IR
M O
B
IL
IT
Y
C O
M M
A N
D D
E P
A R
T M
E N
T O
F D
E F
E N
S E
C H
A R
L E
S T
O N
A F
B S
C
DRAWING SIZE: ARCH D (24"x36")
PROJECT NO.
RECORD DRAWING DATE
SHEET
IF SHEET IS LESS THAN 24"x36" (ARCH D) IT IS A REDUCED PRINT, SCALE ACCORDINGLY.
OF
A/E SEAL
D K
F X
-5
R E
P A
IR
M
A
IN
T E
N A
N C
E F
A C
IL
IT
Y
B L
D G
P .M
U R
R E
N
P .M
U R
R E
N
B
M
IN
O R
B
M
IN
O R
/8
/2
M E
Z Z
A N
IN
E
D E
T A
IL
S
DKFX 1054125
5/14/2021
S-501
/8
/2
/8
/2
/8
/2
SCALE: 3/4" = 1'-0"
S-401
TYPICAL CRIBBING SECTION
SCALE: 1 1/2" = 1'-0"
S-401
TYPICAL MEZZANINE ROOF DEMO SECTION
SCALE: 1 1/2" = 1'-0"
S-401
MEZZANINE ROOF DECK SECTION - PLAN EAST
SCALE: 3/4" = 1'-0"4
NEW PENETRATION FRAMING DETAIL
D R
A W
IN
G
R E
V
IS
IO
N
S R
E V
D
E S
C R
IP
T
IO
N
P R
E P
B Y
D A
T E
A P
P R
'D
S
SCALE: 3/4" = 1'-0"
S-401
TYP. DETAIL AT CRIBBING BEAMS
SCALE: 1 1/2" = 1'-0"
S-401
MEZZANINE ROOF DECK SECTION - PLAN SOUTH
SCALE: 1 1/2" = 1'-0"
S-401
MEZZANINE ROOF DECK SECTION - PLAN NORTH
SCALE: 1 1/2" = 1'-0"
S-401
MEZZANINE ROOF DECK SECTION - PLAN NORTHWEST
SCALE: 1 1/2" = 1'-0"
S-401
MEZZANINE ROOF DECK SECTION - PLAN SOUTHWEST
No. 29581
S
O
UT
H CAROL IN
A
B
R A D L E Y W. M I N
O
R
L I C E N S E D
P
RO
FESS I ONA L
E N G I N E E R
14-M
AY-2021
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
I
R A
D
M
AN
COM
MO
IT Y
B I L
G
E W
B
A IR AS
I N 62 8T H
/1
/2
/1
/2
/1
/2
/1
/2
GENERAL NOTES:
1. THE DRAWINGS INDICATE THE GENERAL EXTENT OF
WORK. THE DRAWINGS ARE NOT INTENDED TO
INDICATE OR DESCRIBE ALL WORK REQUIRED FOR THE
FULL PERFORMANCE AND COMPLETION OF THE
REQUIREMENTS OF THE CONTRACT DOCUMENTS.
2. THE ENUMERATION OF PARTICULAR ITEMS OF WORK IN
ONE PORTION OF THE CONTRACT DOCUMENTS SHALL
NOT BE CONSTRUED TO EXCLUDE OTHER ITEMS
NECESSARY OR IMPLIED THEREFROM.
3. THE CONTRACTOR IS RESPONSIBLE FOR THE
COORDINATION OF ALL PARTS OF THE WORK SO THAT
NO WORK SHALL BE LEFT IN AN UNFINISHED OR
INCOMPLETE CONDITION.
4. ALL WORK SHALL CONFORM TO APPLICABLE INDUSTRY
AND MANUFACTURER'S PUBLISHED STANDARDS FOR
QUALITY OF MATERIALS AND WORKMANSHIP, AS WELL
AS, ALL REQUIREMENTS IN THESE DRAWINGS AND
SPECIFICATIONS. ANY CONFLICTING REQUIREMENTS
OF THE SOURCES LISTED ABOVE SHALL BE BROUGHT
TO THE CONTRACTING OFFICER'S ATTENTION PRIOR TO
PROCEEDING WITH THE WORK.
5. THE CONTRACTOR SHALL PROTECT ANY EXISTING, IN-
PLACE, AND NEW WORK.
6. ALL WORK NOTED "N.I.C." IS NOT MEANT TO BE PART OF
THE CONSTRUCTION SCOPE OF WORK AGREEMENT.
7. THE CONTRACTOR SHALL PAY FOR AND COORDINATE
THE REMOVAL AND LEGAL DISPOSAL OF MATERIALS
AND RUBBISH.
8. ONCE ON SITE, THE CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND SHALL VERIFY ALL NEW AND
EXISTING CONDITIONS, SHOWN ON THESE DRAWINGS.
THE CONTRACTOR SHALL NOTIFY THE CONTRACTING
OFFICER IN WRITING OF ANY DIFFERING CONDITIONS
BEFORE COMMENCEMENT OF WORK.
9. DO NOT SCALE DRAWINGS; DIMENSIONS GOVERN,
LARGE SCALE DETAILS GOVERN OVER SMALL SCALE
DETAILS. THE CONTRACTOR SHALL NOTIFY THE
CONTRACTING OFFICER IN WRITING OF ANY DIFFERING
CONDITIONS BEFORE COMMENCEMENT OF WORK.
10. UNLESS NOTED OTHERWISE, ALL GYPSUM BOARD
SURFACES ARE TO RECEIVE ONE PRIMER COAT AND
TWO COATS OF PAINT.
11. DIMENSIONS NOTED AS 'HOLD' SHALL NOT VARY BY
MORE THAN 1/8" FROM SIDE TO SIDE OR FROM FRONT
TO BACK, FINISHED SURFACE TO FINISHED SURFACE.
12. NFPA 241, STANDARD FOR SAFEGUARDING
CONSTRUCTION, AND ALTERATION OPERATIONS SHALL
BE APPLIED.
13. WALL AND/OR CEILING ASSEMBLIES THAT ARE
IDENTIFIED WITH A FIRE RESISTIVE RATING SHALL BE
CONSTRUCTED AS DETAILED HEREIN.
14. DIMENSIONS SHOWN ARE TO FACE OF STUD OR CMU
(U.N.O.).
15. PROVIDE…